Tender For Repair And Replacement Of Street Lights, High Mast Lights, Isolation Transformers, Voltage Stabilizers, Overhead Lines, Painting Of Steel Poles And Allied Works At 46 Weu, 273 Su And 20 Wing Afs Bagdogra Under Ge (Af) Bagdogra, bagdogra-West Bengal

Military Engineer Services-MES has published Tender For Repair And Replacement Of Street Lights, High Mast Lights, Isolation Transformers, Voltage Stabilizers, Overhead Lines, Painting Of Steel Poles And Allied Works At 46 Weu, 273 Su And 20 Wing Afs Bagdogra Under Ge (Af) Bagdogra. Submission Date for this Tender is 12-06-2024. Voltage Stabiliser Tenders in bagdogra West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

43443654
Tender For Repair And Replacement Of Street Lights, High Mast Lights, Isolation Transformers, Voltage Stabilizers, Overhead Lines, Painting Of Steel Poles And Allied Works At 46 Weu, 273 Su And 20 Wing Afs Bagdogra Under Ge (Af) Bagdogra
Open Tender
Indian
West Bengal
bagdogra
12-06-2024

Tender Details

Repair And Replacement Of Street Lights, High Mast Lights, Isolation Transformers, Voltage Stabilizers, Overhead Lines, Painting Of Steel Poles And Allied Works At 46 Weu, 273 Su And 20 Wing Afs Bagdogra Under Ge (Af) Bagdogra

Key Value

Document Fees
INR 500 /-
EMD
INR 46000.0 /-
Tender Value
INR 23 Lakhs /-

BOQ Items

Name of Work: Repair and replacement of street lights, high mast lights, isolation transformers, voltage stabilizers, overhead lines, painting of steel poles and allied works at 46 WEU, 273 SU and 20 Wing AFS Bagdogra under GE (AF) Bagdogra.
Sl. No. Item Description
1Repair of Street Lights, high mast light at Domestic, Tech & OMQ area Taking down old unserviceable light fittings from pole/wall after disconnection the connecting wires of any type or size and S&F in replacement of Energy efficient LED Street Light/ Roadway Luminaire, high PF, 60W, 6000K, energy saving and environmental friendly long life versatile pressure die cast aluminium housing, toughened glass cover, IP 66 protection, 240V, using 1.5 Sqmm, PVC insulated sheathed three core multistranded copper conductor cable, 1100V grade (upto 3.0 Mtr) for connection passing through bracket/pole as per site requirement, testing & commissioning and complete all as specified and directed.
2All as per item No. 1.00 above, but for energy efficient LED Street Light/ Roadway Luminaire, high PF, 90W, 6000K complete.
3Taking down old unserviceable light fittings from pole/wall after disconnection the connecting wires of any type or size and S&F in replacement ofEnergy efficient LED Flood light Luminaire, high PF,80W, energy saving and environmental friendly and efficacy of not less than 110 Lm/w, long life versatile pressure die cast housing IP 66 protection, 240V, using 2.5 Sqmm, PVC insulated sheathed three core copper conductor cable, 1100V grade (upto 3.0 mtr) for connection etc as per site requirement, testing & commissioning and complete all as specified and directed.
4All as per item No. 3.00 above, but for Energy efficient LED Flood light Luminaire, high PF, 120W complete.
5All as per item No. 3.00 above, but for Energy efficient LED Flood light Luminaire, high PF, 150W complete.
6All as per item No. 3.00 above, but for Energy efficient LED Flood light Luminaire, high PF, 250W complete.
7S&F in repair, LED post top Lantern E-Top 30 Watt with low glare optical design acrylic opal diffuser with spigot made up of cast aluminium and wired with all accessories, 240V, including taking down of old unserviceable light fitting, pre-wired using 1.5 Sqmm, PVC insulated sheathed three core multistranded copper conductor cable, 1100V grade (Upto 3.0 RM) for connection passing through PVC Conduit or pole, from junction box to light fitting as per site requirement, testing & commissioning and complete all as specified and directed.
8S&F in repair, 9/10 watt LED Bollard decorative light Glaze fitting with low glare diffuser including taking down of old unserviceable light fitting and necessary PCC work 1:2:4 of adequate size for fixing of bollard fitting as per site requirement, testing & commissioning and complete all as specified and directed. Make:HPL Cat No. HPLLEDB9Wor equivalent make of C&S/Crompton/Bajaj/ Havells.
9S&F in repair, LED aviation light fitting 10Watt, 240V with comprising of aluminium housing with red polycarbonate dome for better illumination, 302 x 5mm LED, IP 66 protection including taking down of old unserviceable light fitting complete all as per site requirement and complete all as specified and directed. Make: Bajaj Cat Part No BGAV 302 LED or equivalent make ISI Mark as approved.
10S&F in repair, PVC weather proof, hinged door, junction box with 240V, Neutral link, three phase connector, with IP 66/67 protection suitable for outdoor installation on pole/wall surface and including with 1 No MCB SP of 6 Amps, necessary fixing arrangement such as clamps, nut, bolts, etc including dismantling old unserviceable junction box complete all as specified and directed. Make: Sintex Cat Part No. GSMB 2520, Hensel Cat Part No KF 2500H or equivalent of ISI Mark as approved.
11Supply, fixing and connecting in replacement of PVC insulated sheathed multistranded 3 core cable FR grade of size 4.0 sqmm with copper conductor including passing through PVC conduit along the pole, on wall surface or in trenches from existing light fitting to existing junction box and all as per site requirement and complete all as specified and directed.
12All as per item No. 11.00 above, but for PVC insulated sheathed 3 core cable of size 2.5 sqmm with copper conductor complete.
13All as per item No. 11 above, but for PVC insulated sheathed 3 core cable of size 1.5 sqmm with copper conductor complete.
14Repair of Street light, Security light at 46 WEU Taking down old unserviceable light fittings from pole/wall after disconnection the connecting wires of any type or size and S&F in replacement of Energy efficient LED Street Light/ Roadway Luminaire, high PF, 60W, 6000K, energy saving and environmental friendly long life versatile pressure die cast aluminium housing, toughened glass cover, IP 66 protection, 240V, using 1.5 Sqmm, PVC insulated sheathed three core multistranded copper conductor cable, 1100V grade (upto 3.0 Mtr) for connection passing through bracket/pole as per site requirement, testing & commissioning complete all as specified and directed.
15All as per item No. 14.00 above, but for energy efficient LED Street Light / Roadway Luminaire, high PF, 90W, 6000K complete.
16Taking down old unserviceable light fittings from pole/wall after disconnection the connecting wires of any type or size and S&F in replacement ofEnergy efficient LED Flood light Luminaire, high PF,80W, energy saving and environmental friendly and efficacy of not less than 110 Lm/w, long life versatile pressure die cast housing IP 66 protection, 240V, using 2.5 Sqmm, PVC insulated sheathed three core copper conductor cable, 1100V grade (upto 3.0 Mtr) for connection etc as per site requirement, testing & commissioning and complete all as specified and directed.
17All as per item No. 16.00 above, but for Energy efficient LED Flood light Luminaire, high PF, 150W complete.
18S&F in repair, LED Highbay, 80W LED, with high luminous efficacy upto = 100 LPW IP66 protected, front toughened glass, with discrete high lumen LED, energy saving, long life with all accessories, 240V, using 2.5 Sqmm, PVC insulated sheathed three core multistranded copper conductor cable, 1100V grade for connection passing through PVC Conduit upto 25mm size as per site requirement, testing & commissioning and complete all as specified and directed.
19All as per item No. 18.00 above, but for LED Highbay, 120W LED complete.
20S&F in repair, LED post top Lantern E-Top 30 Watt with low glare optical design acrylic opal diffuser with spigot made up of cast aluminium and wired with all accessories, 240V, including taking down of old unserviceable light fitting, pre-wired using 1.5 Sqmm, PVC insulated sheathed three core multistranded copper conductor cable, 1100V grade (Upto 3.0 RM) for connection passing through PVC Conduit or pole, from junction box to light fitting as per site requirement, testing & commissioning and complete all as specified and directed.
21S&F in repair, 9/10 watt LED Bollard decorative light Glaze fitting with low glare diffuser including taking down of old unserviceable light fitting and necessary PCC work 1:2:4 of adequate size for fixing of bollard fitting as per site requirement, testing & commissioning and as directed. Make:HPL Cat No. HPLLEDB9Wor equivalent make of C&S/Crompton/Bajaj/ Havells.
22S&F in repair, LED aviation light fitting 10 watt, 240 V with comprising of aluminium housing with red polycarbonate dome for better illumination, 302 x 5mm LED, IP 66 protection including taking down of old unserviceable light fitting complete all as per site requirement and complete all as specified and directed. Make: Bajaj Cat Part No BGAV 302 LED or equivalent make ISI Mark as approved.
23S&F in repair, PVC weather proof, hinged door, junction box with, 240V, Neutral link, three phase connector, with IP 66/67 protection suitable for outdoor installation on pole/wall surface and including with 1 No MCB SP of 6 Amps, necessary fixing arrangement such as clamps, nut, bolts etc including dismantling old unserviceable junction box complete all as specified and directed. Make: Sintex Cat Part No. GSMB 2520, Hensel Cat Part No KF 2500H or equivalent of ISI Mark as approved.
24Supply, fixing and connecting in replacement of PVC insulated sheathed multistranded 3 core cable FR grade of size 4.0 sqmm with copper conductor including passing through PVC conduit along the pole, on wall surface or in trenches from existing light fitting to existing junction box and all as per site requirement and complete all as specified and directed.
25All as per item No. 24.00 above, but for PVC insulated sheathed 3 core cable of size 2.5 sqmm with copper conductor complete.
26All as per item No. 24.00 above, but for PVC insulated sheathed 3 core cable of size 1.5 sqmm with copper conductor complete.
27Taking down and replacement of brackets made out of 40mm bore GI pipe, medium grade, 1.5M long, bend to shape and fixing with MS clamps made out of flat iron, with replacement of necessary nuts, bolts, washers etc and painting of bracket and clamps with 2 coats of synthetic enamel paint over a coat of red oxide zinc chromate primer complete as per site requirement and complete all as specified and directed.
28Taking down and replacement of existing unserviceable clamps with new clamps made out of 40x6 mm bending to shape, drilling holes for bolts suitable for fixing GI pipe bracket to steel pole, made in two halves, including nuts, bolts, washers and painting with two coats of aluminium paint over a coat of red oxide primer, complete as per site requirement and complete all as specified and directed.
29M&L for rigid non-metallic, ISI marked, PVC conduit, smoke free, fire retardant and temp stable quality of size 25mm external dia exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers etc, and including all fixing accessories such as couplers, lock nuts, saddles/clamps, pipe hooks for securing of electric wires/cables of any type and size as laid alog the pole or on wall surface of ISI make as approved complete all as specified and directed.
30All as per item No. 29.00 above, but of size 32mm external dia complete.
31S&F in repair, rigid non-metallic PVC bend, FRLS grade of size 25mm external dia including all fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc, all as per site requirement and complete all as specified and directed.
32All as per item No. 31.00 above, but of size 32mm external dia complete.
33S&F Junction box with lid and screws of 25mm external dia upto 4 way of ISI make complete all as specified and directed.
34All as per item No. 33.00 above, but of size 32mm external dia complete.
35Taking down and replacement of existing unserviceable clamps with fixing new clamps made out of 25x4 mm MS flat bending to shape, drilling holes for bolts suitable for securing of PVC conduit upto 32 mm dia along the pole or wall from Light fitting to junction box, including nuts, bolts, washers and painting with two coats of aluminium paint over a coat of red oxide primer, complete all as specified and directed.
36M&L for earthing complete with GI earth plate 60x60cmx6mm thick electrode and 4mm dia GI wire as earthing lead, burried directly in ground (earth pit not less then 2.25 metres deep below ground level) with top edge of the plate not less then 1.5 metres below normal ground level, connected to GI wire earth lead 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 5 and incl earth work, PCC pit and RCC cover, watering pipe 20 mm dia light grade, funnel, wire mesh, protection pipe 15 mm dia light grade up to 7.5 mtr length of earth wire, charcoal dust and salt etc and connected to earthing test point complete all as specified and directed.
37M&L for earth continuity conductor /main earthing lead fixed to wall/batten or recess/chases or buried in ground or drawn in conduit /pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire complete all as specified and directed.
38Repair to Isolation Transformers, voltage stabilizers at 273 SU M&L for online dehydration, filtration and cleaning of transformer oil, isolation transformer/ Servo voltage stabilizer etc at different locations by suitable dehydration plant testing of oil sample before and after dehydration for each transformer/equipment and results of transformer insulation oil minimum upto 11 KV with 2.5mm gap, recorded jointly by contractor and Engineer-in-Charge complete including all necessary tools, plants, transportation etc all as specified/directed by Engineer-in-Charge. Note: (i) Oil for toping up/fresh fill shall be measured and paid separately under relevant item. (ii) Certificate for oil testing result before and after filtration shell be submitted to Engr-in-Charge.
39M&L for toping up oil level with and including new insulating oil conforming to IS-335 including all necessary tools, plants, transportation etc complete all as specified and directed. Note: Certificate from manufacturer for oil testing result shell be submitted to Engr-in-Charge immediately after topping up.
40M&L for preparation of surface for steel poles painting of any size by scrapping damaged paint and painting with two coats of silver aluminium paint and writing pole No with black paint on yellow circuit the bottom of pole to be painted with yellow and black paint as per the existing complete all as specified and directed.
41All as per item No 40.00 above, but 2 pole structure complete with all structural steel complete.
42All as per item No 40.00 here-in-before, but 4 pole structure complete with all structural steel.
43M&L for preparation of surface for Isolation transformer/Servo Stabilizer of any type or capacity, painting by scrapping damaged paint and painting with two coats of suitable paint as per existing one and writing MES/MS No with white paint on black circuit all as directed by Engineer-in-Charge complete all as specified and directed.
44M&L for dismantling isolation transformer/ Servo voltage stabilizer for repairs of any make of single phase upto capacity of 5 KVA, including transportation to workshop by removing coils, laminations, tank cleaning, reassembling of core and winding, with old serviceable parts and rewinded coils and other new parts in replacement of damaged parts, including brazing, soldering sleeveing and insulating etc as required and oven drying of core assembly all as per site requirement and directed. Note: (i) Replacement of unserviceable nuts/bolts/ washer to be done within the quoted rate. (ii) Other spares as required shall be measured and paid separately under relevant items.
45All as per item No. 44.00 above, but three phase 5 to 20 KVA complete.
46All as per item No. 44.00 here-in-before, but three phase 25 to 75 KVA complete.
47All as per item No. 44.00 here-in-before, but three phase 100 to 200 KVA complete.
48All as per item No. 44.00 here-in-before, but three phase but above 200KVA to 630 KVA complete.
49Supply only in repair of Under voltage, over voltage and surge protection display (display only) kit at out put section complete suitable for isolation transformer/ Servo voltage stabilizer of any make and capacity upto 20 KVA complete all as specified and directed. Make: Siemens/ L&T or other equivalent & approved make.
50All as per item No. 49.00 above, but capacity above from 20 KVA and upto 200 KVA complete.
51Dismantling only in repair of Under voltage, over voltage and surge protection kit complete of VCT D2 din rail mounting variant with digital display, auto/manual reset (timing and monitoring relay) complete protection kit suitable for isolation transformer/ Servo voltage stabilizer of any make and upto 20 KVA capacity complete all as specified and directed.
52All as per item No 51.00 above, but from 25KVA to 50 KVA complete.
53All as per item No 51.00 here-in-before, but from 200KVA / 315 KVA complete.
54Dismantling and fixing after minor repairing and maintenance of Servo control board and performing suitable repairing and servicing at site, testing the same after required servicing complete for single phase Servo Stabilizers complete all as specified and directed.
55All as per item No. 54.00 above, but for three phase servo stabilizers complete.
56Supply only in repair ofServo control card suitable for Servo voltage stabilizer of any make and single phase all as specified and directed by Engr-in-Charge.
57All as per Item No. 56.00 above, but for three phase complete.
58Supply only in repair of servo motor starting torque of 3KG/Cm complete with necessary fixing arrangements all as specified and directed. Make: L&T/Siemens/HPL.
59All as per Item No. 58.00 above, but for 10 KG/Cm complete.
60All as per Item No. 58.00 here-in-before, but for 20 KG/Cm complete.
61Supply only in repair of Limit switch suitable for isolation transformer/Servo voltage stabilizer of any make and capacity all as specified and directed by Engr-in-Charge.
62Supply only in repair of Carbon brush suitable for Servo voltage stabilizer of any make and capacity all as specified and directed by Engr-in-Charge.
63Supply only in repair of manual change over switch, single phaseMCB change over type suitable for Servo Stabilizer and Isolation Transformer upto 10 KVA capacity complete all as specified and directed.
64All as item No 63.00 above, but Auto change over complete.
65Supply only in repair of Manual change over switch, three phase MCB change over type suitable for Servo Stabilizer and Isolation Transformer of upto 10KVA to 50KVA capacity complete all as specified and directed.
66All as item No 65.00 above, but from 75KVA to 100 KVA capacity complete.
67Supply only of Isolation Transformer over load control card with out cut off relay suitable for any three phase isolation transformer complete all as specified and directed.
68Supply only in repair of DT Switch suitable for isolation transformer of any make and capacity as per site requirement all as specified and directed by Engr-in-Charge.
69Supply only in repair of DT Switch suitable for Servo voltage stabilizer of any make and capacity as per site requirement all as specified and directed by Engr-in-Charge.
70Supply only in repair of selector switch Volt/Amps 3 position complete with necessary fixing all as specified and directed by Engineer-in-Charge.
71Supply only in replacement of new copper coil of short circuit /over heated winding Isolation transformer and servo voltage stabilizer of any make and upto 10 KVA capacity with matching gauge and turns of super enamelled copper winding wire complete with leathered paper, glass sleeves, varnishing, baking etc all as specified and directed by Engr-in-Charge.
72All as per item No. 71.00above, but capacity above 10 KVA and upto 630 KVA complete.
73Supply only in repair of Digital type Voltmeter 0-500 Volt, complete with necessary fixing all as specified and directed by Engineer-in-Charge.
74Supply only in repair of ammeter 0-250 amps, Digital type, with CT operated complete with necessary fixing all as specified and directed by Engineer-in-Charge.
75M&L for taking out old unserviceable MCCB TPN/FP from existing Feeder pillar/ LT panel board and supply and fixing MCCB TPN/FP 63 amps capacity, rup capacity 16 KA, 415 Volts, 50 Hz including necessary modification in panel board for incoming and outgoing cable connection with replacement of brunt lugs of suitable size for aluminium conductor cable, nuts bolts etc as per site requirement and complete all as specified and directed.
76All as per Item No 75.00 above, but 100 amps capacity, 16 KA complete.
77All as per Item No 75.00 here-in-before, but 125 amps capacity, 16 KA complete.
78All as per Item No 75.00 here-in-before, but 160 amps capacity, 36 KA complete.
79All as per Item No 75.00 here-in-before, but 200 amps capacity, 36 KA complete.
80All as per Item No 75.00 here-in-before, but 250 amps capacity, 36 KA complete.
81All as per Item No 75.00 here-in-before, but from 350 amps to 400 amps capacity, 36 KA complete.
82NOTES :- 1.The amount of schedule of credit shall be deducted from the total of this BOQ for arriving at contract sum.