| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 30-08-2024 | Due Date Extended for tenders closing on 29-07-2024 | Admin Corrigendum Date Extend | 04-09-2024 |
| Sl. No. | Item Description |
| 1 | M&L for Dismantling the water mains from the delivery lines, lifting/taking up GI/CI Column pipes, pumping sets of any description upto 200 mtr depth including submersible cable after disconnecting pumping sets from cable, repairs tothe defective submersible cable andjointing of submersible cable, pump and motorsby using water proofing jointing kit, and also jointing of crack/leaked GI pipe with MS sheet jointing clamp,rubber sheet, nut, bolts and washer etc replacement of defective column pipes, and including Loweringof submersible pump Sets, submersible cable, column pipes, reonnecting main delivery mains as existing and testing for satisfactory running and continuous flow of water etc complete all as directed by Engineer in charge in bore wells at various locations.Note: 1Repair to Motor & Pumping sets, cable and column pipes etc. shall be measured and paid seperately.2.Contractor shall take proper precautions while lifting out and removing pump set from bore well so as to avoid any damage to column pipe and submersible cable.All necessary T&P and equipments required for lifting out and lowering pump set etc shall be arranged by the contractor at his own cost.3. replacement of Nut bolts washer & gasket of any qty & size for column pipe upto 50mm dia is deemed to beincluded in quoted rates. |
| 2 | Dismantling and strip opening of submersible pump & motor of any description and in any position for detection of defect (pump or motor)/ servicing/ overhauling, cleaning, oiling/greasing, fixing of serviceable parts in position, removing & replacement of defective / unserviceable parts with new parts and reassembling the pump andmotor, ensuring proper alignment of pump and motor, fixing in position, connecting to existing system and testing at site on full load to the entire satisfaction of the Engr-in-Charge for the following capacities pumps & motors :- |
| 3 | 10 HP, three phase, 415 Volts, 50 Hz, AC supply |
| 4 | 5 to 7.5 HP, three phase, 415 Volts, 50 Hz, AC supply |
| 5 | Note for item No: 2.01 & 2.02: -(i) The replacement of defective / unserviceableparts shall be measured and paid separately as “Supply only” under appropriate item of Sch ‘A’ and fixing rate for new items are deemed to include under these item.(ii)Burnt out windings of motor shall be replaced, measured and paidseparately under appropriate item of Sch ‘A’ for rewinding. (iii) (a) The rates for above items are deemed to include transportation of pumps/ motors to and from workshop as approved by Engineer-in-charge for necessary repairs, alignment and testing of pump and motors at authorised workshop.(b)Re-metalling to Pump shaft, polishing andgrinding and making standard size to matching with Gun Metal Bush / Neck-ring shall be measured and paid for separately under appropriate item of Sch ‘A’(iv)Lifting of pump and motor from bore well and lowering of pump and motor after repairs shall be measured and paid separately under appropriate item of Schedule `A\".- |
| 6 | Taking out and removing old burnt out windings of the submersible/Non clog submersible electric motors ofany description and in any position offollowing capacity and rewinding of submersible electric motors with existing size PVC insulated, copper conductor as approved by the Engineer-in-charge including cleaning the slots with carbon- tetra-chloride solution before rewinding & testing on full load etc complete all as specified and directed :-Note : (i)The winding wire shall be of make ATLAS/FINOLEX(ii)The rate quoted by the contractor shall be deemed to include the cost of transportationfrom site to authorised workshop and back, fixing / lowering in position |
| 7 | 10 to 12.5 HP, three phase, 415 Volts, 50 Hz, AC supply |
| 8 | 5 to 7.5 HP, three phase, 415 Volts, 50 Hz, AC supply |
| 9 | Supply only in replacement of following defective spare parts of submersible motor of any description/make and capacity 05 to 12.5 Hp and in any positioin :- |
| 10 | Lower / upper housing of existing size |
| 11 | Gunmetal bearing bush |
| 12 | CI thrust plate |
| 13 | Carbon bush |
| 14 | Water seal |
| 15 | Bearing bush |
| 16 | Turning and polishing of motor shaft including lathe work |
| 17 | Sand Guard |
| 18 | Rotor Assembly |
| 19 | Body Sleeve |
| 20 | Supply only in replacement of following defective parts of submersible pumps ofany description/make and capacity 05 to 12.5 Hpand in any position :- |
| 21 | Stage casing bowl (SS-410 material) |
| 22 | Rubber bearing bush |
| 23 | Stage casing gun metal bearing bush |
| 24 | Impeller of existing casing size capacity |
| 25 | Neck ring |
| 26 | Defective Stainless steel sleeve |
| 27 | NRV body suitable for any make of submersible pump |
| 28 | MS coupling and key common suitable of pump shaft and motor shaft of any type of submersible pump. |
| 29 | Stainer |
| 30 | Disconnecting the water mains from the suction and delivery pipe line of Monoblock/centrifugal pump sets/open well pump set of any description and in any position and taking out pump set / motor from the base frame including disconnecting electric connections andfoundation, nuts and bolts.for servicing /overhauling, cleaning, oiling/greasing, fixing of serviceable parts in position, removing & replacement of defective / unserviceable parts with new parts and reassembling the pump andmotor of capacity 5 HP capacity, ensuring proper alignment of pump and motor, fixing in position, connecting to existing system and testing at site on full load to the entire satisfaction of the Engineer-in-Charge. Note: -(i) The replacement of defective / unserviceableparts shall be measured and paid separately as “Supply only” under appropriate item of Sch ‘A’ and fixing rate for new items are deemed to include under these item.(ii) The rates for above items are deemed to include transportation of pumps/ motors to and from workshop as approved by Engineer-in-charge for necessary repairs, alignment and testing of pump and motors at workshop. |
| 31 | All as per item No: 06 above, but for centrifugal pumps sets of capacity 7.5 HP to 10 HP capacity, complete all as specified and directed by Engr-in-charge. |
| 32 | All as per item No: 06 above, but for centrifugal pumps sets of capacity 40 HP to 60 HP capacity, complete all as specified and directed by Engr-in-charge. |
| 33 | Supply only in replacement of following defective parts of centrifugal pump sets/open well pump sets, complete all as specified and directed by Engr-in-charge. |
| 34 | Ball bearing for 5 HP Pump |
| 35 | Ball bearing for 7.5 HP/10HP pump |
| 36 | Ball bearing for40/60 HP pump |
| 37 | Gland Collar for 5 HP Pump |
| 38 | Gland Collar for 7.5/10 HP pump |
| 39 | Gland Collar for40/60 HP pump |
| 40 | Stainless steel bush for 5 HP Pump |
| 41 | Stainless Steeel bush for 7.5 HP/10HPpump |
| 42 | Stainless Steel bush for40/60 HP pump |
| 43 | Stainless Steel shaft for 5 HP pump |
| 44 | Stainless Steel shaft for 7.5 HP/10HP pump |
| 45 | Stainless Steel shaft for 40/60 HP pump |
| 46 | Cast Iron Impeller for 5/10HP pump complete with all accsessories. |
| 47 | Cast Iron Impeller for 40 HP pump complete with all accsessories. |
| 48 | Cast Iron Impeller for 60 HP pump complete with all accsessories. |
| 49 | Gland packing off size suitable for pump set capacity 5HP to 60 HP |
| 50 | M&L for Turning /remetalling and polishing of pump shaftwith shaft key including lathe work. |
| 51 | Rubber packing sheet 3mm thick. |
| 52 | Ball bearing grease superior quality in 1 KG containers |
| 53 | MS Nuts, bolts and washers of various sizes as required. |
| 54 | Rewinding of 5 HP motor same gauge with super enamelled copper wire including removing burnt winding cleaning of slotes sepration of rotor and startor making insulation to all joint . and replacement of the following items complete all as specified and directed by Engr-in-charge. (a) Replacement of ball bearing (b) Replacement of cooling fan (c) Replacement of capacitor of suitable mfd (d) Replacement of seal, bush (e) Repair/replacement of shaft Note:The rate quoted by the contractor shall be deemed to include the cost of transportationfrom site to authorised workshop and back, fixing / lowering in position |
| 55 | All as per item No:10 above, but for centrifugal motor of capacity 7.5 HP to 12.5 HP capacity, complete all as specified and directed by Engr-in-charge. |
| 56 | All as per item No:10 above, but for centrifugal motor sets of capacity 40 HP to 60 HP capacity, complete all as specified and directed by Engr-in-charge. |
| 57 | Dismounting of Openwell Submersible/monoblock2 HP pump, 240Volts and motor from foundation including disconnecting all electric connection suction / delivery line connection andtransporation to pumping set civil work shop and return to store after repair including Re- assembing of motor and testing and commissioning complete all as specified and directed by Engr-in-charge. |
| 58 | All as above item No: 13,but for 0.5-1.5HP monoblock pumpset/inline booster pressure, complete all as specified and directed by Engr-in-charge. |
| 59 | Taking out the pump from the motor and rewinding of2 HP motor with super enamelled copper wiresame gauge & size includinng all insulating material ie. sleeves stick and insulation sheet. and replacement of the following parts. (a) Replacement of driving and non driving end ball bearing (b) Balanceing of rotor including straightening of strip (c) Replacement of bearing bush upper and lower(d) Repair/replacement to pump seal, bush bearing, NRV, studs, nut bolts etc.Note:The rate quoted by the contractor shall be deemed to include the cost of transportationfrom site to authorised workshop and back, fixing / lowering in position |
| 60 | All as above item No: 15, but motor of capacity 0.5HP-1.5HP, complete all as specified and directed by Engr-in-charge. |
| 61 | S& F in replacement of surge tank for pressure maintenance in pipeline suitable for 0.5HP inline pressure pump as per OEM specification installed at site, complete all as specified and directed by Engr-in-charge. |
| 62 | Supply, installation, commissioning & testing of centrifugal Monoblock pump set with motor, Single Phase, 230V, 6.83-3.33 LPS at 10.5-22.5 Mtr head, having capacity 2 HP/1.5Kw, 2800 rpm, cross sectional 50x 40mm dia, insulation class \"F\" with all connected accessories complete all as specified and directed by Engr-in-charge.Note: 1) Contractor has to deposite old pump set to MES store in custody of concerned JE.2) Necessary fittings required for connection/header, foundation & shed for pumps is deemed to be included in quoted rates. |
| 63 | Supply, installation, commissioning & testing of Monoblock pumpset 1HP, 25x25mm cross section pipe, head range - 6-39m, discharge 3000-750LPH, 2780 RPM complete all as specified and directed by Engr-in-charge. |
| 64 | Supply, installation, commissioning & testing of inline pressure booster pumpset of capacity 0.5HP/.37Kw, 240 Volts, cross-section size 25x25mm, head range 6-24m, discharge 2000-400LPH, insulation class B, 2780 RPM, complete all as specified and directed by Engr-in-charge. |
| 65 | S&F in replacement of Pressure cutoff switch suitable for 0.5HP inline pressure pump, complete all as specified and directed by Engr-in-charge. |
| 66 | S&F in replacement of Capacitor 50Mfd, 240 Volt suitable for monoblock pumpset, complete all as specified and directed by Engr-in-charge. |
| 67 | S&F in replacement of Capacitor 40Mfd, 240 Volt suitable for monoblock pumpset, complete all as specified and directed by Engr-in-charge. |
| 68 | S&F in replacement of Capacitor 30Mfd, 240 Volt suitable for monoblock pumpset, complete all as specified and directed by Engr-in-charge. |
| 69 | S&F in replacement of Capacitor 20Mfd, 240 Volt suitable for monoblock pumpset, complete all as specified and directed by Engr-in-charge. |
| 70 | S&F in replacement of Capacitor 4-10Mfd, 240 Volt suitable for monoblock pumpset, complete all as specified and directed by Engr-in-charge. |
| 71 | S&F of rubber insulation tape suitable submerged electrical joints of pumpsets, complete all as specified and directed by Engr-in-charge. |
| 72 | M&Lfor minor repairing / rectified and attending the complaint of contactor & other componentsof star-delta stater, DOL starter of any type & borewell/monoblock/shallow/ submersible pumpset by skilled trades man and making functionalby replacing defective/wornout parts as required on site, complete all as specified and directed by Engr-in-charge.Note: defective parts will be paid & measured saperately. |
| 73 | Supply and fix in replacement rubber coupling suitable for 7.5/10/12.5 HP pump set as per existing pattern complete all as specified and directed by Engr-in-Charge. |
| 74 | All as per item No 29 herein before but for 40/60 HP, complete all as specified and directed by Engr-in-charge. |
| 75 | M&Lin replacement of Power contactor 3 pole Type MNX 70 AC 3 rating 100A complete all as specified and directed by Engr-in-charge. |
| 76 | M&L in replacement of Power contactor 3 pole Type MNX 50 AC85 Amp rating complete all as specified and directed by Engr-in-charge. |
| 77 | M&Lin replacement of Power contactor 3 pole Type MNX 32 AC 3 rating 55A complete all as specified and directed by Engr-in-charge. |
| 78 | M&Lin replacement of Power contactor 3 pole Type MNX 25 AC 3 rating 45A complete all as specified and directed by Engr-in-charge. |
| 79 | Supply & fixin replacement of contactor, 3 pole, 415V,MNX 18 complete all as specified and directed by Engr-in-charge. |
| 80 | M&L in replacement of MNX/MCX front mounted block 2NO and 2NC complete all as specified and directed by Engr-in-charge. |
| 81 | M&L in replacement of MNX/MCX front mounted block 1NO and 1NC complete all as specified and directed by Engr-in-charge. |
| 82 | M&L in replacement of MNX/MCX side (left/right) mounted block 1NO and 1NC complete all as specified and directed by Engr-in-charge. |
| 83 | S&F in replacement of Electronic overload relay (Manual reset) relayrange 9-15 amp suitable for Direct Mounting on MNX 9 - 40 complete all as specified and directed by Engr-in-charge. |
| 84 | S&F in replacement of Electronic overload relay (Manual reset) relayrange 14-23 amp suitable for Direct Mounting on MNX 9 - 40 complete all as specified and directed by Engr-in-charge. |
| 85 | S&F in replacement of Electronic overload relay (Manual reset) relayrange 45-75 amp suitable for Direct Mounting on MNX 50-80, complete all as specified and directed by Engr-in-charge. |
| 86 | S&F in replacement of Electronic overload relay (Manual reset) relayrange 66-110 amp suitable for Direct Mounting on MNX 50-80, complete all as specified and directed by Engr-in-charge. |
| 87 | S&F in replacement of MU2 relays 9-14 Amps suitable for DOL starter as per site requirement, complete all as specified and directed by Engr-in-charge. |
| 88 | S&F in replacement of MU2 relays 13-21 Amps suitable for DOL starter as per site requirement, complete all as specified and directed by Engr-in-charge. |
| 89 | S&F in replacement of MK1 relays 9-14 Amps suitable for DOL starter as per site requirement, complete all as specified and directed by Engr-in-charge. |
| 90 | S&F in replacement of MK1 relays 11-18 Amps suitable for DOL starter as per site requirement, complete all as specified and directed by Engr-in-charge. |
| 91 | Supply & fixin replacement of Electronic timer 415 Volt, 50 Hz range 3-10 Secs complete all as specified and directed by Engr-in-charge. |
| 92 | S&F in replacement of Single phase preventer 6 wire, 415Vsuitable for pumps starter as per ground reqirement, complete all as specified and directed by Engr-in-charge. |
| 93 | M&Lin replacement of Single phase preventor VSP 2 auto/manual reset of any size , 415V complete all as specified and directed by Engr-in-charge. |
| 94 | S&F in replacement of Electronic Motor Protection Relay With in-built Earth Fault Protection having protection from Overload,Earth Fault, Locked Rotor, Single Phasing, Current Unbalance, Phase Sequence Reversal, Under Current with Inbuilt CT’s (1 A to 88 A) , Trip indication, Test facility, Selectable trip class - 10A, 10, 20 and 30 as per IEC 60947-4-1 suitable for 240Volt Auxilary supply thermal overload relay range of 8-22 Amp, complete all as specified and directed by Engr-in-charge. |
| 95 | S&F in replacement single phase Direct on line starter for monoblock pumpset of capacity 2 HP overload relay range 9-14 Amp complete all as specified and directed by Engr-in-charge. |
| 96 | S&F in replacement three phase Pre wired DOL starterfor monoblock pumpset ofof capacity 5 HP( 3.7 KW) sheet metal enclosed having relay range of 6-10Amp, 415Volts, with inbuilt: SPPR, current, voltage meter, & On/Off LED lamp indicator, complete all as specified and directed by Engr-in-charge. |
| 97 | S&F in replacement three Phase Pre wired DOL starter for monoblock pumpset of capacity 10 HP ( 7.5 KW) sheet metal enclosed having relay range of 15-25Amp, 415Volts, with inbuilt: SPPR, current, voltage meter, & On/Off LED lamp indicator, complete all as specified and directed by Engr-in-charge. |
| 98 | S&F in replacement of borewell submersible pumpset Pre wired DOL starter suitable for 5HP pumpset, sheet metal enclosed having relay range of 9-14Amp, 415Volts, with inbuilt: SPPR, current, voltage meter, & On/Off LED lamp indicator, complete all as specified and directed by Engr-in-charge. |
| 99 | S&F in replacement of borewell submersible pumpset Pre wired DOL starter suitable for 10HP pumpset, sheet metal enclosed having relay range of 20-32Amp, 415Volts, with inbuilt: SPPR, current, voltage meter, & On/Off LED lamp indicator, complete all as specified and directed by Engr-in-charge. |
| 100 | S&F in replacement Submersible cable PVC insulatedcopper conductor flat 3 core 2.5sqmm 1100 volt complete all as specified and directed by Engr-in-charge. |
| 101 | All as per item No 56 herein before but for 3 core 4 sqmm, complete all as specified and directed by Engr-in-charge. |
| 102 | All as per item No 56 herein before but for 3 core 6 sqmm, complete all as specified and directed by Engr-in-charge. |
| 103 | Supply only copper lugs size varying from 6 sq mm to 35 sqmm for jointing cable complete all as specified and directed by Engr-in-charge. |
| 104 | S&F in replacement of LT panel connector suitable for stater & MCCB connection made of heavy duty plastic with ss nut & bolt suitable for upto 50Amp, 215volts as per site requirement complete all as specified and directed by Engr-in-charge. |
| 105 | S&F in replacement of HRFR PVC Insulated copper conductor, (Unsheathed) Flexible Cables 25sqmm single core, 1100 Volt Conforming to IS 694, complete all as specified and directed by Engr-in-charge.Note: copper thimble of suitable size & any qty as required on site is deemed to be included in quoted rates. |
| 106 | All as above item No: 61,but for 16sqmm copper wire, complete all as specified and directed by Engr-in-charge. |
| 107 | All as above item No: 61,but for 10sqmm copper wire, complete all as specified and directed by Engr-in-charge. |
| 108 | M&L in replacement for MCCB 3 pole 63 amps, 16 KA complete all as specified and directed by Engr-in-charge. |
| 109 | All as above item No: 64, but 100Amps, 3Pole, 16 KA complete all as specified and directed by Engr-in-charge. |
| 110 | All as above item No: 64, but 100Amps, 4Pole, 16 KA complete all as specified and directed by Engr-in-charge. |
| 111 | All as above item No: 64, but 125Amps, 3Pole, 16 KA complete all as specified and directed by Engr-in-charge. |
| 112 | All as above item No: 64, but 160Amps, 3Pole, 36 KA complete all as specified and directed by Engr-in-charge. |
| 113 | All as above item No: 64, but 160Amps, 4Pole, 36 KA complete all as specified and directed by Engr-in-charge. |
| 114 | All as above item No: 64, but 250Amps, 4Pole, 36 KA complete all as specified and directed by Engr-in-charge. |
| 115 | M&L for repair & servicing of APFC Panel of capacity 50KVAr, including checking & testing efficiency of panel, wiring, cleaning, replacing damaged nut bolts & thimbles, complete all as specified and directed by Engr-in-charge. |
| 116 | S&F in replacement of Cylindrical Capacitors with Clamps of capacity 10KVAr, complete all as specified and directed by Engr-in-charge. |
| 117 | S&F in replacement of Cylindrical Capacitors with Clamps of capacity 5KVAr, complete all as specified and directed by Engr-in-charge. |
| 118 | S&F in replacement of reactive power manager realy RPM-8, including wiring 7 connection with system and testing complete all as per OEM specification, complete all as specified and directed by Engr-in-charge. |
| 119 | Supply & fixin replacement of contactor, 3 pole, 415V,MNX 12 complete all as specified and directed by Engr-in-charge. |
| 120 | Taking down old unserviceable and S&F standard duty power capacitor 440 V 3 phase LTBCD series 1 to 30 KVAr, box type for APFC panel ofany capacities including wiring and connection with main LT panel, complete all as specified and directed by Engr-in-charge.Note: Cost of Spreader, wiring of panel, lugs & visiting charges are deemed to be included in quoted rates. |
| 121 | S&F in repair Cast iron foot valve of size 150mm dia with necessary fixing arrangement like nut , bolts washer packing sheet etcincluding taking out existing unserviceable footvalve complete all as directed at site. |
| 122 | All as per item No 77 herein before but for 100mm dia, complete all as specified and directed by Engr-in-charge. |
| 123 | All as per item No 77 herein before but for 65 mm dia, complete all as specified and directed by Engr-in-charge. |
| 124 | All as per item No 77 herein before but for 50 mm dia, complete all as specified and directed by Engr-in-charge. |
| 125 | M & L for preparation of old Cast iron/ GI steel water tubing including all fittings and Sluice valves and applying two coats of synthetic Enamel paint (Colour as decided by Engineer -in- Charge) onsuction,delivery of pump Sets, pipe lines of dia not more than 200mm complete all as specified and directed by Engr-in-charge. |
| 126 | S&F in replacement of CI body & metallic gear water meter class \"A\", confirming to IS:2373of size 40/50mm dia ISI marked including nut bolts & rubber gasket for borewells, complete all as specified and directed by Engr-in-charge. |
| 127 | Re-development of bore well by means ofDTH compressor of suitable capacity & Pressure with Air compressed in deep bore well with high pressure rubber hose inbore well ( Each upto 200 Meter deep) by pushing compressed air pumping muddy water till the clear water is obtained, complete all as specified and directed by Engr-in-charge. |
| 128 | S&F in replacement GI column pipe of size 40 mm dia including welded flange nut bolts, washer, gasket and welding works complete all as specified and directed by Engr-in-Charge. |
| 129 | All as per item No 84 herein before but for size 50mm dia, complete all as specified and directed by Engr-in-charge. |
| 130 | S & F in replacement of indicator lamps suitable for 3 phase LT panel board/as per sample complete all as specified and directed by Engr-in-Charge. |
| 131 | M&Lin replacement of 3Ph Ammeter, 5A, Class 1 digital type, 415V suitable for existing panel CT operated of range 0-100 amp as required complete all as specified and directed by Engr-in-charge. |
| 132 | M&Lin replacement of 3Ph Voltmeter Class 1 digital type, 415V suitable for existing panel CT operated of range 0-500 V complete all as specified and directed by Engr-in-charge. |
| 133 | M&Lin replacement of panel mounted ON/OFF push button with contact block complete all as specified and directed by Engr-in-charge. |
| 134 | M&L in replacement of CT50/5 complete all as specified and directed by Engr-in-charge. |
| 135 | Excavation in trenchesnot exceeting 1.5 Mtr wide and not Exceding 1.5 Mtrin depth and getting outinHard/Densesoil for laying cables and manhole complete all as specified and directed by Engr-in-charge. |
| 136 | Returning, filling in including spreading, levelling, watering and ramming in layers not exc. 25 cms complete all as specified and directed by Engr-in-charge. |
| 137 | Removing excavated material not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engr-in-charge. |
| 138 | Supply and fix bricks subclass B designation70, laid flat in trenches for protection of cable over LT cable complete all as specified and directed by Engr-in-charge. |
| 139 | S&F in replacement of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volt grade, cross-sectional area size 3.5 C 35 Sqmm complete all as specified and directed by Engr-in-Charge. |
| 140 | M&L in replacement of pressure gauge 100mm dial to read in IS/BSunit type KG/cm2 and LB/inc2 reading marked 0-2, 0-30 respectively including taking old one complete all as specified and directed by Engr-in-charge. |
| 141 | Taking out existing U/S NRV of size 50-150 mm bore, complete all as specified and directed by Engr-in-charge. |
| 142 | Suply and fixing cast iron NRV flanged end of size 150 mm dia with all fitting and accessorie, complete all as specified and directed by Engr-in-charge. |
| 143 | All as per item 98 above but 100 mm dia , complete all as specified and directed by Engr-in-charge. |
| 144 | All as per item 98 above but 80 mm dia, complete all as specified and directed by Engr-in-charge. |
| 145 | All as per item 98 above but 65 mm dia, complete all as specified and directed by Engr-in-charge. |
| 146 | Suply and fixing Brass NRV thread end of size 50 mm dia with all fitting and accessorie, complete all as specified and directed by Engr-in-charge. |
| 147 | All as above item No: 102, but 40mm dia complete all as specified and directed by Engr-in-charge. |
| 148 | S&F in replacement of heavy duty GI union of 50mm dia, complete all as specified and directed by Engr-in-charge. |
| 149 | S&F in replacement of heavy duty GI union of 40mm dia, complete all as specified and directed by Engr-in-charge. |
| 150 | S&F in replacement of gun metal globe ball valve with iron handle screwed both ends for iron pipe and fixed of size 50 mm bore, complete all as specified and directed by Engr-in-charge. |
| 151 | All as per Item NoAbove butBore of pipe 40mm, complete all as specified and directed by Engr-in-charge. |
| 152 | S&F in replacement of heavy duty GI long bend (male threaded) elbow suitable for borewell outlet of size 50mm dia column pipe complete all as specified and directed by Engr-in-charge. |
| 153 | All as per Item NoAbove butof pipe 40mm, complete all as specified and directed by Engr-in-charge. |
| 154 | Supply and fixing in replacement of miniature circuit breaker (MCB) SP 5-32 amp rating 240V, 10KA \"C\" curve complete all as specified and directed by Engr-in-charge. |
| 155 | All as per item No: 110 above but SPN 40Amp-63Amp, complete all as specified and directed by Engr-in-charge. |
| 156 | All as per item No: 110 above but 415V, 10 KA, TP 25Amp-63Amp, complete all as specified and directed by Engr-in-charge. |
| 157 | All as per item No: 110 above but 415V, 10 KA, TPN 40Amp-100Amp, complete all as specified and directed by Engr-in-charge. |
| 158 | S&F in replacement of MS heavy duty Borewell column pipe holding clamp of suitable size & thickness including nut bolt & washer of suitable size, complete all as specified and directed by Engr-in-charge. |
| 159 | S&F Borewell Cap upto 200mm dia casing pipe of suitable thicknessincluding nut bolt & washer of suitable size, complete all as specified and directed by Engr-in-charge. |
| 160 | M&L for cleaning of area around borewell & LT panel including cutting grass, shurbs & removing them to a distance 50mtrs away and disposing it, complete all as specified and directed by Engr-in-charge.Note: Any type of tool required by labour at site has to be provided by contractor. |
| 161 | M&L for demolition of cement concrete (unreinforced) in ground floors and pavings n exc 15 cm thickness (below or above ground level) foundations, complete all as specified and directed by Engr-in-charge. |
| 162 | M&L for surface excavation n-exc 30cm deep and averaging 15cm deep and getting out in soft / loose soil complete all as specified and directed by Engr-in-charge. |
| 163 | M&L for broken bricks hard core of gauge n-exc 63mm deposited, spread and levelled in layers n-exc 15cm thick, watered and rammed to a true surface complete all as specified and directed by Engr-in-charge. |
| 164 | M&L for 75mm thick PCC (1:4:8) type D-2, using 40mm graded stone aggregate as in sub base to floor complete all as specified and directed by Engr-in-charge. |
| 165 | M&L factory made vibro compacted precast cement concrete 60mm thick (strength 300Kg / Sqcm) inter locking matt finish coloured blocks/ pavers (make-Nitco / Hindustan / ULTRA) in shape and colour as directed by Enge-in-Charge, comprising of homogeneous cement plaster mixed with quartz, corborandum and required pigment, laid over cement mortar screed base, joints filled by Jamuna sand, including finishing and compacting the top surface of paver blocks with plate vibrator etc complete all as specified and directed by Engr-in-charge. |
| 166 | M&L for factory made precast PCC kerb stone of size 300mmx300mmx150mm manufactured by M-30 grade of concrete fixed on 75mm thick PCC (1:2:4) using 20mm graded stone aggregate, jointed with cement mortar (1:4) including necessary excavation and returning filling etc complete all as specified and directed by Engr-in-charge. |
| 167 | M&L 25mm thick sand cusion for lying of interlocking tiles complete all as specified and directed by Engr-in-charge. |
| 168 | Removal of demolished / excavated material upto 1.5 Km and deposited where directed. |
| 169 | M&L for providing cement concreter PCC 1:4:8 type D2 using 40 mm graded stone aggregate for foundation complete all as specified and directed by Engr-in-charge. |
| 170 | M&L for brick work with sub class \"B\" bricks straight or curved on plan exceeding 6 m mean radius built in cement mortar 1:4complete all as specified and directed by Engr-in-charge. |
| 171 | M&L for rendering 15 mm thick on other than fair faces of brick onfair faces of brick work in cement mortar 1:4 and Surface finished even and smooth with using extra cement complete all as specified and directed by Engr-in-charge. |
| 172 | Repair/maintenance, and servicing ofPressure Switch including removing, cleaning, greasing, checking for wear and tear, refixing, testing, installing, commissioning as directed by Engineer-In-Charge Pressure Rating :- 0 – 10 Kg/sq.cm. |
| 173 | Repair/maintenance, and servicing ofSolenoid Valve 15 mm dia 230 V AC, including removing, cleaning, greasing, checking for wear and tear, refixing, testing, installing, commissioning as directed by Engineer-In-Charge. |
| 174 | Repair/maintenance, and servicing ofSolenoid Valve 20 mm dia 230 V AC, including removing, cleaning, greasing, checking for wear and tear, refixing, testing, installing, commissioning as directed by Engineer-In-Charge. |
| 175 | Repair/maintenance, and servicing of float type point level sensor 230 V AC, including removing, cleaning, greasing, checking for wear and tear, refixing, testing, installing, commissioning as directed by Engineer-In-Charge. |
| 176 | Repair/maintenance, and servicingof Motorised Butterfly Valve- Size 200mm including removing, cleaning, greasing, checking for wear and tear, refixing, testing, and commissioning complete all as specified and directed by Engr-in-charge. |
| 177 | Repair/maintenance, and servicingof Motorised Butterfly Valve- Size 150mm including removing, cleaning, greasing, checking for wear and tear, refixing, testing, and commissioning complete all as specified and directed by Engr-in-charge. |
| 178 | Repair/maintenance, and servicingof Motorised Butterfly Valve- Size 100mm including removing, cleaning, greasing, checking for wear and tear, refixing, testing, and commissioning complete all as specified and directed by Engr-in-charge. |
| 179 | Repair/maintenance, and servicing excluding spares but including regular maintenance of the PLC and Relay Logic based control panels installed at Airforce Station Tughlakabad including carrying out complete maintenance/serving/repairs as required of all the sub systems viz. PLC based control panels (with all the accessories), breakdown maintenance and replacement of unserviceable parts, refixing of old serviceable parts / new parts if any including the followings and complete all as specified and directed by Engr-in-charge.Equipments:- Automation Panel at Vayusenabad Booster Pump House and at Tech Booster Pump HouseNotes:-(i)The scope of work includes the charges required for removing, repairing, refixing, carrying out electrical termination and fixing/installing, testing, commissioning, etc.(ii) New parts if any shall be paid under separate items as supply only. (iii) In addition to above specific emergency complaints from time to time shall be attended after receiving the same.Note:- The already installed Automation Panel is installed and programmed by M/S Universal Switch Gear Control. It is Commanded that the updating of Automation system should be done through OEM(i.e. M/S Universal Switch Gear Control) or through the authorized service provider of the OEM. The bidder shall be obliged to sign an MOU with the OEM (Universal Switch Gear Control ) for carrying out the maintenance and repair work and a copy of MOU shall be uploaded alongwith application and other connecting documents before quoting the tender and without said documents tender shall be rejected. |
| 180 | Supply, installation in replacement including testing, and commissioning in replacement offloat type point level sensor for Over Head tank with the following specification:- Type:- Magnetic Magnet:- Ring Type Switch:- Reed Switch Connecting cable:- 2 core Teflon |
| 181 | Supply, Installationin replacement including testing and Commissioning in replacement of Flow Switch along with all necessary installation accessories like GI barrel piece, double nipple etc with following specification :-Type:- Pedal Designed Line Pressure:- 150 PSIG |
| 182 | Supply, installationin replacement including testing, and commissioning in replacement ofPressure Transmitterwith proper wiring including necessary power pack for supply of DC :-Power supply: 10-36 V DCEnclosure: whether proof IP 65Process temperature: -30 to 120 CelsiusAccuracy: 0.25 % |
| 183 | Supply and fix in replacement Printed Circuit Board (PCB) for Motorized Butterfly valve of size 100,150,200 mm complete all as specified and directed by Engr-in-charge. |
| 184 | Supply, Installation in replacement including testing and Commissioning in replacement of 150 mm dia, single phase, Motor Actuated Butterfly valve with disc material of CI with nylon coating, hand wheel for manual operation and having 02 nos. limit switches for Open / Close condition and valve position indicator in replacement complete all as specified and directed by Engr-in-charge.The mounting shall be directon valve type.Input Voltage: 230 V, A.C. Designed line pressure: 16 kg/sq cm.In built Serial / USB communication PortIn built data logger with memoryIn built SD CardIn built bluetooth transceiver with capability of pairing with any android based smart phone to download logged data. The mounting shall be indirecttype using specialized extended type arrangement of GI pipe of suitable size/thickness, so that actuator mounting is at least 36 inches above ground level. |
| 185 | All as per item No 140 herein before but for 200mm dia, complete all as specified and directed by Engr-in-charge. |
| 186 | All as per item No 140 herein before but for 100mm dia, complete all as specified and directed by Engr-in-charge. |
| 187 | Supply & fix in replacement of 4 Core 1.5sq.mm. PVC sheathed PVC insulated copper armoured cable complete all as specified and directed by Engr-in-charge. |
| 188 | All as per item No 143 herein before but for 6 Core 1.5 Sqmm, complete all as specified and directed by Engr-in-charge. |
| 189 | S&F in replacement of Limiting switch for butterfy Valve Flanged (ISI) PN-1.6 of siz 200mm dia, complete all as specified and directed by Engr-in-charge. |
| 190 | All as above item No: 145 but for 150mm dia complete all as specified and directed by Engr-in-charge. |
| 191 | All as above item No: 145 but for 100mm dia complete all as specified and directed by Engr-in-charge. |
| 192 | S&F in replacement of Solenoid (Device) for Pneumatic Actuator 15/20mm dia complete all as specified and directed by Engr-in-charge. |
| 193 | S&F in replacement of Limit Switch (Position Indicator) complete all as specified and directed by Engr-in-charge. |
| 194 | M&L for welding of MS Flange in MS pipe for butterfly valve of pipe size upto 200mm dia, complete all as specified and directed by Engr-in-charge. |