| 1 | Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft / loose soil for laying / taking up / taking down of cables and getting out and levelling of bottom suface to required level all as specified and directed by Engineer- in- Charge. |
| 2 | Returning filling in including spreading, levelling, watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed. |
| 3 | Removing excavated soil n.exc 50 m and depositing where directed at a level n.exc 1.5 m above from the starting point complete all as specified and as directed. |
| 4 | M&L for providing dry river sand as in sand cushioning below and above cable thickness as specified in SSR to under ground cable including punning down of sand in layer all as specified and directed by Engr-in-Charge.Note: for measurement purpose punned thickness of sand will be consider. |
| 5 | M&L laying well burnt old sizebricks, sub class \"B\" bricks, straight or curved on plan , laid flat with width equal to length of brick , laid dry over electric cable for protection complete all as specified & directed by Engr-in-Charge. |
| 6 | All as per srl item No 5 here-in-before but using old bricks obtained under srl item No1 here in before. |
| 7 | M&L for demolition /cutting of road/ path/hardstading/ concrete in floor, etc for laying of cable complete all as directed at site by Engr-in-charge |
| 8 | Material and labour for PCC1:2:4 type B-2 using 40 mm graded stone aggregates for filling of cutting of roads/path/hardstanding etccomplete all as specified and as directed by Engineer-in-Charge. |
| 9 | Deployment of manpower / tools for Boring / drilling (Horizontally) manually / mechanically under existing road max 10 M in width) suitable for passing tubing 40 to 100 mm bore complete all as specified and directed by Engineer in Charge |
| 10 | M&L for 40 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid onfloors / fixed to poles / or passing under road crossing, for protection of UG cable complete all as specified and directed by Engr-in-Charge. |
| 11 | M&L for 50 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid onfloors / fixed to poles / or passing under road crossing, for protection of UG cable complete all as specified and directed by Engr-in-Charge. |
| 12 | M&L for 80 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid onfloors / fixed to poles / or passing under road crossing, for protection of UG cable complete all as specified and directed by Engr-in-Charge. |
| 13 | Supply, laying jointing and testing LT UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, IS 7098 marked, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 Sqmm 2.0 core, laid in trench / laid under floor or fixed naked with wall / on wall / in ducts / in GI pipes etc. with and including MS Clamps, nuts, bolts, washers and taking down old cable complete all as specified and directed. Note- Excavation, earth works, and sand cushioning, protection bricks / tiles / blocks and pipe shall be measured and paid seprately. |
| 14 | All as per item No. 13 above but LT UG cable of size 16 Sqmm 2 core. |
| 15 | All as per item No. 13 above but LT UG cable of size 16 Sqmm 4 core. |
| 16 | All as per item No. 13 above but LT UG cable of size 25 Sqmm 4 core. |
| 17 | All as per item No. 13 above but LT UG cable of size 35 Sqmm 3.5 core. |
| 18 | All as per item No. 13 above but LT UG cable of size 50 Sqmm 3.5 core. |
| 19 | All as per item No. 13 above but LT UG cable of size 70 Sqmm 3.5 core. |
| 20 | All as per item No. 13 above but LT UG cable of size 95 Sqmm 3.5 core. |
| 21 | All as per item No. 13 above but LT UG cable of size 120 Sqmm 3.5 core. |
| 22 | All as per item No. 13 above but LT UG cable of size 185 Sqmm 3.5 core. |
| 23 | All as per item No. 13 above but LT UG cable of size 240 Sqmm 3.5 core. |
| 24 | M&L for Earthing in replacement complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0 mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end, GI earth strip encased inand including 40 mm dia GI \"lightgrade\" pipe from upper end of earth plate upto equipments, 20 dia bore GI pipe \"light grade\" as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe andPCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS TMT bars 8mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as describedin electric plate of SSR Part I completeall as specified and directed and testing on completion. Note :- Ifthe desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department. |
| 25 | Earthing in replacement complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by mean of GI wire 4 mm dia by means of bolts, nuts check nuts and washers of GI or steel and connecting to earthing test point, main switch board, testing on completion including PCC cover and frame, PCC (1:3:6) type C-2 as in earthing pit, MS funnel with wire mesh GI pipe 20 mm dia light grade for watering and GI pipe 15 mm dia light grade for the protection of GI wire from earth pit to earth point complete including necessary excavation and earth work in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50 m all as specified as shown in electrical plate No 5 SSR Part-I.PCC chamber shall be constructed at least one metre away from the earth pit and GI pipe fittings for watering shall be provided up to chamber and cost of the same is deemed to be included in the rate of earthing.Note :- Ifthe desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department. |
| 26 | Disconnecting the existing cable from Panel / Pole, preparing the end for jointing including all earth work, Supply and fixing Cable end termination heat shrinkable joint including sleeves suitable for LT XLPE cable of size 3.5/4 core 10 to16 Sqmm. |
| 27 | All as per item No 26 abovebut end termination heat shrinkable joint of size 25 to 50 Sqmm |
| 28 | All as per item No 26 abovebut end termination heat shrinkable joint of size 70 to 120 Sqmm |
| 29 | All as per item No 26 abovebut end termination heat shrinkable joint of size 150 to 185 Sqmm |
| 30 | All as per item No 26 above but end termination heat shrinkable joint of size 240 to 300 sqmm |
| 31 | Disconnecting the existing cable from Panel / Pole, preparing the end for jointing including all earth work, Supply and fixing straight through heat shrinkable joint suitable for LT XLPE cable of size 3.5/4 core 10 to 16 Sqmm |
| 32 | All as per item No 31 abovebut straight through heat shrinkable joint of size 25 to 50 Sqmm |
| 33 | All as per item No 31 abovebut straight through heat shrinkable joint of size 70 to 120 Sqmm |
| 34 | All as per item No 31 abovebut straight through heat shrinkable joint of size 150 to 185 Sqmm |
| 35 | All as per item No 31 above but straight through heat shrinkable joint of size 240 to 300 sqmm |
| 36 | Supply & Fixin replacement twin core, 6 sqmm nominal cross sectional area multistranded aluminium conductor cable, over all PVC sheathed, 1100 Volts grade heavy duty cable PVC insulatedcomplete all as specified. |
| 37 | Supply & Fixin replacement twin core, 10 sqmm nominal cross sectional area multistranded aluminium conductor cable, over all PVC sheathed, 1100 Volts grade heavy duty cable PVC insulatedcomplete all as specified. |
| 38 | Supply, fix, connecting and testing in replacement MCCB 63 Amp 4 pole 25 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed. |
| 39 | Supply, fix, connecting and testing in replacement MCCB 100 Amp 4 pole 25 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader after taking down old existing unserviceableMCCB complete all as directed |
| 40 | Supply, fix, connecting and testing in replacement MCCB 125 Amp 4 pole 25 KA 415 volts 50 Hzadjustablethermal & adjustable magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed |
| 41 | Supply, fix, connecting and testing in replacement MCCB 160 Amp 4 pole 25 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed |
| 42 | Supply, fix, connecting and testing in replacement MCCB 200 Amp 4 pole 36 KA 415 volts 50 Hzadjustablethermal & adjustable magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed |
| 43 | Supply, fix, connecting and testing in replacement MCCB 250 Amp 4 pole 36 KA 415 volts 50 Hzadjustablethermal & adjustable magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed |
| 44 | Supply, fix, connecting and testing in replacement MCCB 400 Amp 4 pole 36 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed |
| 45 | Supply, fix, connecting and testing in replacement MCCB 630 Amp 4 pole 50KA 415 volts 50 Hzadjustablethermal & adjustable magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed |
| 46 | S&F in replacementon load change over switch open execution of capacity 400 Amps , 4 pole , 415 volt , 50 Hz fixed in any type of existing LT panel/Feeder piller including taking out old existing unserviceable change over from panels etc complete all as directed |
| 47 | S&F in replacementon load change over switch open execution of capacity 250 Amps , 4 pole , 415 volt , 50 Hz fixed in any type of existing LT panel/Feeder piller including taking out old existing unserviceable change over from panels etc complete all as directed |
| 48 | Supply, fix, connecting and testing in replacement MCCB FP 125 Amps, 25 kA, 415 Volt AC, 50 Hz, complete with sheet metal enclosure of 1.6 mm thick MS sheet factory made with powder coat paint including connecting with existing system with existing cablling network including making good disturbed surfaces complete all as specified and directed.Note : The cost of suitable size fastner/Nut bolts required at site for fixing of cubical is deemed to beincluded in the quoted rate by the contractor. |
| 49 | Supply and fixing in replacement double pole sheet metal enclosure made of 1.6 mm thick MS sheet factory made with powder coat painting including 01x MCB20 Amps 10 kAcomplete all as directed Note : The cost of suitable size clamp/Nut bolts required at site for fixing of enclosure on garden light post/wall is deemed to beincluded in the quoted rate by the contractor. |
| 50 | Supply drawing, connecting and testing in replacement3 core, 1.5 Sqmm PVC insulated and PVC round sheathed`copper conductor (flexible ) industurial cable, 1100 Volts conforming to IS 694 in steel tubular poles from Junction box to street light fitting including providing suitable copper lugs all as specified and directed by Engr-in-charge. |
| 51 | S&F in replacement wheather proof pole mountingPVC junction box, base and door of junction box made out of SMC having outside dimention333 x 233 x 120 mm, inside dimention300 x 200 x 105 mm, single door front openable provided with hinged cover and locking arrangements with 4 Nos aluminium bas bar 63 Amps, mounted on porcelin insulatorincluding M&L for MCB SP10 Amp -1No, fixed on box in Din rail complete with electrical connection fixed to pole with suitable sizeFI clamp nut bolts and washer including embossing / painting of danger notice of size not less than 10cm x 7.5 cm with letters, figures and conventional skull and bones in signal red colour on front face of junction box body Complete all as directed by Engr-in-Charge |
| 52 | Supply & fix in replacement GI brackets made of 40 mm nominal bore GI pipemedium grade of required length not less than 1.5 M long, mounting brackets made out of Mild steel FI 40x6 mm of required shape ( two Nos) duly fitted with Mild steel nuts, bolts and washers and painting with two coats of synthetic enamelled paint over one coat of red oxide primer and fixed to pole / walls etc complete all as specified & directed by Engr-in-Charge. |
| 53 | Supply and fix in replacement CRCA MS sheet for LT panel having thickness 3.15 mm powder coated finish over one coat of red oxide on out side surface and painted in side with two coats of red oxide primer including all fixing acessories i.e. suitable size of hinge, nuts, bolts, washers, cutting and welding works etc complete all as directed by Engr -in-charge |
| 54 | Supply and fix in replacement Digital VAF+PF meter with RS 485 CL1 in LT panel including taking out old existing unserviceable meter from panels etc complete all as directed |
| 55 | Supply and fix in replacement of LED indication lamp including taking down old unserviceable LED indication lamp from LT panel complete as specified and directed. |
| 56 | M&L for Preparation of old painted surfaces of LT steel tubular pole9 mtrs long from bottom to top and applying one coat aluminium paint including painting to bottam up to 1.5 mtr height from top of PCC coping with synthetic enamel paint 2 coats in black and Yellow / white alternate strip including numbering in 8 cm height of number with white paint as approved by Engineer –in-Charge and complete all as directed and specified. |
| 57 | M&L for removal of existing paint from external surface of LT panel by scrapping, making good distrubed surfaces by applying putties on uneven surface to make it even and M&L for spray painting to LT panel of any size with two coat of synthetic enamel paint with desired colour over one coat of red oxide primer complete all as specified and directed. |
| 58 | Material and labour disconnecting faulty /burnt end or portion of cable from LT panel / LT pole /main switch / changeover etc by removing the cable from loop including necessary excavation & earth work , cleaning the surface area not less than 1 mtr surrounding the panel / pole , provision of suitable size of thimble, LT tap , relaying and reconnecting the cable by removing faulty / burnt portion of cable and preparing fresh terminals for 16 Sqmm 3.5 / 4 core to 240 Sqmm3.5 core of LT cable toLT Panel / pole / main switch / changeovercomplete all as directed. |
| 59 | Supply, installing, testing and commissioning in replacementfactory made , CPRI approvedpowder coatedLT Panel board (Dimention of Cubical / enclosure not less than 1200 mm x 900mm x 500mm) ,cubical compartmentalized, out door type double door, plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 HzAC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain / SMC insulator. The panel shall be dust and vermin proofIP-54 class protection and outer shell made of of 3.15 mm CRCA MS sheet, inner shell made of 2.0 mm thick CRCA MS sheet , 50 x 50 x 6mm thick MS angle iron frame work, the cubical have bottom channel of size 75 x 40mm duly coated with zink metal coating, front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked,1100 volts grade of appropriate size ( but not less than 2.5 Sqmm)and comprising of the following:- |
| 60 | (a) Incoming :-(i)MCCB 4 pole , 630Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos(ii)On load change over switch open execution type , 630 Amps , 4 pole , 415 volt , 50 Hz-01 No(iii) Digital VAF+PF meter with RS 485 CL1 -01No (iv) CTsratio 630/5 A ,class 1, ISI marked -01 sets of three (v)Indicating lamp- 01 set of three(vi) Four Pole , Aluminium bus bar 800 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. |
| 61 | (b) Outgoing(i)MCCB 4 pole ,250Amps,50 Hz,415 Volts, 36 KA thermal magnetic release- 03 Nos(ii)MCCB 4 pole ,200Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 03 Nos(iii)MCCB 4 pole ,125Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 02 Nos |
| 62 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The platform shall be such that it is of a height 45 cm above the nearest road level. Note :-(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer |
| 63 | M&L for out door type busbar panel board (Dimention of Cubical / enclosure not less than 600 mm x 450 mm x 450 mm) made out of3.15 mm thick MS sheet and MS angle section 50 x 50 x 6 mm factory made suitable for 3 phase 4 wire 415 Volt, 50 Hz, powder coat painted comprising of the following:- (a)FP, Aluminium bus bar 500 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators.(b) Incoming MCCB 250 Amps 36 KA, 415 Vots, 50 Hz, FP.– 1 No(c)LED Indicator lamp RYB - 01 set of three. |
| 64 | (d) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The platform shall be such that it is of a height 45 cm above the nearest road level. |
| 65 | M&L out door type busbar panel board (Dimention of Cubical/enclosure not less than 600mmx450mmx450mm) made out of3.15 mm thick MS sheet and MS angle section 50x50x6 mm factory made suitable for 3 phase 4 wire 415 Volt, 50 Hz, powder coat painted comprising of the following:- (a)FP, Aluminium bus bar 500 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators.(b) Incoming MCCB 160 Amps 25 KA, 415 Vots, 50 Hz, FP.– 1 No(c)LED Indicator lamp RYB - 01 set of three. |
| 66 | (d) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The platform shall be such that it is of a height 45 cm above the nearest road level. |
| 67 | Disconnecting faulty 1.1 KVLT cables of any size and any lengthfrom both ends Hiring of cable fault detector machine to detect exact position of fault , removal of Fault,Re-connections and testing of cables after removal of fault etccomplete as specified and directed.Note :(a) 1.1KVLT cable & joints shall be measured and paid for seperately under respective items of schedule. (b)Contractor or his rep shall come to the site of breakdown within one hour of notification of breakdownalongwith fault locating machine and manpower.In case the rep or contractor shall not come to the site of breakdown and not to start attending breakdown within 1.00 hour a penalty of Rs 1000 per fault per hour will be imposed over contractor and will be deduct from his dues. |
| 68 | Taking outfaulty underground1100 Volt LT cable of differentsizes by excavation and removingbricksof any size and relaying in the same trenches or re routing after rectification of fault or replacing faulty portion of cable with new cable and removing of surplus soil and using newbricks as required. Note: (a) 1100Volt LTcable & joints shall be measured and paid for seperately under respective items of schedule. (b) Retrieved old serviceable brickswill be laid in trenches for cable protection. If extra bricks and sand required at site shall be measured and paid separately under respective items of BOQs.(c) Excavation and earth work will be measured and paid for seperately under respective items of schedule. |
| 69 | Re-stringing of existingloose over head line having5 NosACSR conductor and 01Nos GI wire any size/type etc of existing LT pole steel and PCC including replacement of aluminium binding wire or suitable size carefully without damaging of insulator etc. complete all as specified and as directed by Engineer-in-Charge. Note:- 5 Run of main conductor with 1 Run GI wire will be mesured as 01 RM for payment |
| 70 | All as per item No 64 above but having 4 NosACSR conductor and 01 Nos GI WireNote:- 4 Run of main conductor with 1 Run GI wire will be mesured as 01 RM for payment |
| 71 | Trimming / pruning of the tree branches coming cross electric power head line LT feeder clearing the span and making the free from touching the tree branches complete all as specified and as directed by Engineer-in-Charge |
| 72 | Supplying and fix in replacement LT spacerin LT overhead line of ACSR conductor , shall be made of high quality regid PVC,the spacer shall be water proof weather proof and shock proof the spacer shall also be suitable for use onboth horizental and vertically configuration of LT O/H lineACSR conductor 5 wire /4 wire system |
| 73 | S&Fin replacement Aluminium conductor, steel reinforced (ACSR) of code name ferret / weaselon LT pole of size as ordered includingstringingandjointing for overhead line on poles including aluminiumbinding wire 14 SWG, jumpers, line tapes etc supplied and fixed in repairs including dismantling of old ACSR conductor fromLT poles complete all as specified and as directed by Engineer-in-Charge. |
| 74 | S&F in replacementCross arms, bracings, supports, clamps and back plates fabricated from structural steel sections conforming to Fe-410-S grade including necessary nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape and size as directed and including applying two coats of aluminium paint (under & finishing coats) over a coat of red oxide zinc chromate primer on exposed steel surfaces, supplied and fixed in repairs, complete all as specified and as directed by Engineer-in-Charge. |
| 75 | Supplying and fixing in replacement Pin type, porcelain, vitreous, white,brown or green insulator including one galvanised mild steel spindle,two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade |
| 76 | S&F in replacement Shackle type , porecelain, vitreous, white , brown or green insulator including galvanised mildsteel straps , washers, insulator bolts, washers and nustsworking pressure in volts1100 Voltsheight 75mm , max dia 90mm , galvanised steel fittings , section of straps 31x3mm, dia of bolts 12mm complete all as specified and directed. |
| 77 | Supply & fixing in replacementautomatic street light timer panel 12 KW /40 Amp switch using Infrared Sensor basedfor automatic switching of street lights based on LUX level of natural light. Required illuminance for switching ON is < 30 Lux and for switching OFF > 10 Lux level. The sensor (nature switch) alongwith suitable power contactors, Input (supply) MCB and output (load) MCB(s), support terminals should be enclosed in pole/ wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR graded SMC junction box conforming to IP-54 degree of ingress three phase 8 KW lightening load capacity including mounting bracket, cable glands, openable doors with lock complete all as specified & directed by Engr-in-Charge. |
| 78 | Supplying and fixing in replacement 3 pole power contractor AC 3rating 40 Amp, 240 Volt AC complete all as specified and directed by Engr-in charge |
| 79 | Supplying and fixing in replacement 3 pole power contractor AC 3rating 70 Amp, 240 Volt AC complete complete all as specified and directed by Engr-in charge |
| 80 | Supplying and fixing in replacement Astronomical Digital Timer Switch240 V AC complete all as specified and directed by Engr-in charge |
| 81 | Supply and fixing in replacement of 120 W LED flood fitting having epoxy powder coated die cast aluminium housing ADC12 in grey finish with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant. PG9 gland is used for cable entry and provision for loopin -loopout , PC lens/IP lens with narrow /wide beam distribution and toughened glass fixed to housing withscrews , floodlightshould haveIP 66 protectionand impact resistance ofIK 07 , Lumen efficiency of LED not less than 110 lumen per wattsystem efficency, power factor >0.95, THD<10% at Full load CRI> 70% ,flood light should have built in pottedelectronic LED driver with , lower THD, open circuit protection , over voltage protection , surge voltage protection ,andprovided with company LOGO ingraved on housing of the floodlightcomplete including taking down of oldUNSV fittings all as specified and directed by Engr -in-Charge.Note :-The contractor should take approval of techincal specification ofluminaries and driver from department before procurement . |
| 82 | All as per itemSer No76 above but 100 Watt & Lumen efficiency of LED not less than 110 lumen per watt system efficiency |
| 83 | Supply and fix in replacement 60 W LED street light fitting with mandatory driver set having pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embaded PC cover /IP lens, street lightshould haveIP 66 protection, impact resistance ofIK 07 , Lumen efficiency of LED not less than 110 lumen per wattsystem efficency ,power factor >0.95, THD<10% at Full load CRI> 70% ,street light should have built in potted electronic LED driver with , lower THD, open circuit protection , over voltage protection , surge voltage protection ,andprovided with company LOGO ingraved on housing of the street lightcomplete including taking down of oldUNSV fittings all as specified and directed by Engr -in-Charge.Note :-The contractor shouldtake approval of techincal specification ofluminaries and driver from department before procurement . |
| 84 | Supply and errectionin replacement07 mtr continuously tapered hot dip galvanised Octagonal cross sectional pole with single dipping method having bottom 130 mm A/F and top 70 mm A/F 3 mm thick confirming to ASTM A 572 Gr with yield 450mpa cut and folded to form an octagonal section and welded in accordance with AWS for wind loading as per IS 875 part 3 1987.Poles shall be provided with base plate of size 225x225x12 mm which shall be free from any lamination or incursion with no cutting or welding on the pole after hot dip galvanising with single arm 1000 mm long bracket tilted to 150 degree from horizontal toward vertices suitable for mounting on the octagonal pole, of company recommendationand one no TPN Connecton 3 phase 4 wire 100 Amps, and one number MCB SP 6 Amps. A triangular flat MS plat of 6mm thick duly coated with GI shall be welded between cap of the octagonal pole and bracket. Welding work shall be done 250mm on bracket and 150 mm on pole\"s cap including all RCC work type (1:2:4) type B-1 including 04 Nos foundation nut bolt and plate as per pole manufacturer\"s drawing and earth work all as per requirement complete all as specified and directed.Note Cost of construction of RCC foundation including construction material, necessary earth work and excavatonas per manufacturer design forabove polecompleteall as required at site and as directed by Engr-in-charge are deemed to be included in the quoted rate. |
| 85 | Supply & fixing in replacementelectronic LED Driver suitable for LED flood light 50 Watt to 100 Wattof existing make and model. |
| 86 | Supply & fixingin replacementelectronic LED Driver suitable for LED flood light 120 Watt to 150 Wattof existing make and model. |
| 87 | Supply & fixingin replacementelectronic LED Driver suitable for LED flood light 200 Watt of existing make and model. |
| 88 | Supply & fixingin replacementelectronic LED Driver suitable for LED Street light fittings 45 Watt to 70 Wattof existing make and model. |
| 89 | Supply & fixingin replacementelectronic LED Driver suitable for LED Street light fittings 90 Watt to 100 Wattof existing make and model. |