Tender For Special Repair/Replacement Of 5 Mva 66/11 Kva Power Transformer At Af Stn Bhisiana, Bhisiana-Punjab

Military Engineer Services-MES has published Tender For Special Repair/Replacement Of 5 Mva 66/11 Kva Power Transformer At Af Stn Bhisiana. Submission Date for this Tender is 17-06-2024. Power Transformer Tenders in Bhisiana Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

43348375
Tender For Special Repair/Replacement Of 5 Mva 66/11 Kva Power Transformer At Af Stn Bhisiana
Open Tender
Indian
Punjab
Bhisiana
17-06-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Tender For Special Repair / Replacement Of 5 Mva 66 / 11 Kva Power Transformer At Af Stn Bhisiana

Key Value

Document Fees
INR 1000 /-
EMD
INR 269000.0 /-
Tender Value
INR 1.94 Crore /-

Attachment

FileName File Description File Size
288f16cb-4064-423c-8dca-3f0b6ce2c517.html Tender Notice 0 KB
BOQ_731008.xls Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB
tendert42.pdf Tender Document 0 KB

BOQ Items

Name of Work : SPECIAL REPAIR/REPLACEMENT OF 5 MVA 66/11 KVA POWER TRANSFORMER AT AF STN BHISIANA
Sl. No. Item Description
1Supply , installation , commissioningof outdoor type step down,copper wound, Power transformer as per IS-2026 & IEC : 60076-1 :2000, 66/11KV, 5 MVA , ONAN, 3 phase , 50 Hz, doublecopper wound, core type with low loss, non ageing, high permeability, prime grade, CRGO core material M4 grade or better with BIS certification, perfectly insulated and clamped to minimise noise and vibration, Delta/star vector group DYn11,ON LOAD Tap changer on HV side to vary secondary voltage from (+) 5% to (-) 10% in 12 steps @ 1.25%. The OLTC shall conform to IS 8468/IEC 60214 (Part 1& 2). The66KV and 11 KV bare condensor type bushing oil filled shall be provided. Thermal sensors and necessary arrangment to get the data on SCADA on Modbus protocol shall be provided.The insulating oil shall be unused inhibited Type A, High Grade conforming to IS 335/ IEC-60396-2020. The transformer shall be designed with particular attention to the suppression of voltages especially the third and fifth harmonic so as to eliminate wave form distortion and any possibility of high frequency disturbances, inductive effects or of circulating currents, between neutral points of different transformer stations reaching such a magnitude as to cause to interference with communication circuits. The transformer shall have following accessories and fittings etc. all as directed.
2(i) Double float Reed type Buchholz Relay(gas operated) with shut off valves at both ends, complying with IS:3637 , 50mm, with two pairs of electrically separated contacts, one pair foralarm and other pair for tripping.The angle of inclination shall be 3 to 7 degree (ii)Oil temperature indicator 150mm diameter for top oil temperature indication with angular sweep of 270°. Range of temperature should be 0-150°C with accuracy of ±1.5% (or better) of full scale deflection, with alarm and trip contact. (iii)Winding temperature indicator about 150mm diameter for measuring the hot spot temperature of each winding [HV, IV & Tertiary (if applicable)]. It shall have angular sweep of 270°. Range of temperature should be 0-150°C with accuracy of ±1.5% (or better) of full scale deflection, with electrical contacts for alarm and trip contacts.
3(iv) Sheet steel weather proof Marshalling box of IP -55 construction and shall have following load disconnect switchfor incoming power supply from auxiliaries, wiring and termination individualy for Buchholz relay alarm for main tank, winding temp high alarm, oil temp high alarm, tank oil level low alarm, tap change incomplete alarm, wiring and termination individually of remote trip alarm,winding temp high trip,oil temp high trip,Buchholz relay trip or sudden gas and sudden oil pressure relay trip , Cubicle illumination lamp with door switch and space heater withthermostat and ON/OFF switch (v)Magnetic oil level gauge with low level alarm contact. (vi)Pressure release valve (PRV) with trip contacts. (vii)Conservator with oil filling hole with cap and drain plug and with built in diaphragm to avoid direct air contact with transformer oil & diaphragm rupture detection relay.Conservator tank shall be provided with two separate compartments( with partition barrier). One for main transformer tank and other for OLTC compartment.
4(viii)Magnetic Oil level indicator 150mm dia with minimum level marking. (ix) Thermometer pockets with thermometer. (x)Silica gel breather with silica gel (xi) Air Release plug. (xii)Lifting Lugs (xiii)Earthing terminals (xiv) Bi-directional Rollers- 4No (xv)Anodized aluminum rating and diagram plate. (xvi) Top filter valve
5(xvii)Bottom drain -cum- filter valve. (xviii) Jacking lugs (xix) Insulation level KV Peak- HV-325KV and LV- 75KV (xx)Insulation level (power frequency with stand) HV- 140KV, LV-28KV (xxi)System fault level 31.5KA at 66KV (xxii) Single float Bucholz relay/oil surge relay with alarm contact for OLTC (xxiii) No load losses and load losses at rated voltage and frequency- Not more than 40 KW (xxiv) % Impedence at 75 degree centigrade at rated current and frequency - not more than 7.15
6(xxv) For electrical operation of OLTC from local as well as remote, motor operated mechanism shall be provided. The tap changer shall be provided with over-current protection in order to prevent the tap-change operation during a short circuit. The Local OLTC Drive Mechanism Box shall house all necessary devices meant for OLTC control and indication.The diverter switch or arcing switch shall be designed so as to ensure that its operation once commenced shall be completed independently of the control relays or switches, failure of auxiliary supplies etc. To meet any contingency which may result in incomplete operation of the diverter switch, adequate means shall be provided to safeguard the transformer and its ancillary equipment. The current diverting contacts shall be housed in a separate oil chamber not communicating with the oil in main tank of the transformer and the chamber shall be designed to withstand the vacuum. It shall be complete with the following:(a) A circuit breaker/contactor with thermal overload devices for controlling the AC Auxiliary supply to the OLTC motor (b) Emergency Push Button to stop OLTC operation (c) Cubicle light with door switch (d) Anti-condensation metal clad heaters to prevent condensation of moisture (e) Pad locking arrangement (or locking arrangement suitable for long term operation) for hinged door of cabinet (f) All contactors relay coils and other parts shall be protected against corrosion, deterioration due to condensation, fungi etc. (g) The cabinet shall be tested at least IP 55 protection class. (xxvi) Remote tap changer control panel(RTCC) (xxvii) Automatic voltage regulator relay (AVR). It shall be supplied together with the timer and under voltage relay. (xxviii) Make: Siemens/ALSTOM/ABB/BHEL/Bharat Bijlee/ Schneider
7(xxix)Supplying, installation, testing and commissioning ofINDOOR TYPE control and relay panelfor the protection and operational working of out door 66KV/11KV , 5MVA transformer and 66 KV feeder all as directed and specified by E-in-Charge . It must be manufactured by OEM of transformer or its authorised system integrator (having type test report), made up of 2mm thick MS sheet, consisting of separate vertical stationary front panel with equipment mounted thereon & having wiring access from the rear. Each cubical assembly shall be provided with double leaf doors as rear having handles with built in locking facility.The height of the panel shall not be more than 2250 mm .The control & relay board shall be on panel at front. It is responsibility of the bidder to ensure that the equipment specification and unspecified complimentary equipment required for completeness of protection & control schemes be properly accommodated in the panels. Test of relays shall be carried out based in general guide lines specified in CIGRE committee for all relays. The drg of panel shall be submitted for Approval of AO along with drg of power transformer. It shall consists of not limited to following certain items but other items required for functional requirement of panel and its acessories
8a. BCU C264 / Micom P3F Rack 4U, 80 TE, IP20 front bus mother board 80TE Power supply Vnom: 220 VDC and230VAC/ Nominal wetting voltage for 2 DI: 220 VDC - 2 serial ports CPU275 (Type 4), with 2*Ethernet RJ45, 128Mb FlashMem, 256Mb SDRAM, 50 ppm Oscill Front Face with LCD & LEDs (80TE) detachable up to 5m 16 DI 1 ms, 220VDC 10 DO Board (8NO+2NO/NC) 4I and 5U direct acquisition board from CT/VT Ration 5 or 10 Amp b. Numerical relay as IEC 61850 with following features:- Two winding differential , overload Protection with 3 Nos O/C elements with setting range (50-200%)of 1A, E/F protection with setting range (10-40%) of 1 A, REF protection, over flux protection over volatge and under voltage protection tripping logic disturbance recorder,LBB (Break failure protection) c. Supervision Relay - (AC Supply Supervision)200ms
9e. DC CHANGEOVER RELAY f. Supervision Relay - (Trip Circuit Supervision) ; 200ms
10m. Multi function meter, CT/PT SEC: 1A/110V CT/PT Primary: User programmableMulti function meter3phase 3 element 4 wire, Class: 0.5, CTR: user programmable/1A, PTR: user programmable/110V, comm: MODBUS via RS485 , auxilary voltage :(100-250V) DC n. Analog Ammeter - 96 mm sq , Class :1.0 o. Voltmeter selector switch,6 position (RY-YB-BR-RN-YN-BN) p. AuxillaryContractor 220VDC, CAD32MD COIL :220V DC contacts : 3 NO & 2 NC contact rating: 10 Amp q. Auxiliary Relay - with S/R contacts & H/R flag.Operating time<20ms. (4 Contacts ), Available ratings: 24, 48,110, 220 V DC Miniature relay, Auxillarycontacts: 4(C/O), Auxillary supply 220V DC r. Relay test block
11(s) LRS/LBB IN/OUT SWITCH LR-2P-20W-SP-LA-25A - TYPE: Stayput, 20 WAYS, 2 positions lockable at all positions, circuit label :local * remote, handle: Pistol, 4 + 4 Contacts, Non-Lockable selector switch 8 ways, 2 positions, stayput, with pistol grip handle t. Auxillary plug in type relays with change over contacts , high speed trip relay , MCBs, Electric hooter 110v DC, Digital multi function meter to show three phase current and voltage, power factor, frequency, three phase energy with SCADA compatable, LED indicator lamps and with standard parameters. illumination lampwith ON/OFF with door switch, Space heater with thermostat and toggle switch, Earth bus and terminal blocks,Three pin 15A socket with ON/OFF switch complete all as specified and directed
12NOTE:(i) Any item specifically not mentioned but requred technically for proper functioning is deemed to be included in quoted rates(ii)The routine test on transformer shall be carried out at OEM premises by rep of Accepting Officer along with rep of contractor before dispatch. The Contractor shall poroduce type test report of similar capacity power Transformer or nearest standard size capacity available. (iii) The drg of transformershall be forwarded by GE and CWE duly recommended for Approval of Acccepting Officer before procurement.OEM musthave NABL accredited LAB for testing and inhouse slitting machine and core cutting facilities and certificate to this effect issued by OEM shall be submitted to AO at the time of Approval of Drgs. (iv) The erection, testing and commissioning of transformer shall be performed under strict supervision of representative of OEMand certificate of this effect will begiven by OEM to GE before payment (v)Core material shall be directly procured either from the manufacturer or through their accredited marketing organisation of repute and not through any agent. The maximum flux density in any part of the cores and yoke at normal voltage and frequency shall be such that it should under 10% over voltagecondition should not be more than 1.9 Tesla. The supplier shall provide saturation curve of the core material, proposed to be used. PVr of core shall be submitted by OEM to GEbefore routine test. Wdg shall be made with 99.9% pure electrlytic grade copper. (vi)Standard Specifications and technical Parameters for Transformers and Reactors (66 kV & above voltage class) issued by power ministry shall be strictly followed.
13(vii) RTCC and AVR panel shall be suitable for automatic voltage regulation with master follower scheme with Tap position indicator as per tap indication in OLTC mechanism. RTCC shall also be provided with control gear in respect of ON/OFF indication auto and manual control switch AC supply on and tap changer in progress indication lamp , tap stuck indication and alarm complete. (viii)Make of transformer:Siemens/ALSTOM/ABB/BHEL/Bharat Bijlee/ Schneider (ix) Technical SLD Drg of control and relay panel shall be submitted by GE and CWE duly recommended to AO for approval before procurement. (x) All relay settings and testing shall be carried out by PSCPL auth in presence of rep of OEM at site to entire satisfaction of Engr-in-Charge (xi)Panel painting shall be done by the modern process of painting. All unfurnished surface of the steel panel and frame work shall be sand blasted or suitably cured to remove rust, scale, foreign adhering matter or grease. A suitable rust resisting primer shall be applied on the interior and exterior surface of steel, which shall be followed by application of an undercoat suitable to serve as base and binder forth finishing coat. Surface treatment by seven tank process, Paint type Powder coated. Pure polyester base grade A structure finish. Paint shade RAL 7032 for external & internal surface. Paint thickness Minimum 80 microns
14Shifting of old unserviceable power transformer 66/11KV, 5MVA from plinth / RTCC panel and 66/11KV control and relay panel to location near MRS witth the help ofhydra cranescomplete all as specified and as directed.
15Supply and laying and connecting up copper strandard unarmoured double sheathed control cable in ducts 1100 V from 66 KV yard to Panel room, 2.5qmm, 24 Core as per the manufacurer design passing through air, pipe, wall, ceiling, etc including necessery connections, complete all as specified and as directed. Note:- (i) Control cable shall be supported with aluminum spacers and saddles in the existing ducts. (ii) Termination and ferruling shall be done as per approved wiring scheme (iii) Identification tags shall be provided in the starting and finishingend of the cable at an interval of 5 meter through out the cable length. (iv) Suitable copper thimbles and lugs are to be provided for marking the connection to the terminals
16All as per items No.3 above but size 2.5 Sqmm 12 core
17All as per items No.3 above but size 6 Sqmm 4 core
18Supply , installation, testing over head bus bar /jumpers at receiveing station for 66 KV comprising of 3 feeder bays inclusive of ACSR conductor of suitable size (ZEBRA) comprising of tee clamps Disc insulators, cross arms or any type of clamps and accessories complete all as specified and directed.
19M & L cable jointing kit for 11 KV (earthed) grade cable for indoor temination heat shrink type joint complete with jointing material and accessories suitabe for 3 core XLPE armoured conductor cable of size 240 to 300 sqmm complete all as specified and directed.
20M&L for cross arms, bracings, supports, clamps, angle iron, flats and back plates fabricated from MS structural steel sections including nuts, bolts and washers of suitable sizes including welding, bending (cold or hot), drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coats of aluminum paint over one coat of red oxide primer, including 66 KV & 11 KV suport insulators for 3 phase system for holding the jumper of 66 KV & 11 KV from transformer body as per site requirement complete all as specified and directed.
21Material and labour for collection of final sample(02 Nos) of transformer oil for testingof power Transformer( before and after dehydration and top of transformer oil) in borosil container of capacity of 5 Ltrs and sending the transformer oil sample to PSPCL oil testing lab patiala by suitable transport by the contractor due care for following tests and submission test report of OLTC & mainbody :- (i) Tan Delta Test (ii) Specific Resistance Test (iii) Brake Down Voltage Test (iv) Water Content Test (v) Total acidity (vi) Interfacial tension (vii) Flash point (viii) Sediment or sludge (ix) Dissolved Gas analysis
22Supply and fixing of 30 volt battery charger with battery bank (15 nosx2 volt battery 100 AH for 11 KV HT panel as existing and site requirement complete all as specified and directed.
23Testing of Power Transformer through liasioning with PSPCL auth incd deposting of testing fees for testing of transformer and associated equipments of 66 KV bay 5 MVA power transformerby ASE /Protection Division P.S.P.C.L Bathinda for clearance and installation of equipment.
24Chemical earthing with copper earth plat 90x60cmx5mm and copper earth strip 60x10mm for transformer complete all as specified and directed.