Repair/ Maintenance Of Lt Distribution System Of Mech Demo, Amu Node, Saragarhi, Pw Div, Sw Div, Mt Area, Dunn Marg, Hpp Of Inf Areaand Repair/ Maint Of Peremeter Security Lights And Periphery Lights With Connected Items At Various Locations Under Ge (Mis, Indore-Madhya Pradesh

Military Engineer Services-MES has published Repair/ Maintenance Of Lt Distribution System Of Mech Demo, Amu Node, Saragarhi, Pw Div, Sw Div, Mt Area, Dunn Marg, Hpp Of Inf Areaand Repair/ Maint Of Peremeter Security Lights And Periphery Lights With Connected Items At Various Locations Under Ge (Mis. Submission Date for this Tender is 27-05-2024. Overhead Line Tenders in Indore Madhya Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

43312504
Corrigendum : Repair/ Maintenance Of Lt Distribution System Of Mech Demo, Amu Node, Saragarhi, Pw Div, Sw Div, Mt Area, Dunn Marg, Hpp Of Inf Areaand Repair/ Maint Of Peremeter Security Lights And Periphery Lights With Connected Items At Various Locations Under Ge (Mis
Open Tender
Indian
Madhya Pradesh
Indore
27-05-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Repair / Maintenance Of Lt Distribution System Of Mech Demo, Amu Node, Saragarhi, Pw Div, Sw Div, Mt Area, Dunn Marg, Hpp Of Inf Areaand Repair / Maint Of Peremeter Security Lights And Periphery Lights With Connected Items At Various Locations Under Ge ( Mis ) Mhow

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 15-May-2024 Other Corrigendum Other 27-05-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 94000.0 /-
Tender Value
INR 47 Lakhs /-

Attachment

FileName File Description File Size
e87783d6-c7db-4379-a442-a2444b6c455b.html Tender Notice 0 KB
BOQ_730402.xls Tender Document 0 KB
PS8645.pdf Tender Document 0 KB
TENDER8645.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

Name of Work: REPAIR/ MAINTENANCE OF LT DISTRIBUTION SYSTEM OF MECH DEMO, AMU NODE, SARAGARHI, PW DIV, SW DIV, MT AREA, DUNN MARG, HPP OF INF AREAAND REPAIR/ MAINT OF PEREMETER SECURITY LIGHTS AND PERIPHERY LIGHTS WITH CONNECTED ITEMS AT VARIOUS LOCATIONS UNDER GE (MIS) MHOW
Sl. No. Item Description
1Excavating in trenches, in any type of soilnot exceeding 1.5m wide and not exceeding 1.5m in depth for laying cable, pole foundation etc complete all as specified.
2All as per item No 02 abovedepth exceeding 1.5m but not exceeding 3.0m
3M&L for plain cement concrete1:2:4 type B2 using 40 mm graded stone aggregateas in foundation, filling and mass concrete all as specified
4M&L for plain cement concrete1:4:8 type D2 using 40 mm graded stone aggregateas in foundation, filling and mass concrete all as specified
5M&L for plain cement concrete1:3:6 type C1using 20 mm graded stone aggregateas in roof kerbs or pole coping of size 300x300 mm, chamfered on edges including necessary form work etc completeall as specified and directed.,
6Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete.
7Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete.
8M&L for sand cushioning with fine dry unwashed sand in trenches for protection of cables complete. Note :- Thickness shall be measured after punning
9M&L for old size sub class ‘B’ bricks, laid in trenches as a cable covers complete.
10S&F steel tubes, galvanised, light grade, ISI marked 40mm bore for protection of cable under floor, road and on wall complete.
11S&F steel tubes, galvanised, light grade, ISI marked 80mm bore for protection of cable under floor, road and on wall complete.
12M&Lfor dismantalingold cracked /unserviceable PCC poles /MS pole struts of any type and size including deposited at a suitable location not more than 50 metreaway complete all as specified and as directed by Engineer-in- Charge.
13M&L for Steel tubular swaged poles complete with base plate 8mm thick welded with pole, finial taper plug, bolt, nut and screws as specified type 410 SP-31 (9m long) including one coat of red-oxide zinc chrome primer and two coats of aluminium paint on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with white and black paint alternately on external surface above PCC benching including numbering with black paint and painting with bituminous paint internally complete and externally complete all as specified and directed. Note : Excavation & earth work and PCC shall be measrued and paid separately under relevant item. Make : India Tube and Co, Kalinga tubes, The National tubing company, India Electric Poles Mfg Co
14Supply and laying copper conductor PVC round sheathed (flexible) industrial cable of size 10 sqmm.Note:- Quoted rate shall be inclusive forcopper lugs as required at site
15Supply and laying copper conductor PVC round sheathed (flexible) industrial cable of size 4 sqmm.Note:- Quoted rate shall be inclusive forcopper lugs as required at site
16M&L for attending external electric complaints by opening / disconnecting the electrical connection of defective / burnt out underground LT cable of any size & any core from main switch / DB / junction box / LT panel / L T O/H line etc. and taking out therequired length of cable from existing loop and remove/ cut the defective cable,replace the same with new cable as per existing size including providing necessarythimbles / connectors at cable end and reconnecting the cable in previous location with existing main switch / DB / Junction box / LT panel / OH line etc. and make electic connection as functionable in all repspects including testing on completion all as specified and directed by Engineer-in-charge.
17Note:- (A) The quoted rateshallbe inclusive of the following: (i) Necessary earth work excavation as required for finding/attemding faullt /in any type of soil, returningfilling and removing extra soil.(ii) Existing bricks, sand,GI protection pipe etc. shall be removed carefully and stackedneatly near site andre- laid the same in position after attending fault/defect.(iii)Distrubed surface of road, floor etc. shall be make good to match with existing surface. (iv) Required numbers of electrician and helper shall be deployed for attending complaints regulerly on daily basis and contractor shall collect the complaints details from complaint cell of AGE E/M No.1 and same shall be rectified/ attanded within an hour and report shall be submitted to Engineer-in-charge or their authorised representative.(B) Please note that payment shall be made to contractor one time only for this items. if any fault/ default occured again on the same location/ DB/junction box/panel during currency of contract, the same shall be rectified by the contractor without any extra cost to Govt. in terms of condition 46 of IAFW 2249of Genral condition of contracts.(C) Additional bricks,sand,GI pipe etc. as required for cable protection and cushioning shall be measured and paid separetely under relevant item.
18M&L for dismantling / disconnecting / removing the faulty / burnt out overheadconductor of any type / size from insulator of HT / LT pole any type by makingproper shutdown from department and removingof tree / branches if any fell on Over Head Line,loose the binding wire in each insulators and disconnecting cable connection as required, remove the burnt / damage conductor / earth wire and making necessary joint with new ACSR conductor of suitable size as per existing as directed, restretching allloose spans of ACSR conductors, earth wire etc. with insulator and providing binding wire of existing size to tigheting and making LT/HT cable in existing position and make electric connection as functionable in all respects including testing on completion allas specified and directed by Engineer in charge.
19NOTE:(a) The quoted rate shall beinclusive of the following:-(i) Tools and plants such as ladder,rope, cutter, axes, knife etc. as required for cutting and removing tree/branches if any fall on OH line.(ii) Insulator,binding wire etc. as required in addition to existing shall be provided by the contractor.(iii) Required numbers of Elecrician and helper shall be deployed for attending complaint regularly on daily basis and contractor shall collect the complaint details from complaint cell of AGE E/M No. 1(b) Additional ACSR conductor and earth wire shall be measured and paid separetely under relevantitems.
20S&F in replacement ofLED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.
21S&F in replacement of LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.
22M&L for Painting of transformerof capacity up to500 KVA,11/.433 KV by applyingtwo coats of synthetic enamelled paint over a coat of primer by using spraying machine includingpreparation of transformer surface andremoval of rusted portioncomplete all as specified and directed.
23M&L for Tracing out fault upto11KV underground cable of any size by usingfault tracing machine and rectifying the same by cutting and removing defective cable ,providing necessary cable of same sizeand jointing with existing cable allas specified and directed by Engineer-in-Chargeto restore the electric supply complete all as specified and directed by Engineer-in-Charge. Note: (i). Joint kit shall be measured and paid separately. (ii)Earth work eacavationshall be measured and paid separately. However, width of trenches shall be allowed for payment as per authorized width as given in SSR part I for each size of cable. (iii) All other necessary arrangements suitable for locating the faultssuch as fault checking instrument etc shall deemed to be included in the unit quoted rate . (iv)T&P required for the entire job shallbe provided by the contractor at his own end and nothing extra shall be admissible on this account. (v) Cable required, if any shall be measured and paid for separately.
24M&L for trimming /pruning of tree branches touching to the LT over head line or near to the LT over head line as per direction of Engineer-in- charge complete including removing the tree branches from site complete all as specified and directed . NOTE : (a) A written shut down shall be obtained from concerned JE / AGE E/M before carrying outthe trimming work in hand by contractor(b) Approximate span between poles shall be 30 to 50m. (c) T & P such as ladder , rope, cutter , axes and other related material shall be provided by the contractor.
25Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and over all PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of size 10 sqmm.
26Supply and Laying LT UG cable 1100 Volts grade XLPE insulated PVC sheathed amoured, heavy duty, in trenches/walls/poles/passing through pipes with multistranded aluminium conductor including lugs/thimble/ferules connection, testing and commissioning complete including taking out old unserviceable UG cable for the following sizes. Note: Earth work, excavation, sand cusioning, bricks for protection, GI pipe etc shall be measured and paid separately under relevant items of this schedule .
2710 sqmm 2.0 core
2810 sqmm 4.0 core
2916 sqmm 4.0 core
3025 sqmm 3.5 core
3135 sqmm 3.5 core
3250 Sqmm 3.5 core.
3370 Sqmm 3.5 core.
3495 Sqmm 3.5 core.
35120 Sqmm 3.5 core.
36185 Sqmm 3.5 core.
37240 Sqmm 3.5 core.
38S&Fin repairs Aluminium lugs of size 16 sqmm
39S&F in repairs Aluminium lugs of size 25 sqmm
40S&F in repairs Aluminium lugs of size 35 sqmm
41S&F in repairs Aluminium lugs of size 50 sqmm
42S&F in repairsAluminium lugs of size 70 sqmm
43S&F in repairsAluminium lugs of size 95 sqmm
44S&F in repairsAluminium lugs of size 120 sqmm
45S&F in repairsAluminium lugs of size 185 sqmm
46S&F in repairsAluminium lugs of size 240 sqmm
47S&F in replacement of MCCB 3 Pole, 415 V, fixed type, 25 to 100 Amps with breaking capacity 16 KA
48S&F in replacement of MCCB 3 Pole, 415 V, fixed type, 125 Amps with breaking capacity 16 KA
49S&F in replacementofMCCB 3 pole, 415 volts, adjustable type 160 Amps with breaking capacity 36 KA
50S&F in replacementofMCCB 3 pole, 415 volts, adjustable type200 Amps with breaking capacity 36 KA
51S&F in replacementofMCCB 3 pole, 415 volts, adjustable type250 Amps with breaking capacity 36 KA
52S&F in replacementofMCCB 3 pole, 415 volts, adjustable type350 Amps with breaking capacity 36 KA
53S&F in replacementofMCCB 3 pole, 415 volts, adjustable type400 Amps with breaking capacity 36 KA
54S&F in replacementof MCCB 4 pole, 415 volts, adjustable type 250 Amps with breaking capacity 36 KA
55S&F in replacementof MCCB 4 pole, 415 volts, adjustable type 350 Amps with breaking capacity 36 KA
56S&F in replacementof MCCB 4 pole, 415 volts, adjustable type 400 Amps with breaking capacity 36 KA
57S&F in replacement of pin type porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volts grade.
58S&F in replacement of shackle type porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts, of height 75 mm and max dia 90 mm suitable for working pressure 1100 volts grade.
59S&F inreplacement of disc insulator, porcelain, vitreous 145 mm high and 255,, dia ball and socket type, white, brown or green suitable forsingle disc asst for tension with tension clamps for conductors, working pressure 11000 volts grade.
60M&L for replacement of broken over head conductor of any type and length as required at site supply and fix ACSR conductor of size and type as per existing complete all as specified and directed .
61M&L for Restringing ofloose over headconductor / GI earth wireof any size and typeafter untyeingbinding wire from insulators / cross arms to achieve permissible sag limit of over head lineincluding new binding wire of proper size and pruning of tree branches of concerned spans and jointing of jumpers properly complete all as specified and directed at site. Note:- (i) Each span shallconsist of 3 phase , 4-wire over head line. (ii) The distance of one span between poles shall be 30 to 50 metre .
62S&F in repalcement ofstraight through joint ( Epoxy joint) for following size PVC insulated and sheathed aluminium conductor cable complete for following sizes :-
633.5 core 50 sq mm
643.5 core 70 sq mm
653.5 core95 sq mm
663.5 core 120 sqmm to 150 sqmm
673.5 core 185 sqmm
68M&L for disconnecting the existing incoming and outgoing cablefrom exiting old LT panel of required length after taking down power shut down and exiting all safety precautions for human safety , including reconnecting the all connections to bus bar after cleaning the dust from LT panel , replacethe aluminium lugs of suitable size , properlyinsulatingthe cable with high class LT insulating tape with proper colour codingand make the LT panel functionable in all respects complete all as specified and directed by Engineer-in-Charge .NOTE : (a)All ammeter , voltmeter and selector switch shallbe functioning in proper way (reading shall bematched with multimeter or clamp on meter up toerror 5 precent) (b) Fuse or MCBfor ammeter and voltmeter in LT pane shall besupplied by contractor (c) All nut bolts with washer of suitable size as required for LTpanelshall besupplied by contractor
69M&L for repairing damaged /corroded portion of existing LT panel board of any size by providing and welding MS sheet of existing thickness, replacing hinges, aldrop bolt as required and made for proper locking system and painting internal and external surface ofLT panel with one coat of synthetic enamel paint of approved colour all as specified & directed by Engineer-in-charge.
70M&L for Maintenance of indoor sub stations, including cleaning of premises and surroundings upto 5m from outer face of wall, checking theoil level of transformers, cleaning and dusting out of transformers, panel boards, cleaning of earth pits to keep free from vegetation and spray Glphosate 41% chemicalby using spraying machine etc complete all as directed by Engineer-in-Charge . Note:-Glphosate 41% chemical shall be measured and paid separatelyunder respective item .
71All as per item No52here in before but for out door sub station /RMUs / SurroundingLT Panellsincluding levelling of loose filled aggregate in proper manner around substation
72Supply only Glphosate 41% chemical
73S&Fin repairs mild steel galvanised stay assembly set complete comprising of 20mm dia, 400mm long stay bow, 1800 mm long stay rod 20mm dia,300mm x 300mm x 6mm stay plate, thimble, GI stay wire of 7/8 SWG upto required length including loop type insulator of vitreous porcelain, small size with overall dimensions 90x140mm, clearance of hole 25.5mm,all as shown in electrical plate No.1 of MES Schedule part I2009 completeall as directed.
74M&L for replacement of Danger notice plate of size 20x15 cm for LT cable and 25x20cm for HT cable with 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with mild steel clamps, bolts and nuts of approved size complete all as directed by Engineer-in-charge.
75M&L forpreparing surface ofstreet light ,steel tubular swaged/ swan neck pole of any typeand painting with two coats of aluminiumpaint over acoat primer fromtop to bottom includingpainting tocross arms /FI clamps/street light brackets of any type including making painting alternative bay withblak and yellow strip with synthethic enemelled paintup to 1.5 meterheight from ground level and writing of polenumbers with black paint onpoles completeall as specified
76M&L for preparation of old painted surface of LTPCCstreet light pole 9m long with one coat of acrylic paint over a two coats of cement base paint and making pole surface smooth including painting cross arms, clamps etc with two coats of aluminum paint and painting up to 1.50 mheight from top of PCC foundation block and painting the pole in alternative strips with black and yellowpaint (each strip 30cm high) and including writing pole nos. and applying one coat of cement base paint on exposed surface of PCC coping and foundation blocks complete all as specified and as directrd by Engineer-in-charge.
77Supply, fabrication, installation, testing and commissioning ofout door typeLT panel board of size 600x600x300 mm cubical type,made out of 3.15mm thick CRCA sheet , factory made,with slantingtop ,minimum10 Cm projection all around, inbuilt industrial type ,fabricatedwith 50x50x6mm angle iron frame workwith frontopenablesingle hinged door / shutter with locking arrangments, floor mounting type duly spray painted with two coat of gray synthetic enamel paint over one coat of red oxide zinc chrome primer after preparation of the surface , with required civil work & wiring with copper cable of suitable size, connecting including indication lamp LED type for each phase, Aluminium bus bar - 400 Amps rating - 03 Nos. for phases and 400 Amp rating - 01 No. for neutral fixing with suitable, clamps,nuts, bolts wahers ,danger notice board , feeder markedincluding necessary earth work excavation , PCC foundation etc as required at sitecomplete all as specified and directed by Engineer-in-Charge
78S&F cable path indicator made of MS sheet of size 200 mm x 150 mm x 3 mm thick and spot welding withangle iron of size 40 x 40 x 5 mm thick, 750 mm long embedded in PCC1:2:4type B1using 12.5 mm graded granite stone aggregateincluding applyingone coat of synthetic enameled black paint over acoat of red oxide primer and sign writing with white paint duly showing size of HT/LT cable complete all as specified and directed.
79M&L for cutting the existing bituminouse road to a width n.exc 0.50m for passing of UG Cable asin road crossing and making good thedisturbed surgace of road with PCC 1:2:4 type B1 using 20mm graded stone aggregate completeall as specified and directed
80M&L for Earthing complete with galvanised steel earth plate electrode of size 60cm×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less"than 1.5 metrebelow normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion.
81Supply, fabrication, installation, testing and commissioning ofout door typeLT panel board of size 1500mm x 1200 mm x 500 mm cubical type,made out of 3.00mm thick CRCA sheet , factory made,with slantingtop ,minimum10 Cm projection all around, fedder pillar type,fabricatedwith 50x50x6mm angle iron frame workwith front and back side openablesingle hinged door / shutter with locking arrangments, floor mounting type, busbars made of copperduly insulated with heat retardent fire proof (HRFR) heat shrinkable sleeves of relevant colours,bus bar shall be properly supported/mounted on epoxy insulators ,all live parts and joints shall be insulated with (HRFR) shrouds, conforming to IS, including provision for connecting suitableearth strips,painting with one coat of anti corrosive coating and finally epoxy polyester powder coating, and confirming relavent IS, comprising the adequate arrangement to supply & fix the following accessories,including connecting cable glands,enamelled danger notice plate of 1.60mm thick miled steel sheet of size 200mm x 150 mm and cable lugs,fixing of earth lead to earth terminal of panel including necessary earth work excavation , PCC foundation etc as required at sitecomplete all as specified and directed by Engineer-in-Charge.Note:- Quoted rate shall inclusive for all following accessories
82Incoming (a) Aluminium bus bar - 400 Amps rating - 03 Nos. for phases and 150 Amp rating - 01 No. for neutral
83(b) MCCB 4 pole 250 Amps, 415 volt, 36 KA - 01 No ( incoming)
84(c)3 phase Voltmeter (0-500V) digital type with selector switch-01 No
85(d)3 phase Ammeter (0-400 Amps) digital type with CT"s of suitable ratio and selector switch - 01 No.
86(e) ON/OFFLED type indication lamp with toggle switch - Set of 03
87Out going:- (a)MCCB 4- pole 160 Amp, 415 volt, 25 KA - 01 Nos
88(b) MCCB 4 pole 100 Amp, 415 volt, 25 KA - 02 Nos
89(c)MCCB 4 pole 63 Amp, 415 volt, 16 KA - 02 Nos
90(d) MCB TPN 40 Amp, 415 volt, - 2 Nos
91S&F in replacement Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP 66 flood light (Area light) of 30 Watt, suitable for highlighting architectural façade and general purpose lighting including all necessary fixing arrangments complete.
92S&F in replacement for LED flood light 120 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp.
93S&F in replacement for post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete. Make:- BAJAJ CAT PART NO- BGCTNP 20W LED WH/WW or equivalent in PHILIPS / WIPRO
94S&F in replacement of LED bollard with opal diffuser and aluminum reflector capacity 09 watt including all necessary fixing arrangments as per site requirement includingPCC work of suitable size and taking down existing unserviceable one complete all as directed at site. Make : BAJAJ Cat Part No.BGBOL 605 9W LED WW or equivalent in PHILIPS/ Wipro
95S&F in repairs moulding compound Street light junction box of size 250 mm x 200 mm x 105mm complete with shock and rust proof, termite resistant, tamper proof , front openable type and including suitable provisionfor single phase, two wire cable (size upto 25 Sqmm 2 Core) incomming & outgoing loop -in loop connection and including one no. MCB SP 6 Amp including non metallic clamps and GI nut bolts and washers of suitable size and fixed on pole / wall complete. Make : Sintex Cat part No GSJB 2520 or equivalent in Hensel/ABB.
96S&F in repairsmoulding compound street lightjunction box of size 250 mm x 250 mm x 160mm complete with shock and rust proof, termite resistant, tamper proof , front openable type and including suitable provision for three phase, four wire cable (size upto 25 Sqmm 4 Core) incomming & outgoing loop -in loop connection and including one no. MCB SP 6 Amp including non metallic clamps and GI nut bolts and washers of suitable size and fixed on pole / wall complete. Make : Sintex Cat part No GSJB 2525 or equivalent in Hensel/ABB.
97M&L for repairing the existing junction box/ control box of street light by disconnecting all connection and reconnect the same after repairing including dusting, proper insulation with LT tape, replacement of lugs, nuts , bolts washer etc as requried including provision of 01 No of MCB06 Amps and making the junction box funcationable complete all as specified and directed by Engineer - in -Charge.
98M&L for repairing existing street light feeder over head conductors by disconnecting electric supply through proper shut down of street light feeders from sub station, to remove oxidise part at the point of connection to street light from LT over head line and reconnect the same to LT over head line after removing the oxidise part and make functionable all as specified and directed by Engineer-in-charge . Note:-Highly skilled Electrician with skilled helper andnecessary tools and sfety equipment shall be provided by the contractor.
99M&L for checking ofstreet light feeder over head conductors /under ground cables using necessary tools, equipments and safty devices by disconnecting electric supply through proper shut down and repairing/attending faults of street light feeders from sub station by tightning of loose jumpers, trimming of tree branches on a particular span, re-tightning of binding wires on insulators, re-tightning of cable lugs etc all as required at site and as directed by Engineer-in-Charge. Note:-(a) Highly skilled Electrician with skilled helped andnecessary tools and sfety equipment shall be provided by the contractor.(b) ACSR conductor, insulator, cables and earthwork as required for repairing / rectification of faults shall be measured and paid separately under relevant items.
100M&L for repairing street / security light ofany type andflood lights / post top lanterns or any other external lights in its position fixed pole / building structure or by taking down to ground, if required and testing all the components / parts, wiring etc, identifying and replacing the defective components like choke (ballast), electronic driver (in case of LED Lights), ignitor, capacitor, lamp, lamp holder, connector, connection wires/ cable, MCB etc and refixing the fitting in its original position (if taken down), including repairing of street light control timer & junction box and makethelight fitting functionable in all respects complete all as directed by Engineer-in-charge.
101Note:-(a) Spares such as choke (ballast), electronic driver, Ignitor, capacitor, lamp, lamp holder, connector, connection wire, MCB, timer spares etc shall be measured & paid separately under respective items. (b) The contractors / Representative shall report to concerned JE E/M at 09.00 hours daily to collect the details of complaints of defective street lightfittings and shall submit the completion report of complaints of fitting on the same day before 17.30 hours to JE E/M. (c) The contractor shall rectify the defects / repair and make the street light functional within 24 hours fromthe time of handing over of complaint over by the concerned JE E/M.An amount ofRs 150/ dayper complaint shall be recovered from contractor if street light shall not be repaired and functionable within 24 hours.
102(d)Contractor shall arrange requisite and sufficient no of labours,ttransport and vehicle mounted hydraulic ladder etc at his own arrangement. (e)The contracor shall maintain proper record of repair/maint of light fittingsin a binded register duly showingthe details of spares replaced on each and every street light and get it authenticated from concerned JE E/M on daily basis. The contractor shall show therecord register to Engineer-in-charge for inspection every Monday or as and when asked for. (f)The contractor shall be fully responsible for the safety of his men engaged for executing this work and provide all requisite safety equipment and clothings etc to Electrician & Helper. Contractor shall be fully responsible for any kind of mishappening /accident / injury etc if any to his employed labours.
103(g) The contractor shall maintain sufficient stock of spares/material as required for repair/maint of street lights. (h) Contractor quoted rateshall be inclusive for screws, insulating tapes, internal wiring wire, gaskets and other minor items as required for repairing and making the street light fittings/security light fittingsin serviceable condition.
104All as per item No 73 but for light fittings from high mast poles of 11 to 13 m long.
105Taking down high mast fitting from high mast structure through motorised system of 16/20m highand chekingall fittings including cleaning & lubricatingof steel rope and repairthe light fittingsto make functional by replacing Flood light. Note:- Flood light and connecting cable shallbe measured and paidseperately under respective items .
106Supply only following items/spares.
107Supply only LED driver for FLOOD LIGHT of capacity 150 watts rating 240 Volt, 50 Hz. Make:- Philips, Bajaj, Havells
108Supply only LED driver for FLOOD LIGHT of capacity 120 watts rating 240 Volt, 50 Hz. Make:- Philips, Bajaj, Havells
109Supply only LED driver for FLOOD LIGHT of capacity 80/100 watts rating 240 Volt, 50 Hz. Make:- Philips, Bajaj, Havells
110Supply only LED driver of capacity 60/70 watts rating 240 Volt, 50 Hz. Make:- Philips, Bajaj, Havells
111Supply only LED driver of capacity 30/36/45 watts rating 240 Volt, 50 Hz.Make:- Philips, Bajaj, Havells
112S&F in repairs, single core pvc insulated and sheathed cable with multistranded aluminium condutor ofsize 2.5 sqmm x two core and drawing in to existing GI pipe bracket and connect tostreet light fittings complete all as specified and directed
113M&L for street light bracket made out of 40mm dia medium grade GI pipe of 1.2m length bent to required shape suitable for fixing street light / security light fitting on M&L for street light bracket made out of 40mm dia medium grade GI pipe of 1.2m length bent to required shape , suitable for fixing street light / security light fitting on Steel tubular pole/ RCC pole / building wallincluding two Nos of clamps made out 30mm X 5mm flat iron with suitable nuts and bolts (clamp type - as per siterequirement ) including two coats of aluminium paint over a coat of red oxide primer and taking down the existing unserviceable rusted street light brackets with clamps, nuts and bolts etc complete all as directed. Make:- TATA/JINDAL/SWASTIK
114M&L Re-stretching ,tightening and fixing in position, the existing OH ACSR conductor LT line 3 phase with neutral and earth wire 440 V, 5/6 wire by loosing and taking down existing binding wire from the insulator of any size of ACSR conductor and bring it to required sag including provision of new binding wire and tightening of cross arm on each pole and required trimming of tree branches. complete all as specified and directed by Engineer-in-charge. Note :-(a) Each line of wire shall be measured separately. (b) Unit ratequoted by the contractor shall deemed to be includefor cutting and trimming branches of the trees coming in contact with ACSR conductor and separators as directed by Engineer-in-charge.
115Supply and fixin repairs MCB TPN, 415V, 40 Amps,
116Supply and fixin repairs MCB TPN, 415V, 63 Amps,
117Supply and fixin repairs MCB SPN, 415V, 40 Amps,
118S&Fin repairs MCCB 125 Amps, 16 KA, FP, 415 volts with neutral link including al cable lugsall as specified
119S&Fin repairs MCCB 100 Amps, 16 KA, FP, 415 volts with neutral link including al cable lugsall as specified
120S&Fin repairs MCCB 200 Amps, 26 KA, FP, 415 volts with neutral link including al cable lugsall as specified
121Supply, install, testing ,commissioning andreplacement of street light control boxas a pole mountable enclosureconforms to IP-64 suitable for 440/230V, AC, 50 Hz,consisting of a light sensitive control system, power contactor for load switching, MCB and terminal suitable for 1 phase, 5 KW load blocks all as specified. Make : Swadeep Nature Switch model No 02EC5kW1P or equivalent in CG/L&T/phillips
122Supply, installation testing and commissioning replacement of street light control boxas a pole mountable enclosureconforms to IP-64 suitable for 440/230V, AC, 50 Hz,consisting of a light sensitive control system, power contactor for load switching, MCB and terminal suitable for 3 phase, 5 KW load blocks all as specified. Make : Swadeep Nature Switch model No 02EC5kW3P or equivalent in CG/L&T/phillips
123S&F in replacement of Single phase contactor 5kW of load capacity 40 Amps, Incoming-Outgoing MCB rating 32-40 Amps & Circuit wiring minimum 10 Sqmm complete all as specified . Make:- ABB/L&T/Schneider
124S&F in replacement of three phase contactor 5kW of load capacity 20-25 Amps, Incoming-Outgoing MCB (03 Nos each) rating 20-25 Amps complete all as specified Make:- ABB/L&T/Schneider
125S&F Nature switch sensor illuminate level for switching on < 30 lux and for switching off > 10 lux alongwith part night operation facility of 4-12 hours. Make:- Swadeep or equivalent in CG
126S&F MCB SP 6 to 32 Amps 230 Volt . Make:- ABB/L&T/Schneider
127S&F in repairs Digital Timer switch for 1x 24 hoursfor controllingstreet light timimng with 150 hours back up.Make:- ABB/L&T/Schneider
128S&F in repairs PVC conduit , medium grade, ISI marked 20mm bore for laying of sub-main wire/cable on Street light Pole fixedon wallincludingnecessary accessories & fixing arrangments like PVC band, clamps , nut -bolts etc.complete all as specified and as directed.