Andaman Public Works Dept-APWD has published Construction Of 04 Nos. Type-Iii Quarters Under Gpa At Naveen Nagar Under Sd-V, Cd, Apwd, Diglipur Sw- Supply Installation Testing Commissioning Of 02 Nos. 1.5 Ton And 10 Nos 2.0 Ton Air Conditioners In Division Office Of Apwd, Department Under Cd, A. Submission Date for this Tender is 30-05-2024. Air Conditioner Tenders in diglipur Andaman And Nicobar Islands. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Wiringforlight/powerplugwith 2X4sq.mmFRLSPVC insulatedcopperconductorsinglecorecableinsurface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
2 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
3 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
4 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar,din bar,interconnections,powderpaintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator) |
5 | 12 way , Double door |
6 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of followingpolesintheexistingMCBDBcompletewith connections, testing and commissioning etc. as required. |
7 | Single pole |
8 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
9 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
10 | 40 A |
11 | Supplying, installation, testing and commisioning offollowing Ton Capacity BEE 5 star( as per2018/2022 BEE Star rating)Inverter High wall SplitType AirConditioner (1 phase,220V), make: HITACHI, Kashikoi 5100X InverterModel No 2.0 TR - RMRG524HEEA and 1.5 TR- RSRG518HEEA or its equivalentwith with copper condenser coil wall bracket, providing standard length of refrigerant copper pipe including cutting drilling holes on the wall for passing gas pipe, cementing, painting to give an smooth finishand wrapping PVC Non adhesive white tape over insulation of gas pipe etc. as required. |
12 | 1.5 Ton |
13 | 2.0 Ton |
14 | Supplying installation testing and commissioning of following rating electronic voltage stabilizer single phase including connection etc. as required.Make V Guard Model VND 400 & VND 500 or its equivalent. |
15 | 4 KVA |
16 | 5 KVA |
17 | Supplying and fixing ofACDB of 20A including MCB with top (plastic enclosure) similar to Havells Cat No.DHDPHDP020 or its equivalent. |
18 | Providing and fixing extra length of refrigerant copperpipes of following sizes (Suction & delivery) of split type AC i/c providing 2.5 sqmm, 4-core electrical cables, insulation, extra gas charging and covering with PVC non adhessive tape over the insulation of refrigerant pipes as per the direction of E-in-C. |
19 | Refrigerant pipes of Sizes 5/8" & 1/4" |
20 | Supplying and fixing of 20mm size of PVC pipe along with accessories for fixing as drain pipe to IDU ofsplit type Air conditioner in surface/recess make: PRECISION or equivalent including connections usingelbows, etc. as required. |
21 | Supplying and fixing Single door 4-way, sheet steel, MCB distribution board, on surface, complete with necessary connetions, make : Anchor : 98292. |
22 | Supplying and fixing of FP MCCB of 10kA, 40Amps make : Havells cat No. IHLGSF0040 including sheet steel enclosure make : Havells cat No. IHEGEP or equivalent including necessary connecions etc. as required. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy