Tender For Restoration And Renewal Of Building Electrical, Electrical Fittings And Connected Works At Varanasi Cantt., varanasi-Uttar Pradesh

Military Engineer Services-MES has published Tender For Restoration And Renewal Of Building Electrical, Electrical Fittings And Connected Works At Varanasi Cantt.. Submission Date for this Tender is 07-06-2024. Electrification Work Tenders in varanasi Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

43348758
Corrigendum : Tender For Restoration And Renewal Of Building Electrical, Electrical Fittings And Connected Works At Varanasi Cantt.
Open Tender
Indian
Uttar Pradesh
varanasi
07-06-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Restoration And Renewal Of Building Electrical, Electrical Fittings And Connected Works At Varanasi Cantt.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 31-May-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 07-06-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 82000.0 /-
Tender Value
INR 41 Lakhs /-

Attachment

FileName File Description File Size
3f6af4b5-d815-4c89-911e-04feb363ebff.html Tender Notice 0 KB
BOQ_731291.xls Tender Document 0 KB
Tender.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

Name of Work:RESTORATION AND RENEWAL OF BUILDING ELECTRICAL, ELECTRICAL FITTINGS AND CONNECTED WORKS AT VARANASI CANTT
Sl. No. Item Description
1Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, including fittings such as switches, ceiling roses, pendants, regulators, sockets etc and removing materials to store for keeping in safe custody for re-use at site and making good distrubed surfaces of walls, floors etc. and matching with existing surface all as directed and specified by Engr-in-charge.
2M&L for point wiring complete with PVC insulated unsheathed, 1100 volts grade cable 1.5 Sqmm (nominal area) FRLS type multi stranded copper conductor, single core drawn in and including not less than 20 mm dia rigid PVC conduit "medium grade" ISI marked including all conduit accessories for concealed wiring for one light/fan/bell/buzzer / exhaust fan point controlled by one, one way switch, including concealed pressed steel terminal box of required size not less than 2 mm thick factory made duly painted inside & outside with two coats of black bituminous paint over & including a coat of red oxide primer, with 2.8 mm thick top cover of plastic laminated sheet of required colour for mounting switch, sockets, fan regulator etc including 1.5 Sqmm FRLS type PVC insulated unsheathed cable solid copper conductor as continuous earth wire and connected to earth dolly as required at site & including chases cutting& making good disturbed surface & applying finishes to match existing surface complete all as specified and directed.
3One light point controlled by one 1 way switch
4One fan point controlled by one 1 way switch
5One 3 pin socket outlet 5 Amps on same board with other switches but with 2.5 sqmm copper conductor cable
6One 3 pin socket outlet 5 Amps on independent board but with 2.5 sqmm copper conductor cable
7One lightpoint controlled by two way switch
8One bell point controlled by one bell push
9All as per Sr item No. 2 above but with 2.5 Sqmm copper conductor cable for socket outlet 15 Amps complete all as specified and directed.
10S & F switch piano type 5 Amp single pole one way flush type, white or ivory, ISI marked complete all as specified and directed.
11S & F switch piano type 15 Amps single pole one way ISI marked complete all as specified and directed.
12S & F switch piano type 5 Amps single pole two way ISI marked complete all as specified and directed.
13S & F bell push piano flush type one way ISI marked complete all as specified and directed.
14S & F socket outlet 3 pin 5 Amps flush type ISI marked complete all as specified and directed.
15S & F socket outlet 6 pin 5 & 15 Amps flush type ISI marked complete all as specified and directed.
16S & F ding dong electric bell 230 V type ISI marked complete all as specified and directed.
17S & F ceiling rose, surface bakelite 65 x 20 mm three terminals complete all as specified and directed.
18S & F sheet metal enclosure for MCB DB , 12 ways with200 amps rated bus bar double door complete all as specified and directed.
19S & F sheet metal enclosure for MCB DB , 8 ways with200 amps rated bus bar double door complete all as specified and directed.
20S & F sheet metal enclosure for MCB DB , 6 ways with200 amps rated bus bar double door complete all as specified and directed.
21S & F sheet metal enclosure for 4 Way TPN MCB DB with 200 amps rated bus bar, double door complete all as specified and directed.
22S&F sheet metal enclosure for VTPN DB double door 415 Volt with 200 amp rated bus bar complete withsuitable for1 x 63Amp MCCB as incomer and MCB SPN as outgoing connection through proper size of lugs and cable glandsincluding taking down existing MCB DBscomplete all as specified and directed.
23S&F in repair sheet metal enclosure 240V SPN with two pin and earth plug socket and top including 20A MCB SP complete all as specified and directed.
24M&L including taking down sub main wiring withPVC insulated 1100V grade FRLS single core multi stranded copper conductor cable of size 2x6 sqmm +1x 6 sqmm as earth continuity cable passing through and including 25/20mm dia PVC conceal conduitas required at site & including chases cutting& making good disturbed surface & applying finishes to match existing surface all as specified and directed by Engr-in-Charge.Note - Two runs of 6 sqmm and one run of 6.0 sqmm including PVC conduit shall be measured as unit length.
25M&L for sub main wiring withPVC insulated 1100V grade FRLS single core multi stranded copper conductor cable of size 2x4 sqmm + 1x 4 sqmm as earth continuity cable passing through and including 25/20mm dia PVC conceal conduitas required at site & including chases cutting& making good disturbed surface & applying finishes to match existing surface all as specified and directed by Engr-in-Charge. Note - Two runs of 4sqmm and one run of 4 sqmm earth continuity cable including PVC conduit shall be measured as unit length.
26Taking down and M & L sub main wiring withPVC insulated 1100V grade FRLS single core multi stranded copper conductor cable of size 2x10 sqmm + 1x10 sqmm as earth continuity cable passing through and including 32/40mm dia PVC conceal conduit as required at site & including chases cutting& making good disturbed surface & applying finishes to match existing surface all as specified and directed by Engr-in-Charge.Note - Two runs of 10 sqmm and one run of 10 sqmm earth continuity cable including PVC conduit shall be measured as unit length.
27S & F including taking down fan regulator electonic step type humming free ISI marked complete all as specified and directed.
28S&F in repair decorative ultra slim aluminium square profile 20/22W LED tube light fitting with high lumen output energy efficientdirect surface mountingincluding connecting up with three core PVC insulated copper conductor cable of suitable size complete all as specified and directed.
29S&F in repair recess mounting 36W 2"x2" LED slim panel (595x595mm) fittings including making connection with PVC insulated three core flexible copper conductor cable with connector block and making good the disturbed suface complete all as specified and directed.
30S&F including connection to existing point,LED edgelite linear & compact 9W mirror light with decorative grey end caps , polycarbonate body and ribbed opal dufuser complete all as specified and directed.
31S&F ultra slim edelit LED downlighter 7W, 220 V AC white powder coated Aluminium housing surface mounting complete all as specified and directed.
32S&F in repair high efficiecy 20 Watt LED retofit tube rod suitable for fixing in existing fittings and taking out old unserviceable tube rod any type complete all as specified and directed.
33Fixing only old light fittings any type received from item No 1.00 above including connection to existing point all as directed and specified
34S&F LED retrofit lamp of capacity 9 watt,B-22 holder base with polycabonate body and aluminium heat sink warm white complete including taking down old/ unserveciable CFL/bulb complete all as specified and directed.
35S&F in repair decorative wall mouting LED bed side lamp 7/9 Watt with cover plate and making electric connection all as specified and directed.
36S&F in repair comet wall light unique Aesthetic white colour modern wall light having suitable holder for B-22 Bulb complete including taking down old/ unserveciable CFL/bulb holder all as specified and directed .
37S&F in repair LED decorative bollard light 10 Watt with IP-65 having step profile placed on top.Ideal for architectural outdoor lighting,typically giving off light from the sides suitable to illuminate walkways complete all as specified and directed.
38S&F in repair LED post top lantern 45W aluminium die cast suitable for fixing on GI pipe complete all as specified and directed.
39M&L for taking out old unserviceable bldg security light any type and S&F LED building security light 25 Watt complete all as specified and directed.
40Supply and replace Bldg security light service bracket made out of 30/40/50 mm dia as reqd at site medium grade GI Pipe bend to shape including 2 x heavy duty fixing clamp made out of not less than 3 mm thick flat iron with nut/bolts and fixing with anchor bolts/fastner including one coat of primer and two coat of alluminium silver paint all as directed and specified.
41S & F angular type Lamp holder, PVC/ Polycarbonate type with back plate suitable for batten fittings complete all as specified and directed.
42Supply and fixing 240V,10 KA "C" curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning all as directed and specified.
43Supply and fixing in repairMCB SPN 40 Amps,240 volts complete all as specified and directed.
44Supply & fixing in repair MCB SPN 63 Amps,240 volts complete all as specified and directed.
45Supply & fixing in repair MCB TPN 63 Amps,415 volts complete all as specified and directed.
46Supplying & Fixing GI electrode chemical earthing of high conductive, corrosion resistant, CPRI tested maintenance free chemical earthing pit to achive earth resistance value less than or equal to 3 Ohm & EN voltage < 02 V,pipe in pipe technology based in which primary conductor (Pipe) having 40 MM dia and primary conductor is inserted into secondray conductor having 80 MM dia. The primary conductor is inserted into secondory conductor and space between secondary and primary conductor of earthing electrode should be crystalline compound. The length of this electrodes is min 3000 MM (3 meters) andearth pit"s bore hole should be of dia 200 to 250 mm and min depth 3.50 meters. Length of electrode will be increase with connecting of 25 x 4 mm GI strip extra,and total depth should not less than 3.50 meters. Around the earth electrode earth pit borehole should be backfilled with minimum 50 Kg of ground enhencement compound ERIC Contains mixture of Silica sulphate,Alumina, Iron Oxide, titanium Oxide, Calcium Oxide,Sodium Oxide, Zink Oxide etc. ). including RCC earthing pit having450 x 450 Cl chamber cover all as directed by Engineer-in-Charge.( Note : If less than 3 Ohm result has not acheived at site the contractor is responsible to do grid system to achieve the desired result and no extra payment shall be made to the contractor for making grid system.)
47M&L for earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25m deep below GL with top edge of plate not less than 1.50 m below normal ground level) connected to galavanised earth lead wire 4.0 mm dia (7.5m)as means of bolts, nuts, check nuts and washer besides brazing at all joints as shown on drawings and including excavation, earth work, GI pipe (ISImark) light grade 15 mm borefor protection of GI wire from earth electrode to and including the earth test point, supplying and laying charcoal dust, common salt, PCC 1:3:6, type C-1(using 20 mm graded crushed stone aggregate ) chamber and mild steel angle iron frame 40 x 40 x 3 mm and 40 mm thick pre-castRCC cover 1:2:4 , type B-1(using 20 mm graded crushed stone aggregate ) reinforced with 8 mm dia TMT bars @ 75 mm C/C both ways with mild steelhandle 12 mmdia, PGIfunnel and wire mesh, 20 mm dia GI pipe light grade(ISI marked) for watering all as shown in electrical plate No 3 of SSR Part-I and connected to earth test point including testing of earthing & dismantling /taking down existing old / unserveciable earthingcomplete all as specified and directed. (Note:-The rates quoted shall also deemed to include the cost of Earth test point and earth wire and protection pipe upto 7.5 meter beyond the earth plates electrode.)
48Supply, fixing and testing of LT distribution board made out of 2mm thick MS sheet of size not less than 1000x1000x150mm duly painted powder coating with two coats of synthetic enamel paint over a coat of red oxide primer, wall mounted/ semi grouted in wall with locking arrangement and provision of tapping for incoming and outgoing electric connections with suitable size of lugs,glands complete all as specified and directed comprising of the following(Make: LT panel shall be manufactured by one make mentioned in the List of makes under PS) :- (i) Aluminium bus bar chamber TPN of 250 amps rating (Set of four strip). (ii) Phase indicating lamp Set of three. (iii) Voltmeter (0-500V), three phase, digital type with inbuilt selector switch-01 set (iv) Ammeter (0-300 Amps) three phase, digital type with inbuilt selector switch incl CT"s - 01 set (v) MCCB four pole 415 volts AC 50 Hz, 160 amps rating breaking capacity 25 KA fixed magnetic and adjustable thermal release - 01 No.
49Contd/... (vi) MCB two pole 415 volts AC 50 Hz, 40 amps rating breaking capacity 16 KA fixed magnetic and adjustable thermal release - 04 No. (vii) fixing and connection of existing energy meter - 04 nos (viii) Name slip holder on each compartment for identification of Accn - 04 Nos (ix) Earthing terminals - 02 Nos (x)MCB SPN 20A 10 KA C series - 01 Nos (xi) Toughten glass infront of each meter compartment for easy view of meter reading without opening door . Note : Contractor will submit drawing of Meter panel box & after approval of GE procurement will be done.
50S&F modular mounting GI Metal box 6 moudule flush type complete all as specified and directed.
51S&F modular mounting GI Metal box 8 moudule square flush type complete all as specified and directed.
52S&F modular mounting GI Metal box 12x16 mouduleflush type complete all as specified and directed.
53S&F modular mounting GI Metal box 3 mouduleflush type complete all as specified and directed.
54S&F modular mounting GI Metal box 1&2 mouduleflush type complete all as specified and directed.
55S&F modular cover plates with grid frames 6 moudulecomplete all as specified and directed.
56S&F modular cover plates with grid frames 8 moudule square type complete all as specified and directed.
57S&F modularcover plates with grid frames12x16 moudule type complete all as specified and directed.
58S&F modular cover plates with grid frames 3 moudule type complete all as specified and directed.
59S&F modular cover plates with grid frames 1&2 moudule type complete all as specified and directed.
60S&F for modular switch 1 way 6 Amp complete all as specified and directed.
61S&F for modular switch 2 way 6 Amp complete all as specified and directed.
62S&F for modular switch 1 way 16 Amp complete all as specified and directed.
63S&Ffor modular switch bell push 6 Amp complete all as specified and directed.
64S&Ffor modular socket universal 6/16Amp combined 2 Module with ISI marked complete all as specified and directed.
65S&Ffor modularsocket universal 6A-2/3 pin type ISI Marked complete all as specified and directed.
66S&Ffor modularfan step regulator 5 step 120 W, 2 module ISI Marked complete all as specified and directed.
67S&F PVC insulated aluminium conductor cable service wiremulti stranded of size 10 Sqmm 2 core complete all as specified and directed.
68S&F PVC insulated aluminium conductor cable service wiremulti stranded of size 6 Sqmm 2 core complete all as specified and directed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy