| 1 | S&F for cross arms, bracings, supports, clamps (including stay clamps, clamps for fixing GI tubes for passing through of cables) and back plates fabricated out of standard steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size as directed and inclusive of providing two coats of aluminum paint over a coat of primer after preparation of steel surfaces including taking down old unserviceable cross arms complete all as specified and directed. |
| 2 | S&F for Aluminium conductor steel reinforced (ACSR) of any description including stretching on overhead line on LT poles to required sag and binding with aluminium binding wire to insulators including jumpering the OH line jointingafter dismantling of old unserviceable over head ACSR conductor of any type and size inlcuding all clamps, jumpering etc and kept in safe custody for reuse of serviceable ACSR etc complete all as specified and directed. |
| 3 | M&L for Shackle type, porcelain viterous white, brown or green insulator working pressure 1100 volts, 75mm height and 90mm dia including one glavanised mild steel straps 31x3mm wide and 12mm dia bolts, washer and nuts after dismantling of old unserviceable shackle type insulator complete all as specified and directed. |
| 4 | S&F for Pin type, porcelain viterous white, brown or green insulator including one glavanised mild steel spindle, two galvanised iron washer and one galvanised iron nut, 50mm height, 65 mm dia for 1100 volts grade after dismantling of old unserviceable pin type insulator complete all as specified and directed. |
| 5 | S&F for stay assembly comprising of 300mmx300xx6mm thick galvanised mild steel stay plate galvanised stay rod of 20mm dia 1800mm long galnanised thimble stay, rod alongwith and fixed with 7/3.15mm stranded stay nuts and washers as shown on electrical plate NO 1 on SSR Part-I including stay wire galvanaised stranded 7/3.15mmafter dismantling of old unserviceable stay assembly including stay wire complete with necessary demolition of concrete, excavation and earth work as required and removing the same from site complete as specified and directed.(Note - Cost of loop type insulators, stay wire clamp with nuts and washers, excavations, earth work and PCC will include in this item) |
| 6 | Supply,laying, jointing and testing,XLPE insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 10 sqmm 2 core laid in trenches, ducts, pipes, on poles and connection with necessary cables lugs, glands nut bolts complete after taking down old unserviceable cable all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 7 | Supply,laying, jointing and testing,XLPE insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 16 sqmm 2 core laid in trenches, ducts, pipes, on poles and connection with necessary cables lugs, glands nut bolts complete after taking down old unserviceable cable all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 8 | Supply,laying, jointing and testing,XLPE insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 25 sqmm 4 core laid in trenches, ducts, pipes, on poles and connection with necessary cables lugs, glands nut bolts complete after taking down old unserviceable cable all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 9 | Supply,laying, jointing and testing,XLPE insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 35 sqmm 3.5 core laid in trenches, ducts, pipes, on poles and connection with necessary cables lugs, glands nut bolts complete after taking down old unserviceable cable all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 10 | Supply,laying, jointing and testing,XLPE insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 50 sqmm 3.5 core laid in trenches, ducts, pipes, on poles and connection with necessary cables lugs, glands nut bolts complete after taking down old unserviceable cable all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 11 | Supply,laying, jointing and testing,XLPE insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 95 sqmm 3.5 core laid in trenches, ducts, pipes, on poles and connection with necessary cables lugs, glands nut bolts complete after taking down old unserviceable cable all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 12 | Supply,laying, jointing and testing,XLPE insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 120 sqmm 3.5 core laid in trenches, ducts, pipes, on poles and connection with necessary cables lugs, glands nut bolts complete after taking down old unserviceable cable all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 13 | Supply,laying, jointing and testing,XLPE insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 240 sqmm 3.5 core laid in trenches, ducts, pipes, on poles and connection with necessary cables lugs, glands nut bolts complete after taking down old unserviceable cable all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 14 | Supply,laying, jointing and testing,XLPE insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 16 sqmm 4 core laid in trenches, ducts, pipes, on poles and connection with necessary cables lugs, glands nut bolts complete after taking down old unserviceable cable all as specified and directed.(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). |
| 15 | M&L for 40mm dia galvanized steel tubing (light grade) with complete all fittings such as elbow, unions, nipples, tees, bends, short pieces, connections, check-nuts, caps, plugs, diminishing pieces and flanges etc as in pole, crossing of roads, laid in trenches, fixed on walls for cable protection including taking down old GI pipe complete all as specified and directed. |
| 16 | M&L for 50mm dia galvanized steel tubing (light grade) with complete all fittings such as elbow, unions, nipples, tees, bends, short pieces, connections, check-nuts, caps, plugs, diminishing pieces and flanges etc as in pole, crossing of roads, laid in trenches, fixed on walls for cable protection including taking down old GI pipe complete all as specified and directed. |
| 17 | M&L for steel tubular swaged poles errected to truly vertical position with 6mm thick mild steel base plate of size 300mm x300mm, welded to Pole, B-118 finial taper plug, bolts, nuts and screws, poles made out of ERW MS tubing conforming to IS-2713 Part-II, type 410-SP-31 (9m long) including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bituminous paint internally and portion embedded in concrete, making five black and white bands at lower portion of pole each 300mm wide at 300mm spacing alternately and marking pole number. with black paint at suitable height including taking down old unserviceable broken steel pole of 9 mtr long complete all as specified and directed.(Note :- Necessary excavation of earth work, removing, returning filling in, PCC foundations of poles, coping etc shall be measured and paid separately) |
| 18 | M&L for PCC 1:4:8 (nominal mix) type D-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete of poles and stay/installation paths complete all as specified and directed. |
| 19 | M&L for plain cement concrete type C-1 , 1:3:6 (using 20mm graded stone aggregate) as in poles foundation including necessary form work complete all as specified and directed. |
| 20 | M&L for plain cement concrete type B-1 , 1:2:4 (using 20mm graded stone aggregate) as in coping of poles, benching, hold fasts, water troughs, bed block and the like including weathering, slightly rounded or chamfered angles and throating including necessary form work complete all as specified and directed. |
| 21 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth not exceeding 10sqm on plan for laying of cable and foundation of poles stays and getting out in soft / loose soil complete all as specified and directed. |
| 22 | All as per Srl item No 19.00 here-in-before but exceeding 1.5 m and not exceeding 3 m in depth and getting out in soft / loose soil complete all as specified and directed. |
| 23 | Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cm (soil) thickness all as specified and directed. |
| 24 | Removing of excavated material (soil) to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 25 | M&L for dry sand cushioning to underground cable, provided with a layer 8 cm thick before and 15 cm deep after laying and stretching jointing and testing the cable complete all as specified and as directed.(Note: Punned thickness of sand shall be measured and paid). |
| 26 | M&L for brick covering with width equal to length of brick as mechanical protection to cable using sub class ‘B’ bricks laid flat,size 230mm x 115mmx 75mm, complete all as specified and as directed. |
| 27 | M&L for complete removal of existing paint by scraping from the steel tubular swaged pole of 9 mtr height without removing accessories and preparation of surfaces for repainting the poles with and including two coats of synthetic enamel paint upt 1.50mtr height having alternative white and black strips of 30cm height each, including one coat of aluminium paint to the remaining part of pole (i.e above 1.50 mtr height) and its corss arms bracing, support and all steel members complete etc all as specified and directed. |
| 28 | Restretching of existing ACSR conductor on LT overhead line of any size and type of span of 1x5 Nos of conductor wires, length 40 to 50mtr approximate of each span including 1run of GI earth wire 4mm dia and including making the jumpher connections and including taking shut down in writing with all safety measure as per electric rule complete all as directed by the Engineer-in-Charge.(Note :- Materials/T&P like, gloves, safety harness etc. and the like will be provided by the contractor without any extra cost) |
| 29 | Supply, Laying, connecting and testing in replacement of service cable of size 10 Sqmm 2 core 1100 volts grade heavy duty cable PVC insulated stranded alumn conductor, served with an inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 mtr apart including 4mm suspension wire or drawn in and including medium grade non metallic rigid PVC conduit as per site requirement, flat or circular including taking out old unserviceable service cable with GI wire complete all as specified and directed. |
| 30 | Cutting/trimming of tree branches upto 100mm thick under OH HT/LT electric line including cleaning upto 1.5.00 mtr horizontal distance on both sides of OH electric line from ground level of the poles including removing all creepers small bushes etc of under OH line upto 60 mtr each sapn and depositing the cut branches upto 50mtr from the pole including taking shut down in writing with all safety measure as per electric rules complete all as directed by Engineer-in-Charge.(Note :- Materials/T&P like Axes, rope, gloves,safety harness etc. and the like will be provided by the contractor without any extra cost ) |
| 31 | S&F for MCCB 400 Amps four pole adjustable thermal and magnetic setting type,36 KA breaking capacity, 415 volts, 50 Hz including taking down old unserviceable MCCB any make and provision of suitable size of lugs for existing cable complete as in repair all as specified and directed. |
| 32 | S&F for MCCB 320 Amps four pole adjustable thermal and magnetic setting type,36 KA breaking capacity, 415 volts, 50 Hz including taking down old unserviceable MCCB any make and provision of suitable size of lugs for existing cable complete as in repair all as specified and directed. |
| 33 | S&F for MCCB 200 Amps four pole adjustable thermal and magnetic setting type, 36 KA breaking capacity, 415 volts, 50 Hz including taking down old unserviceable MCCB any make and provision of suitable size of lugs for existing cable complete as in repair all as specified and directed. |
| 34 | S&F for MCCB 160 Amps four pole adjustable thermal and magnetic setting type,25 KA breaking capacity, 415 volts, 50 Hz including taking down old unserviceable MCCB any make and provision of suitable size of lugs for existing cable complete as in repair all as specified and directed. |
| 35 | S&F for MCCB 125 Amps three pole adjustable thermal and magnetic setting type,16 KA breaking capacity, 415 volts, 50 Hz including taking down old unserviceable MCCB any make and provision of suitable size of lugs for existing cable complete as in repair all as specified and directed. |
| 36 | S&F for MCCB 100 Amps three pole adjustable thermal and magnetic setting type,16 KA breaking capacity, 415 volts, 50 Hz including taking down old unserviceable MCCB any make and provision of suitable size of lugs for existing cable complete as in repair all as specified and directed. |
| 37 | S&F for MCCB 63 Amps three pole adjustable thermal and magnetic setting type,16 KA breaking capacity, 415 volts, 50 Hz including taking down old unserviceable MCCB any make and provision of suitable size of lugs for existing cable complete as in repair all as specified and directed. |
| 38 | S&F for three phase 4 wire secure prodigy bidirectional meter of capacity 40 to 200 amp suitable for KVARH, KVAH, KW, KVA, complete all as specified and directed. |
| 39 | M&Lfor earthing complete with galvanised steel earth plate electrode 600x600x6mm thick burried directly in ground earth pit not less than 2.25m deep below ground level with top edge of the plate not less than 1.5m deep below normal ground levelconnected to and including 25X4mm thick galvanised iron strip by means ofbolts, nuts, checknuts and washers of galvanised iron or steel all as specified in electrical plate No 3 of SSR (2009) part-I including 40mm bore GI pipe light grade for protection of earth strip and PCC 1:2:4 type B-1 as in pit, Precast RCC earth pit cover 8 cm thick reinforced with 8mm dia TMT bars @150mmc/c and two handles, excavation and earth work in any type of soil and alternate layers of charcoal, common salt and 20mm bore galvanised medium grade steel tubing for watering with one end fixed with cast iron funnel and wire mesh and testing on completion complete after dismantling of old unserviceable earthing with all material etc all as specified and directed.(Note:-Earthwork, Earth strip and protection pipe upto board is included in the rate quoted) |
| 40 | Supply , install, testing and commissioning of factory made bus bar chamber panel of size 600mmx 900mmx350mm ( CPRI approved) out door type 3.15 mmwith 4 strips 400 Amps bus bar aluminium, with MCCB of 100 Amp, FP, 16 KA adjustable type duly connected to aluminium strip at incoming side with suitable space for 2 incoming cable and outgoing of 2 cable.Bus bar fixed on insulators in zig-zag position, clearance in each strip and clearnace at both side should not be less than 125mm with sufficient working space, height of bus bar chamber not less than 1 mtr, mounted MS angle 50x50x6mm, made of CRCA sheet 2mm thick outdoor type powder coated after seven tank process both side opening, shutter in two parts, cable opening form bottom side with indicators R,Y,B, hinges through out the length of shutter with half turn locking arrangement, including grounting in PCC, including taking down old bus bar chamber complete all as directed by Engr-in-charge. |
| 41 | Supply , install, testing and commissioning of factory made outdoor type floor mounted LT panel board of size 1800mmx1800mmx600mm cubicle type suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber (copper TPN 600 amps rating) with airinsulated PVC sleeved copper bus bar of rating 600 Amps for phases and neutral installed on porcelain insulators. The panel shall be dust and vermin proof IP-55 class protection and made out of 3.15 mm CRCAsheet double door hinge type with locking arrangement both side openable duly painted with two coats of synthetic enamel paint over a coat of zinc chrome primer with powder coated including 50 X 50 X 6 mm thick MS angle iron frame work front and rear side opening with adequate size for housing LT switch gear and measuring instruments duly powder coated after seven tank process on both sides with PCC (1:2:4) foundation, type B-1 using 20mm graded stone aggregates including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 16sqmm, 1100 Volt grade IS 694 marked including and comprising of followings components after dismantling of old unserviceable panel with all fitting and fixtures etc as under :- |
| 42 | (a) MCCB, 400 Amp, 4 Pole, 50 Hz, 415 V, having rupturing capacity 35 KA-01 No as incoming (thermal magnetic) release and adjustable on load (b) MCCB, 250 Amp, 4 Pole, 50 Hz, 415 hanving rupturing capacity 36 KA-01 No as outgoing (thermal magnetic) release and adjustable on load (c) MCCB 200 Amp, 4 Pole, 50 Hz, 415 hanving rupturing capacity 25 KA-01 Nos as outgoing (thermal magnetic) release and adjustable on load (d) MCCB 100 Amp, 4 Pole, 50 Hz, 415 hanving rupturing capacity 25 KA-03 Nos as outgoing (thermal magnetic) release and adjustable on load (e) MCB, SPN, 40Amps, 50 Hz, 415 Volt, \"B\" curve/series, having rupturing capacity 10KA-1 Nos (f) Indicator set RYB 01 set of 3 pcs LED type - 1 set (f) Digital voltmeter panel mounted of size 96x96 mm range 0-500 volts with in built in selector switch with CT\"s -01 set (g) Digital ammeter panel mounted of size 96 x96 mm range 0 to 100 Amps with in built in selector switch complete with CTs of appropriate ratio- 01 Set (h) Copper bus bar, TPN, 600 Amp rating- 04 nosNotes : (i) Rates are deemed to be inclusive of PCC platform of suitable size of 45 cm height and 04 Nos legs of 50mm x 50mmx6mm & 60cm in height for fixing the panel (ii) MCCB & MCB shall be fixed in suitable sheet metal enclouser made up of 3.15mm thick CRCA sheet. (iii) Danger notice plate (02 Nos) LT size 20cm x 15 cm shall be fixed on the panel (iv) Panel shall be from CPRI approved make.(v) Make of panel and drawing shall be got approved from GE before placing order for procurement |
| 43 | Supply , install, testing and commissioning of factory made outdoor type floor mounted LT panel board of size 1400mmx1400mmx450mm cubicle type suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber (copper TPN 250 amps rating) with airinsulated PVC sleeved copper bus bar of rating 250 Amps for phases and neutral installed on porcelain insulators. The panel shall be dust and vermin proof IP-55 class protection and made out of 3.15 mm CRCAsheet double door hinge type with locking arrangement both side openable duly painted with two coats of synthetic enamel paint over a coat of zinc chrome primer with powder coated including 50 X 50 X 6 mm thick MS angle iron frame work front and rear side opening with adequate size for housing LT switch gear and measuring instruments duly powder coated after seven tank process on both sides with PCC (1:2:4) foundation, type B-1 using 20mm graded stone aggregates including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 16sqmm, 1100 Volt grade IS 694 marked including and comprising of followings components after dismantling of old unserviceable panel with all fitting and fixtures etc :- |
| 44 | (a) MCCB, 160 Amp, 4 Pole, 50 Hz, 415 V, having rupturing capacity 36 KA-01 No as incoming (thermal magnetic) release and adjustable on load (b) MCCB, 63 Amp, 4 Pole, 50 Hz, 415 hanving rupturing capacity 36 KA-05 No as outgoing (thermal magnetic) release and adjustable on load (c) MCB, SPN, 40Amps, 50 Hz, 415 Volt, \"B\" curve/series, having rupturing capacity 10KA-5 Nos (d) Indicator set RYB 01 set of 3 pcs LED type - 1 set (e) Digital voltmeter panel mounted of size 96x96 mm range 0-500 volts with in built in selector switch with CT\"s -01 set (f) Digital ammeter panel mounted of size 96 x96 mm range 0 to 100 Amps with in built in selector switch complete with CTs of appropriate ratio- 01 Set (g) Copper bus bar, TPN, 250 Amp rating- 04 nosNotes : (i) Rates are deemed to be inclusive of PCC platform of suitable size of 45 cm height and 04 Nos legs of 50mm x 50mmx6mm & 60cm in height for fixing the panel (ii) MCCB & MCB shall be fixed in suitable sheet metal enclouser made up of 3.15mm thick CRCA sheet. (iii) Danger notice plate (02 Nos) LT size 20cm x 15 cm shall be fixed on the panel (iv) Panel shall be from CPRI approved make.(v) Make of panel and drawing shall be got approved from GE before placing order for procurement |
| 45 | Supply , install, testing and commissioning of factory made outdoor type floor mounted LT panel board of size 1400mmx1400mmx450mm cubicle type suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber (copper TPN 600 amps rating) with airinsulated PVC sleeved copper bus bar of rating 600 Amps for phases and neutral installed on porcelain insulators. The panel shall be dust and vermin proof IP-55 class protection and made out of 3.15 mm CRCAsheet double door hinge type with locking arrangement both side openable duly painted with two coats of synthetic enamel paint over a coat of zinc chrome primer with powder coated including 50 X 50 X 6 mm thick MS angle iron frame work front and rear side opening with adequate size for housing LT switch gear and measuring instruments duly powder coated after seven tank process on both sides with PCC (1:2:4) foundation, type B-1 using 20mm graded stone aggregates including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 16sqmm, 1100 Volt grade IS 694 marked including and comprising of followings components after dismantling of old unserviceable panel with all fitting and fixtures etc :- |
| 46 | (a) MCCB, 400 Amp, 4 Pole, 50 Hz, 415 V, having rupturing capacity 36 KA-01 No as incoming (thermal magnetic) release and adjustable on load (b) MCCB, 250 Amp, 4 Pole, 50 Hz, 415 hanving rupturing capacity 36 KA-03 No as outgoing (thermal magnetic) release and adjustable on load (c) Indicator set RYB 01 set of 3 pcs LED type - 1 set (d) Digital voltmeter panel mounted of size 96x96 mm range 0-500 volts with in built in selector switch with CT\"s -01 set (e) Digital ammeter panel mounted of size 96 x96 mm range 0 to 100 Amps with in built in selector switch complete with CTs of appropriate ratio- 01 Set (f) Copper bus bar, TPN, 600 Amp rating- 04 nosNotes : (i) Rates are deemed to be inclusive of PCC platform of suitable size of 45 cm height and 04 Nos legs of 50mm x 50mmx6mm & 60cm in height for fixing the panel (ii) MCCB shall be fixed in suitable sheet metal enclouser made up of 3.15mm thick CRCA sheet. (iii) Danger notice plate (02 Nos) LT size 20cm x 15 cm shall be fixed on the panel (iv) Panel shall be from CPRI approved make.(v) Make of panel and drawing shall be got approved from GE before placing order for procurement |
| 47 | S&F in replacement for street light engineering plastic one piece moulding control /junction box (Size 300x200x150mm) with locking arrangment made out of HDPE and FI clamp 25 x 3 mm complete including MCB SP 6 Amp 240 Volts complete with 02 Nos aluminum busbar of rating 200 Amps for phase and neutral on porcelain based insulators and fixing clamps to pole with providing multistranded copper conductor 2.5 Sqmm from PVC junction box to street light fitting connector for street lights complete as ll specified and directed. |