Tender For Replacement Of 1 X 180 Kva Dg Set At Mlc, 4 X 320 Kva Dg Set At Tph-Ii And 1 X 380 Kva Dg Set At Ntph At Ilc, Dhamra, Cce(R And D)E/Enq-02/Dg/Bls/2024-25, Kendujhar-Odisha

Defence Research And Development Organisation-DRADO has published Tender For Replacement Of 1 X 180 Kva Dg Set At Mlc, 4 X 320 Kva Dg Set At Tph-Ii And 1 X 380 Kva Dg Set At Ntph At Ilc, Dhamra, Cce(R And D)E/Enq-02/Dg/Bls/2024-25. Submission Date for this Tender is 18-05-2024. Diesel Generators Tenders in Kendujhar Odisha. Bidders can get complete Tender details and download the document.




Tender Notice

43322100
Corrigendum : Tender For Replacement Of 1 X 180 Kva Dg Set At Mlc, 4 X 320 Kva Dg Set At Tph-Ii And 1 X 380 Kva Dg Set At Ntph At Ilc, Dhamra, Cce(R And D)E/Enq-02/Dg/Bls/2024-25
Open Tender
Indian
Odisha
Kendujhar
18-05-2024

Tender Details

Replacement Of 1 X 180 Kva Dg Set At Mlc, 4 X 320 Kva Dg Set At Tph-Ii And 1 X 380 Kva Dg Set At Ntph At Ilc, Dhamra, Replacement Of 1 X 180 Kva Dg Set At Mlc, 4 X 320 Kva Dg Set At Tph-Ii And 1 X 380 Kva Dg Set At Ntph At Ilc, Dhamra

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 13-May-2024 Corrigendum Other 18-05-2024
2 15-May-2024 Corrigendum-II Other 18-05-2024

Key Value

Document Fees
Refer document
EMD
INR 506000.0 /-
Tender Value
INR 2.52 Crore /-

BOQ Items

Name of Work:REPLACEMENT OF 01 x 180 KVA AT MLC, 04 X 320 KVADG SET AT TPH-II & 01 X 380 KVA DG SET AT NTPH AT ILC, DHAMRA
Sl. No. Item Description
1Supply, transportation, Installation, testing and commissioning of 415 v. 3 phase 50 HZ, 4 wire Radiator Cooled 01 x 180 KVA DG Set CPCB-II norms approved with Acoustic Enclosure and with control panel, AMF Panel etc with all accessories such as selector switches control fuses, erected on the foundation laid by the customer. The Diesel Engine shall be complete with necessary control and safety devices as per IS/ BS specifications. The Engine shall be suitable for continuous operation of Generator duty, inclusive ofFly wheel, flexible coupling air cleaner, corrosion resistor, Radiator, fan with guard. Fuel pump, fuel filter, 990 Ltrsfree standing fuel tank, Electronic governor, Starting system with separate Battery charger with 1 No24 V Sealed maintenance free battery. Voltage regulator. Instrument panel with RPM Indicator, Exhaust Silencer (Residential), Protection against low Lub. oil pressure, high water temperature and with fuel tank, fuel lines from fuel tank to DG Set, Battery stand anti vibration pads and first filling of lubricatingoil and fuel oil for set including earthing. The alternator shall be suitable for 415 V 3 Phases, 4wire, 50HZ AC supply operation and shall be able to deliver full load current at 100% Unbalance load and including dismantling old one or as directedby Engineer-in-Charge.
2Extra Synchronizing panels where ever required.
3Supply, transportation, Installation, testing and commissioning of 415 v. 3 phase 50 HZ, 4 wire Radiator Cooled 04 x 320 KVA DG Set CPCB-II norms approved with Acoustic Enclosure and with control panel, AMF Panel etc with all accessories such as selector switches control fuses, erected on the foundation laid by the customer. The Diesel Engine shall be complete with necessary control and safety devices as per IS/ BS specifications. The Engine shall be suitable for continuous operation of Generator duty, inclusive ofFly wheel, flexible coupling air cleaner, corrosion resistor, Radiator, fan with guard. Fuel pump, fuel filter, 990 Ltrsfree standing fuel tank, Electronic governor, Starting system with separate Battery charger with 1 No24 V Sealed maintenance free battery. Voltage regulator. Instrument panel with RPM Indicator, Exhaust Silencer (Residential), Protection against low Lub. oil pressure, high water temperature and with fuel tank, fuel lines from fuel tank to DG Set, Battery stand anti vibration pads and first filling of lubricatingoil and fuel oil for set including earthing. The alternator shall be suitable for 415 V 3 Phases, 4wire, 50HZ AC supply operation and shall be able to deliver full load current at 100% Unbalance load and including dismantling old one or as directedby Engineer-in-Charge.The rate is including transportation from MLC to ILC.
4Extra Synchronizing panels where ever required.
5Supply, transportation, Installation, testing and commissioning of 415 v. 3 phase 50 HZ, 4 wire Radiator Cooled 380 KVA DG Set CPCB-II norms approved with Acoustic Enclosure and with control panel, AMF Panel etc with all accessories such as selector switches control fuses, erected on the foundation laid by the customer. The Diesel Engine shall be complete with necessary control and safety devices as per IS/ BS specifications. The Engine shall be suitable for continuous operation of Generator duty, inclusive ofFly wheel, flexible coupling air cleaner, corrosion resistor, Radiator, fan with guard. Fuel pump, fuel filter, 990 Ltrsfree standing fuel tank, Electronic governor, Starting system with separate Battery charger with 1 No24 V Sealed maintenance free battery. Voltage regulator. Instrument panel with RPM Indicator, Exhaust Silencer (Residential), Protection against low Lub. oil pressure, high water temperature and with fuel tank, fuel lines from fuel tank to DG Set, Battery stand anti vibration pads and first filling of lubricatingoil and fuel oil for set including earthing. The alternator shall be suitable for 415 V 3 Phases, 4wire, 50HZ AC supply operation and shall be able to deliver full load current at 100% Unbalance load and including dismantling old one or as directedby Engineer-in-Charge. The rate is including transportation from MLC to ILC.
6Extra Synchronizing panels where ever required.
7NOTE: The rates for DG Sets and Synchronizing panels are inclusives of : (a) 04 Core Control Cable 60 RM is required for Synchronise Panel. (b) 300 Sqmm XLPE Aluminum Armoured 3.5 Core Cable 60 RM. (c) 150/200 mm MS Bend 12 Nos. (d) 150/200 mm MS Pipe 50 Mtr is required for extension of silencer. (e) Asbestos rope 50 kg is required for convering of silencer.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail