Tender For Repair/Replacement Of Security Lights/Solar Light Fitting With Led Fittings Incl Other Allied Works At Khalsar And Hunder Under Ge 873 Ews, Leh-Jammu And Kashmir

Military Engineer Services-MES has published Tender For Repair/Replacement Of Security Lights/Solar Light Fitting With Led Fittings Incl Other Allied Works At Khalsar And Hunder Under Ge 873 Ews. Submission Date for this Tender is 27-05-2024. LED Light Tenders in Leh Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

43311111
Tender For Repair/Replacement Of Security Lights/Solar Light Fitting With Led Fittings Incl Other Allied Works At Khalsar And Hunder Under Ge 873 Ews
Open Tender
Indian
Jammu And Kashmir
Leh
27-05-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Repair/Replacement Of Security Lights/Solar Light Fitting With Led Fittings Incl Other Allied Works At Khalsar And Hunder Under Ge 873 Ews

Key Value

Document Fees
INR 500 /-
EMD
INR 36000.0 /-
Tender Value
INR 18 Lakhs /-

Attachment

FileName File Description File Size
9a126295-00b9-4ec4-8272-6df20e23d504.html Tender Notice 0 KB
BOQ_730365.xls Tender Document 0 KB
Tender37.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

Name of Work: REPAIR/REPLACEMENT OF SECURITY LIGHTS/SOLAR LIGHT FITTING WITH LED FITTINGS INCL OTHER ALLIED WORKS AT KHALSAR AND HUNDER UNDER GE 873 EWS.
Sl. No. Item Description
1Checking/taking downcarefully existing unserviceable security/street light/flood light fitting of any shape and size or capacity by unscrewing from steel tubular pole of 9 mtr long/wall of bldg including unserviceable bracket complete and make it serviceable and refixing the same at its original position (if repairable with minor repair) all as specified and as directed. Note :- (i) Spares/New fittings shall be measured and paid separetly. (ii) The T&P vehicle and necessary ladder etc will be arranged by the contractor and thecost deemed to be included in the quoted rates. (iii)The contractor boundto provide daily 01 Electrician and 01 helper for carry out the complaint of street light on daily basis.
2Supply and fixing LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete making all necessary connection with suitable capacity of 3 core circular cable complete all as specified and directed. Make- CG/Havells/Phillips or equivalent
3Supply and fixing LED street light fitting 75 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete making all necessary connection with suitable capacity of 3 core circular cable complete all as specified and directed. Make- CG/Havells/Phillips or equivalent
4Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete making all necessary connection with suitable capacity of 3 core circular cable complete all as specified and directed. Make- CG/Havells/Phillips or equivalent
5Supply and fixing LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp making all necessary connection with suitable capacity cable complete all as specified and directed. Make- CG/Havells/Phillips or equivalent
6Supply and fixing LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp making all necessary connection with suitable capacity cable complete all as specified and directed. Make- CG/Havells/Phillips or equivalent
7Supply and fixing post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. Make: Havells/wipro/CG or equivalent
8Supply only LED driver 70/60 Watt for street light as per existing complete all as specified and as directed by Engineer-in-Charge. Note :- (i) Taking down shall be measured separetly under respective item of BOQ.
9Supply only LED driver 35 Watt for street light as per existing complete all as specified and as directed by Engineer-in-Charge. Note :- (i) Taking down shall be measured separetly under respective item of BOQ.
10Material and labour in replacement of PVC insulated multi stranded aluminum conductor PVC cable weather proof flat twin core cable 2.5 Sqmm and making connection of street light fittings with loop box /OH line complete all as specified and directed by Engr-in-Charge. Make : - Havells/Plaza/Kalinga
11Supply and fixing in repair GI bracket for street light made of 40mm bore GI pipe (medium grade of length 1.5 meter), bend to shape including providing flat iron clamp (of suitable size, made out of 40mm x 5mm mild steel flat) with nuts, bolts and washer of suitable size, including applying two coat of red oxide primerand one coat of aluminium paint complete all as specified and directed.
12S&F weather proof Pole junction box made of thermoplastic polycarbonate with gasket comply with IP-65, dust and jet water proof of size 200x160x100 mm suitable size for cable size upto 10 to 25sqmm alongwith cable inlet with for terminal controlled,1.6mm thick with locking arrangement and rubber gasket including suitable aluminum bus bar of size 25 x 3mm for four pole fixed on porcelain insulator and MCB 6 Amp "C" curve -01 no complete with necessary items including a pair of MS flat iron clamp of size 40mmx5mm with 10 mm nuts bolts of suitable length with washer ,suitable to fix in steel tubular pole/PCC pole after taking down old one complete all asdirected. Make -sintex/hens
13Supply and fixing nature timer switch panel to work as per Lux intensity for ON/OFFof street lightsoutdoor type factory made powder coated all along internal and external surfaces, weather proof with IP 55 protection consisting of one No AC contactor, 3 Phase , one No MCB TPN 63 Amps capacity 25 KA at incoming side and 03 Nossinghle phase MCB SP 63 Amps at outgoing side one astronomical timer switch, max load 25 KW with HRC fuse assembly for cut off supply during fault, selector switch having both auto, manual and by pass system, one NO indicator lamp showingt time ON/OFF position complete wiring including incoming and outgoing terminal port duly grouted in PCC 1:4:8 with 30 cm below ground level and 30cm above gounde level complete all as specified and directed. make : Havells Cat No : IHXTS0912A /L&T
14Supply and erecting and fixing in proper position steel tubular swaged poles complete with cast iron base plate, final taper plug, bolts, nuts and screws as specified type 410 SP-31(9.00metres long) Make: Advance steel tube, National tubing co, Mahindra industries, sohan lal and sons,Sidhartha all as specified and as directed. Note: (i)Excavation ,earth work and PCC shall be measured and paid separately. (ii) Painting will be measured and paid seperately under relevent item.
15Material & Labour for PCC (1:3:6) type C-2 using 40 mm graded aggregate as in foundation of pole/stay and filling of mass concrete including providing necessary form work complete all as specified and as directed.
16Material & Labour for PCC (1:2:4) type B-1 using 20 mm graded aggregate as in coping of pole including providing necessary form work complete all as specified and as directed.
17Material and labour for Cleaning and preparation of old surface of street light steel tublar pole and painting by applying two coats of aluminium paint including bracket and alternative black and Yellow strips on pole with synthetic enamel paintupto 1.5 mtr height from top of PCC foundation(each strip 15 cm height)including applying two coats of cement base paint to coping complete all as specified and directed.
18M&L for servicing the solar street light system complete by checking & cleaning PV Module, battery, charging voltage, discharge voltage, loose contacts & fittingetc including topping up distilled water/electrolite, appling petroleum jelly in terminals. Note: Self supported ladder shall be provided by the contractor for cleaning and checking of SPV module since the normal ladder cannot be used.
19S&F in replacement of LED solar DC streetlight 15 watts (with inbuilt CCU)fitting comprising of epoxy powder coated aluminium housing enclosed with glass cover complete including taking down old fitting of any model Make : LHKTBJU7PA6J015 of Havells or equivalent in Philips/ Crompton Greaves
20S&F in replacement of solar panel of 75/80W suitable for 5W solar BP light and 12 V 50/65 AH battery complete all as specified and directed.
21Supply and fix in replacement Solar street Light charge controller unit,12V suitable for solar street light. Make:Sun/Exide/Amaron
22S&F in replacement of sealed maintenance free battery 12 V 42 AH complete all as specified and directed.
23S&F in replacement of sealed maintenance free battery 12 V 65 AH complete all as specified and directed.
24Supply and fix in repair MS box suitable for placing 50/65AH battery, factory fabricated out of L-Angles and steel sheet 3 mm thick of size 60 cm x 30 cm x 60 cm (approx) complete duly powder coated (ivory) with fixing arrangements on street light pole all as directed.
25Material and labour for painting of solar light pole and all structure by smoke grey colour paint in two coat over one coat of red oxide primer complete all as specified and directed by Engr-in-Charge.
26Supply and fix in repair Solar LED Standalone street light 15 W, 12V, 1500 lumen alongwith 75WP Solar Panel and 40AH Battery and 6 mtr tube pole with 2 days battery backupincluding pcc foundation as per specification as specified and directed by Engineer-in- Charge.. Make : Havells/crompton /SYSKA
27Material and labour for taking down the 6/7 lantern symmetrically fitted system from High mast light of 9/12 metres height with their control gear system for repairing the LED flood light fittings, LED aviation obstruction lights and shiting to the same position after completion of repair/replacement all as directed and specified. Note : The spares & replacement of LED flood light fittings, LED aviation obstruction lights are measured and paid separately under relevent items.
28Supply and fix in repairs LED Aviation Obstruction light fitting 302 LED with all accessories, brackets for fixing arrangements etc., on Hanger. Make: Bajaj, Model: BGAV 302 LED or equivalent in Philips/Crompton Greaves/Havells.
29Taking out un-serviceable/faulty cable/service connection cable of any grade / type / class of size of10/16/25 Sq mm4 core for repair / replacement from pole / wall / cable duct under ground trench etc for re-use or removal from site of work all as specified and as directed. (Note- Excavation and earth work shall be measured and paid separately)
30Supply, laying, Jointing and testing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross- sectional area 25 Sqmm 4 core confirming to IS7098 of 1995 laid in trench/ducts/pipe/wall or on poles complete all as specifed and directed. Note : (i) Excavation and earth work will be measured and paid separately under respective items
31Supply, laying, Jointing and testing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross- sectional area 16 Sqmm 4 core confirming to IS7098 of 1995 laid in trench/ducts/pipe/wall or on poles complete all as specifed and directed. Note : (i) Excavation and earth work will be measured and paid separately under respective items
32Supply, laying, Jointing and testing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross- sectional area 10 Sqmm 4 core confirming to IS 7098 of 1995 laid in trench/ducts/pipe/wall or on poles complete all as specifed and directed. Note : (i) Excavation and earth work will be measured and paid separately under respective items
33Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtrs in depth for laying of cable, fixing of stay etc 10 Sqm on plan and n exc 1.5 in depth and getting out in hard/dence soil complete all as specified and directed.
34Returing, filling in incl spreading, levelling watering and well remming in layers n.exc 25cm, Complete all as specified and directed.
35Removing excavated soil to a distance n.exc 50 m and depositing where directed at a level n.exc 1.5 m above starting point complete all as specified and diercted.
36M&L for sand cushioning to underground cables using new dry river sand laidintrenches 8cm thick below the cable and 15cm thick above the cable after laying and stretching the cable complete, punned to 18cm, complete all asspecified and directed. Note : Punned thickness of 18cms shall bemeasured for payment.
37M&L Un-reinforced precast factory made concreate cable covers, class LV type-I, with flat size 250x150x40 mm complete all as specified and directed.
38Supply and laying GI pipe light grade 40 mm bore including all type fitting such as bends, elbows, tee etc fixed on walls/to poles/laid in trenches/boring as cable protection complete all as specified and directed.
39M&L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6mm thick burried directly in ground not less than 2.25m deep below normal ground level (with the top edge of the plate not less than 1.50 m below the normal ground level) connected to GI strip 32 x 6 mm by means of GI bolts, nuts, check nuts and washers of GI all as shown in electrical plate No.3 of SSR Part-I connected to earthing test point with and including necessary excavation and earth work in any strata PCC pit 1:3:6 type C-1, 20mm bore medium grade GI pipe for watering 15mm bore light grade pipe for GI wire protection and funnel including 40mm thick RCC slab cover and testing on completion all as specified and directed.
40Supply and fix in repair Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required32x6mm galvanised iron strip all as specified and directed.
41Deduct Schedule of Credit of Rs (-) 47,698.00 (Minus) as listed in Schedule "A" Part-II. Contract Sum shall be arrived after deducting the credit amount. Note :- Tenderers will not quote against this item being a firm amount.