Military Engineer Services-MES has published Tender For Special Repair/ Replacement Of Existing Cemented Two Pole Structure Into Four Pole Structure In Argum Line Feeder Under Ge Kamptee. Submission Date for this Tender is 19-06-2024. Feeder Pillar Tenders in kamptee Maharashtra. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 12-Jun-2024 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 19-06-2024 |
FileName | File Description | File Size |
a183b423-3a33-4db4-800f-bf1e1cbe0008.html | Tender Notice | 0 KB |
BOQ_733490.xls | Tender Document | 0 KB |
Tender.pdf | Tender Document | 0 KB |
Tendernotice_1.pdf | Tender Document | 0 KB |
Sl. No. | Item Description |
1 | Dismantling of old unserviceable two pole structures, PCC of any size and type complete all as specified and directed. |
2 | Dismantling of old cross arms/ angles, sections /MS channel etc of any size and type complete all as specified and directed. |
3 | Dismantling of old insulators of any type and size complete all as specified and directed. |
4 | Dismantling of old ACSR or AAC conductors complete all as specified and directed. |
5 | Dismantling and taking down of existing gang operated device of any type and size and re-fixing the same on new four pole structure complete all as specified and directed. |
6 | Dismantling and taking down of existing lightening arrestor of any type and size and re-fixing the sameon new four pole structure complete all as specified and directed. |
7 | Supply, installation, commissioning and testing of air break switch, gang operated HT 11 KV triple pole outdoor type with 12 insulator, 200 amps rating with drop out fuse assembly with fuse carrier and the fuse element mounted on insulator and steel frame, mechanically operated with opertaing mechanism consisting of operating rod of 25mm bore, light grade GI pipe of suitable length, operative from ground level and with locking arrangement with MS flat iron clamp 50 x 6mm including MS channel of suitable size and length to fixing GOD including nuts, bolts and washers complete all as specified and directed. |
8 | Supply and fix single pole, 9KV, horn gap non linear meta oxide resistance surge lightening arrester as per IS-3070 (Part-I) 1985 suitable for working voltage of 11KV with rated system voltage of 12 KV, outdoor type, maximum continuous operating voltage not less than 7.65 KV(rms), nominal discharge current 10 KA (peak), power frequency reference not less than MCOV, max residual voltage for discharge current of 10KA and 8/20 micro sec-current wave 40 KVp, long duration discharge class II (as per IEC), pressure relief class/ current-A/40 KA, 28/75 KV insulationg level, 29.9 KV switching residual discharge voltage, 100 KA (peak) and 25mm/KV minimum creaping distance of highest system voltage with all fittings complete all as specified and directed. |
9 | Supply, erecting, fixing of steel tubular swaged pole (410 SP - 55) 11 metre long conforming to IS-2713 (Part I & II) 1980 complete with cast iron base plate, pole cap/ finial taper plug, bolts, nuts and washers, welded, reduced section and longitudinal weld through out entire length of pole with and including 2 coats of black bituminous paint, internally and externally upto planting depth and remaining exterior portion of pole finished with two coat of aluminium paint over a coat of red oxide primer with and including two coats of synthetic enamel paint in 30cm wide bands/ strips around the poles alternatively with black and red radium strips upto height of 1.5m from top of PCC coping of the pole and including writing pole No in 8cm height letter with black enamelled paint in a circle of 20cm dia with base of synthetic enamelled paint (colour approved by GE) on pole at above top most band with and including necessary excavation and earth work in any type of soil, returning, filling in and disposal of surplus soil to a distance not exceeding 50 mtr, PCC (1:4:8) type D-2 (using 40mm graded sand stone aggregate) in the base and foundation upto ground level and PCC (1:3:6) type C-1 (using 20mm graded black trap /granite /basalt stone aggregate) for coping as per TD drawing complete all as specified and directed. Note:- Cross arms, danger notice board, anti climbing device shall be measured and paid separately. |
10 | Material and labour for cross arms, bracings, supports, clamps and back plates fabricated from steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one coat primer, one under coat and one finishing coat of aluminium paint complete all as specified and directed. |
11 | Supply and fixing danger notice board of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts for HT 25x20 cm size complete all as specified and directed. |
12 | Supply and fixing pin type insulator, vitreous, white, brown or green including one galvanised MS spindle two GI washer and one GI nut of size 150mm height, 150mm dia for 11000 volt grade complete all as specified and directed. |
13 | Supply, fixing, stringing of aluminium conductor steel reinforced (ACSR) including binding wire for binding to aluminium conductor properly on insulators at least 50mm on existing/new pole over head lines, jumpring, connection and jointing and testing complete all as specified and directed. |
14 | Material and labour for earthing as in replacement, complete with galvanised earth plate electrode 600 x 600 x 6mm thick buried directly in ground vertically to a depth not less than 2.25 m below normal ground level with top edge of the plate not less than 1.5m below normal ground level, connected to and including galvanised steel strip 32x6mm as earth lead, soldered and riveted to earth plate by means of nuts, bolts, check nuts & washers of galvanised iron or steel with connected to test point and testing on completion including 20mm pipe medium grade for earth lead protection from earth point to earth plate, including provn of adequate quantity of charcoal dust mixed with 35% common salt to a packed thickness of not less than 15cm in alternate layers of charcoal and salt on all sides of earth plate with 40mm bore GI pipe medium grade for watering, GI check nut, funnel and wire mesh with and including all necessary excavation & earth work in soft/loose soil, returning filling in, removal of surplus soil to a distance 50mtr, PCC 1:3:6 type C-1 as in earth pit, 40mm thick RCC cover using cement concrete 1:2:4 type B-1 reinforced with & including 8mm dia mild steel TMT bar @100mm c/c both way with suitable handle for lifting arrangement & including form work as specified and as shown in electrical plate No 3 of MES SSR Part-I 2009 complete all as specified and directed. Notes:- On testing, after completion of Job, if desired earth resistance is not obtained, the earthing shall be redone at without any extra cost by contractor. |
15 | NOTE : SCHEDULE OF CREDIT (Amount on page No 33 shall be deducted offline from the total quoted amount to arrive at the net contract sum to be considered for acceptance.) |