Tender For Repair/Maintenance Of Vcbs/Acb/Rmu, Ht Feeder Pillars, Calibration Of Vcb And Allied Services At Afs Phalodi., phalodi-Rajasthan

Military Engineer Services-MES has published Tender For Repair/Maintenance Of Vcbs/Acb/Rmu, Ht Feeder Pillars, Calibration Of Vcb And Allied Services At Afs Phalodi.. Submission Date for this Tender is 03-06-2024. Electrification Work Tenders in phalodi Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

43354013
Tender For Repair/Maintenance Of Vcbs/Acb/Rmu, Ht Feeder Pillars, Calibration Of Vcb And Allied Services At Afs Phalodi.
Open Tender
Indian
Rajasthan
phalodi
03-06-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Tender For Repair / Maintenance Of Vcbs / Acb / Rmu, Ht Feeder Pillars, Calibration Of Vcb And Allied Services At Afs Phalodi.; 1 Carrying Out Calibration Of Ht Vcb Panel Including Vcb 800 / 630 / 400 Amps, Make:Abb, After Taking Proper Shut Down And Disconnecting The Cables From Panel And Vcb Breakers, Calibration Of Over Fault Relay, Earth Fault Relay, Checking Of Alignment Of Vcb Isolating Contacts, Rewiring Of Burnt Out / Unsv Vcb Panel Wiring Complete, Servicing Of Operating Mechanism Including Tripping And Closing System Of The Breakers, Dehydrating, Decorbonising Of Panel, Bus Section & Circuit Section Including Incoming / Outgoing Cable And Necessary Ht Insulation At Joints. Removing Perished Monoplus Compound Cleaning And Re-Insulating With Ht Taps Wherever Necessary, With And Including Replacement Of Burnt Out / Defective Spares Like Tension Springs, Tortion Springs, Nut Bolts, Washers Of Suitable Size, Lingers Etc., Under The Supervision Of M / S Abb Or Authorised Dealer / Representative, And Refixing The Panel In Its Original Position With Complete Painting Of Vcb Panel And Testing Entire Satisfaction Of Engineer -In- Charge. Note : ( I ) The Quoted Rate Shall Be Deemed To Include All Minor Spares Etc., ( Ii ) If Any Burnt Out / Defective Items Like Moving / Fixed Contacts, Tripping Coils, Earth Fault Relay, Etc., Will Be Measured And Paid Separately Under Respective Items. ( Iii ) Spare Parts Required Other Than Mentioned Here-In-After Shall Be Deemed To Be Included In The Quoted Rate. 2 Supply And Fix The Following Spares For Vcb 800 / 630 / 400 Amps Capacity, Make:Abb, Type :- Vd4 12.12.25 Note: The Spares Shall Be Measured And Paid Only Requirement At Site During Servecing Of VcbS ( A ) Supply And Fix Master Trip Relay Abb Mechanical 4No + 4Nc , 110 V For Vcb 800 / 630 / 400 Amps Capacity, Make:Abb, Type :- Vd4 12.12.25 3 ( B ) Supply And Fixspring Drum Cat Part No: V4205, Ivyn300950-020 . 4 ( C ) Supply And Fix Spring Cat Part No: V4206, Gce9478006p0102. 5 ( D ) Supply And Fix Spring Charging Motor 230V Dc / Ac Cat Part No V6037, Ivyn300951-002. 6 ( E ) Supply And Fix Tripping / Closing Coil-110Volt Dc Cat Part No: V6084, In54450007-Ab. 7 ( F ) Supply And Fix Emergency Trip Assembly Cat Part No: V6107, Vyn400901-Af. 8 ( G ) Supply And Fix Vacuum Intrupterof Vd4 Type For Vcb. 9 ( H ) Supply And Fix Lever Cat Part No: Ivyng00950-114 Of Vb4 Type Vcb. 10 ( I ) Supply And Fix Roller Cat Part No: V6030 Of Vb4 Type Vcb . 11 ( J ) Supply And Fix Latest Generation Slr140c, Dual Rated Ct, 3 Phase Over Current Relay And Earth Fault Relay Auxiliary Supply 18 -135 Volt Ac / Dc+ / - 15% Operated For Vcb All As Specified And As Directed. Make:- L&T / Abb / Avana / Stelmec 12 Supply And Fix Trivector Meter, 3 Phase 4 Wire ( Kwh, Kvarh, Kvah, Kw, Kva ) , - / 100V / V3, - / 5A, 50Hz Ref Temp: 27°C, Cl: 0.5S, Lb : 5A, Imax:10A, 16000Pulses / Unit Make : Secure Model : Premier 300 Or Equivalent Make 13 Carrying Out Calibration Of Acb Panel Including Acb 630 Amps, Make :Abb, After Taking Proper Shut Down And Disconnecting The Cables From Panel And Acb Breakers, Calibration Of Over Fault Relay, Earth Fault Relay, Checking Of Alignment Of Acb Isolating Contacts, Servicing Of Operating Mechanism Including Tripping And Closing System Of The Breakers, Dehydrating, Decorbonising Of Panel, Bus Section & Circuit Section Including Incoming / Outgoing Cable And Necessary Lt Insulation At Joints. Removing Perished Monoplus Compound Cleaning And Re-Insulating With Lt Taps Wherever Necessary, With And Including Replacement Of Burnt Out / Defective Spares Like Tension Springs, Tortion Springs, Nut Bolts, Washers Of Suitable Size, Lingers Etc., Under The Supervision Of M / S Abb Or Authorised Dealer / Representative, And Refixing The Panel In Its Original Position And Testing Entire Satisfaction Of Engineer -In- Charge . 14 M&L For Repairing / Servicing, Calibrating / Testing / Setting Of Fault Tripping Andrecommissioning With Painting Complete As Mentioned In Maintanceand Operation Manual Of 11 Kv Ht Rmu Sf6 Breaker 1 Way / 3 Way / 4 Way / 6 Way All As Per Oem Instructions. ( Make:- Cg / Abb ) ( Note : Sf6 Gas Charging Will Be Measured And Paid Seperately ( I ) Repairing / Servicing Shall Be Carried Out Through O.E.M Of Manufactures Engineering / Technician Only. ( Ii ) Cost Of Small Spares Like Gasket, Battery, O Ring Nuts, Bolts And Lubricants / Cleaning Required For Servicing Of Rmu Is Deemed To Be Included In The Coated Rate. However Cost Of The Major Spare Parts Will Be Measured And Paid Separatly Under Revelant Items Of SchA. ( Iii ) Job Of Repairing / Servicing / Calibrating / Testing / Setting Of Fault Tripping Andrecommissioning Has Been Considered Forcomplete Set Of RmuS I.E 1 Way / 2Way / 3 Way / 4 Way / 6 Way As Per Location 15 M&L For Gas Charging Breaker By Using Sf 6 Gas All As Specified And Directed. 16 M&L For Saver Mechanism On / Off Operating Complete With Main Spring, Fire Stick, Triping Coil System Etc.For Rmu 17 M&L For Actuator Motor For Operating Mechanism Charging Motoron / Off For ( Rmu ) 18 M&L For Self Powered Relay Cgi14s Suitable For Rmu . 19 M&L For Lemun Type Live Indicator Complete With Electrical Circuit Suitable For Rmu . 20 M&L For Power Card ( Smps Card ) Complete With All Electrical Circuit Suitable For Rmu . 21 M&L For Right Angle Boot For Rmu 22 Supply And Fix Vaf Meter, Accuracy Class 1.0, Input Vtg Measurement Rand 50-520Vac ( P-P ) , Flush Mounting, Showing Parameters Vll, Vln, A, F, Pf Etc Complete Incl Taking Down Old U / S Meter All As Specified And Directed By Engr-In-Charge Cat - Vl411010 Make : L&T Or Equivalent Make 23 Supply And Fixing Of Mcb Sp 06 To 32A, Upto Rupturing Capacity Of 10Ka, C Curve Type To Be Fixed In Vcb Panel All As Specified And As Directed. Make :Indoasian Cat : 811054-59Or Equivalent Inlegrand / Abb / Schneider Incl Taking Down Old U / S Mcb Sp 24 Supply And Fixing Of Mcb Dp 20A, Upto Rupturing Capacity Of 10Ka, C Curve Type All As Specified And As Directed. Make : Indoasian Cat No : 810074 Or Equivalent In Legrand / Abb / Schneider Incl Taking Down Old U / S Mcb Spn 25 Supply And Fix Indoor Medium Voltage Epoxy Resin Cast Potential Transformer, Single Phase 11Kv Of Ratio 11Kv / V3 / 110V / V3, 200Va, Class-1.0, 50 Hz Complete All As Specified And As Directed Make Vdyut Udyog Or Equivalent Make 26 Supply And Fix Cabinet T Handle Door Lock, Matt Finish Type Complete All As Specified And Directed By Engr-In-Charge Make Kripston Electricals Or Equivalent Make 27 Supply And Fix Polyamide Mushroom Emergency Push Button Switch Complete All As Specified And Directed By Engr-In-Charge Make Essen Or Equivalent Make 28 Supply And Fix Led Indicator Ryb To Be Fixed On Panel Size 22.5Mm Of Voltage Range 110A-110Vac Complete All As Specified And Directed By Engr-In-Charge Make L&T Or Equivalent Make 29 Opening / Disconnecting The Electrical Connection Of Defective / Burnt Out Underground Ht Cable Of Any Size From Junction Boxes Ht Oh Line / Ht Panel, Taking Out The Required Length Of Cable From Existing Loop, Cutting The Defective Portion Of Cable, Providing Required Thimbles / Connectors At Cable End And Reconnecting The Cable In Previous Location With Existing Junction Boxes Ht Oh Line / Ht Panel Etc All As Directed. Note ( I ) The Cost Of Required Earth Work Ie Excavation, Returning Filling Relaying Of Sand And Bricks And Cost Of Drawing The Required Length From Protection Pipe Breaking Of Required Brick Work / Concrete And Redoing The Required Work To Match The Existing Surface Shall Be Measured And Paid Separately ( Ii ) Additional Cable / Protection Pipe Required At Stie If Any Shall Be Measured And Paid Separately.Note For Serial No. 40 To 45: - ( I ) Contractor Should Depute Electrician And Helper And Other Required Equipments Such As Transportation, Hydra, Minor Excavation Etc To Attend The Faults / Complaints On Daily Basis As Per Complaint Trace Out And No Extra Payment Will Be Made Out On This Account And As Directed By Engineer-In-Charge. ( Ii ) Contractor / Supervisor Will Collect Complaint Of Electric Faults, Cable Faults, No Light Faults From Concern Je On Daily Basis And Will Complete Them The Same Day. ( Iii ) Contractor Should Provide Equipments Like Excavation Tools, Discharge Rod, Tester, Test Lamp, Multi Meter, Side Plier & Related Essential Tools, Industrial Safety Helmet, Hand Gloves, Safetymaterials Etc On His Own Arrangement As Per Site Requirement For Rectifying The Complaint And No Other Payment Will Be Made For The Same. 30 Material And Labour For Surface Excavation N Exceedind 15 Cm Deep Including Site Clearance In Soft / Loose Soil All As Sepcified And As Directed By Engr-In-Charge 31 Ht Feeder Pillar Box Factor Made Cubical Type Dust Proof, Out Door Type Both Side Opening Of Size 120 X 110 X 80 Cm Of Ms Sheet 3 Mm Thick Power Coated Machine Pressed Front Opening In Two Halves With Rubber Gasket / Bedding , Locking Arrangement With Sliding Bolt Including Aluminium Bus Bar Of Size 50 X 10 Mm And 80 Cm Long3 Strips Mounted On Ht Insulators Each Strip Should Be Munted Minimum Two Insulator And Nut Bolt Panel Shall Be Mounted On Angle Iron Frame And Legs Made From Angle Iron Of Size 50X 50 X 6 Mm And Legs 40 Cm Long Duly Spray Painted Internally And Externally With Two Coat Of Synthetic Enamel Paint Over A Coat Of Red Oxide Primer Grouted In Pcc 1:2:4 Type ‘B’ ( Using 20 Mm Graded Stone Aggregate Complete Incoming / Outgoing Cable Provision.

Key Value

Document Fees
INR 500 /-
EMD
INR 36000.0 /-
Tender Value
INR 18 Lakhs /-

Attachment

FileName File Description File Size
bde6b948-1af1-4486-b7fe-c84d613c3eac.html Tender Notice 0 KB
BOQ_731154.xls Tender Document 0 KB
tender.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

Name of Work:REPAIR/MAINTENANCE OF VCBS/ACB/RMU, HT FEEDER PILLARS, CALIBRATION OF VCB AND ALLIED SERVICES AT AFS PHALODI.
Sl. No. Item Description
1Carrying out calibration of HT VCB panel including VCB 800/630/400 Amps, Make:ABB, after taking proper shut down and disconnecting the cables from panel and VCB Breakers, calibration of over fault relay, earth fault relay, checking of alignment of VCB isolating contacts, rewiring of burnt out/unsv VCB panel wiring complete, servicing of operating mechanism including tripping and closing system of the breakers, dehydrating, decorbonising of panel, bus section & circuit section including incoming/outgoing cable and necessary HT insulation at joints. Removing perished monoplus compound cleaning and re-insulating with HT taps wherever necessary, with and including replacement of burnt out/defective spares like tension springs, tortion springs, nut bolts, washers of suitable size, lingers etc., under the supervision of M/s ABB or authorised dealer/ representative, and refixing the panel in its original position with complete painting of VCB Panel and testing entire satisfaction of Engineer -in- Charge. Note : (i) The quoted Rate shall be deemed to include all minor spares etc.,(ii) If any burnt out/defective items like moving/fixed contacts, tripping coils,earth fault relay, etc., will be measured and paid separately under respective items. (iii) Spare parts required other than mentioned here-in-after shall be deemed to be included in the quoted rate.
2Supply and fix the following spares for VCB 800/630/400 Amps capacity, Make:ABB, Type :- VD4 12.12.25 Note: The spares shall be measured and paid only requirement at site during servecing of VCB"s (a) Supply and fix master trip relay ABB mechanical 4NO + 4NC , 110 V for VCB 800/630/400 Amps capacity, Make:ABB, Type :- VD4 12.12.25
3(b) Supply and fixspring drum Cat part No: V4205, IVYN300950-020 .
4(c) Supply and fix spring Cat part No: V4206,GCE9478006P0102.
5(d) Supply and fix spring charging Motor 230V DC/AC Cat part No V6037, IVYN300951-002.
6(e) Supply and fix tripping/closing coil-110Volt DC Cat part No: V6084, IN54450007-AB.
7(f) Supply and fix emergency trip assembly Cat part No: V6107, VYN400901-AF.
8(g) Supply and fix vacuum intrupterof VD4 type for VCB.
9(h) Supply and fix lever Cat part No: IVYNG00950-114 of VB4 type VCB.
10(i) Supply and fix roller Cat part No: V6030 of VB4 type VCB .
11(j) Supply and fix latest generation SLR140C,Dual rated CT, 3 Phase Over current relay and earth fault relay Auxiliary supply 18 -135 Volt AC/DC+/- 15% operated for VCB all as specified and as directed. Make:- L&T/ABB/Avana/Stelmec
12Supply and fix Trivector meter, 3 phase 4 wire (kWh, kVArh, kVAh, kW, kVA),-/100V/v3, -/5A, 50Hz ref Temp: 27°C, CL: 0.5s, LB : 5A, Imax:10A, 16000Pulses/unit Make : Secure Model : Premier 300 or equivalent make
13Carrying out calibration of ACB panel including ACB 630 Amps, Make :ABB, after taking proper shut down and disconnecting the cables from panel and ACB Breakers, calibration of over fault relay, earth fault relay, checking of alignment of ACB isolating contacts, servicing of operating mechanism including tripping and closing system of the breakers, dehydrating, decorbonising of panel, bus section & circuit section including incoming/outgoing cable and necessary LT insulation at joints. Removing perished monoplus compound cleaning and re-insulating with LT taps wherever necessary, with and including replacement of burnt out/defective spares like tension springs, tortion springs, nut bolts, washers of suitable size, lingers etc., under the supervision of M/s ABB or authorised dealer/ representative, and refixing the panel in its original position and testing entire satisfaction of Engineer -in- Charge .
14M&L for repairing/ servicing, calibrating / testing /setting of fault tripping andrecommissioning with painting complete as mentioned in maintanceand operation manual of 11 KV HT RMU SF6 breaker 1 way/3 way/ 4 way/6 way all as per OEM instructions.(Make:- CG /ABB) (Note : SF6 Gas charging will be measured and paid seperately (i) Repairing / servicing shall be carried out through O.E.M of manufactures engineering / technician only. (ii) Cost of small spares like gasket, battery,O ring nuts, bolts and lubricants / cleaning required for servicing of RMU is deemed to be included in the coated rate. However cost of the major spare parts will be measured and paid separatly under revelant items of Sch"A". (iii) Job of repairing/ servicing/calibrating / testing /setting of fault tripping andrecommissioning has been considered forcomplete set of RMU"s i.e 1 way/2way/3 way/ 4 way/6 way as per location
15M&L for gas charging breaker by using SF 6 gas all as specified and directed.
16M&L for saver mechanism ON/OFF operating complete with main spring,fire stick,triping coil system etc.for RMU
17M&L for actuator motor for operating mechanism charging motorON/OFF for (RMU)
18M&L for self powered relay CGI14S suitable for RMU .
19M&L for lemun type live indicator complete with electrical circuit suitable for RMU .
20M&L for power card (SMPS card) complete with all electrical circuit suitable for RMU .
21M&L for right angle boot for RMU
22Supply and fix VAF meter, accuracy class 1.0, input vtg measurement rand 50-520VAC (P-P), flush mounting, showing parameters VLL,VLN, A, F, PF etc complete incl taking down old u/s meter all as specified and directed by Engr-in-Charge Cat - VL411010 make : L&T or equivalent make
23Supply and fixing of MCB SP 06 to 32A, upto rupturing capacity of 10KA, C curve type to be fixed in VCB panel all as specified and as directed. Make :indoasian Cat : 811054-59or equivalent inLegrand/ABB/Schneider incl taking down old u/s MCB SP
24Supply and fixing of MCB DP 20A, upto rupturing capacity of 10KA, C curve type all as specified and as directed. Make : Indoasian Cat No : 810074 or equivalent in Legrand/ABB/SchNeider incl taking down old u/s MCB SPN
25Supply and fix indoor medium voltage epoxy resin cast Potential Transformer, single phase 11KV of ratio 11KV/v3/110V/v3, 200VA, Class-1.0, 50 Hz complete all as specified and as directed Make Vdyut Udyog or equivalent make
26Supply and fix cabinet T handle door lock, matt finish type complete all as specified and directed by Engr-in-Charge make Kripston Electricals or equivalent make
27Supply and fix polyamide mushroom emergency push button switch complete all as specified and directed by Engr-in-Charge make ESSEN or equivalent make
28Supply and fix LED indicator RYB to be fixed on panel size 22.5mm of voltage range 110A-110VAC complete all as specified and directed by Engr-in-Charge make L&T or equivalent make
29Opening / disconnecting the electrical connection of defective / burnt out underground HT cable of any size from Junction boxes HT OH Line/HT Panel,taking out the required length of cable from existing loop,cutting the defective portion of cable, providing required thimbles/connectors at cable end and reconnecting the cable in previous location with existing Junction boxes HT OH Line/HT Panel etc all as directed. Note (i) The cost of required earth work ie excavation,returning filling relaying of sand and bricks and cost of drawing the required length from protection pipe breaking of required brick work/concrete and redoing the required work to match the existing surface shall be measured and paid separately(ii) Additional cable/protection pipe required at stie if any shall be measured and paid separately.Note for serial no. 40 to 45: - (i) Contractor should depute Electrician and helper and other required equipments such as transportation,hydra,minor excavation etc to attend the Faults / Complaints on daily basis as per complaint trace out and no extra payment will be made out on this account and as directed by Engineer-in-charge. (ii) Contractor / Supervisor will collect complaint of Electric faults,cable faults,No light faults from concern JE on daily basis and will complete them the same day. (iii) Contractor should provide equipments like Excavation Tools, Discharge rod, Tester, Test lamp, Multi meter, Side plier & related essential tools, Industrial Safety helmet, Hand gloves,safetymaterials etc on his own arrangement as per site requirement for rectifying the complaint and no other payment will be made for the same.
30Material and Labour for surface excavation n exceedind 15 cm deep including site clearance in soft/loose soil all as sepcified and as directed by Engr-in-Charge
31HT feeder pillar box factor made cubical type dust proof, out door type both side opening of size 120 x 110 x 80 cm of MS sheet 3 mm thick power coated machine pressed front opening in two halves with rubber gasket / bedding , locking arrangement with sliding bolt including aluminium bus bar of size 50 x 10 mm and 80 cm long3 strips mounted on HT insulators each strip should be munted minimum two insulator and nut bolt panel shall be mounted on angle iron frame and legs made from angle iron of size 50x 50 x 6 mm and legs 40 cm long duly spray painted internally and externally with two coat of synthetic enamel paint over a coat of red oxide primer grouted in PCC 1:2:4 type ‘B’ ( using 20 mm graded stone aggregate complete incoming / outgoing cable provision.