Provision Of 600 Kw Solar Power Plant At Ge ( Af ) Bamrauli

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 17-May-2024 1st Date Corrigendum dated 17 May 2024 Date 01-06-2024

Key Value

Document Fees
INR 3000 /-
EMD
INR 610000.0 /-
Tender Value
INR 5.70 Crore /-

Attachment

FileName File Description File Size
5a760c0a-c5c3-4a39-b6d0-8d0a7844ea89.html Tender Notice 0 KB
BOQ_730030.xls Tender Document 0 KB
Drgs3Nos.rar Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB
Tenderps.rar Tender Document 0 KB

BOQ Items

Name of Work: PROVISION OF600 KWSOLAR POWER PLANTAT GE (AF) BAMRAULI
Sl. No. Item Description
1PHASE-I [ SOLAR POWER PLANT AND MISCELLANEOUS B/R & E/M ITEMS]
2Surface dressing not exceeding 15cm deep in soft and loose soil including cutting of shrubs, grass, sapling ,vegetation and brushwood not exceeding a girth of 30cm etc complete all as specified and directed. Note:-This item shall not be allowed in addition to items 03001 to 03009, 03009A, 03009B, 03009C and 03010 of SSR Part - II (Rates) 2020.
3M&L for forming embankments including raising (or lowering) earth, spreading in layers not exceeding 30 cm thick, watering, ramming/ rolling and finishing to required size, shape, etc not exceeding 1.5 m high from base complete all as specified and directed. Note:Required soil shall be obtained from the earth obtained from drain work.
4Taking down chowkats with shutters not exceeding 1.5 Sqm each (without taking off shutters from the frames) complete all as specified and directed.
5Demolition of stone slabsand tiles of any description or thickness in floors aprons etc including cement mortar bedding (but not backing), removingun-serviceable tiles to store and rubbish off the premisescomplete all as specified and directed.
6M&L for dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing) and rubbish off the premises complete all as specified and directed.
7Demolition of brickwork or stone boulder masonry, built in cement mortar including all quoins, arches, pillars, etc., but excluding ashlar facings, dressed stonework and precast concrete articles all as specified and as directed.
8Taking out existing aluminum frame including aluminium composite panel, glass, cleat, silicon etccomplete all as specified and directed.
9Taking down cement plaster on brick or stone walls etc, including raking out joints, hacking for key, scrubbing down with water, etc & prepare to receive new plaster complete all as specified and directed.
10S&F for powder coatedaluminium frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc. complete all as specified. Note : Minimum thickness of powder coating shall not be less than 50 micron.
11S&F for powder coated (thickness of powder coating not less than 50 micron) aluminium door ofsize 101.502x44.50x1.42 mmStyle & rail of shutter of size 101.6 X44.45 X1.42mm (Section shall be as per Drawing No CE/ALD/TD -224 Sheet No.1/1) with 4 numbers hinges powder coated including one hydraulic door closer,with glazingclips rubber packing for air lock purposealuminiumanodized snapbeadingof weight not less than0.71 Kg/RM screw for fixed glass panes with frame & shutter covered with selected quality of tinted glass 5.0 mm thick including necessary builderhardware fittingssuch as aluminum powder coated tower bolts 200mmlong02 Nos for each shutter, 150mm long handle 02 Nos and 100mm size brass mortice lock four lever suitable forshutter 01 No complete all as specified and directed. Note : Aluminium fittings shall be powder coated of not less than 50 micron.
12S&F powder coated(thickness of powder coating not less than 50 micron) aluminium (shutter/ sliding/ fixed type) windows/ventilators with frame size 60x40x2.00mm thick and shutter with section bearing bottom 25x18x1.50 mm top 39.4x17.7 X1.50 mmfixed over top of frame work , top and side section of size 61.6 x 31.75x1.5mm and bearing bottom track of size 61.6x 31.75x1.5mm or fixing with hinges including necessary aluminium jointing cleats, glazing cleats, rubber packing anodised snape beading, screws etc with 5mm thicksun control plain glass in panels including all fittings and fixtures complete all as specified and directed.Note : Aluminium fittings shall be powder coated of not less than 50 micron.
13S&F 4.8mm thick sheet glass ordinary quality any size and in any type of frame and glazing withrubber beading in square/rectangular not exceeding 0.5 Sqm in each pane complete all as specified and directed.
14S&F 4.8mm thick sheet glass ordinary quality any size and in any type of frame and glazing withrubber beading in square/rectangularexceeding 0.5 Sqm in each panes complete all as specified and directed.
15Supply only Stainless steel wire cloth, 0.36mm nominal dia of wire and average width of aperture 1.40mm and fixed with stainless steel wire staplesetc complete all as specified and directed.
16S&F in repairs 3mm thick Aluminium composite panel cladding using aluminiumcomposite panel sheet 3mm thick (Vita 25mm aluminium foil with PVDF coating) at aheight of 4 to 5 mtr (ACP will be fixed over aluminum framed works) and filling the gap with silicon, sealantandother materials ofapproved quality etc completeallas specified and directed.
17Taking down and refixing of aluminum frame after minor repairs replacement of rubber/silicon beading , aluminum strips, glass, Aluminium composite panel etccomplete all as specified and directed.
18S & F Glazed ceramic coloured printed tiles of size 450mm x 300mm x 7mm thick as in dados, skirting, wall etc set jointed in neat cement slurry and pointed in coloured cement to match the tiles over 10mm thick rendering as backing coatin CM 1:4 for fixing of tiles complete all as specified anddirected.
19S&FNon Skid ceramic coloured tiles 7 to 8 mm thickjoint free (square/ rectangular) area of each tile exceeding 0.06 Sqm but not exceeding 0.11 Sqm,in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to matchthe shade of tile and laid over and including 15mm thick screed bed layer in CM (1:6) complete all as specified and directed
20S&F Machine cut kota stone slab flooring of size 550 mm x 550 mm x 20-25mm thick laid over 20mm thick cement mortar screed bed in cement mortar 1:6 and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete all as specified and as directed.
21Cutting andMirror polishing only on existing surfaces of marble/ granite/ Kota stone/ stone work where ever required to give high gloss finish complete all as specified and as directed.
22Taking down steel tubing and connections of 15 mm borepipe complete all as specified and directed.
23Taking down steel tubing and connections of 20 mm borepipe complete all as specified and directed.
24S&F 15mm bore steel water tubing medium grade , galvanized ISI marked with all fittings fixed to wall & ceiling or laid in floors complete all as specified and directed.
25S&F 20 mm bore steel water tubing medium grade , galvanized ISI marked with all fittings fixed to wall & ceiling or laid in floors complete all as specified and directed.
26S&F in repairs 25mm bore gun metal gate valvewith iron wheel head screwed both ends for iron pipes complete all as specified and directed.
27S&F in repairs vitreous china wash hand basin, white, flat back, size 580x450mm excluding taps, chain and plug and porcelain stopper butincluding PVC connection pipe of 450mm length, waste coupling of 32mm bore, waste pipe of PTMT and MSbrackets including cutting for and pining in ends of bracketscomplete all as specified and directed.
28S&F in repairs15 mm dia cast copper alloy, chromium plated, fancy type pillar/sink tap swivel spout deck mounted 15mm dia size withscrewed down high pressure, screwed both ends for iron pipe or for unions and fixed complete all as specified and directed.
29S&F in repairs new bevelled edged looking mirror of size 600mmx450mmof selected quality glass not less than 5.5 mm thick mounted with stainless steel studs complete all as specified and directed.
30S&F Rotational moulded polythenewater storage tanks of triple layered, ISI marked, hoisted and fixed in position 500ltrs capacity including 2 Nos GI unions, check nuts and 25mm bore PTMT float valve,gate valveincluding taking down of old PVC tank and removing to store complete all as specified and directed.
31S&F in repairs Vitreous China urinals, solo bowl type (back or corner wall type) of size385mmx295mmx500mm mm complete including providing and fixing plugs, bedding urinal against wall in cement mortar 1:2, securing urinal to plugs with and including 60mm long brass screws, pointing around urinal back in cement, fixing automatic flushing cistern with brackets, flush pipe, grating, PVC connection pipe, union fixing supply pipe to flushing for discharge pipe and including all necessary fittings complete all as specified and directed.
32M & L for 75mm bore dia PVC floor trap with chromium plated grating, with grating including jointing to waste pipe fixed in cement concrete 1:2:4, type B1 (Using 20 mm graded crushed stone aggregate) complete all as specified and directed.
33S&FVitreous china squatting pan of Orissa pattern size 580 mm x 440 mm white with integral foot rests (excluding flushing cistern and flush pipe) including provision of concrete bedding complete all as specified and directed.
34S&F in repairs15mm diaBib tap cast copper alloy with fancy handle, screwed for iron pipe or for ferrule and fixed complete all as specified and directed.
35S&F in repairs for 15mm dia Angle cock, fancy type,cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions complete all as specified and directed.
36S & F chromium plated grating doom 100mm/110mm dia complete all as specified and directed.
37S&F in repairs 110mm dia PVC SWR pipe of pressure 6Kgf/Sqcm fixed complete to walls, ceilings, in floors etc including all necessary fitting arrangements, bends, couplings etc in rainwater pipe complete all as specified and directed.
38M&L for complete removal of existing treatmenton wall surfaces and applying three coats of white wash complete all as specified and directed.
39M&L for complete removal of existing treatmenton ceiling surfaces and applying three coats of white wash complete all as specified and directed.
40M&L for preparation of old plastered surfaces of walls and applying two coats of cement base paint over a coat of primercomplete all as specified and directed.
41M&L for Brickwork with sub class "B" bricks of class designation 100, straight or curved on plan exceeding 6m mean radius built in cement mortar 1:6complete all as specified and directed.
42M&L for 15mm thick rendering in CM 1:6 on fair faces of brick work, surfaces finished even & smooth without using extra cementcomplete all as specified and directed.
43M&L for 15mm thick rendering in CM 1:4 on fair faces of brick work, finished even and smooth without using extra cement complete all as specified and directed.
44M&L for preparing new plastered/un-plasteredsurfaces of walls and applying three coats of white washcomplete all as specified and directed.
45M&L for preparation of new plastered surfaces of walls and applying two coats of cement base paint over a coat of primer complete all as specified and directed.
46S&F Factory made solid panel PVC door shutter 30 mm thick (style) both side prelaminated PVC sheet of decorative choice consisting of frame made out of M.S. tubes for top & bottom rails. M.S. frame shall be covered with heat mouldedPVC ‘C’ channel having a PVC sheet strip of 20mm width stuck inside with solvent cement for stiles and plain colour PVC sheets for top rail, lock rail & bottom rail on either side & as gap insert for top rail & bottom rail Panelling of plain colour PVC sheet to be fitted in the M.S. frame welded / sealed to the stiles & rails with suitable PVC sheet beading, and joined together with solvent cement, suppling & fixing in the frame at site asperspecification &drawing complete all as specified and directed.
47M & L for Solid PVCFrame of size 50mm x 47mm made out of 5mm plain colour PVC sheet reinforced with M.S Square tube, supplying & fixing in opening as per specification & drawingcomplete all as specified and directed.
48S & F in repairs 150 mm long extruded aluminium alloy handles, fabricated type, anodised complete all as specified and directed.
49S & F 150mm longAluminium anodised barrel tower bolts of extruded section complete all as specified and directed.
50Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exceeding1.5 mtr in depth for foundation, laying of cables/pipesetc or for shafts wells manholes etc not exceeding in 10 Sqm on plan and getting out complete all as specified and directed. Note : Excavation shall be made carefully in order to avoid damage of existing buildings, cables, protection covers etc.
51M&L forplain cement concrete 1:4:8 type D-2 ( using 40 mm graded crushed stone aggregate)as in foundations, filling and mass concrete complete all as specified and as directed.
52M&L for brick work with sub class ‘B’ bricks of class designation 75, straight or curved on planexceeding 6 M mean radius built in CM (1:6) complete all as specified and directed.
53M&L forplain cement concrete 1:2:4 type B-1 ( Using 20 mm graded crushed stone aggregate) as in copings, bed plates, hold fast and the like including necessary form work complete all as specified and directed.
54M&L for plain cement concrete 1:2:4 type B0 (using 12.5mm graded crushed stone aggregate) as in coping, padding etc including necessary form work complete all as specified and directed.
55M&L for precast cement concrete 1: 2: 4, type B-1 (using 20 mm graded crushed stone aggregate) as in landing, covers slabs, manhole covers, with plain fair faces including chamfers, weathering throttling etc and set in cement mortar (1:4) complete with joint to match including necessary form work complete all as specified and directed.
56M&L for 6mm to 8 mm dia mild steel TMT reinforcement bars cut to length, bent to shape required including cranking, bending, binding with and including mild steelwire(annealed) not less than 0.9 mm dia and necessary welding to reinforcement complete all as specified and as directed
57S&F Joist, channel, angle, flat or tee sections, fixed independently, without connecting plates of Fe-410-W Gde E-250 Quality A, etc. (cut to ordinary lengths i.e. within 20mm of the length indicated) complete all as specified and as directed.
58Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cmas in foundations, trenches etc complete all as specified and directed by Engineer-in-Charge.
59Removing of excavated material/soil to a distance not exceeding 50M and depositing where directed at a level not exceeding 1.5M above the starting point complete all as specified and as directed.
60M&L for sanding newly tarred or painted surfaces with clean sharp sand etc complete all as specified and directed. Note :For embedded portion of angle iron in PCC block.
61Removing excavated material/soil to a distance exceeding 250 m but not exceeding 500 m and depositing where directed at a level not exceeding 1.5 .5M above the starting point complete all as specified and directed.
62M&L for laying of coarse sand free from sharp materials as filling in trenches for cable protection, laid to a uniform thickness of 23 cm (15 cm under the cable and 8 cm over the cable) and gently punned down to 18 cm thickness as required complete all as specified and directed. Note :Punned thickness shall be measured and paid
63M&L for laying well burnt old size, sub class "B" bricks laid in trenches as in electric cable protection complete all as specified and as directed.
64Supply and laying galvanised iron pipes 40 mm bore of medium grade with ISI marked with all tube fittings (such as bend, elbows, tees, short pieces of medium grade, connectors, back nuts, caps , plugs and unions etc) laying in trenches/floor/ducts and also cutting pipes, screwing and for making forged bends on piping as required and complete all as specified and directed.
65S & F Gun metal gate valve 40 mm bore with iron wheel head screwed both ends for iron pipes complete all as specified and directed.
66S& F Bib tap standard of PTMT any colour high pressure screwed for iron pipe complete all as specified and directed.
67M&L for construction of Valve pit brick masonry chamber with internal size 600 mm x 600 mm x 600 mmcomplete with mild steel sheet cover 3mm thick and angle iron frame of size 40x40x6mm duly painted with two coats of synthetic enamel paint over a coat of red oxide primerand including locking arrangement and lifting handleincluding PCCbed all as specified and shown on drawing . Brick work of inner surfaces shall be plastered in cement mortar 1:6 and outer surfaces above GLof pit shall be plastered in cement mortar 1:4 completeincluding three coats of white wash completeall as specified and shown on drawing.
68Supply, installation, commissioning and testing of inverter type Split Air Conditioner of 1.5 TR (4500 Kcl/Hour) capacity, complete with cordless remote control unit and with minimum 5 Star rating.Indoor unit Hi wall mounted type, suitable for 230 Volt, 50 Hz single phase AC supply and capable for performing the function as cooling / heating, dehumidifying, air circulating and filtering.The air conditioners shall be complete with automatic temperature control, cut in, cut out for variable temperature range 16 to 30°C.The differential of cut-in, cut - out shall not be greater than + 1.75ºC to be provided with electronic thermostat as per IS 11338 of 1985.Out door unit of Air Conditioner shall be fitted with discharge cooled type rotary / scroll compressor operating on non-CFC refrigerants (like R410A or equivalent) with suitable rated capacitor start electric motor equipped with overload protection and mounted on resilient mountings for quiet operations.The casing of indoor unit shall be made of ABS/HIPS/GS and shall be impact resistant.The filter packs provided shall be washable.Remote cordless control with LCD/LED display shall be provided withy one ON/OFF timer, selecting fan speed (3-speed) and setting-up of temperature.Display shall be provided on indoor unit and on handset.Overall power factor of the unit shall not be less than 0.85 at operating conditions.The EER values shall correlate to the latest values specified by the BEE star level for 5 star rating certification complete all specified and directed. Note :- The installation shall includemounting/fitting indoor units at respective locationLaying refrigerant piping of upto 6 metre length and connecting the both the units after drilling the holes as required.The thickness of copper tubing shall not be less than 0.70 mm.Suction pipe shall be insulated with expanded polythene foam not less than 5 mm thick.Laying 15 mm drain pipe to drain out the condensate water being form in the condensing unit.Leak testing of the entire system.Charging refrigerant gas in the unit and suitable wiring between indoor and outdoor unit upto 6 metre length and upto switch within 3 metre of location of indoor unit.
69S&F voltage stabilizer 4 KVA capacity for automatic operation, single phase naturally air cooled indoor type and designed for input variation between 170 V to 250 V with out put voltage stabilizer at 230 V with accuracy of ± 2.5%complete all as specified and directed.
70Demolition of cement concrete of any description and in any position not other wise specifically provided for complete all as specified and directed.
71M&L forHardcore (Broken stone or boulders) of gauge not exceeding 63 mm, deposited, spread and levelled in layers not exceeding 15 cm thick, watered and rammed to a true surface complete all as specified and directed.
72M&L for providing 75mm thick PCC 1:4:8, Type D-2 (Using 40 mm graded crushed stone aggregate) laid in floors in bays as sub base to precast interlocking paver blocks flooring complete all as specified and directed.
73M&L for providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5 mm), including making drainage opening wherever requiredetc complete all as specified and directed. Note : (i) Kerb stones shall be tested in CTL/NABL approved laboratory for grade of concrete and test certificate shall be produced by the contractor for each consignment before incorporation in the work. (ii) Testing charges shall be borne by the contractor.
74M&L for Machine pressed precast concrete interlocking Colour paver blocksglazed anyshape and size confirming to IS 15658-2006 of 80 mm thickness, M-40 grade of cement concrete with grey cement and no pigment etccomplete all as specified and directed. Note : Paver blocks shall be tested in CTL/NABL approved laboratory for grade of concrete and test certificate shall be produced by the contractorfor each consignment before incorporation in the work (ii) Testing charges shall be borne by the contractor.
75M&L for 25mm thick sand cushion below inter-locking pavingblocks/tiles including spreading, levelling and compaction complete all as specified and directed.
76M&L for PCC 1:3:6, type C-1 (Using 20 mm graded crushed stone aggregate) in aprons, plinth, strings, lacing courses etc complete all as specified and directed.
77S&F galvanized iron (GI)pipe 50 mm bore medium grade including necessary fittings laid in trenches complete all as specified and directed.
78S&F Gun-metal globe or gate valve 50 mm bore with iron wheel head, screwed both ends for iron pipe and fixed completeall as specified and directed.
79M&L for cutting andscrewing existing steel tubing for alterations or additions(or lengthening screw on pipe to form connector)(Each cut measured) and inserting GI Tee of size 100mm x 100mm x 50mm including excavation and returning, filling in layers,ramming and removing of surplus soil to a distance of 50 mtrcomplete all as specified and directed.
80Supplying, laying & testing HT cable XPLE insulated, screened,PVC bedded, galvanized steel strip,armoured, electric power cables (heavy duty) with aluminum conductor 11000 volts (earthed) grade laid in trenches / drawn through pipe / poles or laid under road / drains / path complete of cross sectional area 120 Sqmm3 corecompleteall as specified and directed.
81M&L for cable jointing kit for 11 KV grade cable for indoor termination, heat shrink type joints complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 120 Sqmm to 185 Sqmm complete all as specified and directed.
82Supply, installation, testing & commissioning of HT 11 KV, 3 Phase, 50 HZ,630 Amps, indoor type, totally enclosed / metal clad switch gear Vacuum circuit breaker (VCB) panel, rupturing capacity of 350 MVA, overload, earth fault and short-circuit protection,Voltmeter range (0-15 KV) and Ammeter (0-630 Amps), required battery bank with charging arrangement including additional suitable adopter panel for fixing with the existing VCB,complete of following specifications mentioned inIS/IEC 62271-201 including latest amendments / additions:- (a) Motorized spring charging mechanism with 24 volts DC universal motor and having charging time less than 10 seconds. (b)Earthing switch rated for full making capacity with provision for safe & reliable position indicator. (c)Assembly of Vacuum circuit breaker shall be completely insulated as per the relevant IS/IEC. (d) The rating of VCB shall be 11 KV, 630 Amps, 21 KA (for 3 sec), 50 Hz, 3 phases.
83(e) Electrically charged and electrically operated independent closing / tripping, trip free, operating mechanism including manual closing / tripping push button and breaker close / open portion shall be provided. (f) Strip Heaters with thermostat to be provided with following specifications:- Power input 80 watts with voltage rating 230 volts AC single phase. (g) Dual core dual ratio Current Transformer (CT) chamber comprising of 3 Nos, Single phase resin cast / ring core CTs of 100-50/ 5+5,burden not less than 15 VA and accuracy class 0.5,for metering, having class SP10 for protection as per IS:2705-01 Sets and including suitable size Potential Transformer (PT) as required. (h) SCADA compatibleself-powered IDMT numerical relays L&T, over current & earth fault relay with high adjustablesetting, short circuit fault relayfor complete protection of HT, 11 KV, 3 Phase feeder having facility to record fault current with MODBUS communication on RS 485 communication port - 01 No, including 1 No voltage monitoring relay for under voltage / over voltage protection.
84(j) Digital SCADA compatible meter of accuracy class 1, as per IEC 62052-11 / IEC 62053-22 monitoring all electrical parameters likevoltage & current per phase and watts, VA, VAR etc. Also to monitor all instantaneous integrated demand, parameters, neutral current, frequency, power factor, % load, % unbalance (V&I), phase angle, THD working on MODBUS protocol. (k) One set of mechanical indicator for ON / OFF indication forVCB breaker. (l) One set of capacitive voltage indication for R-Y-B (m) One set of battery and battery charger to provide suitable back up as per Original Equipment Manufacturer’s (OEM) instruction.
85Supply and laying un-reinforced Precast concrete cable cover. Class HVP type-1 flat of size 300mmx180mmx40mm complete all as specified and directed.
86M & L for earthing with Galvanised steel earth plate 600mm x 600mm x 6mm thick buried directly in ground vertically in pit of depth not less than 2.25 mtr below normal ground level with top edge of the earth plate not less than 2.25 mtr below normal ground level connected to continuous (without joint) GI strip 32mm x 6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel connected to earthing test point all as specified including excavation and earth work and disposal of surplus soil including 40 mmbore GI tubing medium grade and necessary fitting for protection of GI strip including laying of charcoal, dust and common salt in alternate layers, PCC pit (1:2:4) type B-1 (Using 20 mm gradedcrushed stone aggregate) earth pit with 40 mm x 40 mm x 6mm mild steelangle iron frame, 40 mm thick pre- cast RCC cover (1:2:4) type B-0 ( using 12.5 mmgradedcrushed stone aggregate ) reinforced with 8mm dia TMTbar @ 75mm c/c both way with mild steelhandle 12 mm dia round bar, 15 mm thick plasteringin cement mortar (1:4) internally and upto 150mm below ground level externally, funnel with wire mesh 20mm dia medium grade GI pipe for watering complete all as shown on electrical plate No.3 of SSR Part- 1( 2009 ) and connected in earth testpoint includingtesting and marking Building numbers / Name of equipment and writing test results on a 3.00 mm thick painted mild steel earth pit marking plate (200 mm x 200 mm ) duly welded with a 450 mm long 10 mm dia round MS rod fixed with the earth pit chamber b y grouting completed all specified and directed.Notes: (a) The unit rate quoted is deemed to be inclusive of cost of Earth lead & protection pipes length upto & including 7.50 metre (b) Earth filling shall be done by approved soil (c) Soil should be free from stone, boulders, aggregate, gravels etc. (d) The earth resistance of the whole system shall be as near as possible to 0 but shall not in any case exceed 05 ohm in any case (e)Any joints in earth lead from earth electrode to test point shall not be allowed / permitted.
87M& L for PCC 1:3:6, Type C2 (Using 40 mm gradedcrushed stone aggregate) as in foundations,filling and mass concrete completed all specified and directed.
88M&L for rendering 15mm thick on brickwork or concrete surfaces in cement mortar 1:3 finished even and smoothwithout using extra cement complete all as specified and directed.
89M&L for PCC 1:3:6, Type C1 (Using 20 mm gradedcrushed stone aggregate) as incoping etc including necessary form workcomplete all as specified and directed.
90M&L for PCC 1:2:4, Type B0 (Using 12.5 mm gradedcrushed stone aggregate) as insurface channel, benching etc complete all as specified and directed.
91Extra for forming fair finished drain or channel 30cm inner girth in cement concrete, using extra cement including forms, moulds, mitred/ stopped ends etc complete all as specified and directed
92Add or deduct for each 25mm girth or part thereof over or under 30 cm (for adjustment only) etc complete all as specified and directed.
93Dismantling posts or struts (wood, steel or R.C.C.) any section, including taking out embedded portion in concrete or brick work and making good disturbed ground complete all as specified and as directed.
94Excavation in post holes in soft/loose soil not exceeding0.5cumand getting out returning, filling in, ramming earth or broken rubble mix with earth around on layers not exceeding25cm watering and removing surplus soil to distance not exceeding50m and making good to surface complete all as specified and directed.
95M&L for PCC 1:2:4, type B-2 (Using 40 mm graded crushed stone aggregate) a in foundation filling and mass concrete etc complete all as specified and directed.
96S&F Hand rails, half round or other steel section or core for wooden hand-rail straight portion, drilled and countersunk for balusters running bars, for doors, balusters, nosing to steps including embedding in concrete and screwing etc. wind ties for roof including securing bolts posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc, flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 etc complete all as specified and directed.
97S&F GI chain link fencing of mesh size 100mm x 100mm square mesh of 4mm dia wire confirming to IS 278 : 2009 & 2721-2003 with electro galvanised as per IS 12753 : 1989 type etc complete all as specified and directed.
98S&F Mild steel bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed.
99S&F galvanised 2 strand steel barbed wire 2.24 mm dia barbed with 2 mm dia barbs at 75 mm spacing and straining fixing to any type of standard rail straining bolts, including securing or tyingat crossing with provision of galvanised mild steel wire, staples or steel pins etc complete all as specified and directed. Note : Each line wire to be measured.
100S&F mild steel screw bolts (machine made)with hexagonal or square heads at one ends and screwed the other ,or screwed both ends each ends to be fitted with washers and one hexagonal or square nut not exceeding 10cm but not exceeding 15cm long of 11 to 15mm dia shank etc complete all as specified and directed.
101M & L for preparation of new steel surfaces of any description,over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide primer (ordinary tint) complete all as specified and directed.
102M&L for preparation of new steel surfaces not exceeding 10CM in width or girth and applying 2 coats of synthetic enamel paint over one coat of red oxide primer complete all as specified and directed.
103S&F in repairs concertina coil 600mm dia (in stretched position) hot dip galvanized steel wire coated with CLR anti corrosive paint, making diamond shape with the help of dovetail clips (18 SWG) fixed over and including razor wire, medium barb, hot dip galvanized steel wirerazor wire with angle iron. The concertina coil to be fixed with razor wire at points wherever coil touches bottom of razor wire with the help of hog rings (14 SWG) including all fittings like fastener clips, steel lug rings etc complete all as specified and directed. Note- (i) Stretched length of each coil shall be 6 mtr complete all as specified and directed. (ii) Angle iron supports shall be measured paid separately underrespective item of BOQ.
104Taking down/dismantling chain link fencing of any size & type complete all as specified and directed.
105S&F in repairs galvanised 2 strand steel barbed wire 2.24 mm dia barbed with 2 mm dia barbs at 75 mm spacing and straining fixing to any type of standard rail straining bolts, including securing or tyingat crossing with provision of galvanised mild steel wire, staples or steel pins etc complete all as specified and directed. Note : Each line wire to be measured.
106S&F for 10 mm dia and over mild steel TMT reinforcement bars and spacers cut to length, bent to shape required including cranking, bending, binding with and including mild steelwire(annealed) not less than 0.9 mm dia and necessary welding to reinforcement complete all as specified and as directed.
107S&F Mild steel TMTbars 5 mm dia and over upto and including 10 mm diain stirrups, spacers and binders, cut to length bend to shape required including cranking bending spirally for hooping for columns, hooking ends and binding with MS wire (annealed) not less than 0.9 mm dia complete all as specified and as directed.
108M&L for RCC, M-25 Design Mix (Using 20mm graded crushed stone aggregate) as in foundations including rafts, footings, foundation beams, plinth beams, bases for columns, etc basement slabs, under-reamed piles and mass concrete etc complete all as specified and directed.
109M&L for RCC M-25 Design Mix (Using 20mm graded crushed stone aggregate) as in columns, pillars, piers, posts and struts etc complete all as specified and directed.
110Use and waste of formwork to sides of rough finished surface of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams, and similar work, vertical or to batter complete all as specified and directed.
111Use and waste of formwork to sides of pillars, posts, struts, piers, columns and stanchionsfor fair finished surfaces of concrete complete all as specified and directed.
112M & L for rendering 15mm thick in cement plaster 1:4 on fair faces of brick work or concrete surfaces finishedfair & even complete all as specified and directed.
113S&F framed work as in doors or gates of angle or other section with gusset plates, rails braces etc complete drilled for fixing of steel sheeting or other covering, doors etc sliding with and including either hooks and hinges or steel hanging door fittings and hanging also fastening and fixing complete all as specified and directed.
114Dismantling of structural steel work including doors, gates but excluding framed truss complete all as specified and directed.
115S&F Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) triple layered, ISI marked, hoisted and fixed in position 2000 Ltrs capacity including 2 Nos GI unions, check nuts 25 mm bore PTMT float valve, gate valve and fixed in position complete all as specified and directed
116S&F 01 HP centrifugal mono block pump, copper wound, operating rated voltage 220 volts, self priming with in-built thermal over load protector, inlet/outlet size 20 mm and flow rate 8 LPM with cast iron body complete all as specified and directed.
117S&F sheet metal enclosure single pole and neutral with two pin and earth plug and socket capacity 20-32 Amps modular type complete with one No SP MCB capacity 20-32 Amps complete all as specified anddirected.
118M&L for sub main wiring with 2 single core 4 Sqmm PVC unsheathed and PVC insulated stranded copper conductor cable in and including rigid 25 mm dia PVC conduit and 4 Sqmm PVC insulated unsheathed continuous earth wire and connected to earth dolly and making good disturbed surfaces with cement mortar and paintto match existing surface complete all as specified and directed
119M& L for fabrication, supply, installation, testing and commissioning CPRI approved electrical cubical control panel board factory assembled made outdoor type feeder pillar box double door type weather and vermin proof fabricated of 3.15 mm CRCA MS Sheet of suitable size, 3 phase 4 wire 415 V AC 50Hz complete duly painted with powder coating complete with locking arrangement, earthling terminal including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 90 cm long angle iron size 50x50x6mm welded on all four corner embedded in PCC 1:2:4 (using 20mm graded crushed stone aggregate) upto 30cm complete all as specified and directed by the Engineer-in-Charge. Feeder pillar box shall be consisting the following:- (a) INCOMMING: MCB SPN 32 Amps 415 volts thermal adjustable, type with 16 KA breaking capacity & spreader both side as Incoming control device :01 No. (b) OUTGOING: Starter for mono block pump 1 HP 220 volt with auto start timer, Dry run & Overload Protection, Low and High Voltage Protection, Fully Automatic Water level Controller, Auto Starting Capacitor cut-off etc :01 No.
120Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 Sq mm 2 core complete all as specified and directed
121SOLAR POWER PLANT
122Design, Supply, install,testing and commissioning of ground based solar power generating system without battery of capacity 600 KW AC output peak grid tied solar photo voltaic system complete with the components specified below :- (a)Solar power modules of minimum rating 540 WP with minimum 144 cells, mono PERC (Passivation emitter rear contact cell) Half cut cells types modules shall be certified as IEC edition -II, IEC 61646 and IEC 61730 1 & 2complete all as specified quantity of Solar PV modules shall be tentatively 1321 Nos for 0.6 MW AC output. Note:- (i) Design shall be done as per latest IS code, latest MNRE guidelines and specifications mentioned in tender from MNRE approved channel partner of rating as specified in Notice Inviting tender (NIT). Final design and drawing shall be vetted by any of the approved agency as mentioned in the Particular specifications of tender.
123(ii)Solar Modules and solar cells therein shall be ofMade in India. The contractor shall submit manufacturer"s/company"s declaration in the format to be provided by GEat the time of request for approval of sample/Make for modules. Each PV module used in this work shall have RF Identification tag. (iii) Solar PV Modules shall be warranted for a minimum period of 25 years. PV modules shall be warranted for their output peak watt capacity, which shall not be less than 90% at the end of 10 years and 80% at the end of 25 years. PV modules shall be warranted for any manufacturing defect or bad workmanship for a period of 25 years from the date of completion of Phase-I of the work. The contractor shall submit necessary warranty certificate for 25 years to GE. The condition 46 of IAFW 2249 shall be amended to the extent as mentioned above.
124(iv)Modules should be of Make as approved by MNRE. If no make has been approved, modules confirming to IEC standards mentioned above or latest specification issued by MNRE will be used in SPV system. (v)An amount equal to Rs 5,00,000/- (Rupees Five Lakhs Only) shall be retained from the contractor"s bill against the warranty as performance guarantee for a period of 25 years from date of completion of Phase-I. Alternatively, the contractor may give a separate interest-bearing security deposit/BGB in favour of GE valid for 25 years. This amount shall be refunded to him by GE after a period of 25 years under the conditions provided from by the contract and arising solely from faulty materials or workmanship provided such defective parts are not repairable at site. (vi)During the period of warranty of modules, the contractor shall remain liable to replace any defective parts that become defective in the plant.
125(b) Hot dip galvanized MS angle module mounting structure for solar panels of combined capacity 600 KW, AC output with double pole static structure of suitable size alongwith concrete grouting for required rigid support as required at site capable to with stand maximum wind load as designed for angle of modules all as required as per site. (c)Central Inverter/PCU, DC to AC (indoor type) of capacity suitable for 600 KW(Minimum 02 Nos) AC each with SCADA capabilities as specified and as per approved OEM instructions. Note:- (i)Power Conditioning Units (PCU) PCUs shall be warranted for minimum period provided by the manufacturer but not less than 5 years. PCUs shall be warranted for any manufacturing defect or bad workmanship for a minimum period of 05 years from the date of completion of Phase-I of the work. The condition 46 of IAFW 2249 shall be amended to the extent as mentioned above.
126(ii)During the period of Warranty the contractor shall remain liable to replace any defective parts that become defective in the plant under the conditions provided for by the contract and arising solely from faulty materials of workmanship, provided such defective parts are not repairable at site. After replacement,the defective parts shall be returned to the contractor . (d)String monitoring/combiner box of suitable number of inputs & 1 output with 10 Amp MCB/fuse on positive side, minimum 350 Amps manual DC disconnector switch & 22 Channel monitoring as required at site complete. (e)Copper DC String cables of different sizes of suitable size as required at site of Solar grade, including suitable lugs/male, female connectors etc. UV resistant 1.0 KV DC Cables confirming to IEC 62930:217/BSEN50618 temperature range -5° C to +90° C complete. (f)Data monitoring system communication cable RS 485 [screen twisted] as required at site complete. (g)Inverter communication Shielded CAT-5 cables as required at site complete. (h)EXISTING Solar Observatory system shall beused for Inverter Data Monitoring, Energy Meter Data Monitoring and Weather Station Monitoring. Note : M&L only for connecting the EXISTING Solar Observatory system is deemed to be included in the unit rate quoted.
127(i)Lightening protection system of Early Streamer Emission type Lightening Spike with 107 m protection at level 3 for Protection (duly supported by technical literature) against lightning strikes with GI mast of 8.5 Mtrs long.Quantity of lightening arresters shall not be less than3 Nosincluding suitable size of copper strip up to earthing pit . Foundation of system should be as advised by OEM / NISE.Earthing shall be provided for string monitoring/combiner box, Inverter, Solar PV module, mounting structure, panels, LA complete with suitable size of Copper earthing and copper Cable / strip as earthing lead as per design including termination accessories as required at site & confirming to latest IS/IEC all as specified and directed.Earthing for isolation transformer and equipments thereafter downstream will be through GI strip earthing with GI earthing lead. Main distribution board, Floor Mounted DC Panel, DC Bus, Auxiliary Buses for required load as per site requirement on DC side of inverter complete all as specified and directed.
128Main distribution board Floor Mounted AC Panel, AC Bus, Auxiliary Buses for required load as per site requirement on AC side of inverter complete all as specified and directed. UPS with battery bank of 5 KVA with 60 minutes backup at 100% load as per design & specifications for Solar System critical components, Industrial type online UPS with static switches for bypass complete. UPS distribution board of Floor Mounted UPS DB, indication lamp complete all as required at site. (j)Main DC Cables of size as required at site, Aluminium, armouredcable confirming toIEC 62930:217/BSEN50618 temperature range -5°C to +90° C complete. (k)1.1KV Aluminium armouredLT power Cable as per IS 7098 from inverter to transformer of AC Cables of sizes as required at site including end joints, mid joints complete all as specified and directed. (l)LT Aux (DC & AC) control cables for UPS input, transformer, Inverter, panels of suitable size,1.1KV copper LT cable as per relevant IS complete all as specified and directed. (m)Earth continuity conductor or main earthing lead copper cable or GI strip of suitable size as per design and as required at site.
129(n)Suitable size HDPE pipe 6kgf/cm² rating for cable protection including all necessary fitting and fixing arrangement complete as required at site all as specified and directed. Note: Necessary earth work, sand cushioning, protection pipe, bricks etc shall deemed to be included for laying of cables HDPE pipe up to power transformer. (o)Industrial type computer One Number rugged & robust in nature to operate in a hostile environment. The computer shall be of HP make or of equivalent make having i10 of better processor with minimum 1 TB of hard drive, 21’’ LCD colour monitor, DVD Drive with writer,multimedia kit and UPS with 30 minutes Power back up. (p)Coloured laser printer : One Number as per HP model number M1005 or techno commercially equivalent model in other make as approved by GE. The printer shall be equipped for printing, scanning and copying complete. (q)Generation Metering : Suitable capacity generation digital meter arrangement with associated accessories viz CT, PT, metering box, wiring etc for commissioningwith initial inspection from local electricity supply company. (r)-Blank-
130(s)Inverter duty step up transformer - 01 No, BEE Level 5, copper wound, outdoor typeof 750 KVA or nearest size on higher side suitable for stepping up AC voltage from Power Conditioning Unit / Invertor to 11 KV confirming toIS-2026 including all latest amendments including first fill of transformer oil confirming to IS 335 , suitable plinth of size and design as per manufacture instruction with slot and clamps for incoming and outgoing cable protection pipe complete all as specified and directed (t)Isolation Transformers -2 Nos of 375 KVA or nearest higher capacity compatible with AC voltage of PCU including first fill of transformer oil confirming to IS 335 , suitable plinth of size and design as per manufacturer"s instruction with slot and clamps for incoming and outgoing cable protection pipe complete all as specified and directed (u) Isolation Transformer and step up transformer shall be installed separately. (v)Surge Protection device complete all as specified and directed. (w) Any other equipment/device/Items which are required for completion of the Solar power generation system shall be provided by the contractor without any extra cost to the MES.
131PHASE II [MAINTENANCE, MANNING & OPERATION ]
132Services for maintenance, manning, operation and repair of Solar Power Plant for 55 months after completion of Phase I works in two shifts [08 Hours Each shift] including Saturday, Sunday & holidays after completion of work under Phase Ias per conditions of contract including the following:- (a)Work orders for outsourcing of services shall be placed for eleven months period & no price adjustment for its extension shall be permissible. The Solar Power Plant shall be operated in 02 shifts per day as directed by the GE. (b)The contractor shall deploy minimum tradesman as follows:- (i) One trained Electrical Engineer and One helper (Unskilled) in each shift as directed by Engineer-in-Charge for attending/monitoring the breakdown and preventivemaintenance. (ii) Penalty Clause:If the installation (Solar Power Generation Station) is not operated by the Electrical Engineer and Helper or found absent from duty the penalty for this lapse shall be final and binding as under:- (iii) Electrical Engineer : - Double the rate of minimum fair wages of Highly Skilled as published by the Govt of India during the absent period. (iv) Helper (Unskilled) :Double the rate of minimum fair wages of Unskilled as published by the Govt of India during the absent period.
133(c)The Electrical Engineer with minimum of a relevant degree in electrical engineering with atleast 02 years experience of working in Operation & maintenance of Solar PV plants (or)aDiploma holder in Electrical Engineering with atleast 03 years experience of working in Operation & maintenance of Solar PV plants and familiar with SCADA operating system, weathering monitoring system, HT/LT installation and security and safety features complete. The Necessary technical qualification certificate shall be produced for verification of Engineer-in-Charge & get the written approval on record before deploying for works (d) Contractor shall offer service for entire system as per inspection/ maintenance schedule as given in particular specifications and as directed by Engineer-in-Charge and maintain necessary record for the same. Contractor shall also ensure the following:- (i) Servicing of all solar equipment’s HT/LT control system, Transformers weather monitoring equipment’s SCADA system etc all as per OEM instructions. (ii) Cleaning of Solar PV modules by washing, sprays, brushes, tools and plants, any washing solutions as per OEM recommendations & as per laid down norms for solar power plant complete as directed by the Engineer-in-Charge/GE including providing arrangements for taking water from tapping point to modules.
134(iii) Checking of meter readings and recording in log book in the format and as per instruction given by Engr-in-charge/GE (iv) The Engineer shall submit reports in soft and hard copy format as required by the Engineer in charge. (v) Safety, security of all E&M equipment’s solar panels, T&P and Sub Station complete all as directed by the Engineer-in-charge/GE. (vi) Area cleaning including removing of grass, bushes etc as per the instructions of Engineer-in-Charge/GE. (e)Permissions/passes shall be provided to work force/manpower of the contractor by the GE through Security Officer. (f) Repairing of all installation if required shall be carried out on site or at service centre by the contractor. Quoted rates shall be all inclusive and also include for required spares, services labour, handling and transportation charges etc.
135(g) Proper & efficient functioning of the plant must be ensured through regular inspection by qualified engineer of MNRE approved vendor of Category ‘A’as per inspection/ maintenance schedule and rate quoted shall deemed to be included for the same. (h) Contractor shall arrange one month trainingfor operation and maintenance to MES tradesman before handing over the installation to MES as directed by GE Note: Contractor shall also provide portable fire extinguisher of required capacity and quantityat the installation/Solar power plant as per MNRE approved consultant instructions. Note:- All stationery, T&P, items required to maintain the Installations,for keepingin a presentable manner and to keep plant in 100% functionable condition, payment of requisite charges and fees for SCADAto third party / SCADA OEM,are deemed to be Included in the cost of quoted rate.
136(a)For first 11 Months [The rate to be quoted by contrator shall be equal to or more thanRs. 10,31,000/- which is as per prevailing minimum fair wages]
137(b)For second 11 Months [The rate to be quoted by contrator shall be equal to or more thanRs. 11,34,000/- which is as per anticipated minimum fair wages]
138(c)For third 11 Months [The rate to be quoted by contrator shall be equal to or more thanRs. 12,47,000/- which is as per anticipated minimum fair wages]
139(d)For fourth11 Months [The rate to be quoted by contrator shall be equal to or more thanRs. 13,72,000/- which is as per anticipated minimum fair wages]
140(e) For fifth11 Months [The rate to be quoted by contrator shall be equal to or more thanRs. 15,09,000/- which is as per anticipated minimum fair wages]
141Schedule of Credit (MINUS) Rs. 58,975.00 brough forwarded from Serial Page No. 56(R) [Note : Detailsof items for schedule of credit is given on Sl Page No. 56(R)]. This amount shall be automatically deducted to arrive at tendered contract sum