| 1 | Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for1.1 KV. to be laidon wall / cable tray or in existing trench/ pipe of following size of cables(i) 3 1/2 core 300 Sq. mm (150 Sq. mm1/2core) ( necessary clamps/ties to be provided by agency.). |
| 2 | Making trench in soft soil of suitable width of 90 cm deep for laying cable or locating the faultall over the run and back filling the same and making the surface as normal ground. |
| 3 | Covering of cable with second class bricks or cement tileslaid cover the cable crosswise & also on both sides with covering of 7. 5 Cm. layer of sand above & below cable (16 bricks per meter.). |
| 4 | (A) Making trench in Hard Murrum / Tar Road of suitable width of 90 cm or requireddepth for laying any size of cable or locating the faultall over the run and back filling the same and making the surface as normal ground. |
| 5 | (B) If additional machineries like hammer driller or JCB use [Add.]. |
| 6 | Providing and fixing approved make Perforated C type cable tray.Made fromsheet steel. The cable tray should be single or double bended as per required and as per IS 2062/1079 and shall becoated with hot dip galvanizing as per IS 2629/4759 with max 17.5% perforationwith coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erection with necessary support(included)as per Specification and as per instruction of engineer in charge. (i)300 X 50 X 2.0 mm Thick. |
| 7 | Providing and fixing approved make \"T\" Junction for Perforated C type cable tray.Made from sheet steel. The Junction should be bended as per IS 2062/1079 and shall be coated with hot dip galvanizing as per IS 2629/4759. with max 17.5% perforationwith coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing supportas per Specification and as per instruction of engineer in charge of following size (i) 300 X 50 X 2.0 mm Thick. |
| 8 | Providing and fixing approved make \"90° Elbow\" for Perforated C type cable tray.Made from sheet steel. The Junction should be bended as per IS 2062/1079 and shall be coated with hot dip galvanizing as per IS 2629/4759.with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing supportas per Specification and as per instruction of engineer in charge.(i) 300 X 50 X 2.0 mm Thick90° Elbow. |
| 9 | Providing , erecting , fabricating the M.S. structure as per requirement on site incorporating proper size of M.S. angles, flats, bars, channels, sections complete with cutting, welding, grinding, fastners& finishing duly painted with one coat of red oxidewith erection on site as per direction of engineer in charge with necessary grouting, cementing, plastering & finishing complete. |
| 10 | Providing and erecting Epoxy Indoorendtermination Kit suitable for LTPVC insulated armoured cable1.1 KV grade complete with ferrule bushing and accessories and suitable clamps duly erected and connected to the supply for all cores cables of following size. (i) 300 Sq. mm. |
| 11 | Providing and, fixing heavy duty flange type brass cable gland with rubber ring for PVC insulated armoured cable complete with out going tails, insulating tape etc for following size of cables.(i)3 & 1/2core 300 Sq. mm. |
| 12 | Disconnecting the cable connection and Providing straight joint with PVC mould using heat shrink /cast resin type epoxy compound Insulating material and making the joint complete using necessary in line connectors, hardener, earth continuity connection, spacers etc. and reconnecting the same & ensure the joint resistance within the limits as per IS. (i)120 to 300 Sq. mm cable. |
| 13 | Solder less crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner. |
| 14 | (i) 300 Sq.mm. |
| 15 | (ii) 150 Sq.mm. |