|
| 1 | Dismantling and removing and setting aside PCC pole / struts any type by breaking PCC foundation after disconnecting electrical connection including site clearance complete all as specified and as directed by Engineer-in-Charge. |
| 2 | Material and labour for steel swagged poles complete poles 9 metre long complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-31 with one coat of red oxide primer and two coats of aluminium paint and including marking alternate 5 no\"s black and white strip 30 cm height with two coats of synthetic paint over a coat of primer including preparation of new surfaces complete all as specified and as directed. |
| 3 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in soft / loose soil or hard / dense soil for taking up or laying of cable complete all as specified and as directed. |
| 4 | Description all as per Ser item No 3.00 here-in-before but depth exceeding 1.5 m and not exceeding 3.0 m complete all as specified and as directed. |
| 5 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cms complete all as specified and as directed. |
| 6 | Removing excavated material not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above starting point complete all as specified and as directed. |
| 7 | Supplying and laying including replacement of bricks common burnt clay sub class \"B\" old size for cable protection complete all as specified and as directed. |
| 8 | Supply and laying dry river sand laid in trenches as cable cushioning and covering. Sand cushioning to underground electric cable 8cm before laying and 15cm after laying the cable in trenches complete all as specified and as directed. |
| 9 | Material and labour for PCC (1:4:8) type D-2 (using 40mm graded crushed stone aggregate) mechanically crushed stone for mass filling in pole, pit and foundation etc including provision of necessary formwork to achieve fair finished surfaces complete all as specified and as directed. |
| 10 | Material and labour for PCC (1:3:6) type C-2 (using 40 mm graded crushed stone aggregate) as in pole foundation, stay pits etc including provision of necessary formwork to achieve fair finishes surfaces complete all as specified and as directed. |
| 11 | Material and labour for PCC (1:2:4) type C-2 (using 20 mm graded crushed stone aggregate) as in pole foundation, coping etc including provision of necessary formwork to achieve fair finishes surfaces complete all as specified and as directed. |
| 12 | Disconnecting and taking out defective underground cable any size and any type from trenches, pole, pipe, floor, wall etc complete all as specified and as directed. |
| 13 | Material and labour for LT underground cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade cross-sectional area 16 Sqmm, 2 core complete all as specified and as directed. |
| 14 | Material and labour for LT underground cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade cross-sectional area 10 Sqmm, 4 core complete all as specified and as directed. |
| 15 | Material and labour for LT underground cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade cross-sectional area 16 Sqmm, 4 core complete all as specified and as directed. |
| 16 | Material and labour for LT underground cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade cross-sectional area 25 Sqmm, 4 core complete all as specified and as directed. |
| 17 | Supply and fixing indoor / outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 / 4.0 x 10-25 Sqmm complete all as specified and as directed by Engineer-in-Charge. |
| 18 | Material and labour in replacement of PVC insulated and sheathed cable of size 1.5 Sqmm 3 core copper conductor multistranded 1100 Volts grade 230 volts running through PVC conduit of dia 20 mm with strip clamping on poles at 3 places complete all as specified and as directed by Engineer-in-Charge. |
| 19 | Material and labour for fixing in replacement of GI tubing 50 mm bore light grade, on poles, on walls, under floors, road crossing, as required at site complete all as specified and as directed by Engineer-in-Charge.Note: - Clamps, Nut, bolts, saddle etc will be measured and paid separately. |
| 20 | Supply and fixing in repair Off load change over switch with sheet steel enclosure 415 V, 4 pole, 100 Amps capacity fixed on walls for electric supply distribution between main and DG set including necessary connection of cables from LT panels to change over switches complete all as specified and as directed by Engineer-in-Charge. |
| 21 | Supply and fixing in repair Off load change over switch with sheet steel enclosure 415 V, 4 pole, 200 Amps capacity fixed on walls for electric supply distribution between main and DG set including necessary connection of cables from LT panels to change over switches complete all as specified and as directed by Engineer-in-Charge. |
| 22 | Supply and fixing in replacement MCCB TPN 200 Amps, 415 Volts, 25 KA, 4 Pole, Ics=100% Icu, overload adjustable short circuit fixedtype including complete connection complete all as specified and as per directions of Engineer-in-Charge. |
| 23 | Supply and fixing in replacement MCCB TPN 160 Amps, 415 Volts, 25 KA, 4 Pole, Ics=100% Icu, overload adjustable short circuit fixedtype including complete connection complete all as specified and as per directions of Engineer-in-Charge. |
| 24 | Supply and fixing in replacement MCCB TPN 100 Amps, 415 Volts, 25 KA, 4 Pole, Ics=100% Icu, overload adjustable short circuit fixedtype including complete connection complete all as specified and as per directions of Engineer-in-Charge. |
| 25 | Supply and fixing and fabrication including replacement of street light bracket made out of GI tubing suitable for 45/60/90 watt LED light grade upto 1.2 metre length, bend to shape suitable for security light fitting with necessary mild steel clamps with one coat of red oxide and two coats of aluminium paint including nut, bolt, washers etc and including taking out unserviceable bracket and removing from site of work complete all as specified and as directed. |
| 26 | Labour for repair / maintenance to old / unserviceable LED security / street / flood light of any capacity including taking down existing fitting from pole / building for repair of driver, cable terminal block and connection wire and refixing the same in position after repair including testing complete all as specified and as directed by Engineer-in-Charge.Note: Spares shall be measured and paid separately under respective item. |
| 27 | Taking down unserviceable street / security light fitting of any type from the pole / building after disconnecting electric connection carefully for replacement of drivers complete all as specified and as directed.Note: - Repair / replacement of spares shall be measured separately. |
| 28 | Supply and fixing in replacement of electronic driver of capacity 45 watt of existing make for LED street light fitting complete all as specified and as directed by Engineer-in-Charge. |
| 29 | Supply and fixing in replacement of electronic driver of capacity 60 watt of existing make for LED street light fitting complete all as specified and as directed by Engineer-in-Charge. |
| 30 | Supply and fixing in replacement of electronic driver of capacity 90 watt of existing make for LED street light fitting complete all as specified and as directed by Engineer-in-Charge. |
| 31 | Supply and fixing in replacement of electronic driver of capacity 120 watt of existing make for LED street light fitting complete all as specified and as directed by Engineer-in-Charge. |
| 32 | Supply and fixing in replacement of electronic driver of capacity 200 watt of existing make for LED flood light fitting complete all as specified and as directed by Engineer-in-Charge. |
| 33 | Dismantling and taking down old unserviceable street / security lights and material and labour for new LED street light fittings of 30 watt, suitable for upto 50 mm outer dia holder fixed on existing pole, system wattage and high pressure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66 protection suitable for pole mounting SMD LED array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 110 Lm/W, 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor >0.95, working temperature range - 20º C to 60º C, built in surge protection more than 10 KV with facility of power supply shall be removed without removing light fitting from pole complete all as specified and as directed. |
| 34 | Dismantling and taking down old unserviceable street / security lights and material and labour for new LED street light fittings of 45 watt, suitable for upto 50 mm outer dia holder fixed on existing pole, system wattage and high pressure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66 protection suitable for pole mounting SMD LED array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 110 lm/W, 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor >0.95, working temperature range - 20º C to 60º C, built in surge protection more than 10 KV with facility of power supply shall be removed without removing light fitting from pole complete all as specified and as directed. |
| 35 | Dismantling and taking down old unserviceable street / security lights and material and labour for new LED street light fittings of 60 watt, suitable for upto 50 mm outer dia holder fixed on existing pole, system wattage and high pressure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66, TOP opening separate driver compartment with frame, suitable for pole mounting SMD LED array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 110 lm/W, 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor >0.95, working temperature range - 20º C to 60º C, built in surge protection more than 10 KV with facility of power supply shall be removed without removing light fitting from pole complete all as specified and as directed. |
| 36 | Dismantling and taking down old unserviceable street / security lights and material and labour for new LED street light fittings of 90 watt, suitable for upto 50 mm outer dia holder fixed on existing pole, system wattage and high pressure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66, TOP opening separate driver compartment with frame, suitable for pole mounting SMD LED array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 110 lm/W, 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor >0.95, working temperature range - 20º C to 60º C, built in surge protection more than 10 KV with facility of power supply shall be removed without removing light fitting from pole complete all as specified and as directed. |
| 37 | Dismantling and taking down old unserviceable street / security lights and material and labour for new LED street light fittings of 120 watt, suitable for upto 50 mm outer dia holder fixed on existing pole, system wattage and high pressure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66, TOP opening separate driver compartment with frame, suitable for pole mounting SMD LED array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 110 lm/W, 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor >0.95, working temperature range - 20º C to 60º C, built in surge protection more than 10 KV with facility of power supply shall be removed without removing light fitting from pole complete all as specified and as directed. |
| 38 | Dismantling and taking down old unserviceable street / security lights and material and labour for new LED flood light fittings of 120 watt system wattage and high pressure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66 protection suitable for pole mounting SMD LED array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 90 lm/W, 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor >0.95, working temperature range - 20º C to 60º C, built in surge protection more than 10 KV with facility of power supply shall be removed without removing light fitting from pole complete all as specified and as directed. |
| 39 | Dismantling and taking down old unserviceable street / security lights and material and labour for new LED flood light fittings of 200 watt system wattage and high pressure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66 protection suitable for pole mounting SMD LED array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 90 lm/W, 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor >0.95, working temperature range - 20º C to 60º C, built in surge protection more than 10 KV with facility of power supply shall be removed without removing light fitting from pole complete all as specified and as directed. |
| 40 | Material and labour for LT feeder pillar box size (1.0 X 1.0 X 0.6 metre) having thickness of 3.15mm and inner shell made out of 2mm thick mild steel sheet and mild steel angle section 50 x 50 x 6 mm mounted on PCC (1:2:4) type B-1 platform 60 cm above and 45 cm below the ground level, frame factory fabricated with front openable double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable / openable by keys having chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricated followed by powder coat painting with suitable gasket to make it dust/vermin proof and general construction confirming to IS:8623/93 complete all as specified and as directed. Details of MCCB/MCBs are as follows: -Incoming: - (a) MCCB, 160 Amps, 4 Pole, 415 V, 16 KA - 01 Each, Al busbar of capacity 200 Amps - Set of three.Outgoing: - (b) MCCB, 63 Amps, 4 Pole, 415 V, 10 KA - 03 Each.(c) Digital Ammeter 0-400 A of size 96 Sqmm with selector switch - 01 No.(d) Digital Volt meter 0-500 V of size 96 Sqmm with selector switch - 01 No.(e) Indicator Lamp RYB 22.5mm dia LED type 240 volts AC.(f) CT coils of suitable ratio - 01 Set. |
| 41 | Supply and fixing SMC Pole mounted box of size 10\" x 8\" x 4\" with hinged door including clamp, nuts, bolts and washers complete all as specified and as directed and including taking down of old unserviceable junction boxes. The Box includes: -(a) MCB single pole 10 Amp, 10 KA \"C\" series mounted on din rail - 1 No.(b) Connector block suitable for 3 phase, 4 wire minimum 16 Sqmm cable - 1 No. |
| 42 | Dismantling and taking down unserviceable earthing and material and labour for earthing complete with galvanized steel earth electrode plate of size 60 x 60 x 6mm thick buried directly in ground / earth pit not less than 2.25 metre deep below normal ground level and top edge of earth electrode not less than 1.5 metre below normal ground level and connected with GI earth strip of size 25x4mm by means of nut, bolts, washers etc to equipment / machinery all as shown in electric plate No 3 of SSR Part - I including PCC (1:3:6) pit, pit cover 50mm thick RCC (1:2:4) type B-1 using 8mm for steel bars @10cm centre to centre both ways, 40mm bore medium grade GI protection pipe, watering pipe 20mm bore medium grade, funnel, wire mesh, also including earth work, common salt, charcoal dust complete all as specified and as directed by Engineer-in-Charge. |