Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | 11 KV DOUBLE POLE STRUCTURE |
| 2 | Supply, erection, testing and commissioning of 2 pole structure for providing 1 No. 11KV,200A GOS in accordance with IE rules, & local authority specification and drawings and comprising of the following. |
| 3 | a. 2 Nos 11 mtr. long MS STEEL poles complete with, pole excavation, MS STEEL foundation, and back filling complete MS steel channel/angle iron etc. |
| 4 | b. 1 Set of cross arms, branching, clamps and painting complete with GI nut, bolts & washers as required (for GO & DO), LA connection. |
| 5 | c .1 set 11KV Insulator complete with spindles & hardware complete as required. |
| 6 | d .1 No. 11KV 400A TP Gang operated Air break switches complete with 25mm dia GI pipe operating machanism, handle & locking arrangement. |
| 7 | e. 1 set of 3 Nos11KV single pole drop out fuse complete with barrel fuses, and mounting arrangement. |
| 8 | f. 1 set (3 Nos) 11KV lightning arrestor and connecting to all phases. |
| 9 | g. 1 No. 150 mm dia GI pipe class \"B\" (for XLPE cable protection) as required. |
| 10 | h. 2 Set 50mm dia 3m long GI pipe earting with 25 x 6 mm GI earth strip complete as required (for GO & DO & LA) |
| 11 | i 1 Nos 11KV HT danger boards and 2 set of anticlimbing devices. |
| 12 | HT Panel, (Main) |
| 13 | S.I.T.C. ofVCB\"s Indoor Type as per enclosed specification and UPPower Corporations, make prefered Cromptron,Schneider or any Equivalent make approved by UP Power Corporation.Including construction of Plinth and earthing etc. with all material as per Technical Requirment with 02 years warranty & 3 years AMC |
| 14 | 11 KV incoming |
| 15 | 11 KV Bus Coupler |
| 16 | 11 KV Outgoing |
| 17 | BUILDING WORK |
| 18 | Construction of 11KV Sub station building for housing of 33 KV panels, maintenance rooms, etc with supply of all civil works, labour, T&P including plumbing and electrical works, cable trenches, chequered steel plates as per standard designs. As per detail below:- |
| 19 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil |
| 20 | Earth work in filling including cartage upto 5 km and loading & unloading including cost of earth etc. complete |
| 21 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 22 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 23 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. |
| 24 | All works upto plinth levelConcrete of M25 grade with minimum cement content of 330 kg /cum |
| 25 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. |
| 26 | All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum |
| 27 | Applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil. |
| 28 | Providing and injecting chemical emulsion for reconstructional antitermite treatment and creating a chemical barrier under and alround the coloumn pitswall tench basement excavation top surface if plinth filling junction of wall and floor along the external perimer of binding expansion joints,surrounding of pipes and conduits etc.complete(plinth area of the building at ground floor only shall be measuredas per I.S.6313(Part ll 1981) aldrine emulsifiable concrete or any other approved material such as hepthachlor or chlordance will be used.The rate of application of chemical emulsion shall be as follows:-(1)treatment for masonary & foundation 5 litres per sq.m.(2)back fill in immediate contract with foundation 7.5 litre per sq.m(3)treatment of top surface of plinth filling 5 liters per sq.m.(4)treatment of soil along external parameter of building 7.50 lire per sqm. (For payment plinth area to be measured as per IS Code). |
| 29 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level & above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 30 | Centering and shuttering including strutting, propping etc. and removal of form for : |
| 31 | Foundations, footings, bases of columns, etc. for mass concrete |
| 32 | Suspended floors, roofs, landings, balconies and access platform |
| 33 | Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 34 | Columns, Pillars, Piers, Abutments, Posts and Struts |
| 35 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 36 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 37 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:3 (1 cement : 3 coarse sand) |
| 38 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish, (Barrel type) with necessary screws etc. complete : |
| 39 | 150x10 mm |
| 40 | Providing and fixing ISI marked oxidised M.S. handles conforming to IS:4992 with necessary screws etc. complete :125 mm |
| 41 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 42 | Providing & fixing glass panes with putty and glazing clips in steel doors,windows, clerestory windows, all complete with : |
| 43 | 5.0 mm thick glass panes |
| 44 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. |
| 45 | In grill, gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 46 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. |
| 47 | 80x1.25 mm M.S. laths with 1.25 mm thick top cover |
| 48 | Providing and fixing ball bearing for rolling shutters. |
| 49 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. |
| 50 | (c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin- charge. (d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin- charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test.“All above operations to be done in order and as directed and specified by the Engineer-in-Charge : |
| 51 | With average thickness of 120 mm and minimumthickness at khurra as 65 mm. |
| 52 | 12 mm cement plaster of mix : 1:6 (1 cement: 6 coarse sand) |
| 53 | 15 mm cement plaster on the rough side of single or half brick wall of mix : |
| 54 | 1:6 (1 cement: 6 coarse sand) |
| 55 | 15 mm cement plaster on the rough side of single or half brick wall of mix : |
| 56 | 1:4 (1 cement: 4 coarse sand) |
| 57 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 58 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 59 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 60 | 40 mm thick with 20 mm nominal size stone aggregate |
| 61 | Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. 18 mm thick |
| 62 | Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone - III) : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth. |
| 63 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors. 40 mm wide and 4 mm thick |
| 64 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre, of approved manufacturer, of required shade and colour complete, as per manufacturer’s specification. |
| 65 | Finishing walls with water proofing cement paint of required shade : |
| 66 | New work (Two or more coats applied @ 3.84 kg/10 sqm) |
| 67 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/ 10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture |
| 68 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. |
| 69 | 110 mm diameter |
| 70 | Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. |
| 71 | 110 mm Coupler |
| 72 | 110 mm Bend 87.5° |
| 73 | 110 mmShoe (Plain) |
| 74 | Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. |
| 75 | 110 mm |
| 76 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 77 | Part-B Electrical Work |
| 78 | Wiring for light point/ fan point/ exhaust fan point/call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 79 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 80 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 81 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 82 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 83 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 84 | 2 Pair |
| 85 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 86 | 25 mm |
| 87 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 88 | Telephone socket outlet |
| 89 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 90 | Supplying and fixing following size/ modules, GI box alongwithmodular base & cover plate for modular switches in recess etc.as required. |
| 91 | 1 or 2 Module (75mmX75mm) |
| 92 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 93 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 94 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 95 | Supplying and fixing stiff pendent with 300 mm long, 20 mm dia X 1.6 mm thick steel conduit, aluminium cast back plate and brass holder complete, including wiring the down rod with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and painting etc. as required. |
| 96 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 97 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
| 98 | Upto 450 mm sweep |
| 99 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 100 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator) |
| 101 | 12 way , Double door |
| 102 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 103 | Single pole |
| 104 | Double pole |
| 105 | Supply and fixing of LED Tube Light with batten suitable for up to 2 X 22 watt LED tube light fitting including tube on Surface complete in all respect. |
| 106 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 Nos blades, 30 cm long down rod, 2 Nos canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 107 | Supply of Totally enclosed exhaust fan, 300mm sweep continously rated highly efficient heavy-dutymotor similar to Crompton Cat. Ref. Trans Air 12\" or equivalent. |
| 108 | Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern with manually controlled device (handle lever), conforming to IS : 7231, Parryware/ Hindware/ Seabrid /Orient (Coral) with all fittings and fixtures complete including cutting and making good the walls and floors wherever required : |
| 109 | W.C. pan with ISI marked black solid plastic seat and lid |
| 110 | CP Brass fittings 15 mm nominal bore |
| 111 | Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to Eureopean & Wall moutain type W.C. of quality and make as approved by Engineer - in - charge. |
| 112 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 |
| 113 | a) 15 mm nominal bore |
| 114 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards andweighing not less than 690 gms. ( for sink) |
| 115 | a) 15 mm nominal bore |
| 116 | Providing and fixing C.P. brass angle valve for basin mixer and gyser points of approved quality conforming to IS:8931 |
| 117 | a) 15 mm nominal bore |
| 118 | Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905 |
| 119 | b)75mm dia centrifugally cast iron S & S pipe. |
| 120 | Providing & fixing M.S. holder bat clamps of approved design to sand cast iron/centrifugally cast (Spun) iron S & S pipe embeded in & including cement concrete blocks 10x10x10cm. of 1:2:4 mix (1 cement : 2 coarse : 4 graded stone aggregate 20mm nominal size).Including cost of cutting holes & making good the walls etc. |
| 121 | a) for 100mm dia pipe. |
| 122 | b) for 75mm dia pipe. |
| 123 | Providing & fixingcast iron coller. |
| 124 | a) 100mm dia. |
| 125 | b)75mm dia. |
| 126 | Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : |
| 127 | a) 100mm inlet & 100mm outlet. |
| 128 | a) 100mm inlet & 75mm outlet. |
| 129 | Providing and fixing bend of required degree with access door, insertion rubber washer 3mm thick, bolts and nuts complete. |
| 130 | a) 100mm |
| 131 | b) 75mm |
| 132 | Providing and fixing plain bend of required degree.Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905 |
| 133 | a) 100mm |
| 134 | b) 75mm |
| 135 | Providing and fixing single equal plain junction of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. |
| 136 | 100x100x100mm |
| 137 | 75x75x75mm |
| 138 | Providing and fixing centrifugaly cast iron single equal plain junction of required degree. |
| 139 | 100x100x100mm |
| 140 | 75x75x75mm |
| 141 | Providing and fixing single unequal junction of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete : |
| 142 | 100x100x75mm |
| 143 | Providing and fixing single unequal plain invert branch of required degree : |
| 144 | 100x100x75mm |
| 145 | Providing and fixing door piece, insertion rubber washer 3mm thick, bolts & nuts complete :( c.o.p.) |
| 146 | a) 100mm |
| 147 | b) 75mm |
| 148 | Providing and fixingcast iron terminal guard. |
| 149 | 100 mm |
| 150 | 75 mm |
| 151 | Providing and fixing on wall face unplasticised PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS:13592Type A including jointing with seal ring conforming to IS:5382 leaving 10mm gap for thermal expansion. |
| 152 | Coupler 110 mm |
| 153 | Bend 87.5 degree 110 mm |
| 154 | 110 shoe plain |
| 155 | Providing and fixing unplasticised- 110 mm PVC pipe clips of approved design to unplasticised-PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with MS screws of required length including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. |
| 156 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. |
| 157 | Ordinary rock |
| 158 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 159 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) |
| 160 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: |
| 161 | Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 162 | Structural steel work in single section, fixed with or without connecting plate,including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 163 | CEMENT PLASTER (IN FINE SAND) |
| 164 | 12 mm cement plaster of mix : |
| 165 | 1:6 (1 cement: 6 fine sand) |
| 166 | R.C.C. Standards post/ struts/rails/ pales of mix 1:1.5:3 (1 cement : 1.5 coarsesand : 3 graded stone aggregate 12.5 mm nominal size) with wooden plugs or 6mm bar nibs wherever required as per direction of Engineer-incharge (cost of earth works in excavation, concrete works in foundation to be paid separately). |
| 167 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. |
| 168 | Made of G.I. wire of dia 4 mm |
| 169 | Providing corrugated G.S. sheet roofing including vertical / curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (up to any pitch in horizontal/ vertical or curved surfaces), excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 170 | 1.00 mm thick with zinc coating not less than 275 gm/m² |
| 171 | HOSPITAL BUILDING MAIN L.T PANEL |
| 172 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 173 | The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall haveAMF facilityto achieve electrical interlocking, synchronizing, buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers,microprocessor release for overload, short circuit, instantaneous & earthfaultprotection with Current & Voltage metering & LCD display & should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec) |
| 174 | Air Circuit Breaker with microprocessor release ge metering & LCD display , with ready to clsoe indicator, should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec).MCCB, with microprocessor release with protection functionLCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet. (50 kA Ics) |
| 175 | INCOMING |
| 176 | 4 Nos 800 Amp FP EDO ACB 50KA , |
| 177 | BUSCOUPLER |
| 178 | 1 Nos 800Amp ACB 50KA , |
| 179 | AUTO OPERATION OF INCOMER / BUSCOUPLERACB\"s. |
| 180 | Load Management through PLC |
| 181 | Contactor for Load Management System |
| 182 | Auto changeover. |
| 183 | Buscoupler switching. |
| 184 | Electrial & Mechnical Interlocking. |
| 185 | BUSBARS |
| 186 | 2 Nos 1000 Amp TPN busbars of aluminium alloy as per SLD. |
| 187 | OUTGOING |
| 188 | 6Nos 200 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 189 | 3Nos 500 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 190 | 1Nos 400 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 191 | 2Nos 315 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 192 | 2 Nos 250 Amp FP MCCB50 kA, with On, Off Indication lamp and A/V/KW meter |
| 193 | 2 Nos 160 Amp FP MCCB50 kA, with On, Off Indication lamp and A/V/KW meter |
| 194 | 1 Nos 125 Amp FP MCCB50 kA, with On, Off Indication lamp and A/V/KW meter |
| 195 | 4 Nos 100 Amp FP MCCB50 kA, with On, Off Indication lamp and A/V/KW meter |
| 196 | INSTRUMENTS |
| 197 | 4 sets of multifunction meter with parameter current, voltage, KWH, KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. |
| 198 | 4 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 199 | 4 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 200 | 4 Sets auto trip indicating lamp . |
| 201 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 202 | Short Circuit Breaking capacity should not less than 50KA. |
| 203 | MEDICINE WARD & BURN WARD SIDE L.T PANEL |
| 204 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 205 | The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall haveAMF facilityto achieve electrical interlocking, synchronizing, buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers,microprocessor release for overload, short circuit, instantaneous & earthfaultprotection with Current & Voltage metering & LCD display & should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec) |
| 206 | Air Circuit Breaker with microprocessor release ge metering & LCD display , with ready to clsoe indicator, should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec). MCCB, with microprocessor release with protection functionLCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet. (50 kA Ics) |
| 207 | INCOMING |
| 208 | A.E |
| 209 | 1 Nos 315 Amp FP MCCB 25 kA, |
| 210 | BUSBARS |
| 211 | 1 Nos 400 Amp TPN busbars of aluminium alloy as per SLD. |
| 212 | OUTGOING |
| 213 | 1 Nos 160 Amp FP MCCB 25 kA, with On, Off Indication lamp and A/V/KW meter |
| 214 | 5 Nos 125 Amp FP MCCB 25 kA, with On, Off Indication lamp and A/V/KW meter |
| 215 | INSTRUMENTS |
| 216 | 1 sets of multifunction meter with parameter current,voltage,KWH,KVAH,Power factor on incoming from transformers. With RS 485 |
| 217 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 218 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 219 | 1 Sets auto trip indicating lamp . |
| 220 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 221 | Short Circuit Breaking capacity should not less than 25KA. |
| 222 | ICU & EMERGENCY BLOCK MAIN L.T PANEL |
| 223 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 224 | The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall haveAMF facilityto achieve electrical interlocking, synchronizing, buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers,microprocessor release for overload, short circuit, instantaneous & earthfaultprotection with Current & Voltage metering & LCD display & should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec) |
| 225 | Air Circuit Breaker with microprocessor release ge metering & LCD display , with ready to clsoe indicator, should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec).MCCB, with microprocessor release with protection functionLCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet. (50 kA Ics) |
| 226 | INCOMING |
| 227 | 4 Nos 800 Amp FP EDO ACB 50KA , |
| 228 | BUSCOUPLER |
| 229 | 1 Nos 800Amp ACB 50KA , |
| 230 | AUTO OPERATION OF INCOMER / BUSCOUPLERACB\"s. |
| 231 | Load Management through PLC |
| 232 | Contactor for Load Management System |
| 233 | Auto changeover. |
| 234 | Buscoupler switching. |
| 235 | Electrial & Mechnical Interlocking. |
| 236 | BUSBARS |
| 237 | 2 Nos 1000 Amp TPN busbars of aluminium alloy as per SLD. |
| 238 | OUTGOING |
| 239 | 2Nos 800 Amp FP EDO ACB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 240 | 2Nos 500 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 241 | 2Nos 400 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 242 | 2Nos 250 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 243 | 2Nos 200 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 244 | 2Nos 63 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 245 | INSTRUMENTS |
| 246 | 4 sets of multifunction meter with parameter current, voltage, KWH, KVAH, Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. |
| 247 | 4 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 248 | 4 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 249 | 4 Sets auto trip indicating lamp . |
| 250 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 251 | Short Circuit Breaking capacity should not less than 50KA. |
| 252 | OPD BLOCK MAIN L.T PANEL |
| 253 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be OUTDOOR, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 254 | The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall haveAMF facilityto achieve electrical interlocking, synchronizing, buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers,microprocessor release for overload, short circuit, instantaneous & earthfaultprotection with Current & Voltage metering & LCD display & should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec) |
| 255 | Air Circuit Breaker with microprocessor release ge metering & LCD display , with ready to clsoe indicator, should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB(Icu=Ics=Icw=50 kA (1 sec).MCCB, with microprocessor release with protection functionLCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet. (50 kA Ics) |
| 256 | INCOMING |
| 257 | 1 Nos 1600 Amp FP EDO ACB 50KA , |
| 258 | 2 Nos 800 Amp FP EDO ACB 50KA , |
| 259 | AUTO OPERATION OF INCOMER / BUSCOUPLERACB\"s. |
| 260 | Load Management through PLC |
| 261 | Contactor for Load Management System |
| 262 | Auto changeover. |
| 263 | Buscoupler switching. |
| 264 | Electrial & Mechnical Interlocking. |
| 265 | BUSBARS |
| 266 | 1 Nos 2000 Amp TPN busbars of aluminium alloy as per SLD. |
| 267 | OUTGOING |
| 268 | 1Nos 1000 Amp FP EDO ACB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 269 | 1Nos 800 Amp FP EDO ACB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 270 | 4Nos 500 Amp FP MCCB 50 kA,, with On, Off Indication lamp and A/V/KW meter |
| 271 | INSTRUMENTS |
| 272 | 3 sets of multifunction meter with parameter current ,voltage,KWH,KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. |
| 273 | 3 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 274 | 3 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 275 | 3 Sets auto trip indicating lamp . |
| 276 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 277 | Short Circuit Breaking capacity should not less than 50KA. |
| 278 | NURSES HOSTEL & RESIDENCES OUTDOOR TYPE PANEL |
| 279 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be OUTDOOR, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 280 | INCOMING |
| 281 | 1 Nos 500 Amp FP MCCB 25 KA, |
| 282 | BUSBARS |
| 283 | 1 Nos 630 Amp TPN busbars of aluminium alloy as per SLD. |
| 284 | OUTGOING |
| 285 | 1 Nos 200 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 286 | 1 Nos 125 Amp FP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 287 | 3 Nos 100 Amp FP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 288 | 2 Nos 63 Amp FP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 289 | INSTRUMENTS |
| 290 | 1 sets of multifunction meter with parameter current, voltage, KWH, KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. |
| 291 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 292 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 293 | 1 Sets auto trip indicating lamp . |
| 294 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 295 | Short Circuit Breaking capacity should not less than 25KA. |
| 296 | NURSES HOSTEL MAIN L.T PANEL |
| 297 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 298 | INCOMING |
| 299 | 1 Nos 200 Amp FP MCCB 25 KA, |
| 300 | BUSBARS |
| 301 | 1 Nos 250 Amp TPN busbars of aluminium alloy as per SLD. |
| 302 | OUTGOING |
| 303 | 5 Nos 100 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 304 | 1 Nos 63 Amp TP MCCB50 KA, with On, Off Indication lamp and A/V/KW meter |
| 305 | INSTRUMENTS |
| 306 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 307 | 1 sets of 0-200Amp. digital type ammeter with ammeter selector switch. |
| 308 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 309 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 310 | 1 Sets auto trip indicating lamp . |
| 311 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 312 | Short Circuit Breaking capacity should not less than 25KA. |
| 313 | 12 FLAT NURSES BLOCK METER PANEL 1/2 |
| 314 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 315 | INCOMING |
| 316 | 1 Nos 100 Amp FP MCCB 25 KA, |
| 317 | BUSBARS |
| 318 | 1 Nos 125 Amp TPN busbars of aluminium alloy as per SLD. |
| 319 | OUTGOING |
| 320 | 14 Nos 40 Amp DP MCB |
| 321 | 12Nos 40Amp. KWh 1 Phase Energy meter |
| 322 | INSTRUMENTS |
| 323 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 324 | 1 sets of 0-100Amp. digital type ammeter with ammeter selector switch. |
| 325 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 326 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 327 | 1 Sets auto trip indicating lamp . |
| 328 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 329 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 330 | 13 FLAT NURSES BLOCK METER PANEL 3/4 |
| 331 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 332 | INCOMING |
| 333 | 1 Nos 100 Amp FP MCCB 25 KA, |
| 334 | BUSBARS |
| 335 | 1 Nos 125 Amp TPN busbars of aluminium alloy as per SLD. |
| 336 | OUTGOING |
| 337 | 15 Nos 40 Amp DP MCB |
| 338 | A.E |
| 339 | 13Nos 40Amp. KWh 1 Phase Energy meter |
| 340 | INSTRUMENTS |
| 341 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 342 | 1 sets of 0-100Amp. digital type ammeter with ammeter selector switch. |
| 343 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 344 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 345 | 1 Sets auto trip indicating lamp . |
| 346 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 347 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 348 | MARRIED DOCTOR NRH HOSTEL & WARD BLOCK |
| 349 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be OUTDOOR, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 350 | INCOMING |
| 351 | 1 Nos 1250 Amp FP EDO ACB 50 KA, |
| 352 | BUSBARS |
| 353 | 1 Nos 1600 Amp TPN busbars of aluminium alloy as per SLD. |
| 354 | OUTGOING |
| 355 | 3 Nos 400 Amp FP MCCB 50 KA, with On, Off Indication lamp and A/V/KW meter |
| 356 | 2 Nos 250 Amp FP MCCB 50 KA, with On, Off Indication lamp and A/V/KW meter |
| 357 | 1 Nos 200 Amp FP MCCB 50 KA, with On, Off Indication lamp and A/V/KW meter |
| 358 | A.E |
| 359 | 2 Nos 125 Amp TP MCCB50 KA, with On, Off Indication lamp and A/V/KW meter |
| 360 | INSTRUMENTS |
| 361 | 1 sets of multifunction meter with parameter current,voltage,KWH,KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. |
| 362 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 363 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 364 | 1 Sets auto trip indicating lamp . |
| 365 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 366 | Short Circuit Breaking capacity should not less than 50KA. |
| 367 | MARRIED DOCTOR HOSTEL L.T PANEL |
| 368 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 369 | INCOMING |
| 370 | 1 Nos 400 Amp FP MCCB 25 KA, |
| 371 | BUSBARS |
| 372 | 1 Nos 500 Amp TPN busbars of aluminium alloy as per SLD. |
| 373 | OUTGOING |
| 374 | 5 Nos 125 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 375 | 1 Nos 63 Amp TP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 376 | INSTRUMENTS |
| 377 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 378 | 1 sets of 0-400Amp. digital type ammeter with ammeter selector switch. |
| 379 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 380 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 381 | 1 Sets auto trip indicating lamp . |
| 382 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 383 | Short Circuit Breaking capacity should not less than 25KA. |
| 384 | 12 FLAT DOCTORS BLOCK METER PANEL 1/2/3/4 |
| 385 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 386 | INCOMING |
| 387 | 1 Nos 125 Amp FP MCCB 25 KA, |
| 388 | BUSBARS |
| 389 | 1 Nos 150 Amp TPN busbars of aluminium alloy as per SLD. |
| 390 | OUTGOING |
| 391 | 14 Nos 40 Amp FP MCB |
| 392 | 12Nos 40Amp. KWh 3 Phase Energy meter |
| 393 | INSTRUMENTS |
| 394 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 395 | 1 sets of 0-150Amp. digital type ammeter with ammeter selector switch. |
| 396 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 397 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 398 | 1 Sets auto trip indicating lamp . |
| 399 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 400 | Cost of 3 Phase Energy meter is inclusive in above rates. |
| 401 | NRH HOSTEL L.T PANEL |
| 402 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 403 | INCOMING |
| 404 | 1 Nos 400 Amp FP MCCB 25 KA, |
| 405 | BUSBARS |
| 406 | 1 Nos 500 Amp TPN busbars of aluminium alloy as per SLD. |
| 407 | OUTGOING |
| 408 | 3 Nos 160 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 409 | 1 Nos 125 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 410 | 1 Nos 63 Amp TP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 411 | INSTRUMENTS |
| 412 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 413 | 1 sets of 0-400Amp. digital type ammeter with ammeter selector switch. |
| 414 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 415 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 416 | 1 Sets auto trip indicating lamp . |
| 417 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 418 | Short Circuit Breaking capacity should not less than 25KA. |
| 419 | PRIVATE WARD MAIN L.T PANEL |
| 420 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 421 | INCOMING |
| 422 | 1 Nos 250 Amp FP MCCB 25 KA, |
| 423 | BUSBARS |
| 424 | 1 Nos 320 Amp TPN busbars of aluminium alloy as per SLD. |
| 425 | OUTGOING |
| 426 | 6 Nos 125 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 427 | INSTRUMENTS |
| 428 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 429 | 1 sets of 0-250Amp. digital type ammeter with ammeter selector switch. |
| 430 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 431 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 432 | 1 Sets auto trip indicating lamp . |
| 433 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 434 | Short Circuit Breaking capacity should not less than 25KA. |
| 435 | 4TH CLASS EMPLOYEE TYPE-1 RESIDENTIAL AREA MAIN L.T PANEL (OUTDOOR TYPE) |
| 436 | SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be OUTDOOR, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate statuslike ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. |
| 437 | INCOMING |
| 438 | 1 Nos 800 Amp FP EDO ACB 25 KA, |
| 439 | BUSBARS |
| 440 | 1 Nos 1000 Amp TPN busbars of aluminium alloy as per SLD. |
| 441 | OUTGOING |
| 442 | 3 Nos 125 Amp FP MCCB 25 KA, with On, Off Indication lamp and A/V/KW meter |
| 443 | 8 Nos 100 Amp FP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 444 | 3 Nos 63 Amp FP MCCB25 KA, with On, Off Indication lamp and A/V/KW meter |
| 445 | INSTRUMENTS |
| 446 | 1 sets of multifunction meter with parameter current,voltage,KWH,KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. |
| 447 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 448 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 449 | 1 Sets auto trip indicating lamp . |
| 450 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 451 | Short Circuit Breaking capacity should not less than 25KA. |
| 452 | Type-II Block Main L.T Panel |
| 453 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 454 | INCOMING |
| 455 | 1 Nos 125 Amp FP MCCB 25 KA, |
| 456 | BUSBARS |
| 457 | 1 Nos 150 Amp TPN busbars of aluminium alloy as per SLD. |
| 458 | OUTGOING |
| 459 | 2 Nos 100 Amp DP MCB |
| 460 | 2 Nos 63 Amp DP MCB |
| 461 | INSTRUMENTS |
| 462 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 463 | 1 sets of 0-150Amp. digital type ammeter with ammeter selector switch. |
| 464 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 465 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 466 | 1 Sets auto trip indicating lamp . |
| 467 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 468 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 469 | 12 TYPE-II RESIDENCE OUTDOOR TYPE METER PANEL 1/2/3/4 |
| 470 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 471 | INCOMING |
| 472 | 1 Nos 100 Amp FP MCCB 25 KA, |
| 473 | BUSBARS |
| 474 | 1 Nos 150 Amp TPN busbars of aluminium alloy as per SLD. |
| 475 | OUTGOING |
| 476 | 15 Nos 40 Amp DP MCB |
| 477 | 12Nos 40Amp. KWh 1 Phase Energy meter |
| 478 | INSTRUMENTS |
| 479 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 480 | 1 sets of 0-150Amp. digital type ammeter with ammeter selector switch. |
| 481 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 482 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 483 | 1 Sets auto trip indicating lamp . |
| 484 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 485 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 486 | 17/15 TYPE-1 RESIDENCE OUTDOOR TYPE METER PANEL 1/2 |
| 487 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 488 | INCOMING |
| 489 | 1 Nos 100 Amp FP MCCB 25 KA, |
| 490 | BUSBARS |
| 491 | 1 Nos 150 Amp TPN busbars of aluminium alloy as per SLD. |
| 492 | OUTGOING |
| 493 | 18 Nos 40 Amp DP MCB |
| 494 | 17Nos 40Amp. KWh 1 Phase Energy meter |
| 495 | INSTRUMENTS |
| 496 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 497 | 1 sets of 0-150Amp. digital type ammeter with ammeter selector switch. |
| 498 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 499 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 500 | 1 Sets auto trip indicating lamp . |
| 501 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 502 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 503 | 13 TYPE-1 RESIDENCE OUTDOOR TYPE METER PANEL 1/2 |
| 504 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 505 | INCOMING |
| 506 | 1 Nos 100 Amp FP MCCB 25 KA, |
| 507 | BUSBARS |
| 508 | 1 Nos 125 Amp TPN busbars of aluminium alloy as per SLD. |
| 509 | OUTGOING |
| 510 | 14 Nos 40 Amp DP MCB |
| 511 | 13Nos 40Amp. KWh 1 Phase Energy meter |
| 512 | INSTRUMENTS |
| 513 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 514 | 1 sets of 0-100Amp. digital type ammeter with ammeter selector switch. |
| 515 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 516 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 517 | 1 Sets auto trip indicating lamp . |
| 518 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 519 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 520 | RELAYS AS PER SLD |
| 521 | 11 TYPE-1 RESIDENCE OUTDOOR TYPE METER PANEL 1/2 |
| 522 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 523 | INCOMING |
| 524 | 1 Nos 100 Amp FP MCCB 25 KA, |
| 525 | BUSBARS |
| 526 | 1 Nos 125 Amp TPN busbars of aluminium alloy as per SLD. |
| 527 | OUTGOING |
| 528 | 12 Nos 40 Amp DP MCB |
| 529 | 11Nos 40Amp. KWh 1 Phase Energy meter |
| 530 | INSTRUMENTS |
| 531 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 532 | 1 sets of 0-100Amp. digital type ammeter with ammeter selector switch. |
| 533 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 534 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 535 | 1 Sets auto trip indicating lamp . |
| 536 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 537 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 538 | 8 TYPE-1 RESIDENCE OUTDOOR TYPE METER PANEL 1/2 |
| 539 | Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheetas per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT\"s, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading. |
| 540 | INCOMING |
| 541 | 1 Nos 100 Amp FP MCCB 25 KA, |
| 542 | BUSBARS |
| 543 | 1 Nos 125 Amp TPN busbars of aluminium alloy as per SLD. |
| 544 | OUTGOING |
| 545 | 9 Nos 40 Amp DP MCB |
| 546 | 8Nos 40Amp. KWh 1 Phase Energy meter |
| 547 | INSTRUMENTS |
| 548 | 1 sets of 0-500V digital type Voltmeter with voltmeter selector switch. |
| 549 | 1 sets of 0-100Amp. digital type ammeter with ammeter selector switch. |
| 550 | 1 Sets of phase indicating lights (RYB) with protection fuses (one set for Nos incoming breaker). |
| 551 | 1 Sets breaker \"ON\" & \"OFF\" indicating lamp (one set for Nos incoming breaker). |
| 552 | 1 Sets auto trip indicating lamp . |
| 553 | Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams. |
| 554 | Cost of 1 Phase Energy meter is inclusive in above rates. |
| 555 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge ,complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 556 | 6 sq. mm 2 core |
| 557 | 10 sq. mm 2 core |
| 558 | 25 sq. mm 3-1/2 core |
| 559 | 35 sq. mm 3-1/2 core |
| 560 | 50 sq. mm 3-1/2 core |
| 561 | 70 sq. mm 3-1/2 core |
| 562 | 95 sq. mm 3-1/2 core |
| 563 | 150 sq. mm 3-1/2 core |
| 564 | 240 sq. mm 3-1/2 core |
| 565 | 300 sq. mm 3-1/2 core |
| 566 | 400 sq. mm 3-1/2 core |
| 567 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 568 | 6 sq. mm 2 core |
| 569 | 10 sq. mm 2 core |
| 570 | 25 sq. mm 3-1/2 core |
| 571 | 35 sq. mm 3-1/2 core |
| 572 | 50 sq. mm 3-1/2 core |
| 573 | 70 sq. mm 3-1/2 core |
| 574 | 95 sq. mm 3-1/2 core |
| 575 | 150 sq. mm 3-1/2 core |
| 576 | 240 sq. mm 3-1/2 core |
| 577 | 300 sq. mm 3-1/2 core |
| 578 | 400 sq. mm 3-1/2 core |
| 579 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. |
| 580 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 581 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 582 | 450 mm width X 62.5 mm depth X 2 mm thickness |
| 583 | 600 mm width X 62.5 mm depth X 2 mm thickness |
| 584 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 Way SPN DB |
| 585 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But withoutMCB/RCCB/Isolator) 4WAY TPN DB |
| 586 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4WAY VTPN DB |
| 587 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6WAY TPN DB |
| 588 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8WAY V TPN DB |
| 589 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8WAY TPN DB |
| 590 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 591 | Single pole |
| 592 | Double pole |
| 593 | Triple pole |
| 594 | Triple pole and neutral |
| 595 | S&F of 40 Amp. TP MCB (10 KA) C CurveCAT-A |
| 596 | S&F of 63 Amp. TP MCB (10 KA) C CurveCAT-A |
| 597 | S&F of 6 Amp. to 40 Amp. 4 pole MCB (10 KA) C Curve CAT-A |
| 598 | S&F of 6 Amp. to 63 Amp. 4 pole MCB (10 KA) C Curve CAT-A |
| 599 | Dismantlinmg of ExistingPanel & shifting of same at appropriate location as per Direction of Engineer In-charge |
| 600 | Repairing of Floor L.T panel including painting, fixing of rating plates, repairing of door lock etc. as required. |
| 601 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 602 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 603 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy