Tender For Repair / Maintenance To Lt External Electrifications Zone I, Ii, Iii And Repair And Maintenance To Security/ Perimeter High Mast Lights/ Solar Lights/ Garden Lights And Connected Items At Likabali Mil Stn Under Ge 872 Ews, likabali-Assam

Military Engineer Services-MES has published Tender For Repair / Maintenance To Lt External Electrifications Zone I, Ii, Iii And Repair And Maintenance To Security/ Perimeter High Mast Lights/ Solar Lights/ Garden Lights And Connected Items At Likabali Mil Stn Under Ge 872 Ews. Submission Date for this Tender is 27-05-2024. Tube Light Tenders in likabali Assam. Bidders can get complete Tender details and download the document.




Tender Notice

43306430
Tender For Repair / Maintenance To Lt External Electrifications Zone I, Ii, Iii And Repair And Maintenance To Security/ Perimeter High Mast Lights/ Solar Lights/ Garden Lights And Connected Items At Likabali Mil Stn Under Ge 872 Ews
Open Tender
Indian
Assam
likabali
27-05-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Tender For Repair / Maintenance To Lt External Electrifications Zone I, Ii, Iii And Repair And Maintenance To Security/ Perimeter High Mast Lights/ Solar Lights/ Garden Lights And Connected Items At Likabali Mil Stn Under Ge 872 Ews

Key Value

Document Fees
INR 500 /-
EMD
INR 99800.0 /-
Tender Value
INR 49.90 Lakhs /-

Attachment

FileName File Description File Size
5787843b-e548-4475-9ed5-c7e7143713af.html Tender Notice 0 KB
BOQ_730252.xls Tender Document 0 KB
Tender8586.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

Name of Work: REPAIR / MAINT TO LT EXTERNAL ELECTRIFICATIONS ZONE I, II & III AND REPAIR AND MAINT TO SECURITY/ PERIMETER HIGH MAST LIGHTS/ SOLAR LIGHTS/ GARDEN LIGHTS AND CONNECTED ITEMS AT LIKABALI MIL STN UNDER GE 872 EWS
Sl. No. Item Description
1Excavation in trenches, not exceeding 1.5 M wide and not exceeding 1.5 M depthfor foundation, trenches for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10sq m on plan and n exc 1.5m in depth and getting out in soft/loose soil complete all as specified and directed.
2Excavating in trenches not exc. 1.5 metre wide and exc. 1.5 metre & not exc. 3 metre depth (beyond the first 1.5 metre) for foundation of poles etc and getting out in soft/loose soil complete all as specified and directed.
3Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm as in soft/loose soil complete all as specified and directed.
4Removing excavated material not exc. 50 m and depositing where directed at a level not exc 1.5 m above the starting pointcomplete all as specified and directed.
5Supply and laying cable XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 core, fixing along the poles or passing through pipes or laid under floor of through walls etc jointing and testing including taking out existing unserviceable cable complete all as specified and directed. (Note: Excavation and earth work will be measured and paid seperately)
6All as per Serial item No. 05 above but for 70 Sqmm 3.5 Core cable complete ditto
7All as per Serial item No. 05 above but for 95 Sqmm 3.5 Core cable complete ditto
8All as per Serial item No. 05 above but for 120 Sqmm 3.5 Core cable complete ditto
9All as per Serial item No. 05 above but for 150 Sqmm 3.5 Core cable complete ditto
10All as per Serial item No. 05 above but for 185 Sqmm 3.5 Core cable complete ditto
11All as per Serial item No. 05 above but for 240 Sqmm 3.5 Core cable complete ditto
12M & L for Sand cushioning with clean dry sand in trenches for protection of under ground cables (below, above and around the cable laid in trenches) complete all as specified and directed. (Note: Thickness after punning down shall be measured for payment)
13Supply and laying locally available best quality, well burnt sub class B bricks (old size), laid dry in trenches for protection of UG cables complete all as specified and directed.
14M & L for boring of horizontally holes by manual method under road and dia of hole not exc 100mm without damaging the exsting road, getting out and disposal of excavated soil, etc to a distance not exc. 50 meter from the site of work complete all as directed by Engineer in charge.
15S & F in repair for 40 mm bore, steel tubes, galvanised, light grade with all fittings, laid in floor/road crossing/drain etc as in cable protection complete to walls and ceilings or laid in floors complete all as specified and directed.
16S & F in repair for 50 mm bore, steel tubes, galvanised, light grade with all fittings, laid in floor/road crossing/drain etc as in cable protection complete to walls and ceilings or laid in floors complete all as specified and directed.
17S & F in repair for 80 mm bore, steel tubes, galvanised, light grade with all fittings, laid in floor/road crossing/drain etc as in cable protection complete to walls and ceilings or laid in floors complete all as specified and directed.
18Dismantling of unserviceable broken LT steel pole/Strut any size including demolition of foundation as required and making good disturbed surface complete all as directed. (Note : Earth work wherever invloved shall be measured and paid separately)
19Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting aside serviceable materials for re-use with in 50m and removing unserviceable materials from site of work complete all as directed by the Engr-in-Charge
20Dismantling LT Stay assembly, of any size and unserviceable materials removing from the Site(s), complete all as specified and directed. (Note: (a) Unserviceable Stay assembly shall be taken off/dismantled at Ground Level and making good disturbed ground surface. (b)Earthwork for demolition of cement concrete shall be measured and paid separately under relevant Items of this Schedule.)
21M & L for Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.0 metres long) including one coat of aluminium paint over a coat of red oxide zinc chrome primer and providing 03 Nos band/strap with black/yellow colour paint 300mm apart from the plinth block, numbering of pole painting embedded portion of pole with one coat of black bitumenous paint complete all as specified and directed. (Note : Excavation and Earth work shall be measured and paid separately)
22M & L for Cross arms bracing supports clamps and back plates fabricated from structural steel sections including nut bolt washers welding bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and including one primer coat of red oxide zinc chrome primer, one under coat and one finishing coat of aluminium paint complete all as specified and directed..
23Materials and labour for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for LT, 20 x 15 cm size including dismantling of old one complete all as specified and directed.
24Supply and fix in replacement synthetic insulating mat recommended for safety of worker, black or blue colour Class A of size 2m x 1m x 12 mm thick, ISI marked complete all as specified and directed
25M & L for Plain cement concrete 1:4:8, type D-2 (using 40 mm graded stone aggregate) as in foundation, filling and mass concrete, etc complete all as specified and directed.
26M & L for Plain cement concrete 1:3:6, type C-2 (using 40 mm graded stone aggregate) as in foundation, filling and mass concrete, etc complete all as specified and directed.
27M & L for plain cement concrete (1:2:4), type B1 (using 20mm graded stone aggregate) as in lintels upto 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs and the like including weathering, slightly rounded or chamfered angles and throating, including necessary formwork complete all as specified and as directed.
28M & L for taking down faulty/ unserviceable LT cable of any size and make of 1100 Volt grade from any situation, finding out cable fualt and rectifications of cable fualt as directed, replaying/ re-fixing the cable after rectifications complete all as directed by the Engr-in-Charge. (Note: Neassary earth work and excavation, sand cushioning and brick protection shall be measured and paid seperatel) complete all as specified and as directed.
29S & F Cable jointing kit for 1.1 KV grade cable for straight through, outdoor epoxy type joint for LT XLPE/PVC insulated cable including all asseccories and connections for 25 Sqmm to 50 Sqmm, 3.5/4 core cable complete all as specified and directed (Excavation and earth work shall be measured and paid seperately).
30S & F Cable jointing kit for 1.1 KV grade cable for straight through, outdoor epoxy type joint for LT XLPE/PVC insulated cable including all asseccories and connections for 70 Sqmm to 95 Sqmm, 3.5/4 core cable complete all as specified and directed (Excavation and earth work shall be measured and paid seperately).
31S & F Cable jointing kit for 1.1 KV grade cable for straight through, outdoor epoxy type joint for LT XLPE/PVC insulated cable including all asseccories and connections for 120 Sqmm to 150 Sqmm, 3.5/4 core cable complete all as specified and directed (Excavation and earth work shall be measured and paid seperately)
32M & L for Earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level, connected to galvanized steel earth lead wire4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel, all as shown in Electrical Plate No 3 of SSR Part - I, including necessary excavation and earth work, P.C.C (1:3:6) type C-I with 50 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab (reinforced with 8 mm dia deformed bar @ 10 cm C/C both ways and suitable handle of 12 mm dia round bar),including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel and 20 mm bore galvanized iron watering pipe (light grade), wire mesh, aluminium lugs, complete in all respect, GI earth wire protected by 15 mm bore (medium grade) galvanized iron pipe and other end connected with main switch board or Earthing test point as directed,including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessarytesting on completion inclduing taking down old one complete all as specified and as directed by the Engineer-in-Charge.
33Supply, Install, Commissioning and testing LT cubical type panel board, CPRI approved factory made, outdoor type, suitable for 415 Volts, 3 Phase, 4 Wire system, 50 Hz supply, made out of 3.15mm thick CRCA sheet, Dust and vermin proof, weather proof (IP54), powder coated with front and rear openable door shutter with seperate hinge door with locking arragnement, totally enclosed type including PCC 1:2:4, Type B-1 foundation of suitable size, and internal wiring with copper conductor cable including taking down old unserviceable panel board complete all as specified and directed comprising with the following items: (A) Incomming: (i) MCCB 250 Amps, 4 pole, 36 KA, 415 Volts, adjustable tharmel magnetic release:- 01 No (B) Outgoing (i) MCCB 160 Amps, 3 pole, 36 KA, 415 Volts, adjustable tharmel magnetic release:- 01 No (ii) MCCB 100 Amps, 3 pole, 16 KA, 415 Volts, adjustable tharmel magnetic release:- 02 Nos (iii) Digital multifunction meter with 3 Nos CTs of 20/5A - 01 Set (iv) Phase indicator for (RYB) - 01 set of three (v) Bus bar 4 strips aluminium of capacity 400 Amps, TPN of suitable size - 01 Set (Note: (i) Panel shall be of factory made and CPRI approved (ii) External terminals with tinned copper has to be provided for trimming the incoming and outgoing cables with suitable lugs of MCCB/MCB (if required) (iii) Necessary excavation and earth work for foundation shall deemed to be included in the unit quoted rate)
34Supply, Install, Commissioning and testing LT cubical type panel board, CPRI approved factory made, outdoor type, suitable for 415 Volts, 3 Phase, 4 Wire system, 50 Hz supply, made out of 3.15mm thick CRCA sheet, Dust and vermin proof, weather proof (IP54), powder coated with front and rear openable door shutter with seperate hinge door with locking arragnement, totally enclosed type including PCC 1:2:4, Type B-1 foundation of suitable size, and internal wiring with copper conductor cable including taking down old unserviceable panel board complete all as specified and directed comprising with the following items: (A) Incomming: (i) MCCB 160 Amps, 3 pole, 36 KA, 415 Volts, adjustable tharmel magnetic release:- 01 No (B) Outgoing (i) MCCB 63 Amps, 3 pole, 16 KA, 415 Volts, adjustable tharmel magnetic release:- 01 No (ii) MCB 06 Amps, SP, 10 KA, :- 02 Nos (iii) Digital multifunction meter with 3 Nos CTs of 20/5A - 01 Set (iv) Phase indicator for (RYB) - 01 set of three (v) Bus bar 4 strips aluminium of capacity 300 Amps, TPN of suitable size - 01 Set (Note: (i) Panel shall be of factory made and CPRI approved (ii) External terminals with tinned copper has to be provided for trimming the incoming and outgoing cables with suitable lugs of MCCB/MCB (if required) (iii) Necessary excavation and earth work for foundation shall deemed to be included in the unit quoted rate)
35Supply, Install, Commissioning and testing LT cubical type panel board, CPRI approved factory made, outdoor type, suitable for 415 Volts, 3 Phase, 4 Wire system, 50 Hz supply, made out of 3.15mm thick CRCA sheet, Dust and vermin proof, weather proof (IP54), powder coated with front and rear openable door shutter with seperate hinge door with locking arragnement, totally enclosed type including PCC 1:2:4, Type B-1 foundation of suitable size, and internal wiring with copper conductor cable including taking down old unserviceable panel board complete all as specified and directed comprising with the following items: (A) Incomming: (i) MCCB 125 Amps, 3 pole, 36 KA, 415 Volts, adjustable tharmel magnetic release:- 01 No (B) Outgoing (i) MCCB 100 Amps, 3 pole, 16 KA, 415 Volts, adjustable tharmel magnetic release:- 03 Nos (ii) Onload chage over switch 125 Amps, :- 01 No (iii) Digital multifunction meter with 3 Nos CTs of 20/5A - 01 Set (iv) Phase indicator for (RYB) - 01 set of three (v) Bus bar 4 strips aluminium of capacity 200 Amps, TPN of suitable size - 01 Set (Note: (i) Panel shall be of factory made and CPRI approved (ii) External terminals with tinned copper has to be provided for trimming the incoming and outgoing cables with suitable lugs of MCCB/MCB (if required) (iii) Necessary excavation and earth work for foundation shall deemed to be included in the unit quoted rate)
36Supply, Install, Commissioning and testing LT cubical type panel board, CPRI approved factory made, outdoor type, suitable for 415 Volts, 3 Phase, 4 Wire system, 50 Hz supply, made out of 3.15mm thick CRCA sheet, Dust and vermin proof, weather proof (IP54), powder coated with front and rear openable door shutter with seperate hinge door with locking arragnement, totally enclosed type including PCC 1:2:4, Type B-1 foundation of suitable size, and internal wiring with copper conductor cable including taking down old unserviceable panel board complete all as specified and directed comprising with the following items: (A) Incomming: (i) MCCB 100 Amps, 3 pole, 36 KA, 415 Volts, adjustable tharmel magnetic release:- 02 Nos (B) Outgoing (i) MCCB 63 Amps, 3 pole, 16 KA, 415 Volts, adjustable tharmel magnetic release:- 03 Nos (ii) Digital multifunction meter with 3 Nos CTs of 20/5A - 01 Set (iii) Phase indicator for (RYB) - 01 set of three (iv) Bus bar 4 strips aluminium of capacity 200 Amps, TPN of suitable size - 01 Set (Note: (i) Panel shall be of factory made and CPRI approved (ii) External terminals with tinned copper has to be provided for trimming the incoming and outgoing cables with suitable lugs of MCCB/MCB (if required) (iii) Necessary excavation and earth work for foundation shall deemed to be included in the unit quoted rate)
37S & F in repairs Air Circuit Breaker, 630 Amps, 4 Pole, 50 kA, 415 Volt, 50 Hz, front operated with thermal magnetic release (Manual drawout type) complete all as specified and as directed . (Make: L & T Cat Part No. SL95351or equivelant of make as per List of Manufacturer"s)
38S & F in repairs MCCB 415 Volt 16 KA, 4 Pole,63 Amps Capacity complete all as specified and as directed . (Make: Legrand Cat Part No. 4200 13 or equivelant of make as per List of Manufacturer"s)
39S & F in repairs MCCB 415 Volt 16 KA, 4 Pole,100 Amps Capacity complete all as specified and as directed . (Make: Legrand Cat Part No. 4200 15 or equivelant of make as per List of Manufacturer"s)
40S & F in repairs MCCB 415 Volt 16 KA, 4 Pole,125 Amps Capacity complete all as specified and as directed . (Make: Legrand Cat Part No. 4200 16 or equivelant of make as per List of Manufacturer"s)
41S & F in repair MCCB 415 Volt, 36 KA, 4 Pole, 200 Amps Capacity complete all as specified and as directed. (Make: Legrand Cat Part No. 4202 48or equivelant of make as per List of Manufacturer"s)
42S & F in repair MCCB 415 Volt, 36 KA, 4 Pole, 250 Amps Capacity complete all as specified and as directed. (Make: Legrand Cat Part No. 4202 49or equivelant of make as per List of Manufacturer"s)
43S & F in repairMCCB 415 Volt, 36 KA, 4 Pole, 400 Amps Capacity complete all as specified and as directed. (Make: Legrand Cat Part No. 4220 07or equivelant of make as per List of Manufacturer"s)
44S & F in repair Power contactor, 4 Pole, 415 Volt, Current Rating 255 Amps, 50 Hz with auxillary contacts including Outgoing and Incoming busbar connection and fixing to existing panel board complete all as specified and as directed. (Make:L & T Cat Part No. CS97022or equivelant of make as per List of Manufacturer"s)
45S & F in repairon load Change over switch, general purpose with side handle, current rating 200Amps,4 pole, 415 V, 50 Hzcomplete all as specified and directed. (Make: L & T Cat No. CO22000OOOA or equivelant approved make as per list of manufacturer)
46S & F in repairon load Change over switch, general purpose with side handle, current rating 315Amps,4 pole, 415 V, 50 Hzcomplete all as specified and directed. (Make: L & T Cat No. CO33150OOOO or equivelant approved make as per list of manufacturer)
47M & L for repair to broken/hanging MS door of LT panel/Geeder Pillar/ Pole box indoor / outdoor of any size by necessary welding and replacing hinges, locking arrangement nad handle for smooth functioning of the door complete all as specified and directed.
48Material and Labour forpreparation of oldmetal surfaces of Panel Boards/ Feeder pillar board/ pole box inddor/ outdoor type of any descriptions over 10cm width or girth not otherwise described and applying one coats of synthetic enamelpaint (1st quality)and marking the Panel Board No etc in front side complete allas specified and directed by engineer in Charge. (Note: Adjoing areas there to properly covered befor painting. Adjoing areas, floor, walls are to cleaned free of paint spillage after painting work).
49Dismantling of insulators of any type from LT poles of any size and type and setting aside complete all as specified and directed.
50M & L for pin type porcelain vitreous white/brown insulator including one galvanised mild steel spindle two galvanised iron nut 100 mm height 65 mm dia suitable for 1100 volts grade complete all as specified and directed.
51M & L for shackle type porcelain, insulator vitreous, white, brown or green, including galvanised mild steel, straps, washers, insulator bolts, washers and nuts, 100 mm height and 115 mm dia, size of strap 31 mm x 5 mm and dia of bolt 14 mm suitable for 1100 volts complete all as specified and directed.
52M & L for loop type insulator, vitreous porcelain, white, brown or green of overall dimension 65 x 90 mm, clearance of hole 25.5 mm etc complete all as specified and directed.
53S & F PVC/fibre separator for LT over head line 1100 volts conductor 3/4 wire system for horizontal spacing of conductor complete with nuts and bolts minimum 2 Nos to prevent the line touching each other on heavy wind including taking down old separator complete all as specified and as directed .
54M & L for dismantling of Voltage stabilizer 150 KVA capacity, 3 phase, 240 Volts AC, after disconnecting and removing to AGE EM store yard for opening and checking of defects repairing as required, and re-assmebling and re-instal the same and testing on completion complete all as specified and as directed. (Note: (i) Spare parts required for repairing shall be measured and paid seperately as S & F here-in-under. (ii) Replacement of any minor spares/ parts not included below required to make the System fully fucntional shall deemed to be included in the unit quoted rate)
55Taking out control wiring complete from voltage stabilizer of capacity 150 KVA, 3 phase, 415 Volts of unbalanced load and S & F wiring loom complete made out of suitable size of PVC insulated copper conductor cable including cable lugs, connector channel etc complete all as specified and as directed.
56S & F in replacement of analog voltmeter square type of size 72x72mm, range 30 to 300 Volts complete all as specified and as directed.
57S & F in replacement of 3/5 step universal painted circuit board suitable for 150 KVA voltage stabilizer complete all as specified and as directed.
58S & F in replacement of Synchronous motor single phase AC, 230 Volts suitable for 150 KVA voltage stabilizer complete all as specified and as directed.
59S & F in replacement of Dimmer stat suitable for 150 KVA voltage stabilizer complete all as specified and as directed.
60S & F in replacement of Indicator lamp of colour red, yellow and blue of 230 Volts complete all as specified and as directed.
61Supply and filling new transformer oil to 150 KVA voltage stabilizer of dielectric strength not less than 40 KV complete all as specified and as directed.
62Material and Labour forpreparation of oldmetal surfaces of Voltage stabilizer of 150 KVA capacity after complete removal of existing paintingand applyingtwo coats of enamelpaint (1st quality)over a coat red oxide zinc chrome primerand marking the MES/SM number and machine serial number in front side complete allas specified and directed by engineer in Charge.
63M & L Earthing complete with GI earth plate electrode 600 mm x 600mm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 m below ground level with the top edge of earth plate at depth not less than 1.5 m below ground level connected with galvanised earth strip of size 32x6mm by means of bolts, nuts,check nuts and washers protected by 40mm bore light grade GI pipe, funnel with 20mm bore GI medium grade pipe for watering, wire mesh, including concrete pit in PCC (1:3:6) type C-1, with 40 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab of size 350x350x50mm (reinforced with 10 mm dia deformed bar @ 10 cm C/C both ways and suitable handle of 12 mm dia round bar),including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel, wire mesh, aluminium lugs, complete in all respect and other end connected with main switch board or Earthing test point as directed,including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessarytesting on completion inclduing taking down old one complete all as specified and as directed by the Engineer-in-Charge.
64M & L Earthing complete with copper earth plate electrode 600 mm x 600mm x 3.15 mm thick burried directly in ground vertically to a depth not less than 2.25 m below ground level with the top edge of earth plate at depth not less than 1.5 m below ground level connected with copper earth strip of size 20x3mm by means of bolts, nuts,check nuts and washers protected by 40mm bore light grade GI pipe, funnel with 20mm bore GI medium grade pipe for watering, wire mesh, including concrete pit in PCC (1:3:6) type C-1, with 40 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab (reinforced with 8 mm dia deformed bar @ 10 cm C/C both ways and suitable handle of 12 mm dia round bar),including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel, wire mesh, aluminium lugs, complete in all respect and other end connected with main switch board or Earthing test point as directed,including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessarytesting on completion inclduing taking down old one complete all as specified and as directed by the Engineer-in-Charge.
65M & L for chemical earthing with Solid Rod Technology, CPRI Yested Rod of dia 17.2mm, 3.0m in length having copper coating of 250 micron along with poly Plastic Pit cover and 2 Bags of Ground Enhancement Materials with Exothemic Brazing for joints as per IS: 3034 including all necessary earth work and excavation etc complete all as shown in MES Schedule Part-I and testing on completion including taking down/out of old unservceable earthing of any descriptions complete all as specified and directed. (Make: OBO BETTERMAN/ ERICO/ FURSE/ INGESCO/ JMV LPS and any other E-in-C"s approved make)
66M & L for taking down Street/ Perimeter light fittings of any descriptions from any height after disconnecting electric connections and opening cover and checking of light fittings for serviceability and repaired as required and re-fixing the light fittings in existing position after repair and providing connections including replacement of defective/ unserviceable spares/ parts etc as required to make the fittings in smooth serviceable condition and testing complete all as specified and as directed. (Note: (i) Replacement of unserviceable parts shall be measured and paid seperately as "supply only" (ii) Replacement of minor spares/ parts such as nuts, bolts & washer, worn out cables as per existing size etc shall deemed to be included in the unit quoted rate)
67Supply only Driver (as approved) suitable forLED street/ security light fittings of 30/35 Watt complete all as specified and directed.
68Supply only Driver (as approved) suitable forLED street/ security light fittings of 40/45 Watt complete all as specified and directed.
69Supply only Driver (as approved) suitable forLED street/ security light fittings of 60 Watt complete all as specified and directed.
70M & L for taking down High mast light fittings of any descriptions from any height after disconnecting electric connections and repair the same by applying greasing, oiling etc as required and re-hoisting light fittings after reqpair including replacement of defective/ unserviceable spares/ parts etc as required to make the fittings in smooth serviceable condition and testing complete all as specified and as directed. (Note: (i) Replacement of unserviceable parts shall be measured and paid seperately as "supply only" (ii) Replacement of minor spares/ parts such as nuts, bolts & washer, worn out cables as per existing size etc shall deemed to be included in the unit quoted rate)
71Supply only Driver (as approved) suitable forLED Flood light fittings of 120 Watt complete all as specified and directed.
72S & F in repair LED 70 Watt flood light luminaire, Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium, IP66, suitable for highlighting architectural facade and general purpose lighting with lamp and all accessories including mounting clamps, bolts, nuts and washers and copper conductor cable of suitable size to fittings of suitable length fixed as in High mast light at any height complete all as specified and as directed. (Make: Havell"s Cat No. JETAALBAFLOODLIGHT70W or equivelant of make as per list of manufacturer)
73S & F in repair LED 100 Watt flood light luminaire, Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium, IP66, suitable for highlighting architectural facade and general purpose lighting with lamp and all accessories including mounting clamps, bolts, nuts and washers and copper conductor cable of suitable size to fittings of suitable length fixed as in High mast light at any height complete all as specified and as directed. (Make: Havell"s Cat No. JETAALBAFLOODLIGHT100W or equivelant of make as per list of manufacturer)
74S & F in repair LED 120 Watt flood light luminaire, Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium, IP66, suitable for highlighting architectural facade and general purpose lighting with lamp and all accessories including mounting clamps, bolts, nuts and washers and copper conductor cable of suitable size to fittings of suitable length fixed as in High mast light at any height complete all as specified and as directed. (Make: Havell"s Cat No. JETAIRISFL120WLED757APWBLTG or equivelant of make as per list of manufacturer)
75M & L for taking down Solar light fittings of any descriptions from any height after disconnecting electric connections and repair the same by replacing of defective/ unserviceable spares/ parts etc as required and applying Jelly to the battery terminals, tightening of all connections, cleaning of solar panel thoroughly, filling distilled water to solar light battery to make the fittings in smooth serviceable condition and re-fixing the solar light fittings in its original position and testing complete all as specified and as directed. (Note: (i) Replacement of unserviceable parts, distilled water etc shall be measured and paid seperately as "supply only" (ii) Replacement of minor spares/ parts such as nuts, bolts & washer, worn out cables as per existing size etc shall deemed to be included in the unit quoted rate)
76Supply only Solar light Battery, 12 Volts, 75 AH, Dry Gel (as approved) suitable for 3 days backup capacity complete all as specified and directed.
77Supply only Tinned copper battery terminal (as approved) complete all as specified and directed.
78Supply only Distilled water suitable for Solar light batteries complete all as specified and directed.
79S & F in repairs 35 Watt LED Street light fittings, New generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high efficiency LED as lighting source and lens embedded PC cover having Bottom Opening seperate driver compartment with IP66 protection and impact resistance of IK08 including lamp and connections complete all as specified and as directed. (Make: Havell"s Cat No. ENDURASUNDOWNSL35WLED765PASYBOPC or equivelant of make as per list of manufacturer)
80S & F in repairs 45 Watt LED Street light fittings, New generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high efficiency LED as lighting source and lens embedded PC cover having Bottom Opening seperate driver compartment with IP66 protection and impact resistance of IK08 including lamp and connections complete all as specified and as directed. (Make: Havell"s Cat No. ENDURASUNDOWNSL45WLED765PASYBOPC or equivelant of make as per list of manufacturer)
81S & F in repairs 60 Watt LED Street light fittings, New generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high efficiency LED as lighting source and Toughened glass having Bottom Opening seperate driver compartment with IP66 protection and impact resistance of IK07 including lamp and connections complete all as specified and as directed. (Make: Havell"s Cat No. ENDURASUNDOWNSL60WLED765PASYBOTG or equivelant of make as per list of manufacturer)
82S & F in repair 25 Watt, 230 Volts AC Post Top Lantern, outdoor type New generation, IP 65 LED post-top family, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source. Clear Cover offers bright illumination for different applications with driver and lamp, fixing accessories and connecting up with suitable copper conductor complete all as specifiedand directed. (Make: Havell"s Cat No. RUBYPT25WLED830SSYMTOPCor equivelant of make as per list of manufacturer)
83S & F in repair 40 Watt, 230 Volts AC Post Top Lantern, outdoor type New generation, IP 65 LED post-top family, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source. Clear Cover offers bright illumination for different applications with driver and lamp, fixing accessories and connecting up with suitable copper conductor complete all as specifiedand directed. (Make: Havell"s Cat No. RUBYPT40WLED757PSYMTOPCor equivelant of make as per list of manufacturer)
84S & F in repairs 08 Watt, LED Bollard light fittings, New generation, energy saving, environmental friendly, long life aesthetically designed aluminium landscape IP 65 luminaire for diffused lighting with high power LED as light source. including lamp and making good disturbed surfaces complete all as specifiedand directed. (Make: Havell"s Cat No. BAMBOOBL8WLED830SSYMTOPCM or equivelant of make as per list of manufacturer)
85Dismantling/taking down old aluminium steel reinforced (ACSR) conductor of any size from LT overhead line including all jumper etc and keeping serviceable materials in safe custody for reuse in the work complete all as specified and directed.
86S & F aluminium conductor steel reinforced (ACSR) conductorincluding binding, straining in LT over head line including all jumper connection and binding on insulator with new wire complete all as specified and directed.
87Re-straining and tightening of existing serviceable ACSR conductor of any size without taking down including all arangement and including bindingwire 2 mm dia and colour sleeve Jumpers complete all as specified and directed.
88S & F in repair jumper made of ACRS conductor of suitable size and binding with and including aluminium binding wire properly on the existing LT OH line complete all as specified and as directed .
89Dismantling existing unserviceable GI earth wire, cradles of any type from service feeder or distributor span complete all as specified and directed.
90M & L for galvanised steel continuous earth wire 3.15mm or 4 mm dia suitable for LTover head line complete all as specified and directed.
91M & L for galvanised steel earth wire 4 mm dia (hexagonal/rectangular) used for craddle guarding suitable for LT/HT over head line complete all as specified and directed.
92M & L for Stay assembly complete with all accessories as shown in electrical plate No 1 of MES Schedule Part I dia of stay rod 20mm with and including 7 / 3.15 mm galvanised stay strand complete all as specified and directed. (Note : Loop insulator, excavation & earthwork and cement concrete measured and paid separately under relevant items of this Schedule.)
93Trimming of tree branches around the overhead conductor, poles & stays (not less than 3 metre) to clear the approach of overhead lines including removing of nest, wild grass creepers, unwanted vegetation, etc from pole/stay including cleaning of creepers climbed on poles and angles, channels and disposed off from site beyond 50m and upto a total distance of 250m complete all as specified and directed by the Engr-in-Charge.
94M & L for Preparation of old painted surface above the planting depth/PCC coping of steel tubular LT pole upto 11.00 metre long including MS clamps, cable protection pipe, bracket fitted with steet light fittings etc by scraping with steel wire brush and applying one coat of aluminium paint to external surface of poles, MS cross arms, MS clamp, cable protection pipe etc to give even shade including 5 Nos strips painting of 300mm high each around the pole with two different colour (black/yellow) of synthetic enamel paint and numbering of poles complete all as specified and as directed by the Engr-in-Charge.
95S & F in repair PVC insulated and FRLS PVC Round Sheathed, multi-stranded Copper Conductor (flexible) industrial cable, 1100 Volt, conforming to IS 694 of size 1.5 Sqmm 3 core nominal cross sectional areacomplete all as specified and directed.
96Supply and laying cable XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 Sqmm 2 core, fixing along the poles or passing through pipes or laid under floor of through walls etc jointing and testing including taking out/down existing cable complete all as specified and directed.
97All as per Serial item No. 96 above but 25 Sqmm 4 Core cable complete ditto
98All as per Serial item No. 96 above but 35 Sqmm 3.5 Core cable complete ditto
99Supplying and laying un-reinforced precast concrete cable cover, class LV, type 1, flat, size 250mm x 150mm x 40mm complete all as specified and directed.
100S & F in repairMCCB 415 Volt, 36 KA, 4 Pole, 160 Amps Capacity complete all as specified and as directed. (Make: Legrand Cat Part No. 4200 97or equivelant of make as per List of Manufacturer"s)
101S & F in repairon load Change over switch, general purpose with side handle, current rating 100Amps,4 pole, 415 V, 50 Hzcomplete all as specified and directed. (Make: L & T Cat No. CO11000OOOO or equivelant approved make as per list of manufacturer)
Disclaimer :