| 1 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or water supply pipes lines etc or not exceeding 10 sqm on plan and getting out in soft/ loose soil complete all as specified and as directed. |
| 2 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed. |
| 3 | Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and as directed. |
| 4 | Supply & spreading in trenches sand cushioning to underground cable in trenches including spreading, levelling hand punning down complete all as specified and directed Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly. |
| 5 | Supply and laying well burnt bricks sub class \"B\" in trenches for cable protection of U/G cable all as specified and directed by Engr-in-Charges. |
| 6 | Taking out the existing ACSR Conductor /PVC/XLPE, 1100 volts grade,LT UG electric cable of any size and any type intrenches/ walls/ overhead lione(or) passing through pipes/in floorcompleteall as specified and directed by the Engr-in- chargeNote:- Excavation and Earth work shall be measured and paid separately under appropriate items:- |
| 7 | Laying only the under ground cable any typeobtained fromItems No -06 abovein trench/wall/floor etc are connecting with suitable cable lugs/sleevs etcandsize 25 sqmm 3.5 corecomplete all as specified and directed by Engr-in Charge . |
| 8 | Laying only the under ground cable any typeobtained fromItems No -06 abovein trench/wall/floor etc are connecting with suitable cable lugs/sleevs etcandsize 35 sqmm 3.5 corecomplete all as specified and directed by Engr-in Charge . |
| 9 | Laying only the under ground cable any typeobtained fromItems No -06 abovein trench/wall/floor etc are connecting with suitable cable lugs/sleevs etcandsize 50 sqmm 3.5 corecomplete all as specified and directed by Engr-in Charge . |
| 10 | Laying only the under ground cable any typeobtained fromItems No -06 abovein trench/wall/floor etc are connecting with suitable cable lugs/sleevs etcandsize 70 sqmm 3.5 corecomplete all as specified and directed by Engr-in Charge . |
| 11 | Laying only the under ground cable any typeobtained fromItems No -06 abovein trench/wall/floor etc are connecting with suitable cable lugs/sleevs etcandsize 95 sqmm 3.5 corecomplete all as specified and directed by Engr-in Charge . |
| 12 | Laying only the under ground cable any typeobtained fromItems No -06 abovein trench/wall/floor etc are connecting with suitable cable lugs/sleevs etcandsize 150 sqmm 3.5 corecomplete all as specified and directed by Engr-in Charge . |
| 13 | Laying only the under ground cable any typeobtained fromItems No -06 abovein trench/wall/floor etc are connecting with suitable cable lugs/sleevs etcandsize 185 sqmm 3.5 corecomplete all as specified and directed by Engr-in Charge . |
| 14 | Laying only the under ground cable any typeobtained fromItems No -06 abovein trench/wall/floor etc are connecting with suitable cable lugs/sleevs etcandsize 240 sqmm 3.5 corecomplete all as specified and directed by Engr-in Charge . |
| 15 | Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 25sqmm 3.5 core complete all as specified and directed by Engr-in Charge. |
| 16 | Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 35sqmm 3.5 core complete all as specified and directed by Engr-in Charge. |
| 17 | Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 50sqmm 3.5 core complete all as specified and directed by Engr-in Charge. |
| 18 | Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 70 sqmm 3.5 core complete all as specified and directed by Engr-in Charge. |
| 19 | Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 95sqmm 3.5 core complete all as specified and directed by Engr-in Charge. |
| 20 | Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 150sqmm 3.5 core complete all as specified and directed by Engr-in Charge. |
| 21 | Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 185sqmm 3.5 core complete all as specified and directed by Engr-in Charge. |
| 22 | Supply & Lay in trenches fixed on wall (or) passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 240sqmm 3.5 core complete all as specified and directed by Engr-in Charge. |
| 23 | Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable for 25 to 50 sqmm 3.5 core complete all as specified and directed by Engr-in Charge. |
| 24 | Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable for 95 sqmm 3.5 core complete all as specified and directed by Engr-in Charge. |
| 25 | Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable for 150 to 185 sqmm 3.5 core complete all as specified and directed by Engr-in Charge. |
| 26 | Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable for 240 to 300 sqmm 3.5 core complete all as specified and directed by Engr-in Charge. |
| 27 | Supplying & laying in repair 50 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed. |
| 28 | Supplying & laying 80 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed. |
| 29 | Supplying & laying in trenches 100 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed. |
| 30 | M&L preparing old painted surfaces by scraping and removing old paints, rust, etc. from steel tubular poles (above the planting depth and PCC copings of 11.0 Metre length Pole) and mild steel cross arms, cable protection pipe, brackets, etc. and applying one coat of red oxide zinc chrome primer, alternate yellow & black strips painting (4 Nos. each strip 200 mm wide) and remaining portion of pole and cross arms, cable protection pipe, brackets, etc. treated with two coats of Aluminium paint,complete all as specified and as directed. |
| 31 | Taking out the existingLT poleof any size and any type completeall as specified and directed by the Engr-in- charge |
| 32 | Supply & erecting steel tubular swaged pole type 410-SP-55 (11.0 Metre long) including cast iron base plate, finial taper plug, cap, mild steel bolts, nuts, screws, including necessary excavation and earth work, PCC 1:4:8 type D2 in foundations below pole, PCC 1:3:6 type C1 as in plinth block and coping, disposal of surplus soil to a distance not exceeding 50m and depositing where directed, paintingofexposed surafaces of steel tubular poles with two coats of Aluminium paintover one coat of red oxide primer and providing 300 mm wide bands (3 bands/ straps with synthetic enamel paint and 2 bands with Black bituminous paint) from plinth block and numbering of poles, painting embedded portion of poles with one coat of bituminous paint complete all as specified and directed.complete all as specified and as directed. |
| 33 | Re Fixing ofSteel tubular swaged poles any type and any sizeafter taking dwon with proper shut dwon without damage of pole any location within 100 mtscompleteincluding cast iron base plate, finial taper plug, cap, mild steel bolts, nuts, screws, including necessary excavation and earth work, PCC 1:4:8 type D2 in foundations below pole, PCC 1:3:6 type C1 as in plinth block and coping, disposal of surplus soil to a distance not exceeding 50m and depositing where directed, paintingofexposed surafaces of steel tubular poles with two coats of Aluminium paintover one coat of red oxide primer and providing 300 mm wide bands (3 bands/ straps with synthetic enamel paint and 2 bands with Black bituminous paint) from plinth block and numbering of poles, painting embedded portion of poles with one coat of bituminous paint complete all as specified and directed.complete all as specified and as directed. |
| 34 | M & L in repair for danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with mild steel clamps, bolts and nuts of approved size, for HT, 250 mm X 200 mm complete all as specified and as directed. |
| 35 | Road cutting for passing through pipes/in floors connecting up testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 25 sqmm 3.5 core. Complete all as specified and directed |
| 36 | M & L for cement concrete in foundation, filling and mass concrete in M15(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 37 | S & F in repair earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25 mm X 4 mm galvanised mild steel strip complete all as specified and as directed. |
| 38 | Supply and fixing in repair 32 mm X 6 mm galvanised mild steel strip for horizontal conductors and down conductors including suitable design of fixing components of galvanised steel as per fig 28 of IS 2309: 1989 complete all as specified and as directed. |
| 39 | Supply , install, testing and commissioning of cubical housing cabinet type LT feeder pillar of (CPRI Approved) outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openablefrom both front and rear side made out of 3.15 mm thick CRCA (Cold Rolled Cold Annealed) MS Sheet, Powder coated, CPRI approvedhaving front and rear hinged doors, lifting lugs (2 Nos) , earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers.Necessaryfoundation work as per manufacturer instractionincluding foundation and including taking down the old panelrequired at site and comprising following:-Incoming (a) S&Ffor Electrolytic grade high conductivitysolid 4 Nos Alubus bars, rated 800 amps supported at required intervals sleeved with heat shrinkable PVC sleevings.The bars shall be colour coded at required intervals for identification- 04 Nos(b )S&F for LED Indicating lamps for Main Supplyindicating R\", Y\" B\"- 01 Set of 3 (C ) S&F Ammeterand voltmeter digitalmulty meterNos -01(d )S&F for MCCB 400 Amp 36 KA 4 pole Thermal magnatic setting complete- N0s -01 outgoing (a )S&FMCCB of 4 poleof capacity100 amps, with breaking capacity of16 KA with fixed thermal & fixed magnetic setting- 04 Nos (b )S&FMCCB of 4 poleof capacity125 amps, with breaking capacity of16 KA with fixed thermal & fixed magnetic setting- 02 Nos (c )S&FMCCB of 4 poleof capacity200 amps, with breaking capacity of36 KA with fixed thermal & fixed magnetic setting- 02 Nos (d )S&FMCCB of 4 poleof capacity250 amps, with breaking capacity of36 KA with fixed thermal & fixed magnetic setting- 01 Nos |
| 40 | Supply , install, testing and commissioning of cubical housing cabinet type LT feeder pillar(CPRI Approved) of outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openablefrom both front and rear side made out of 3.15 mm thick CRCA (Cold Rolled Cold Annealed) MS Sheet, Powder coated, CPRI approvedhaving front and rear hinged doors, lifting lugs (2 Nos) , earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers.Necessaryfoundation work as per manufacturer instractionincluding foundation and including taking down the old panelrequired at site and comprising following:-Incoming (a) S&Ffor Electrolytic grade high conductivitysolid 4 Nos Alubus bars, rated 800 amps supported at required intervals sleeved with heat shrinkable PVC sleevings.The bars shall be colour coded at required intervals for identification- 04 Nos (b )S&F for LED Indicating lamps for Main Supplyindicating R\", Y\" B\"- 01 Set of 3(C ) S&F Ammeterand voltmeter digitalmulty meterNos -01(d )S&F for MCCB 250 Amp 36 KA 4 pole Thermal magnatic setting complete- N0s -01 outgoing (a )S&FMCCB of 4 poleof capacity 63 amps, with breaking capacity of16 KA with fixed thermal & fixed magnetic setting- 03 Nos (a )S&FMCCB of 4 pole160amps, with breaking capacity of25 KA with fixed thermal & fixed magnetic setting, - 01 Nos |
| 41 | Supply , install, testing and commissioning of cubical housing cabinet type LT feeder pillar of(CPRI Approved) outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openablefrom both front and rear side made out of 3.15 mm thick CRCA (Cold Rolled Cold Annealed) MS Sheet, Powder coated, CPRI approvedhaving front and rear hinged doors, lifting lugs (2 Nos) , earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers.Necessaryfoundation work as per manufacturer instractionincluding foundation and including taking down the old panelrequired at site and comprising following:- Incoming (a) S&Ffor Electrolytic grade high conductivitysolid 4 Nos Alubus bars, rated 800 amps supported at required intervals sleeved with heat shrinkable PVC sleevings.The bars shall be colour coded at required intervals for identification- 04 Nos (b )S&F for LED Indicating lamps for Main Supplyindicating R\", Y\" B\"- 01 Set of 3 (C ) S&F Ammeterand voltmeter digitalmulty meterNos -01(d )S&F for MCCB 250 Amp 36 KA 4 pole Thermal magnatic setting complete- N0s -01( e )Change over switch 250Amp 4 pole front loaded operated 415 voltsNos -01 outgoing : (a )S&FMCCB of 4 poleof capacity 100 amps, with breaking capacity of25 KA with fixed thermal & fixed magnetic setting- 03 Nos (a )S&FMCCB of 4 poleof capacity 63 amps, with breaking capacity of25 KA with fixed thermal & fixed magnetic setting- 03 Nos |
| 42 | Earthing complete with galvanisedsteel earth plate electrode of size60cm x 60cm x6.3 mm thick burried directly in ground( earth pit not less than 2.25 m deep below the normal groungnd level) with top edgee of the plate not less than 1.5m below normal GL connected to GI earth strip of size 25x4mm by means ofbolts, nuts, check nuts washers of GI or steel all asshown in electrical plate No-3 of SSR Part I connected to machanery/equipments installed power house/sub station all as specified including testing on completion.Note No-1the unit rate shall also include for excavation earth work in any type of soil PCC (1:3:6) type C1 pit RCC 1:2:4 type B-1 cover reinforced with 8 mm dia CTD bars @ 150mm C/C both ways funnel with 15mm bore GI watering pipe 20mm dia bore GI protection pipe wire mesh and copper lugs complete all as specified & shown in eletrical plate No.3 of SSR Part-1 2009. |