Tender For Repair / Maint Of Dg Sets, Central Ac Plant, Lt Ug Cable, Street / Garden Lights And Other Misc Wks At Samudrika, Satavahana, Virbahu, Csp And Other Allied Areas Under Age E/M No-I Of Ge(U-I) Visakhapatnam, visakhapatnam-Andhra Pradesh

Military Engineer Services-MES has published Tender For Repair / Maint Of Dg Sets, Central Ac Plant, Lt Ug Cable, Street / Garden Lights And Other Misc Wks At Samudrika, Satavahana, Virbahu, Csp And Other Allied Areas Under Age E/M No-I Of Ge(U-I) Visakhapatnam. Submission Date for this Tender is 12-06-2024. Tube Light Tenders in visakhapatnam Andhra Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

43449375
Tender For Repair / Maint Of Dg Sets, Central Ac Plant, Lt Ug Cable, Street / Garden Lights And Other Misc Wks At Samudrika, Satavahana, Virbahu, Csp And Other Allied Areas Under Age E/M No-I Of Ge(U-I) Visakhapatnam
Open Tender
Indian
Andhra Pradesh
visakhapatnam
12-06-2024

Tender Details

Repair / Maint Of Dg Sets, Central Ac Plant, Lt Ug Cable, Street / Garden Lights And Other Misc Wks At Samudrika, Satavahana, Virbahu, Csp And Other Allied Areas Under Age E/M No-I Of Ge(U-I) Visakhapatnam

Key Value

Document Fees
INR 500 /-
EMD
INR 96000.0 /-
Tender Value
INR 48 Lakhs /-

BOQ Items

NAME OF WORK :REPAIR / MAINT OF DG SETS, CENTRAL AC PLANT, LT UG CABLE, STREET / GARDEN LIGHTS AND OTHER MISC WKS AT SAMUDRIKA, SATAVAHANA, VIRBAHU, CSP AND OTHER ALLIED AREAS UNDER AGE E/M NO-I OF GE(U-I) VISAKHAPATNAM
Sl. No. Item Description
1Maint and servicing of DG set 500 KVA canopy type, through authorized service agencyofOEM, including replacement of defective/worn out parts with new spares such as gaskets, rubber hoses with clamps, nuts bolts including greasing of bearings of engine and alternator, tappet setting, checking of batteries, adding distilled water and cleaning of POL tankand radiator etcall as specified and directed. Note:-Cost of S&F for replacing spare parts mentioned here-in-below under relevant items shall not considered to be included in this item.
2All as per Sl Item No 1.00 Above but for DG set of capacity 125-160 KVA
3All as per Sl Item No 1.00 Above but for DG set of capacity 20-100 KVA
4S&F in repair Fuel filter with O ring suitable for 500 KVA DG set & make as per OEM complete all as specified and directed.
5S&F in repair Fuel filter with O ring suitable for 125-160 KVA set & make as per OEM complete all as specified and directed.
6S&F in repair Fuel filter with O ring suitable for 20-100 KVA set & make as per OEM complete all as specified and directed.
7S&F in repair Lub oil filter for 500 KVA DG set & make as per OEM complete all as specified and directed.
8S&F in repair Lub oil filter for 125-160 KVA DG Set & make as per OEM complete all as specified and directed.
9S&F in repair Lub oil filter for 20-100 KVA DG Set & make as per OEM complete all as specified and directed.
10S&F in repair Air cleaner filter ( inner and outer ) for 500 KVA DG set & make as per OEM complete all as specified and directed.
11S&F in repair Air cleaner filter ( inner and outer ) for 125-160 KVA DG set & make as per OEM complete all as specified and directed.
12S&F in repair Air cleaner filter ( inner and outer ) for 20-100 KVA DG set & make as per OEM complete all as specified and directed.
13S&F in repair Bypass filter for 500 KVA DG set & make as per OEM complete all as specified and directed.
14S&F in repair Bypass filter for 125-160 KVA DG set & make as per OEM complete all as specified and directed.
15S&F in repair V belt for 500 KVA DG set & make as per OEM complete all as specified and directed.
16S&F in repair V belt for 125-160 KVA DG set & make as per OEM complete all as specified and directed.
17S&F in repair V belt for20-100 KVA DG set & make as per OEM complete all as specified and directed.
18S&F in repair Display control panel (LED Board) for 20 to 500 KVA DG set & make as per OEM complete all as specified and directed.
19S&F in repair Fuel actuator with O Ring for 20 to 500 KVA DG set & make as per OEM complete all as specified and directed.
20S&F in repair Key switch for 20 to 500 KVA DG set & make as per OEM complete all as specified and directed.
21S&F in repair coolant temperature sensor (coolent control safety) for 20 to 500 KVA DG set & make as per OEM complete all as specified and directed.
22S&F in repair AMF controller assy for auto/manual operation for 20 to 500 KVA DG set & make as per OEM complete all as specified and directed.
23S&F in repair Control assy main generator panel any type for 20 to 500 KVA DG set & make as per OEM complete all as specified and directed.
24S&F in repair Lube oil pressuresensor adaptor (oil control safety ) for 20 to 500 KVA DG set & make as per OEM complete all as specified and directed.
25S&F in repair Stop solenoid switch 12 Volts of make as per OEM complete all as specified and directed.
26S&F in repair Stop solenoid switch 24 Volts of make as per OEM complete all as specified and directed.
27Supply & Filling Coolant suitable for radiators & of make as per OEM complete all as specified and directed.
28S&F in repair Turbo charger for any capacity DG set & make as per OEM complete all as specified and directed.
29Supply & Filling engine oil multi grade 15W40 of following make or as per OEM all as specified and directed. Make: Servo / Bosch / Castrol / Valvoline / HPCL / ELF Oil
30S & F in repair Automatic Voltage Regulator suitable for DG set of any capacity and of make as per OEM complete all as specified and as directed.
31M & L for calibration of FIP and fuel injector from authorised dealer including petty repairs to make the FIP and injectors functional for DG set of capacity of 20-500 KVAcomplete all as specified and directed.
32Disconnecting the electric connection of Alternator of capacity 20 to 500 KVA DG set, taking the accumalator and cleaning the core assemblythrough air blower, heat varnishing with insulating material complete all as specified and as directed.
33S & F in repair Lub Oil cooler plate suitable for DG set of any capacity and of make as per OEM complete all as specified and as directed.
34S & F in repair Lub Oil pressure gauge pipe of required standard size suitable for DG set of any capacity and of make as per OEM complete all as specified and as directed.
35S & F in repair Oil spray nozzle assembly suitable for DG set of any capacity and of make as per OEM complete all as specified and as directed.
36S&F in repair Main Bearing as per existing, suitable for DG set of 20 to 500 KVA capacity and of make as per OEM complete all as specified and as directed.
37S & F in repair Water temp switch suitable for DG set of any capacity and of make as per OEM complete all as specified and as directed.
38S & F in repair Magnetic Pick Up Unit ( MPU) suitable for DG set of any capacity and of make as per OEM complete all as specified and as directed.
39S & F in repair water pump suitable for DG set of any capacity and of make as per OEM complete all as specified and as directed.
40S & F in repair Lub Oil pump high discharge of required standard size suitable for DG set of any capacity and of make as per OEM complete all as specified and as directed.
41S & F in repair field coil assembly suitable for 20-500 KVA DG set and of make as per OEM complete all as specified and as directed.
42S & F in repair Eye bolt suitable for 20-500 KVA DG set and of make as per OEM complete all as specified and as directed.
43S & F in repair fan key suitable for 20-500 KVA DG set and of make as per OEM complete all as specified and as directed.
44S & F in repair fan assembly suitable for 20-100 KVA DG set and of make as per OEM complete all as specified and as directed.
45S & F in repair fan assembly suitable for 125-160 KVA DG set and of make as per OEM complete all as specified and as directed.
46S & F in repair fan assembly suitable for 500 KVA DG set and of make as per OEM complete all as specified and as directed.
47S & F in repair fan suitable for 20-100 KVA DG set and of make as per OEM complete all as specified and as directed.
48S & F in repair fan suitable for 125-160 KVA DG set and of make as per OEM complete all as specified and as directed.
49S & F in repair fan suitable for 500 KVA DG set and of make as per OEM complete all as specified and as directed.
50S & F in repair Circlip suitable for 20-100 KVA DG set and of make as per OEM complete all as specified and as directed.
51S & F in repair Circlip suitable for 125 to160 KVA DG set and of make as per OEM complete all as specified and as directed.
52S & F in repair Circlip suitable for 500 KVA DG set and of make as per OEM complete all as specified and as directed.
53S & F in repair Brush holder spindle suitable for 20-100 KVA DG set and of make as per OEM complete all as specified and as directed.
54S & F in repair Brush holder spindle suitable for 125 to160 KVA DG set and of make as per OEM complete all as specified and as directed.
55S & F in repair Brush holder spindle suitable for 500 KVA DG set and of make as per OEM complete all as specified and as directed.
56S & F in repair NDE bearing cap suitable for 20 to100 KVA DG set and of make as per OEM complete all as specified and as directed.
57S & F in repair NDE bearing cap suitable for 125 to160 KVA DG set and of make as per OEM complete all as specified and as directed.
58S & F in repair NDE bearing cap suitable for 500 KVA DG set and of make as per OEM complete all as specified and as directed.
59S & F in repair Slipring assembly suitable for 20 to 100 KVA DG set and of make as per OEM complete all as specified and as directed.
60S & F in repair Slipring assembly suitable for 125 to 160 KVA DG set and of make as per OEM complete all as specified and as directed.
61S & F in repair Slipring assembly suitable for 500 KVA DG set and of make as per OEM complete all as specified and as directed.
62S & F in repair Exicitation (CX) unit suitable for 20 to 100 KVA DG set and of make as per OEM complete all as specified and as directed.
63S & F in repair Exicitation (CX) unit suitable for 125 to 160 KVA DG set and of make as per OEM complete all as specified and as directed.
64S & F in repair Exicitation (CX) unit suitable for 500 KVA DG set and of make as per OEM complete all as specified and as directed.
65S & F in repair Battery terminal made with brass suitable for 12/24 volt battery and of make as per OEM complete all as specified and directed.
66S & F in repair 12 volt, 180 AH battery complete all as specified and directed. Make:- Exide / Luminous / Nicco / AMCO / Amara Raja
67Material and labour for cleaning external surface of DG set of any capacity and make with cleaning agent including cleaning of radiators coil with with mild acid (or caustic soda) and cleaning of fuel tank etccomplete all as specified and as directed.
68S & F in repair self starter 24 volt DC suitable for DG set of any capacity and of make as per OEM complete all as specified and as directed
69S & F in repair self starter 12 volt DC suitable for DG set of any capacity and of make as per OEM complete all as specified and as directed
70M&L for taking down, transporting, dismantling, repairing and servicing of self starter 12/24 volt DC at authorized service centre of OEM including assembling, bringing back, installing, commissioning and testingthe same complete all as specified and as directed.
71M & L for maintanence and servicing of AMF panel including replacing unserviceable items, testing and replacing unserviceable wiring connection in panel for automatic operation through relay, contactor, timer, sensor etc all as directed. Note:- Cost of M&L for replacing spare parts mentioned here-in-below under relevant items shall not considered to be included in this item.
72S&F in repair multifunction meter, digital type (displaying A, V, PF etc.) complete all as specified and as directed. Make:- Elmeasure / L&T / Schneider / HPL / SOCOMEC
73S&F in repair phase indicator lamps (Red, Yellow and blue) suitable for AMF Panel complete all as specified and directed. Make:-L&T / Siemens / GE / RR Micro / BCH / Schneider
74S&F in repair three pole power contractor type AC3, 250 A with Aux contracts 2 Nos, 2 NC suitable for AMF panel complete all as specified and directed. Make: L&T / Indoasian / GE / BCH / HPL / C&S / ABB / Siemens
75S&F in repair three pole power contractor type AC3, 300 A with Aux contracts 2 Nos, 2 NC suitable for AMF panel complete all as specified and directed. Make: L&T / Indoasian / GE / BCH / HPL / C&S / ABB / Siemens
76S&F in repair AC Control contactor - M00AC - 15 4A at 415 Volt suitable for AMF panel complete all as specified and directed. Make: L&T / Indoasian / GE / BCH / HPL / C&S / ABB / Siemens
77S&F in repair DC control contactor M00DC 15 4A at 415 Volt suitable for AMF panel complete all as specified and directed. Make: L&T / Indoasian / GE / BCH / HPL / C&S / ABB / Siemens
78S&F in repair LED street light fitting of capacity 60 watt, IP-66 (minimum), integrated typewith high efficiency electronic driver, SPD of capaciity 10 KV, 5700 K pressure die cast aluminium housing with toughened glass cover, internally prewired and including electrically connecting complete all as specified and as directed. Make:- Signify Innovations India Ltd (Formerly Phillips) / Havells / Crompton / Bajaj Note:- Supply of new GI Pipe bracket if requiredshall be measured and paid separately under relevant item.
79All as per serial Item No. 78.00 above but LED street light fitting of capacity 100 W
80S&F in repair LED flood light fitting of capacity 120 watt, IP-66 (minimum) with luminous efficacy 100 Lumen/watt (minimum), SPD of capaciity 10 KV, 5700K, pressure die cast aluminium housing, toughened glass cover, internally prewired and including electrically connecting complete all as specified and as directed. Make:- Signify Innovations India Ltd (Formerly Phillips) / Havells / Crompton / Bajaj
81All as per serial Item No. 80.00 above but LED flood light fitting of capacity 200 W
82S&F in repair bracket suitable for street light made out of GI pipe light grade of 40 mm bore & 1.50 mtr length (minimum), bend to shape including 2 pairs of MS flat iron clamps made out of 40 x 5 mm MS flat, nuts, bolts & washers etc,& painting the bracket with two coat of aluminium paint over a coat of red oxide primer complete all as specified and directed. Make of Pipe :- Tata / Jindal Steel / Surya Roshni Ltd. /Bhushan Power & Steel Ltd. / M/s APL Apollo Tubes Ltd
83M&L cross arms,bracings,supports, clamps and back plates fabricated fromstructuralsteelsections and includingnuts,bolts,washers, welding,bendingcoldorhot, drilling holes for bolts, in any shape or size as indicated or directed and including preparation of surfaces and applying two coats of aluminium paint over a coat of primer and dismantling complete all as specified and directed. Make of paint : Jotun India Pvt Ltd / Asian Paints / Berger / Jenson & Nicholson Paints Ltd / Shalimar Paints Ltd
84S&F in repair PVC insulated 3 core multistranded sheathed cable with 1.5 Sqmm copper conductor for connection of street / security light etc, including PVC conduit of suitable size and medium grade for cable protectioncomplete all as specified and directed. Make:- Havells / KEI / Polycab / RR Kabel Ltd. / HPL
85S&F in repair 1 x 9 / 10 watt LED bollard light fitting, inverted conical shape, opal acrylic diffuser, IP-65, including hot dip galvanized pole, driver, all fixing arrangement etc. including electrically connecting complete all as specified and directed. Make:- Signify Innovations India Ltd (Formerly Phillips) / Havells / Crompton / Bajaj
86S&F in repair 35 watt LED post top lantern with polycarbonate opal diffuser, pressure die cast aluminium housing, IP-65 (minimum),high efficient constant current electronic driver including electrically connecting complete all as specified and directed. Make :- Signify Innovations India Ltd (Formerly Phillips) / Havells / Crompton / Bajaj
87Supply & laying LT XLPE insulated, armoured heavy duty electric cable with alumimium conductor, 1100 volts grade, cross sectional area 25 Sqmm x 4 Core, laid in trenches / duct / on pole including taking down existing cablecomplete all as specified and directed. Make :- Havells / KEI / Polycab / Gloster / Finolex
88All as per Sl Item No 87.00 above but50 Sqmm x 3.5 core
89Excavation in trenches, not exc 1.5 m wide and not exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, laying cable etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out all excavated material in soft / loose soil complete all as specified and directed.
90Returning, filling in and including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and as directed.
91Removing of excavated surplus soil to a distance n. exc 50 m and depositing wheredirected at a level n. exc. 1.5 m above the starting point complete all as specified and directed.
92M&L sand cushioning with clean and dry sand in trenches for protection of UG cable and including punning down complete all as specified and directed. Note:- Punned thickness shall only be measured and paid.
93Supply & laying sub class "B", class designation 75 bricks of old size, laid along alignment of cable as protection to cable in trenches complete all as specified and directed.
94S&F in repair steel tubular swaged poles conforming toIS-2713, complete with cast iron base plate, finial taper plug, bolts, nuts & screws, type 410 SP-31 (9 m long) and including painting with two coat of aluminium paint over a coat of primer on exposed surfaces and black bituminous paint on steel surface embeded in concrete and 05 Nos band / strips with black and yellow synthetic enamel paint alternatively, 30 cm wide each at a distance of 30 cm from top of plinth block and numbering of poles complete all as specified and directed. Note:- Excavation, earth work and PCC work will be measured and paid for separately under respective items. Make of Pole:-Calcutta Poles & Tubes / Skipper Limited / Jindal Steel / National tubing Co / Bombay tube & Store Make of paint :- Jotun India Pvt Ltd / Asian Paints / Berger / Jenson & Nicholson Paints Ltd / Shalimar Paints Ltd
95M&L PCC 1:3:6 type C-2 (using 40 mm graded crushed stone aggregate) as in foundation, filling and mass concrete including demolition of old concrete complete all as specified and directed.
96M&L plain cement concrete 1:2:4 type B1, (using 20 mm graded crushed stone aggregate) as in copings, benching and the like etc. including necessary formwork & demolition of old concrete complete all as specified and directed.
97Boring holes horizontally under road, manually, in soft / loose soil, without cutting / disturbing the existing road surface, suitable for inserting pipe of n exc. 100 mm bore at a depth 0.75 m to 1.0 m from road surface for passing of UG cable, getting out and disposal of soil to a distance not exceeding 50 m complete all as specified and as directed. Note:- GI Pipe shall be measured and paid separately.
98S&F in repair 50 mm bore galvanised steel tubing, medium grade with necessary fittings, laid under road crossing, for cable protection complete all as specified and directed. Make - Tata / Jindal Steel / Surya Roshni Ltd. /Bhushan Power & Steel Ltd. / M/s APL Apollo Tubes Ltd
99M&L for cable route indicator for LT UG cable, 1100 Volt grade made out of 4mm thick MS sheet in round shape of dia not less than 200mm, embossed with LT Cable on it, bolted with 2 nut of suitable size at top of 40 x 6 mm MS flat iron of length not less than 1 meter, complete metal surfaces painted with 2 coats of synthetic enamel paint over a coat of primer & bottom of flat iron embedded in PCC 1:3:6 type C2 of size 200mm x 200mm x 500mm (400mm below ground level an 100mm above ground level), exposed surface of concrete painted with 3 coats of white wash including necessary earth work complete all as specified and directed.
100Taking down existing loop in loop out junction box, disconnecting the cable connections and refixing the same loop in loop out junction box with new cable connections including providing new set of aluminium lugs / thimbles of size 10 to 35 sqmm (as reqd) for 3.5/4 core existing LT cable of any type, necessary insulation with tape, clamps for fixing of cables, fittings and fixtures, nut bolts etc complete all as specified anddirected.
101M&L for disconnecting electrical connection of defective / burnt out UG LT cable of any size 2 to 4 core from main switch / DB / Junction boxe / LT Panels, excavating, taking out the required length of existing cable from loop, cutting the defective portion of cable old termination at end, providing new aluminiumthimbles / lugs of suitable size and reconnecting the same with existing location and refilling of cable trench with existing sand and bricks complete all as specified and as directed. Note :- (i) The rate quoted shall deemed to include cost of necessary earth work, matching the disturbed surfaces as per existing. (ii) Additional length of cable or joint required shall be measured and paid seperately
102S&F in repair weather proof cable junction box of size not less than 210 mmx 310 mm x 116 mm with terminals, IP 66 (minimum), suitable for outdoor installation,suitable for 10 to 25 sqmm cable, including 01 No 5/6 Amp MCB, 100 Amp rated 3 pole connector, fixing arrangement with MS flat of size 25 x 3 mm with necessary nuts, bolt and washers complete all as specified anddirected. Make :- Hensel / Sintex Industries Ltd. / C&S electric Ltd. / National
103M&L preparation of old painted surface of existing 9 m long old steel poles with connected cross arms, cable protection pipes, clamps, street light brackets etc, and including applying one coat of aluminium paint on complete height of the pole and applying one coat of synthetic enamel paint upto 1.50 m height (05 Nos band / strips with black and yellow strips alternatively, 30 cm wide each at a distance of 30 cm) from top of of coping with multi colour strips as per the colour code, writing pole details & applying one coat of white wash on pole coping complete all as specified and directed. Make of paint :- Jotun India Pvt Ltd / Asian Paints / Berger / Jenson & Nicholson Paints Ltd / Shalimar Paints Ltd
104S & F in repair powered by inbuilt, isolated electronic LED driver (SMPS based constant current supply) suitable for 120-200 watt LED street lights / flood lights / Post top lantern / Bollard light fittings, site selectable with lower THD, Output Open / Short Circuit protection, Phase to Phase protection, Over Voltage protection, Surge Voltage protection complete all as specified and directed.
105All as per Sl Item No 104.00 above but suitable for 45 to 100 watt LED.
106Supply only surge protection device of capacity 10 KV & make as per existing, suitable for street light / flood light / post top lantern complete all as specified and directed.
107M&L in repair for wiring from LED panel to driver for 120-200 W LED fittings as per existing complete all as specified and directed.
108All as per Sl Item No 107.00 above but suitable for 45 to 100 watt LED.
109M&L earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground in vertical position (earth pit not less than 2.25 m deep below the normal ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to earth lead of galvanised iron strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, all as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point including dismantling old earthing complete all as specified and directed. Note:- The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, RCC 1:1.5:3, type A1 cover slab, 50 mm thick reinforced with 8 mm dia TMT bar @ 140 mm C/C both ways, 10 mm dia plain bar lifting handle embedded in cover slab, Main earthing lead from earth electrode to test point upto 7.5 m length, 20 mm bore medium grade GI watering pipe, 40 mm bore GI medium grade earth lead protection pipe, funnel, wire mesh, copper lugs, charcoal and common salt in alternate layer etc.
110S&F in repairs 12 KW, three phase Nature Switch (using Infrared Sensor technology) based automatic street light timer switch for automatic switching on / off street light based on lux level of nature light (Required Illuminance Level for Switching ON is = 60 Lux and for Switching OFF = 10 Lux). The Sensor should also have part night operation facility of min. 4 hrs to max 12 hrs, consisting of sensor, overload protection fuse gear, 3 Nos contactor, 3 nos Incoming MCBs & 3 nos. Outgoing MCBs of 32-40 Amps each and Circuit wiring (Copper) of min.10 sqmm, terminal blocks for cable entry & control unit enclosed in pole / wall mountable enclosure made out of rust proof, Electric shock proof, termite proof thermoplastic polycarbonate Enclosure (with HINGED LID) conforming to IP66 protection class 2 , complete all as specified and as directed. Make:- Havells / GE / Kakatiya energy system Pvt Ltd / Indo Asian
111S&F in repair 4 pole connector 440V AC complete all as specified and as directed.
112S&F MCCB 4 pole 40 to 63 Amp, breaking capacity 16 kA, Ics = 100% Icu, thermal magnetic release type with adjustable overload setting (0.8-1.0 ln), adjustable short circuit setting (6-10 lr)including necessary modification in the panel & taking down existing MCCB complete all as specified and as directed. Make :- L&T / Havells / Panasonic/ Hager / ABB / Legrand / Indo Asian / HPL
113M&L for complete leak testing of indoor and outdoor units of central AC plant of capacity 48 TR, complete refrigerant pipe with Nitrogen gas, locating the leaks, rectify the leak by brazing / welding and pressure testing the complete systemall as specified and as directed by Engineer-in-Charge.
114Supply and charge refrigerant gas R407 Call as directed by Engineer-in-Charge. Make: Mafron/ Freon/ Floron / Refron / National
115S&F in repair 3 pole contactor of capacity 40 Amp capacity suitable for central AC plant of capacity 48 TR complete all as specified and directed. Make: L&T / Havells / Indoasian / GE / BCH / HPL / C&S / ABB / Siemens
116S&F in repair EWT/LWT sensor suitable for central AC plant of capacity 48 TR complete all as specified and directed.
117M&L for dismantling defective induction motor of 7.5 HP capacity & any make, 415 V, of any duty or any class of insulation from the bed duly coupled with pump, transporting to work shop, removing burnt out winding from stator, rotor and re-winding the same with existing gauge super enameled copper wire of approvedmake and supply & replacing driven end and non driven end bearings, insulation materials, varnishing, heating, reassembling, testing and commissioningcomplete all as specified and directed. Notes :-Motor removed for rewinding shall be overhauled completely and quoted rate shall be deemed to be inclusive for the same.
118Dismantling pump/motor set 7.5 HP and disconnecting water and electric connection removing shaft from impeller and dismantling, grinding, polishing to shaft & suction cover and replacing , Gun metal bushes for shaft , Key for shaft , Graphite packing , water slinger , Gland bush, coupler etc fixing gland rope, greasing and fixing same shaft and impeller and reassembling properly testing all as specified
119Dismantling pump/motor set of capacity 8000 CFM and disconnecting water and electric connection removing shaft from impeller and dismantling, grinding, polishing to shaft & suction cover and replacing, Gun metal bushes for shaft, Key for shaft, Graphite packing, water slinger, Gland bush, coupler etc fixing gland rope, greasing and fixing same shaft and impeller and reassembling properly testing all as specified.
120All as per Sl Item No 119.00 above but for capacity 37500 CFM
121M&L for removing the wornout duct insulation carefully, cleaning / preparation of duct surface by scrapping carefully with wire brush etc. to make the surface completely free of millscale, dirt, dust, grease and other foreign materials, providing new duct insulation, not less than 13mm thick with nitrile rubber insulation with aluminium film reflective surface including taking special care to ensure duct joints sealed against any leakage complete all as specified and directed.
122M&L for taking down 48 TR Chiller package unit direct expansion type outdoor including dismantling the units carefully, chemical cleaning of compressor, condenser tube and control piping, with appropriate cleaning agents, flushing through proper air flow across the coils to improve the cooling efficiency, reassembling & re-installing the units in their original position including replacing defective spare parts and testing & commissioning complete all as directed by Engr-in-Charge. Note : Minor spares required other than spare parts under item No 123 to 127 of BOQ shall considered to be included in the unit rate quoted of this item.
123S & F in repair Scroll compressor suitable for AC plant of capacity 48 TR (Bluestar, Model - XAC2YS-048AR2) and of make as per OEM complete all as specified and directed.
124S & F in repair Filter Drier suitable for AC plant of capacity 48 TR (Bluestar, Model - XAC2YS-048AR2) and of make as per OEM complete all as specified and directed.
125S & F in repair Expansion Valve suitable for AC plant of capacity 48 TR (Bluestar, Model - XAC2YS-048AR2) and of make as per OEM complete all as specified and directed.
126S & F in repair Pressure Controller suitable for AC plant of capacity 48 TR (Bluestar, Model - XAC2YS-048AR2) and of make as per OEM complete all as specified and directed.
127S & F in repair ODU Fan Motor-2 HP suitable for AC plant of capacity 48 TR (Bluestar, Model - XAC2YS-048AR2) and of make as per OEM complete all as specified and directed.
128M&L for complete leak testing of indoor and outdoor units of VRF type AC plant of capacity 28 HP X 2 + 26 HP X 1 (Make- Bluestar), complete refrigerant pipe with Nitrogen gas, locating the leaks, rectify the leak by brazing / welding and pressure testing the complete systemall as specified and as directed by Engineer-in-Charge.
129All as per Sl Item No 128.00 abovebut for VRF AC plant of capacity 18 HP + 24 HP (Make- Bluestar)
130All as per Sl Item No 128.00 abovebut for VRF AC plant of capacity 14 HP + 24 HP (Make- Bluestar)
131Supply and charging R-410A Refrigerant Gas complete all as specified and as directed. Make: Mafron/ Freon/ Floron / Refron
132S & F in repair outdoor fan motor DC8 P, E class, 910 W suitable for VRF unit and of make as per OEM complete all as specified.
133S & F in repair programable circuit board suitable for VRF unit (Bluestar ) and of make as per OEM complete all as specified.
134S&F MCCB 3 pole 63 to 100 Amp, breaking capacity 36 kA, Ics = 100% Icu, thermal magnetic release type with adjustable overload setting (0.8-1.0 ln), adjustable short circuit setting (6-10 lr)including necessary modification in the panel & taking down existing MCCB complete all as specified and as directed. Make :- L&T / Havells / Panasonic/ Hager / ABB / Legrand / Indo Asian / HPL
135S&F MCCB 4 pole 160 Amp, breaking capacity 36 kA, Ics = 100% Icu, thermal magnetic release type with adjustable overload setting (0.8-1.0 ln), adjustable short circuit setting (6-10 lr)including necessary modification in the panel & taking down existing MCCB complete all as specified and as directed. Make :- L&T / Havells / Panasonic/ Hager / ABB / Legrand / Indo Asian / HPL
136S&F in repair butterfly valve 100mm bore, PN 1.6 with necessary rubber gasket, bolts, nuts and washer complete all as specified and as directed by Engineer-in-Charge. Make: Zoloto / L&T/ Audco / Leader
137S&F in repair butterfly valve 80mm bore, PN 1.6 with necessary rubber gasket, bolts, nuts and washer complete all as specified and as directed by Engineer-in-Charge. Make: Zoloto / L&T/ Audco / Leader
138S&F in repair pressure gauge with syphon & valve complete all as specified and directed
139S&F in repair thermometer with valve complete all as specified and directed
140M&L for opening the outer sheets of Air Handling Unit (AHU) to access cooling coil, washing / cleaning of cooling coil externally with mild acid (or caustic soda hot water solution) followed by water jet including cleaning / washing of air filter and re-fixing, complete all as specified and directed by GE.
141S & F in repair Communication module suitable for 48 TR chiller unit (Bluestar) and of make as per OEM complete all as specified and directed.
142S & F in repair AC/DC converter suitable for 48 TR chiller unit (Bluestar) and of make as per OEM complete all as specified and directed.
143S & F in repair condenser water temperature sensor suitable for 48 TR chiller unit (Bluestar) and of make as per OEM complete all as specified and directed.
144S & F in repair discharge pressure sensor suitable for 48 TR chiller unit (Bluestar) and of make as per OEM complete all as specified and directed.
145S&F in repair of single phase preventor 40V AC asymmetry including connecting accessories complete all as specified. Make :- L&T / Havells / Panasonic/ Hager / ABB / Legrand / Indo Asian
146S&F in repair Intermediate relay 220V AC including connecting accessories complete all as specified. Make :- L&T / Havells / Panasonic/ Hager / ABB / Legrand / Indo Asian
147S&F in repair microprocessor controller cord module for chilled water system suitable for 48 TR chiller unit (Bluestar) and of make as per OEM complete all as specified and directed.
148S&F in repair liquid level sensor suitable for 48 TR chiller unit and of make as per OEM complete all as specified and directed.
149S&F in repair Solenoid Coil suitable for 48 TR chiller unit and of make as per OEM complete all as specified and directed.
150S&F in repair Oil Filter suitable for 48 TR chiller unit and of make as per OEM complete all as specified and directed.
151S&F in repairDP switch suitable for 48 TR chiller unit and of make as per OEM complete all as specified and directed.
152S&F in repair PRE filter 10 micron, a layer of non woven media stitched along with layer of GI wire mesh on the downstream side to obtain required filtration and efficiency, pleats separated by spacers for maximum air flow of size 610x610x50mm complete all as specified and directed.
153S&F in repair Suction pressure sensor suitable for 48 TR chiller unit and of make as per OEM complete all as specified and directed.
154S&F in repair of V belt A/B Series as per site requirement complete all as specified and directed. Make : Fenner/Dunlop
155S&F in repair of Timer 3-30 Secondscomplete all as specified and directed. Make :- L&T / Legrand / Siemens / ABB / Schnieder / Havells
156S&F in repair of overload relay type MN-2 range 24-40 A complete all as specified and directed. Make :- L&T / Legrand / Siemens / ABB / Schnieder / Havells
157S&F in repair digital ammeter 0 - 500 Amp, 3 phase, accuracy class 1 with LED display & in-built selector switch complete all as specified and directed. Make:- Havells India Ltd. / HPL India Ltd. / L&T / AE / Schneider / BCH
158S&F in repair digital voltmeter 0-520 volts (P-P), 3 phase, accuracy class 1 with LED display & in-built selector switch complete all as specified and directed. Make :- Havells India Ltd. / HPL India Ltd. / L&T / AE / Schneider / BCH
159S&F in repair on-load change over switch 400 Amp capacity, 3 phase, 415 volts suitable for panel mounting complete all as specified and directed. Make:- L&T / Legrand / ABB / Siemens / Schnieder / Havells India Ltd./ Indo Asian