| 1 | Excavation in trenches n. exc. 1.5 mtr in wide and n. exc. 1.5 mtr in depth for laying of underground cable and getting out in soft/loose soil complete all as specified and directed by Engr-in-Charge. |
| 2 | Description all as per Srl item No.1 here in before but depth exceeding 1.5m but not exceeding 3m complete all as specified and directed by Engr-in-Charge. |
| 3 | Returning, filling in excavated soil in trenches including spreading, leveling, watering and well rammingin layers n. exc. 25 cm thick complete all as specified and directed by Engr-in-Charge. |
| 4 | Removing of excavted soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engr-in-Charge. |
| 5 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system,dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs areto busbar spadles to fitted complete panelheight 1000mm, Width 800 mm, Depth 600 mm,base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete with followingpanel should be 61439 part I&II & should be Foem 3 B all MCCB should be Extendable Rom will speady teeming will on/off trip :-Incoming:-(a)MCCB 160 A4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-01 No. |
| 6 | Outgoing:- (a) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 300 Amp,4 pole, not less than 75 cmlong mounted on insulators 01 set.Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work.(ii) Panels shall be placed above 0.6 mtr from ground level.(iii) Outgoing MCCBs shall be fed with solid busbar connectors.(iv) Cables shall be terminated using gun metal /SS glands. (v) includingsuitable thimbles/lugs, nut bolts ,washersfitted the cables.(v) cable glands for incomingand out going suitable cables is including rate quated by vendor. |
| 7 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system,dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs areto busbar spadles to fitted complete panelheight 1000mm, Width 800 mm, Depth 600 mm,base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete with followingpanel should be 61439 part I&II & should be Foem 3 B all MCCB should be Extendable Rom will speady teeming will on/off trip :-Incoming:-(a)MCCB 160 A4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-01 No.(b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 240 Amp,4 pole, not less than 75 cm long mounted on insulators 01 set. |
| 8 | Outgoing:- ( a) MCCB100 A 4 pole ,Ics=100%Icu- 25 KA, 415 Volts,with thermal adjustable and fixed magnetic setting with extended terminals-01 No.( b) MCCB 63 A 4 pole ,Ics=100%Icu- 35/36 KA, 415 Volts,with thermal adjustable and fixed magnetic setting with extended terminals-02 No. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work.(ii) Panels shall be placed above 0.6 mtr from ground level.(iii) Outgoing MCCBs shall be fed with solid busbar connectors.(iv) Cables shall be terminated using gun metal /SS glands.(v) includingsuitable thimbles/lugs, nut bolts ,washersfitted the cables.(v) cable glands for incomingand out going suitable cables is including rate quated by vendor. |
| 9 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system,dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs areto busbar spadles to fitted complete panelheight 1000mm, Width 800 mm, Depth 600 mm,base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete with followingpanel should be 61439 part I&II & should be Foem 3 B all MCCB should be Extendable Rom will speady teeming will on/off trip :-Incoming:-( a) MCCB160 A 4 pole ,Ics=100%Icu- 25 KA, 415 Volts,with thermal adjustable and fixed magnetic setting with extended terminals-01 No. (b) Bus bar electrolytic grade Copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 200 Amp,4 pole - 01 set. |
| 10 | Outgoing :-(a) MCCB 100 amps 4 pole ,Ics=100%Icu- 25/26 KA, 415 Volts,with thermal adjustable and fixed magnetic setting with extended terminals-01 No.(b) MCCB63 amps 4 pole ,Ics=100%Icu- 25/26 KA, 415 Volts,with thermal adjustable and fixed magnetic setting with extended terminals-02 No. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work.(ii) Panels shall be placed above 0.6 mtr from ground level.(iii) Outgoing MCCBs shall be fed with solid busbar connectors.(iv) Cables shall be terminated using gun metal /SS glands.(v) includingsuitable thimbles/lugs, nut bolts ,washersfitted the cables.(v) cable glands for incomingand out going suitable cables is including rate quated by vendor. |
| 11 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system,dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs areto busbar spadles to fitted complete panelheight 800 mm, Width 800 mm, Depth 600 mm,base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete with followingpanel should be 61439 part I&II & should be Foem 3 B all MCCB should be Extendable Rom will speady teeming will on/off trip:-Incoming :-( a) MCCB 100 A 4 pole ,Ics=100%Icu- 25/26 KA, 415 Volts,with thermal adjustable and fixed magnetic setting with extended terminals-01 No. |
| 12 | Outgoing :-(a) Bus bar electrolytic grade Copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 200 Amp,4 pole - 01 set.Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work.(ii) Panels shall be placed above 0.6 mtr from ground level.(iii) Outgoing MCCBs shall be fed with solid busbar connectors.(iv) Cables shall be terminated using gun metal /SS glands.(v) includingsuitable thimbles/lugs, nut bolts ,washersfitted the cables.(v) cable glands for incomingand out going suitable cables is including rate quated by vendor. |
| 13 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system,dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs areto busbar spadles to fitted complete panelheight 800 mm, Width 800 mm, Depth 600 mm,base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete with followingpanel should be 61439 part I&II & should be Foem 3 B all MCCB should be Extendable Rom will speady teeming will on/off trip:-Incoming :-( a) MCCB 63 A 4 pole ,Ics=100%Icu- 25/26 KA, 415 Volts,with thermal adjustable and fixed magnetic setting with extended terminals-01 Nos. |
| 14 | Outgoing :-(a) Bus bar electrolytic grade Copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 150 Amp,4 pole - 01 set.Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work.(ii) Panels shall be placed above 0.6 mtr from ground level.(iii) Outgoing MCCBs shall be fed with solid busbar connectors.(iv) Cables shall be terminated using gun metal /SS glands.(v) includingsuitable thimbles/lugs, nut bolts ,washersfitted the cables.(v) cable glands for incomingand out going suitable cables is including rate quated by vendor. |
| 15 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system,dust and vermin proof, made of2 mm CRCA MS sheet with Bus bar electrolytic grade Aland supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 200Amp,4 pole spadles to fitted complete base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hingedwith aprons for cable entryand locking arrangement complete all as specified and directed by Engr-in-Charge. |
| 16 | S&F in replacement MCCB 4 pole, Ics=100%Icu- 35/36 KA, 415 Volts, 200 Amps ,with thermal adjustable and fixed magnetic setting with extended terminals complete all as specified and directed by Engr-in-Charge. |
| 17 | S&F in replacement MCCB 4 pole, Ics=100%Icu- 35/36 KA, 415 Volts, 160 Amps ,with thermal adjustable and fixed magnetic setting with extended terminals complete all as specified and directed by Engr-in-Charge. |
| 18 | S&F in replacement MCCB 4 pole, Ics=100%Icu- 35/36 KA, 415 Volts, 250 Amps ,with thermal adjustable and fixed magnetic setting with extended terminals complete all as specified and directed by Engr-in-Charge. |
| 19 | S&F in replacement MCCB 4 pole, Ics=100%Icu- 25/26 KA, 415 Volts, 100 Amps,with thermal adjustable and fixed magnetic setting with extended terminals complete all as specified and directed by Engr-in-Charge. |
| 20 | S&F in replacement MCCB 4 pole, Ics=100%Icu- 35/36 KA, 415 Volts, 320 Amps ,with thermal adjustable and fixed magnetic setting with extended terminals complete all as specified and directed by Engr-in-Charge. |
| 21 | S&FLED Streetlight 60 watt made uppressure diecast aluminium housing with toughned glass and high power leds and secondary lens with IP 66 protection system of efficasy >110 LPW including 10 KV SPDincluding taking down old UNSV Streetlights complete all as specified and directed by Engr-in-Charge. |
| 22 | GI pipe bracket Suitable size of light single swan neck shape suitable to fix on top of tubular pole complete with clamps, nuts, bolts and washers, complete all as specified and directed by Engr-in-Charge. |
| 23 | S&F of Steel tubular swaged poles erected to truly vertical or planted as strut complete with 6 mm thick mild steel base plate, welded to Pole, B-118 finial taper cap, bolts, nuts and screws, poles made out of ERW MS tubing conforming to IS-2713 Part-II type 410-SP-31 (9m long) including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bituminous paint on the and portion embedded in concrete, making five black and white bands at lower portion of pole above ground level/coping each300 mm wide alternately and marking pole number. with black paint at suitable height complete all as specified and directed by Engr-in-Charge. |
| 24 | S&F of Steel tubular swaged poles erected to truly vertical or planted as strut complete with 6 mm thick mild steel base plate, welded to Pole, B-118 finial taper cap, bolts, nuts and screws, poles made out of ERW MS tubing conforming to IS-2713 Part-II type 410-SP-31 (12 m long) including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bituminous paint on the and portion embedded in concrete, making five black and white bands at lower portion of pole above ground level/coping each300 mm wide alternately and marking pole number. with black paint at suitable height complete all as specified and directed by Engr-in-Charge. |
| 25 | S&Fthermoplastic, polystyrene unbreakable junction box size 260 x 210 x 116 mm suitable for pole mounted outdoor type IP 65 insulated complete with FI clamp & nut, bolts, washers and including phase seperator between R, Y, B terminals and one MCB SP 6 amp 10 KA, all duly mounted on din cannel, cable glands for cable entry complete all as specified and directed by Engr-in-Charge. |
| 26 | Material and labour in replacement of PVC insulated multi stranded copperconductor PVC cable sheathed 2.5 sqmm 3 coreand making connections of streetlight fittings and bollards lights complete all as specified and directed by Engr-in-Charge. |
| 27 | S&F inLED flood lightwith lens 150 watt made uppressure diecast aluminium housing with toughned glass and high power leds and secondary lens with IP 66 protection system of efficasy >110/125LPW including 10 KV SPDincluding taking down old UNSV Streetlights complete all as specified and directed by Engr-in-Charge. |
| 28 | S&F in replacement of automatic street light control switch of 8 KW three phase using Infrared sensor based Nature Switch for automatic switching of street light. Nature switch operation should be based on Natural Light Lux*level. Reqd illuminance level also have part night operation facility for min 4 hrs to max 12 hrs. The sensor along with suitabe rating power contractor (s), one Incoming and three Outgoing MCBs rating of 20-32 Amps & main load circuit wiring (copper) of min 10 sqmm should be enclosed in a pole/wall mountable rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonate enclosure conforming to IP66 protection class-2 (Hansel make). The circuit should be also have provision for manual operation (i.e. sensor by pass option) complete all as specified and directed by Engr-in-Charge. |
| 29 | Supply and Laying and fixing in replacement of along the poles or passing through pipes or laid under floor of through walls etc jointing and testing LTCross Linked Polythene Insulated (XLPE insulated) galvanized steel striparmoured electric cable 1100volt grade heavy duty size of185 sqmm 3.5 core, ISI marked with aluminium conductor and overall served with an outer sheath of PVC, of cross sectional area as under including taking out old UNSV LT cables:-Note :Excavation, earthwork, Pipe for cable protection to be measured and paid for separately. |
| 30 | All as per serial item No 24.00 here-in-before but of size 120 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 31 | All as per serial item No 24.00 here-in-before but of size 95 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 32 | All as per serial item No 24.00 here-in-before but of size 50 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 33 | All as per serial item No 24.00 here-in-before but of size 35 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 34 | All as per serial item No 24.00 here-in-before but of size 25 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 35 | All as per serial item No 24.00 here-in-before but of size 16 Sqmm 4 core complete all as specified and directed by Engr-in-Charge. |
| 36 | All as per serial item No 24.00 here-in-before but of size 16 Sqmm 2 core complete all as specified and directed by Engr-in-Charge. |
| 37 | All as per serial item No 24.00 here-in-before but of size 10 Sqmm 2 core complete all as specified and directed by Engr-in-Charge. |
| 38 | S&F in replacement of LED bollard with robust design and efficient garden lights Whistling Oyster/LB12of 11 watt capacity, IP65 including taking down old UNSV garden lights complete all as specified and directed by Engr-in-Charge. |
| 39 | Supply and fix LEDwarm white Post Toplight fitting 40watts, IP66, Energy Saving LED light with PDC , Aluminium body & secondary Optical lens for superior light distrubution , Efficacy > 110 Lm/W. 5700k, complete all as specified and directed by Engr-in-Charge. |
| 40 | Supply & fixing or laying galvanised steel tubing light grade80 mm dia (ISI marked) for protection of under ground cable on poles / walls under road crossing etc of following sizes includingdismantling & taking down existing pipe complete all as specified and directed by Engr-in-Charge. |
| 41 | M&L forRoad cutting/ boring of existing road/path for laying of GI pipe protection for UG cable including making good distrurbed area/surface complete all as specified and directed by Engr-in-Charge. |
| 42 | M & L for providing earthing with GI earth plate electrode 600 X 600 X 6mm buried directly in ground (earth pit not less than 2.25M deep below ground level ) with top edge of the earth plate not less than 1.5M below ground level connected to GI strip 25 x 4 mm thick for earthing lead fixed by means of nuts,bolt,washers etc connected to earth test point complete all as specified in electrical plate NO 3 of SSR1996 part 1 ,including necessary excavation and earth work in any strata of soil,comman salt, charcoal dust, 40 mm dia light grade GI pipe for protection to earth lead, GI water pipe20mm dia with funnel &wire mesh , PCC pit with CI cover and frame etc all as specified and directed by Engineer-in-charge. Note:- All the joints shall be made with welding to get proper conductivity.Note:On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire complete all as specified and directed by Engr-in-Charge. |
| 43 | S&F double walled corrugated (DWC) pipe of size 90 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of HT/LT cable in under ground complete all as specified and directed by Engr-in-Charge. |
| 44 | S&F double walled corrugated (DWC) pipe of size 50 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of HT/LT cable in under ground complete all as specified and directed by Engr-in-Charge. |
| 45 | Ring suitable for 12 m long pole for semi highmast light and for fixing of six nos flood lights with bolts, nits and screws, ring made out of ERW MS tubing confirming to IS-2713 including drilliing of holes of required size for fixing of brackets, painting the exposed surfaces of ring with coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of silver paint on the surfacecomplete all as specified and directed by Engr-in-Charge. |
| 46 | M&L Plain cement concrete 1:3:6 type C-2 as in foundations filling and mass concrete using 40 mm graded stone aggregate complete all as specified and directed by Engr-in-Charge. |
| 47 | M&L Plain cement concrete 1:2:4 type B-1 using 20 mm graded stone aggregate for coping of poles incl dismantling of old broken PCC foundation complete all as specified and directed by Engr-in-Charge. |