| 1 | REPAIR/REPLACEMENT OF HANGER LIGHTS IN HANGER (P/235) AT BSF (GOA)AND REPLACEMENT OF OLD CONVENTIONAL LIGHTS WITH NEW LED LIGHTS AT INAS 339 HANGAR (P-219A) AT INS HANSA |
| 2 | Taking down unserviceable/ serviceablehigh bay luminaires / Flood light fitting from hanger upto 15 mtr height andcomplete all as specified and as directed.Note: Serviceable fitting shall be handed over to MES store immediately on disconnection etc and the rate quoted is demmed tobe included for all charges such as transportation etc |
| 3 | Taking down old unservisable / perishable sub main wiring of any size / core / type from the ceiling of hanger complete with PVC / steel conduit / PVC casing capping including earth continuty conductor, junction boxes etc and making good the disturbed surfaces complete all as specified and as directed |
| 4 | Supply and fixing LED Highbay 200Wsuitable for Hangers / industrial application, integral industrial SMD LED with pressure die-cast aluminium housing, anodised aluminium reflector, complete with all accessories ,lumen efficiency > 150 lm/w, CRI > 85% ,THD < 15%UL certified.The luminarie should have 5 KV surge protection,PF > 0.95. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie.Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report including hooks etc made of iron, clamps with suitable size and strength complete all as specified and as directed Make- Bajaj CP BGHBM PRO B 300L WH NB SD/Wipro LH17-282-060-50-XX/ or equivalent in Phlips |
| 5 | Supply and fixing LED Flood Light250Wsuitable for Hangers / industrial application, with secondary optics with pressure die-cast aluminium housing, and heat sink in aluminium , complete with all accessories ,lumen efficiency > 120 lm/w, CRI > 85% ,THD < 15%UL certified.The luminarie should have 5 KV surge protection,PF > 0.95. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie.Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report completeincluding hooks etc made of iron, clamps with suitable size and strength complete all as specified and as directed Make- Bajaj CP BJFL 250W LED WH MB/Wipro LF30-342-060-57-XX/ or equivalent in Phlips |
| 6 | S & F MCBTPN 63 Amps 415 volts complete all as specified and as directed. |
| 7 | S & F MCB SP 6 to 32 Amps 240 Volts all as specified and directed. |
| 8 | S & FRCCB 4 Pole 30 mA 63 Amps complete all as specified and as directed. |
| 9 | S & F vertical MCB DBs VTPN 8 Way sheet steel, phospetised, powder coated with 200 Amps rated bas bar double door, 415 Volt complete all as specified and as directed |
| 10 | M/L for wiring for circuit/submain wiring along with earth wire the following sizes of FRLS PVC insulating copper conductor,single core cable in steel conduit in surface/recessed as required. Note : Steel conduit will be measured and paid seperately |
| 11 | 2 x 2.5 sq mm +1 x 2.5 sq mm earthwireNote: 3 Running meter of wire will be measured as one RM Unit. |
| 12 | 3 x 2.5 sq mm +1 x 2.5 sq mm earthwireNote: 4 Running meter of wire will be measured as one RM Unit |
| 13 | 4 x 2.5 sq mm +1 x 2.5 sq mm earthwireNote: 5 Running meter of wire will be measured as one RM Unit. |
| 14 | 5 x 2.5 sq mm +1 x 2.5 sq mm earthwireNote: 6 Running meter of wire will be measured as one RM Unit. |
| 15 | S & F Mild steel black conduit medium grade including all fittings / fixture, boxes (junction/terminal) etc fixed on wall, ceiling / roof / structure etc for hanger lightening complete of the size 25 mm to 40 mm dia. |
| 16 | S&F ceiling rose 3 terminal 230 volts, PVC polycarbonate, isolated body completed all as specified and directed. |
| 17 | M & L for Earthing complete with GI earth plate, electrode,600x600x6.0 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) filled with common salt and charcoal and connected to GI earth strip 25 x 4 mm thick dia by means of GI nuts, bolts, & washers as shown in electrical plate No. 5 of SSR Part-I and Connected to earthing test point all as specified and including necessary PCC earth pit chamber of 1:3:6 and chamber cover of 50mm thick PCC 1:2:4 with 6mm dia mild steel reinforcement of 10 cm c/c spacing both ways in lieu of CI cover, watering arrangement shall be made with GI pipe light grade of 20mm dia including funnel and protection to earth lead shall be provided with GI pipe light grade 40 mm dia upto 7.5 from the earth plate electrode & refilling of soil with mixture of Paddy earth, connecting up complete, testing on completion etc including necessary excavation & earth work in any strata and PCC chamber all as specified and directed. |
| 18 | REPLACEMENT AND REPOSITIONING OF HANGAR MAIN JUNCTION BOXES AND CIRCUIT BREAKERS OUTSIDE BUILDING (P-644, P-452, P-453, P-454) AT NAY GOA UNDER AGE E/M I OF GE (NW) VASCO |
| 19 | Supply and laying under ground LT Cable XLPE insulated heavy duty armoured sheathed 1100 volts grade of cross sectional area 400 Sq mm, 3.5 core, with aluminium conductor, ISI marked as per IS : 7098( Part-1) along with suitable size aluminium cable lugs, gland if required and jointed in any description complete all as specified. |
| 20 | Supply and fix or laying in trenches GItubing light grade for road crossing (for cable protection) of 80 mm sizes complete as required all as directed. |
| 21 | M & L for Earthing complete with GI earth plate, electrode,600x600x6.0 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) filled with common salt and charcoal and connected to GI earth strip 32x 6 mm thick dia by means of GI nuts, bolts, & washers as shown in electrical plate No. 5 of SSR Part-I and Connected to earthing test point all as specified and including necessary PCC earth pit chamber of 1:3:6 and chamber cover of 50mm thick PCC 1:2:4 with 6mm dia mild steel reinforcement of 10 cm c/c spacing both ways in lieu of CI cover, watering arrangement shall be made with GI pipe light grade of 20mm dia including funnel and protection to earth lead shall be provided with GI pipe light grade 40 mm dia upto 7.5 from the earth plate electrode & refilling of soil with mixture of Paddy earth, connecting up complete, testing on completion etc including necessary excavation & earth work in any strata and PCC chamber all as specified and directedincluding demolish existing earth pit taking out old materials. |
| 22 | Excavation in trenches 1.5 Mtr wide and not exc 1.5 Mtr deep in hard/dense soil getting out and levelling of bottom surface to required level for laying UG cable / erection of poles all as specified. |
| 23 | Excavation in trenches 1.5 Mtr wide and not exc 1.5 Mtr deep in soft/ disintegrated rock getting out and levelling of bottom surface to required level all as specified. |
| 24 | Excavation in trenches by cutting of road crossing/PCC hard standing, under boundary wallfor laying of pipe/cable including making good the existing surface with same finish to match the original finish all as all as directed by Engr-in-Charge. |
| 25 | Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25cm thick all as specified. |
| 26 | Removing excavated material of soils from site to a distance not exc 50 mtr away and depositing where directed not exc 1.5mtr from the starting point.all as specified. |
| 27 | Supplying & Laying in trenches Clear Sand/m- Sand for cushioningunder ground cable 8 cm below and 15 cm above complete in level all as specified.Note: Punned thickness only will be measured and paid. |
| 28 | Supplying & Layingprecast concrete cable cover, class LV, type 1, flat, size 250mm x 150mm x 40mm in trenches for protect to under ground cable complete all as specified. |
| 29 | Supply, installation and testing LT panel outdoor floor mounted side open with locking arrangement of suitable size weather & vermin proof suitable for 415 volts 3 phase 4 wire 50 HZ AC factory made fabricated from CRCA sheet steel 3.15 mm thick with aluminium bus bar 600 Amps for 3 phases and 300 Amps cap for neutral and mounted on 70cm long legs of angle iron 50 x 50 x 6mm thick and 30cm shall be embeded in the foundation with PCC of 1:2:4 type B-I, 20mm stone aggregate comprising with the following accessories complete with internal panel wiring with suitable size copper conductor multistrand with proper thimbling and lugs, and painting with smoke grey heat resistant enamelled paints two coat over a coat of red oxide primer complete all as specified and directed . |
| 30 | The panel shall comprising the following:- On board CPRI Approved, Indoor type, front openable door, One incomming compartment and one for alluminiumbusbar compartment and outgoing compartment having, provision ofhaving oneincomming in MCCBswitch of 250 Amps, and each out going feeders connected to busbar,dust and vermin proof & lockable, factory made, fabricated out of 3.15 mm thick CRCA sheetsuitable for 3 Phase 415 volts 50 Hz, AC supply, bus bar chamber with alluminium bus bar of600 Amp rating for 3 phase and neutral4 wire system duly insulated incl necessaryconnections, common earth bus bar ofGI Strip 32 x 6 mm at bottom with panel board at oneearth terminals, cable glands with independent plates at bottom for each out going and in coming cables in cable alley panel board and painted with powder coatingin siemens grey colour. |
| 31 | includingprovision for the following incoming and out going (connected with busbar) accessories all as approved andcomprising as under (for SFC Room 415 v)(a) MCCB 415 Volts 630 Amps rating 4 pole with breaking capacity of 35 KA with adjustable thermal & adjustable magnatic release = 01 No (Incoming) (b) ON-load change over switch I-O-II with advance neutral conforms to IS:13947 (Part-3); IEC:60947-3 of capacity 400 Amps(c) MCCB 415 Volts 250 Amps rating 4 pole with breaking capacity of 25 KA with adjustable thermal & fixed magnatic release = 04 Nos (outgoing) (d) Digital type Amp meter 0 to 500 Amps with adequate size CTs - 01 Set(e) Digital type volt meter 0 to 500 volts - 01 No(f) Indicating lamp LED type for 3 phase electric system - 01 Set |
| 32 | Taking down old serviceable LT UG cable of any size and location by disconnecting electric supply and proper procedure by taking shutdown and refixing cables in the new LT Panels and connection will be done as per direction. |