Tender For Periodical Services And Connected Work At Bana Singh Vihar Md Accn In U Area Including Repair Replacement Of Internal Wiring Fittings Under Age Br I Of Ge Sukna
Tender Value
45 Lakhs
Estimated cost
Bid Submission
15 Jun 2024
0 days left
EMD
90000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
sukna → West Bengal
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Periodical Services And Connected Work At Bana Singh Vihar Md Accn In U Area Including Repair Replacement Of Internal Wiring Fittings Under Age Br I Of Ge Sukna
BOQ
| Sl. No. | Item Description |
| 1 | M&L for repair to broken/damaged RCC chajjas by making good with PCC 1:2:4 type B1 or rendering 15 mm thick in cement mortar 1:4 mixed with water proofing compound to top and sides and rendering 5 mm thick to soffits in cement mortar 1:3 including necessary form work, reinforcement duly welded if required including demolition of broken/loose PCC or taking down old plaster at any storey of building complete all as specified and as directed.(Note: Rate shall be included for necessary scaffolding and safety arrangement) |
| 2 | Supply only liquid water proofing compound ISI mark. |
| 3 | Taking down cement plaster on brick or stone walls, etc., including raking out joints, hacking for key, scrubbing down with water, etc complete all as specified and directed. |
| 4 | M&L for rendering 15 mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:6 finished the surface even and smooth without using extra cement complete all as specified and directed. |
| 5 | M&L for rendering 15 mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:4 finished even and smooth without using extra cement using WPC compound complete all as specified and directed.Note:- WPC shall be measured and paid separately. |
| 6 | M&L preparation of old decorated wall surface and including applying one coat of oil bound distemper completeall as specified and directed. |
| 7 | M&L preparation of old decorated ceiling surface and including applying one coat of oil bound distemper completeall as specified and directed. |
| 8 | M&L preparation of old decorated wall surfaces and including applying one coat of cement base paint complete all as specified and directed. |
| 9 | M&L complete removal of existing treatment of old decorated wall surfaces and including applying two coats of oil emulsion distemper overa coat of alkali resistant primer over a thin layer of wall care putty to obtained smoothness of plastered surfaces complete all as specified and directed. |
| 10 | M&L complete removal of existing treatment of old decorated wall surfaces and including applying two coats of weather coat acrylic exterior emulsion paint overa coat of primer including all necessary scaffolding complete all as specified and directed. (Note: rate shall be included for necessary scaffolding and safety arrangement) |
| 11 | M&L for complete removal of existing treatment of old decorated wall surfaces by Vacuum based sanding machine, removal of nails etc & filling cracks / hole with putty, applying one coat of primer using auto roller and applying a thin layer of wall care puttyand sanding the same by Vacuum based sanding machine till obtaining even and smooth finishand applying two coats of oil bound distemper by auto roller complete all as specified and directed as per manufacturers instructions.Note:-Multipurpose mixer shall be used for uniform and proper mixing of putty. |
| 12 | M&L for preparation of newly plastered surfaces of wall by Vacuum based sanding machine, applying one coat of primer using auto roller and applying a thin layer of thick wall care putty and sanding the same by Vacuum based sanding machine till obtaining even and smooth finishand applying two coats of oil bound distemper by auto roller complete all as specified and directed as per manufacturers instructions.Note:-Multipurpose mixer shall be used for uniform and proper mixing of putty. |
| 13 | M&L for preparation of newly plastered surfaces of wall by Vacuum based sanding machine, applying one coat of primer using auto roller and applying a thin layer of thick wall care puttyand sanding the same by Vacuum based sanding machine till obtaining even and smooth finishand applyingtwo coats of exterior weather coat paint using auto roller complete all as specified and directed as per manufacturers instructions.Note:-Multipurpose mixer shall be used for uniform and proper mixing of putty. |
| 14 | M&L for complete removal of existing treatment of old decorated wall surfaces by washing with jet washer machine, removal of nails etc & filling cracks / hole with putty, applying one coat of primer using auto roller and applying a thin layer of thick wall care putty and sanding the same by Vacuum based sanding machine till obtaining even and smooth finishand applying two coats of exterior weather coat paint using auto roller complete all as specified and directed as per manufacturers instructions.Note:-Multipurpose mixer shall be used for uniform and proper mixing of putty. |
| 15 | M&L preparation ofold decorated wooden surfaces of any description, not otherwise described over 10 cm width or girth and including applying one coats of synthetic enamel paint complete all as specified and directed. |
| 16 | M&L for preparation of old painted steel surfaces of any description, over 10 cm width or girth, not otherwise described and applying one coats of synthetic enamel paint complete all as specified and directed. |
| 17 | M&L preparation of old painted surfaces of CGI / PGI sheet surface exc. 10 cm width or girth in roof and including applying one coat of anti-corrosive paint complete all as specified and directed. |
| 18 | M&L writing letters or figures (Block. Roman, Italic or Indian) n exc. 30 cm high with synthetic enamel paint completeall as specified and directed. |
| 19 | S&F GI tubing light grade 40 mm dia for protection pipe along the wall to TPN DB for protection of cable if requiredcomplete all as specified and directed . |
| 20 | M&L point wiring with 1.5 sqmm single core, PVC insulated, unsheathed FRLSH copper cable, 1100 volts grade, with multi stranded copper conductor drawn through and including non-metallic, rigid non mettalic PVC conduit (medium grade) concealed in wall / ceilingwith and including 1.5 sqmm single core PVC insulated, multistranded, unsheathed, FRLSH copper conductor cable as continuous earth continuity conductor (green in colour) with cast Iron / pressed steel terminal boxes 60 mm deep, modular plate and frame on walls with 3 mm thick plastic laminated / hylam sheet cover, fixed on wall / other surfaces with brass screws for mounting or housing switches, socket outlets, fan regulators, etc. including all other fixing accessories for one light / fan / exhaust fan / call bell point controlled by one 5 / 6 Amps switch, all necessary cutting chasing (as required) and making good the disturbed surfaces including finishes to match with adjacent surfaces and including taking down old unsv ones complete all as specified and directed. |
| 21 | All as per Sl. item No. 20.00 above but for one 5 / 6 Amps socket outlet point on independent board. |
| 22 | All as per Sl. item No. 20.00 above but for one 16 Amps socket outlet point on independent board with 2.5 sqmm cable and 2.5 sqmm earth wire |
| 23 | All as per Sl. item No. 20.00 above but for one 5 / 6 Amps socket outlet point on same board. |
| 24 | All as per Sl. item No. 20 above but for one light point controlled by two, 2 - way switches. |
| 25 | M&L in replacement point wiring with 1.5 sqmm single core, PVC insulated, unsheathed FRLSH copper cable, 1100 volts grade, with multi stranded copper conductor drawn through and including PVC casing caping (double lock pattern) and accessories on wall / ceiling surfaces etc. with and including 1.5 sqmm single core PVC insulated, multistranded, unsheathed,FRLSH copper conductor cable as continuous earth continuity conductor (green in colour) with cast Iron / pressed steel terminal boxes 60 mm deep, on walls with 3 mm thick plastic laminated / hylam sheet cover, fixed on wall / other surfaces with brass screws for mounting or housing switches, socket outlets, fan regulators, etc including all other fixing accessories for one light / fan / exhaust fan point controlled by one 5 / 6 Amps switch complete all as specified and directed. |
| 26 | All as per Sl. item No. 25 above but for one 3 / 5 Amps socket outlet point on independent board. |
| 27 | All as per item No. 25.00 here-in-before but one 3 pin socket outlet / 5 amps on the independent board with other switches, with cables 2.5 sqmm size complete all as specified and directed |
| 28 | All as per Sl. item No. 25.00 above but for one 3 / 5 Amps socket outlet point on the same board. |
| 29 | All as per Sl. item No. 25.00 above but for one light point controlled by two, 2 - way switches complete all as specified and directed |
| 30 | M & L concealed sub main wiring with 2 runs of 2.5 sqmm main wire along with 1 run of 2.5 sqmm earth wire (green in colour) single core FRLSH PVC insulated, unsheathed, multi-stranded, 1100 volts grade ISI marked copper conductor cable, drawn through and including adequate size rigid non-metallic PVC conduit (medium grade) with all fittings & accessories including cutting chases for conduits as required, sinking for terminal boxes, making good the disturbed surfaces including finishes to match with adjacent surfaces and including taking down complete all as specified and directed.NOTE:- Two runs of main copper conductor, one run of earth wire and one run of PVC conduit shall be measured as one unit length. |
| 31 | M & L concealed sub main wiring with 2 runs of 4 sqmm main wire along with 1 run of 4 sqmm earth wire (green in colour) single core FRLSH PVC insulated, unsheathed, multi-stranded, 1100 volts grade ISI marked copper conductor cable, drawn through and including adequate size rigid non-metallic PVC conduit (medium grade) with all fittings & accessories including cutting chases for conduits as required, sinking for terminal boxes, making good the disturbed surfaces including finishes to match with adjacent surfaces and including taking down complete all as specified and directed.NOTE:- Two runs of main copper conductor, one run of earth wire and one run of PVC conduit shall be measured as one unit length. |
| 32 | M & L concealed sub main wiring with 2 runs of 6 sqmm main wire along with 1 run of 6 sqmm earth wire (green in colour) single core FRLSH PVC insulated, unsheathed, multi-stranded, 1100 volts grade ISI marked copper conductor cable, drawn through and including adequate size rigid non-metallic PVC conduit (medium grade) with all fittings & accessories including cutting chases for conduits as required, sinking for terminal boxes, making good the disturbed surfaces including finishes to match with adjacent surfaces and including taking down complete all as specified and directed.NOTE:- Two runs of main copper conductor, one run of earth wire and one run of PVC conduit shall be measured as one unit length. |
| 33 | M & Lin replacement for sub main wiring with 2 runs of 2.5 sqmm main wire alongwith 1 run of 2.5 sqmm earth wire (green in colour) single core FRLSH PVC insulated, unsheathed, multi-stranded, 1100 volts grade copper conductor cable, drawn through and including adequate size PVCcasing caping (double lock pattern) with all fittings & accessories on walls / ceiling surfaces etc., complete all as specified and directed.NOTE :- Two runs of main copper conductor, one run of earth wire and one run of PVC casing caping shall be measured as one unit length. |
| 34 | M & Lin replacement for sub main wiring with 2 runs of 4.0 sqmm main wire alongwith 1 run of 4.0 sqmm earth wire (green in colour) single core FRLSH PVC insulated, unsheathed, multi-stranded, 1100 volts grade copper conductor cable, drawn through and including adequate size PVCcasing caping (double lock pattern) with all fittings & accessories on walls / ceiling surfaces etc., complete all as specified and directed.NOTE :- Two runs of main copper conductor, one run of earth wire and one run of PVC casing caping shall be measured as one unit length. |
| 35 | All as per item No. 34 above but with 2 runs of 6.0 Sqmm main wire along with 1 run of 6.0 Sqmm earth wire. |
| 36 | S&F of rigid non-metallic PVC conduit 20mm inclusive of tees, bends, elbow, reducer and fixing accessories concelled on wall including necessary cutting / chasing of wall and making good distub surface complete all as specified and as directed. |
| 37 | S&F in repairs switch pianoflush typeone way, 5 / 6 Amps, 240 voltcomplete all as specified and directed. |
| 38 | S&F in repairs Switch piano 5 Amps single pole two waycomplete all as specified and directed. |
| 39 | S&F in repairs switch piano modular typeone way, 5 / 6 Amps, 240 volt complete all as specified and directed. |
| 40 | S&Fin repairsswitch piano modular typeone way, 15 /16 Amps independent, 240 volt complete all as specified and directed. |
| 41 | S & Fin repairs Switch Socket combination 16 Amps 3 pin flush type complete all as specified and as directed. |
| 42 | S & Fin repairs Socket outlet 5 Amps 3 pin flush type complete all as specified and as directed. |
| 43 | S&F in repairs socket outlet modular type 3 pin 5 / 6 Amps, 240 volts combined 2 modular complete all as specified and directed. |
| 44 | S&Fin repairs socket outlet modular type 3 pin 15/16 Amps, 240 volts combined 2 modular complete all as specified and directed. |
| 45 | S&F MCB SPN 40 Amp, 10 kA, 240V\"C\" curve including taking downcomplete all as specified and as directed. |
| 46 | S&F MCB SP 6 to 32 Amp, 10 kA, 240V\"C\" curve including taking downcomplete all as specified and as directed. |
| 47 | S&F ceiling rose, 3 phase / PVC / polycarbonate isolated body complete all as specified and directed. |
| 48 | S&F modular type electronic fan regulator, flush type 230V, AC 50 Hz not less than 100 Watt complete all as specified and directed. |
| 49 | S&Flamp holder, PVC/Polycarbonate type with cord grip cap suitable for pendant fittings including taking down old unsv ones complete all as specified and as directed. |
| 50 | S&F MCB DB, SPN 12 way, IP-43, IK09, double door, metal door type, with 100A copper neutral and earth bus bar for fixing MCB including taking down, fixed flush to wall & making good the disturbed surfaces complete all as specified and directed. |
| 51 | S&F VTPN DB, 4 way, IP-43, IK 09, single door type with metal door, with 250 A copper neutral and earth bus bar, suitable for fixing upto 160 Amp MCCBs as incomer fixing DPX 250+12 flush to wall & making good the disturbed surfaces complete all as specified and as directed. |
| 52 | S&F MCCB 4 pole 125 Amps breaking capacity 25 KA, type DU 250 C, Ics = 100% Icu including spreader link & taking down complete all as specified and directed. |
| 53 | S &F Bell buzzer, Ding Dong AC. 230 volts, single pole completed all as specified and directed. |
| 54 | M &L ofEarthingwith galvanised steel earth plate electrode 600 mm x 600 mm x 6 mm thick, buried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below ground level connected using galvanised iron earth lead wire 4 Sqmm as earthing electrode by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe (medium grade) and other end connected to earthing test point as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C both ways andsuitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth up to a distance not exceeding 50 Mtr etc all as shown on electrical plate No. 5 of MES Schedule Part-I complete including testing on completion. On testing after completion if the desired earth resistance is not obtained the earthing will be made again by the contractor at no additional cost and including dimantling complete all as specified and directed. |
| 55 | S&F Exhaust fan 250 mm sweep, non metallic plastic body, AC single phase, 230 V, 50Hz with & including self closing louvers, nuts, screws, bolts of specified sizes, electrical connection with twisted three core PVC insulated unsheathed flexible cord of size 0.75 sqmm copper conductor from ceiling rose to exhaust fan and writing MES number in 2 cm height with synthetic enamel paint and cutting wall for making hole awriting MES number in 2 cm height with synthetic enamel paint and cutting wall for making hole and making good the disturbed surface to match the existing surface complete all as specified and directed.Note: The quoted rate is including for taking down and depositing old fan to Mes store |
| 56 | S&F exhaust fan 300 mm sweep, metal body, 1200 RPM (minimum), AC single phase, 230 V, 50Hz with bird guard, nuts, screws, bolts including electrical connection, writing MES number in 2 cm height with synthetic enamel paint and cutting wall for making hole and making good the disturbed surface to match the existing surface complete all as specified and directed.Note :- The quoted rate is including for taking down and depositing old fan to MES store |
| 57 | M&L for cutting and making and enlarging existing hole for fixing of exhaust fan, nuts, bolts washer including plastering and make good the disturbed surface with the existing all as specified and directed. |
| 58 | S&F in repairs of energy saving BLDC ceiling fan complete with all connected accessories as specified below: -Input Power: - 26 watts with full speed and reduced power consumption with reduced speed technology.Voltage: - 90-300 V AC, 50Hz, single Phase.RPM: - 340 to 375 rpmBlades: - DecoratedSweep: - 1200 mm.Air delivery: - Not less than 210 CFMColour: - Glow white/Toast Brown/Gloss Black/or others as approved by Engr-in-Charge Speed/power control: -Without Remote through existing regulator. Star rating: - BEE 5 Star RatingWarranty: - As specified by the manufacturer, contractor shall produce original warranty and test certificate from the manufacturer.Note :- The quoted rate is including for taking down and depositing old fan to Mes store |
| 59 | S&F Single pole and neutral enclosure witha two pin and earthplug and socket complete with Double pole MCB 20 A complete all as specified and as directed.. |
| 60 | S & FBell push, flush type, 5 Amps single polecomplete all as specified and as directed. |
| 61 | S&F modular type Bell push 6 A, 1 module complete all as specified and directed. |
| 62 | S&F LED batten light fitting 1 x 10 watt inverter (backup) type, 230 Volts, suitable for surface mounting, lithium ion battery with minimum 4 hrs backup time, extruded polycarbonate housing & extruded polycarbonate diffuser, lumen efficacy 100 Lm/watt (minimum), colour temperature 6500K (minimum), CRI 80 (minimum), IP-20 (minimum), PF 0.90 (minimum), in-built surge protection 3.5 KV (minimum) inlcuding all fixing arragnement and electrically connecting from ceiling rose to light fitting & taking down complete all as specified and directed. |
| 63 | S&F in repairs LED battery backup inverter bulb of Lamp wattage: - 9 to 12 Watts, Battery: - Not less than 2200mAh or not less than 4 hrs backup,Efficeacy: - Not less than 110 Lm/Wattincluding taking down old unsv ones complete all as specified and directed. |
| 64 | S&F in repairs LED Bulk Head fitting 10 watt with Injection molded polycarbonate housing IP66, IK10, 3.5kV inbuilt surge protection, PF =0.95,total System Lumens not less than 1100 lm, 6500k CRI = 80, Operating Voltage range 140 V - 270 V. complete all as specified and as directed. |
| 65 | S&F wall decorative light fitting made up of high grade engineering material, (up to 14 watt LED bulb can be use in this lamp) complete all as specified and dircted |
| 66 | S&F 09 watt LED bulb for fixing in decorative wall lights complete all as specified and directed. |
| 67 | S&F in repairs Surface and wall mounted LED batten 20 watt 4ft long with Aluminum extrudedhousing , high quality polycarbonate diffuser & integrated Electronic Driver with IP20, PF 0.95, Efficiency not less than 110 lm / W color temp6500k CRI = 80, Operating Voltage range 140 V - 270 V complete all as specified and directed. |
| 68 | S&F in repairs LED Street Light 20 watt made up of pressure die cast aluminiun housing with highly efficient LEDs and PC cover with integrated lens with IP66, IK07, System Lumen Efficasy =100 Lm/W, 5 kV Surge Voltage Protection,Operating Voltage range 140 V - 270 V andbracket suitable for street light made out of GI pipe light grade of 25 mm bore & 0.75 mtr length (minimum), bend to shape including 2 pairs of MS flat iron clamps made out of 40 x 5 mm MS flat, nuts, bolts & washers etc,& painting the bracket with two coat of aluminium paint over a coat of red oxide primer complete all as specified and as directed. |
AI Tender Summary
Tender Timeline
May 24, 2024
11:30 IST
Tender Published
Tender notice published.
CompletedJun 15, 2024
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedJun 17, 2024
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer