| 1 | Supply, installation, testingand commissioning of BUILDING PANEL with 630A FP ATS as INCOMER along with all accessories for successful commissioning with the following features:- |
| 2 | (a) 6A 1P 10kA C-Curve MCB- 22 Nos.32A Neutral Link, Channel Mounting, Color: Black/Grey- 10 Nos.630A 4P 50kA MCCB,Microprocessor Based Micrologic 2 Release-2 Nos.Motor Mechanism Module with SDE Adaptor, Voltage: 220-240V AC 50/60Hz forCompact NSX 400/630A -2 Nos.Auxiliary Contacts (Changeover) Multifunction, OF or SD or SDE or SDV for EasyPact CVS 100-630A -3Nos.160A 4P 25kA MCCB,Microprocessor Based Micrologic 2 Release -8 Nos.Motor Mechanism Module with SDE Adaptor, Voltage: 220-240V AC 50/60Hz for Compact NSX 250A – 8 Nos. |
| 3 | (b) Indoor Type, Floor Mounted, Single Front, Single Door, IP 44, Fixed Type, Compartmentalized Panel, Extensible on both side, Earthing studs, Earthing strip for connection to nearest earth pit, Front Access Structure, Door, Mounting Plate: 2mm, Gland Plate: 3mm undrilled Cable Termination At: I/C - Top & O/G – Top, Powder Coated with RAL 7032. |
| 4 | (c) 630A 4P ATS with bridging bars, Red Direct Integral LED indicating lamp,Voltage: 230V AC, Yellow Direct Integral LED indicating lamp,Voltage: 230V AC, Blue Direct Integral LED indicating lamp,Voltage: 230V AC, 10A Auxiliary Contactor, Coil: 220V AC, Aux. Contact: 2NO+2NC, Phase Loss + Phase Sequence + Under Voltage + Over Voltage Monitoring Relay, (UV: -5% to -25% of (Un), OV: 5% to 25% of (Un)),ON Delay 5s and Selectable OFF Delay (0 to 15 ses), Phase Asymmetry 10% fixed, Voltage: 208 - 480 VAC, 1 C/O,3Ph 3W. |
| 5 | (d) A Set of 630A Electrolyte Grade Aluminum Busbar for TPN System (Current Density- 0.8A/sq.mm, Aluminum Busbar For Neutral - 50% of Phase. |
| 6 | Supply, Installation, Testingand Commissioning of 630A FP AUTO TRANSFER SWITCH (AS IN/OUTGOING) along with all accessories for successful commissioning with the following features:- |
| 7 | (a) Indoor Type, Floor Mounted, Single Front, Single Door, IP 44, Fixed Type, Compartmentalized Panel, Extensible on both side, Front Access Structure, Earthing studs, Earthing strip for connection to nearest earth pit, Door, Mounting Plate: 2mm, Gland Plate: 3mm undrilled Cable Termination At: I/C - Top & O/G – Top, Powder Coated with RAL 7032 |
| 8 | (b) 630A 4P ATS with bridging bars, Red Direct Integral LED indicating lamp,Voltage: 230V AC, Yellow Direct Integral LED indicating lamp,Voltage: 230V AC, Blue Direct Integral LED indicating lamp,Voltage: 230V AC, 10A Auxiliary Contactor, Coil: 220V AC, Aux. Contact: 2NO+2NC, Phase Loss + Phase Sequence + Under Voltage + Over Voltage Monitoring Relay, (UV: -5% to -25% of (Un), OV: 5% to 25% of (Un)),ON Delay 5s and Selectable OFF Delay (0 to 15 ses), Phase Asymmetry 10% fixed, Voltage: 208 - 480 VAC, 1 C/O,3Ph 3W, 6A 1P 10kA C-Curve MCB, 32A Neutral Link, Channel Mounting, Color: Black/Grey. |
| 9 | (c) A Set of 630A Electrolyte Grade Aluminum Busbar for TPN System (Current Density- 0.8A/sq.mm, Aluminum Busbar For Neutral - 50% of Phase. |
| 10 | Supply, installation, testingand commissioning of 1.1kv cable along with Cable Lugs and Glands including excavation, cable tray of 150mm, Sand and Brick protection for the following size:- |
| 11 | (a) 3.5C x 240 Sq mm |
| 12 | (b) 3.5C x 120 Sq mm |
| 13 | (c) 3.5C x 70 Sq mm |