| 1 | M & Lfor LT UG cable 2 corex 16 sq mm 1100 Volts grade XLPE insulated, armoured, heavy duty with aluminium conductor laid in trenches or fixed to walls/ poles or passing through pipes with and including,cable glandlugs/ thimbles/ ferrules including connecting, testing and commissioning complete for the following sizes including taking down existing LT UG cable of any sizeat site all as specified and as directed.Notes:-(a)Excavation, RFR andprotection pipeetc. shall be measured and paid separately under relevant item of schedule (b)Rate quoted deemed to include for cutting and removing of defective jointswhere required as directed. |
| 2 | All as per item No. 1.00but size 2 core10 Sqmm. |
| 3 | All as per item No. 1.00 but size 4 core25 Sqmm. |
| 4 | All as per item No. 1.00but size 4 core35 Sqmm. |
| 5 | All as per item No. 1.00but size 3.5 core 50 Sqmm. |
| 6 | S&F LT Cable joining kit outdoor end termination heat shrinkable type joint complete with jointing material and accessories suitable for LT Armoured cablesof size 50 Sqmm 3.5 core complete all as specified and directed by the Engr-in-Charge. |
| 7 | Excavating in trenches in Hard and dense soil not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundation, laying of cable etc not exc 10 Sq mtr on plan and not exc 1.5 mtr in depth and getting out complete all as specified and directed by the Engr-in-Charge. |
| 8 | Removing excavated surplus soil to a distance upto 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed by the Engr-in-Charge |
| 9 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick in hard/dense soil complete all as specified and directed by the Engr-in-Charge. |
| 10 | Supply and fixingGI tubing light grade 40 mm bore as in cable protection fixed to poles/walls or laid in trenches/under road crossing etc. all as specified and as directed. |
| 11 | Supply and laying double wall corrugated HDPE (DWC) pipe of size (Outer Dia x Inner Dia= 50 mm x 38 mm)in trenches for protection of cable complete all as specified and directed. |
| 12 | Supply and laying double wall corrugated HDPE (DWC) pipe of size (Outer Dia x Inner Dia= 63 mm x 50 mm) in trenches for protection of cable complete all as specified and directed. |
| 13 | Supply and laying double wall corrugated HDPE (DWC) pipe of size (Outer Dia x Inner Dia= 77 mm x 63 mm) in trenches for protection of cable complete all as specified and directed. |
| 14 | Supply, installing, testing and commissioning factory made LT (415 Volts, 50 Hz, 3-phase, 4 wire supply ) CPRI approved, factory assembled LT Panel Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated Aluminium bus bars of 150 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, ingress protection class ( IP-54) and made of 3.15 mm thick CRCA mild steel sheet and mild steel, Angle iron frame work made out of 40 mmX 40mm X 5 mm), front and rear opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR wire of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. embedded in ground with and including block of PCC 1:2:4 type B1 of block size 30cmx30cmx30 cm comprising of the following:- ( LOCATION :- 7/11 GR ) (Make of Panel :-L&T/ UNIVERSAL SWITCH GEAR CONTROL/SIEMENS/ SCHENIDER)Note:- Drawing of LT Panel shall be submitted before fabrication of paneland same shall be approved by GE. |
| 15 | Srl item No. 14.00 (Contd...)BUS BAR CHAMBER :- (a) 150 Amps 4 StripsAluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings.INCOMING SUPPLY :-(i) MCCB 100 Amps 25 KA 4 Pole with Adjustable release 415 volts , 50Hz,=01 No., Make of MCCB:-L&T/ Schneider / Havells.INSTRUMENT FEEDER :- (a)Digital Volt Meter, 96X96mm, flush type rated 0-500 V, with Volt meter selector switch- 01 Set. (b) Digital Amp Meter, 96X96mm, flush type rated 0-100 A, with Amp meter Selector switch- 01 Set.(c) C.T\"s 100/5 A CL 1.0 Tape Wound- 01 Set. (Set of three)(d) Red, Yellow, Green Phase indicating Lights LED type 220 V AC- 1 Set. (Set of three).(e) Protection MCB 6 A SP C Series- 1 Set. (Set of three). Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. |
| 16 | Srl item No. 14.00 (Contd...)OUTGOING SUPPLY :- (i) MCCB 63 Amps 16 KA 4 pole,415 volts , 50Hz - 01 Nos, (ii) MCB 32 Amps, 10 KA, SPN 230 Volts, 50Hz - 02 Nos,(iii) MCB 40 Amps 10 KA, SPN 230 volts , 50Hz - 01 Nos,Make of MCCB/MCB:- L&T/ Schneider / Havells. |
| 17 | Supply, installing, testing and commissioning factory made LT (415 Volts, 50 Hz, 3-phase, 4 wire supply) CPRI approved, factory assembled LT Panel Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated Aluminium bus bars of 300 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, ingress protection class ( IP-54) and made of 3.15 mm thick CRCA mild steel sheet and mild steel, Angle iron frame work made out of 40 mmX 40mm X 5 mm ), front and rear opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR wire of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. embedded in ground with and including block of PCC 1:2:4 type B1 of block size 30cmx30cmx30 cm comprising of the following:- ( LOCATION :- 7 COMPO) (Make of Panel :-L&T/ UNIVERSAL SWITCH GEAR CONTROL/SIEMENS/ SCHENIDER)Note:- Drawing of LT Panel shall be submitted before fabrication of paneland same shall be approved by GE. |
| 18 | Srl item No. 15.00 (Contd...)BUS BAR CHAMBER :- (a) 300 Amps 4 StripsAluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings.INCOMING SUPPLY :-(i) MCCB 200 Amps 36 KA 4 Pole with Adjustable release 415 volts , 50Hz,=01 No., Make of MCCB:-L&T/ Schneider / Havells.INSTRUMENT FEEDER :- (a)Digital Volt Meter, 96X96mm, flush type rated 0-500 V, with Volt meter selector switch- 01 Set. (b) Digital Amp Meter, 96X96mm, flush type rated 0-200 A, with Amp meter Selector switch- 01 Set.(c) C.T\"s 200/5 A CL 1.0 Tape Wound- 01 Set. (Set of three)(d) Red, Yellow, Green Phase indicating Lights LED type 220 V AC- 1 Set. (Set of three).(e) Protection MCB 6 A SP C Series- 1 Set. (Set of three). Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. |
| 19 | Srl item No. 15.00 (Contd...)OUTGOING SUPPLY :- (i) MCCB 125 Amps 25 KA 4 Pole Adjustable release415 volts , 50Hz - 01 Nos, (ii) MCB 100 Amps, 25 KA, 4 Pole Adjustable release 415 Volts, 50Hz - 01 Nos,(iii) MCB 63 Amps 10 KA, TPN 415 Volts , 50Hz - 01 Nos,(iv) MCB 40 Amps 10 KA, SPN 230 Volts, 50Hz -01 Nos,Make of MCCB/MCB:- L&T/ Schneider / Havells. |
| 20 | Supply, installing, testing and commissioning factory made LT (415 Volts, 50 Hz, 3-phase, 4 wire supply ) CPRI approved, factory assembled LT Panel Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated Aluminium bus bars of 200 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, ingress protection class (IP-54 ) and made of 3.15 mm thick CRCA mild steel sheet and mild steel, Angle iron frame work made out of 40mm X 40mm X 5 mm ), front and rear opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR wire of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. embedded in ground with and including block of PCC 1:2:4 type B1 of block size 30cmx30cmx30 cm comprising of the following:- ( LOCATION :-BTC) (Make of Panel :-L&T/ UNIVERSAL SWITCH GEAR CONTROL/SIEMENS/ SCHENIDER)Note:- Drawing of LT Panel shall be submitted before fabrication of paneland same shall be approved by GE. |
| 21 | Srl item No. 16.00 (Contd...)BUS BAR CHAMBER :- (a) 200 Amps 3 Strips & Netural, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings.INCOMING SUPPLY :-(i) MCCB 200 Amps 25 KA 4 Pole with Adjustable release 415 volts, 50Hz,=01 No., Make of MCCB : L&T/ Schneider / Legrand.INSTRUMENT FEEDER :- (a)Digital Volt Meter, 96X96mm, flush type rated 0-500 V, with Volt meter selector switch- 01 Set. (b) Digital Amp Meter, 96X96mm, flush type rated 0-200 A, with Amp meter Selector switch- 01 Set.(c) C.T\"s 200/5 A CL 1.0 Tape Wound- 01 Set. (Set of three)(d) Red, Yellow, Green Phase indicating Lights LED type 220 V AC- 1 Set. (Set of three).(e) Protection MCB 6 A SP C Series- 1 Set. (Set of three). Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.OUTGOING SUPPLY :- (i) MCB 40 Amps 10 KA SPN 230 volts , 50Hz - 08 Nos, Make of MCB:- L&T/ Schneider / Legrand. |
| 22 | Supply, installing, testing and commissioning factory made LT (415 Volts, 50 Hz, 3-phase, 4 wire supply ) CPRI approved, factory assembled LT Panel Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated Aluminium bus bars of 200 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, ingress protection class ( IP-54 ) and made of 3.15 mm thick CRCA mild steel sheet and mild steel, Angle iron frame work made out of 40mm X 40mm X 5 mm ), front and rear opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR wire of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. embedded in ground with and including block of PCC 1:2:4 type B1 of block size 30cmx30cmx30 cm comprising of the following:- (LOCATION :-BTC) (Make of Panel :-L&T/ UNIVERSAL SWITCH GEAR CONTROL/SIEMENS/ SCHENIDER)Note:- Drawing of LT Panel shall be submitted before fabrication of paneland same shall be approved by GE. |
| 23 | Srl item No. 17.00 (Contd...)BUS BAR CHAMBER :- (a) 200 Amps 3 Strips & Netural, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings.INCOMING SUPPLY :-(i) MCCB 125 Amps 25 KA 4 Pole with Adjustable release 415 volts, 50Hz=01 No., Make of MCCB:-L&T/ Schneider / Legrand.INSTRUMENT FEEDER :- (a)Digital Volt Meter, 96X96mm, flush type rated 0-500 V, with Volt meter selector switch- 01 Set. (b) Digital Amp Meter, 96X96mm, flush type rated 0-150 A, with Amp meter Selector switch- 01 Set.(c) C.T\"s 150/5 A CL 1.0 Tape Wound- 01 Set. (Set of three)(d) Red, Yellow, Green Phase indicating Lights LED type 220 V AC- 1 Set. (Set of three).(e) Protection MCB 6 A SP C Series- 1 Set. (Set of three). Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.OUTGOING SUPPLY :- (i) MCB 32 Amps 10 KA SPN 230 volts , 50Hz - 06 Nos, Make of MCB:- L&T/ Schneider / Legrand. |
| 24 | Supply, installing, testing and commissioning factory made LT (415 Volts, 50 Hz, 3-phase, 4 wire supply) CPRI approved, factory assembled LT Panel Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated Aluminium bus bars of 200 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, ingress protection class ( IP-54 ) and made of 3.15 mm thick CRCA mild steel sheet and mild steel, Angle iron frame work made out of 40mm X 40mm X 5 mm), front and rear opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR wire of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. embedded in ground with and including block of PCC 1:2:4 type B1 of block size 30cmx30cmx30 cm comprising of the following:- ( LOCATION :-KBS) (Make of Panel :-L&T/ UNIVERSAL SWITCH GEAR CONTROL/SIEMENS/ SCHENIDER)Note:- Drawing of LT Panel shall be submitted before fabrication of paneland same shall be approved by GE. |
| 25 | Srl item No. 18.00 (Contd...)BUS BAR CHAMBER :- (a) 200 Amps 3 Strips & Netural, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings.INCOMING SUPPLY :-(i) MCCB 160 Amps 25 KA 4 Pole with Adjustable release 415 volts , 50Hz,=01 No., Make of MCCB:-L&T/ Schneider / Legrand.INSTRUMENT FEEDER :- (a)Digital Volt Meter, 96X96mm, flush type rated 0-500 V, with Volt meter selector switch- 01 Set. (b) Digital Amp Meter, 96X96mm, flush type rated 0-150 A, with Amp meter Selector switch- 01 Set.(c) C.T\"s 150/5 A CL 1.0 Tape Wound- 01 Set. (Set of three)(d) Red, Yellow, Green Phase indicating Lights LED type 220 V AC- 1 Set. (Set of three).(e) Protection MCB 6 A SP C Series- 1 Set. (Set of three). Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.OUTGOING SUPPLY :- (i) MCB 32 Amps 10 KA SPN 230 volts , 50Hz - 06 Nos, (ii) MCB 40 Amps 10 KA, SPN 230 Volts, 50Hz -02 Nos,Make of MCB:- L&T/ Schneider / Legrand. |
| 26 | Supply and fixing as in repairs MCCB, 250A, rupturing capacity 36 KA, 415 volts 4 pole adjustable type complete all as specified and directed by the Engr-in-Charge |
| 27 | Supply and fixing as in repairs MCCB, 200A, rupturing capacity 36 KA, 415 volts 4 pole adjustable type complete all as specified and directed by the Engr-in-Charge. |
| 28 | Supply and fixing as in repairs MCCB, 160A, rupturing capacity 36 KA, 415 volts 4 pole adjustable type complete all as specified and directed by the Engr-in-Charge. |
| 29 | Supply and fixing as in repairs MCCB, 125A, rupturing capacity 16 KA, 415 volts 4 pole adjustable type complete all as specified and directed by the Engr-in-Charge. |
| 30 | Supply and fixing as in repairs MCCB, 100A, rupturing capacity 16 KA, 415 volts 4 pole adjustable type complete all as specified and directed by the Engr-in-Charge. |
| 31 | Supply and fixing as in repairs MCCB, 63A, rupturing capacity 16 KA, 415 volts 4 pole adjustable type complete all as specified and directed by the Engr-in-Charge. |
| 32 | Material and Labour for earthing complete with GI earth plate electrode 600mmx600mmx6mm thick burried in ground vertically to a depth not less than 2.25meters below ground level with top edge of the earth plate at a depth not less than 1.5 meter below the ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same.GI plate connected with galvanised iron strip 32×6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel. GI Strip laid in 40mm dia light grade GI pipe as protection from top of the plate up to test point (cost of protection pipe up to 7.5 meters from earth electrode will be included in the rates quoted by the contractor) with following complete all as specified and shown in electrical plate No 3 of SSR Part-I & testing on completion :-(a)GI strip 32x6 mm.(b) Watering pipe GI medium grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit.(MS Funnel should properly tightned on GI watering pipe and embeded in PCC floor of earth pit with open top suitable for watering of earth pits)(c)Excavation & earthwork in any type of soil PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 plaster including RCC pit cover 50mm thick 1:2:4 type B1 reinforced with 8mm dia mild steel bar 75mm centre to centre with 2 Nos MS handles of 12mm dia suitable for carrying of pit cover. |
| 33 | Supply and fixing in repair 3 phase Busbar chamber, wall mounted type, 200A, 6 way, busbar made of ETP grade copper complete all as specified and directed. Make- Havells Cat part No-IHBC020006/Equivalent in L&T/Legrand |
| 34 | Supply and fixing electric water heater, storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc. Make- Havells, Model Bianca/ or equivalent approved make. |
| 35 | M&L for 15mm GI tubing medium grade ISI marked complete with all necessary fittings on wall, floor etc complete all as specified and directed by Engr-in-Charge |
| 36 | M&L for 15mm bore bib taps, cast copper alloy chromium plated with crutch or butterfly handle screwed for 15mm bore iron pipe or for brass ferrule and fixed complete all as specified and directed by Engr-in-Charge |
| 37 | M&L for 15mm bore stop valve/angle valve cast copper alloy chromium plated with crutch or butterfly handle screwed for 15mm bore iron pipe or for unions and fixed complete all as specified and directed by Engr-in-Charge |
| 38 | Supply & fixing of 3-layer PP-R Polypropylene random copolymer) surface pipes SDR 7.4 (PN16) Outer diameter of pipes in 20 mm UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded polypropylene random fittings fixed complete to walls, ceilings or in floors etc. complete all as specified and directed by Engr-in-Charge. |
| 39 | M&L for Point wiring for socket outlet with FRLS cable of 2.5 sqmm PVC insulated (red/blue/yellow for phase, black for neutral and green for earth) unsheathed multistranded copper conductor 1100 volts grade in and including not less than 2 mm thick PVC casing capingwith all accessories and 2.5 sqmm green in colour PVC insulated multistranded copper conductor FRLS cablefor earth continuity connected to common earth dolly incl MS/GI sunken box with 3mm thick pre laminated hylum sheet/PVC box with back plate, flush/surface type for mounting fittings such as switches, socket, and regulator complete all as specified and directed for socketpoint on independent complete. |
| 40 | M&L Switch Socket combination 2 in 1, 3pin, 5 and 15 Amp flush type universal including PVC Box. |
| 41 | Supply & fixing sheet metal enclosure for DB\"s Single Door, Single pole andneutral, 240V, 2 way including blanking plates where required complete all as specified and directed. |
| 42 | Supply & fixing MCB SPN 240V, 10KA, C Series and current carrying capacity in the MCB DB complete with connection testing and commissioning of single pole size 32 amp. |
| 43 | Supply & fixing of PVC connections 15mm size with PTMT nuts of length 300 mm |
| 44 | Supply & fixing of water heater Hamam of capacity 200 ltr. SS steel body with 2 outlet taps run by Kerosene/Diesel with electric driven bowler of suitable size. Model No. WHH001 of LABORATE or equivalent. |
| 45 | Supply & fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections of size 2 Core 6 Sqmm. |
| 46 | Supply & fixing MCB SPN 20 Amp, 240V, 10KA, C curve in the MCB DB complete with connection testing, complete all as specified and directed. |
| 47 | Surface dressing n.exc 15cm deep and getting out in hard/dense soil all as directed. |
| 48 | M&L for hardcoe with broken stone or boulders of gauge n.exc 63 mm, deposited, spread and levelled in layers n.exc 15 cm thick, watered and rammed to a true surface, complete all as specified and directed. |
| 49 | M&L PCC (1:4:8) type D-2 using 40 mm graded stone aggregates as in foundations, mass filling, sub base and the like all as specified. |
| 50 | M&L chequered cement concrete tiles 30cm X 30cm X 25mm thick, set, jointed and pointed in neat cement slurry with grey cement and pigment in floors over 15mm thick screed bed or bedding layer in cement mortar 1:6. |
| 51 | Supply & fixing MS steel work roof trusses (framed), trussed, purlins, crane gantries, rails and fastenings and heavy bracket framing (Beam, tee, angle, channel or flat sanctions) including distance pieces, cleats etc., using Fe-410-W (Gde-E-250) quality-B, complete all as specified and directed. |
| 52 | Supply & fixing pre-painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/ cladding to wall, fixed with self tapping screws complete all as specified and directed. |
| 53 | M&L for preparing previously untreated steel surfaces of any description over 10 cm width/girth and applying two coats of synthetic enamel paint over one coat of redoxide primer including preparation of surface. |
| 54 | Note : Deduction for amount of Rs 52,945.00 as listed in Schedule A Part - II ( Schedule of Credit) shall be made while awarding of contract. |