Tender For Procurement Of 150 Tr Pcm Storage Tanks For The Hvac System , Main Item - Ms Tanks ( As Per Technical Specifications Mentioned At Point 4 And Warranty As Per Schedule Of The Tender Document ) , Supply, Fabricate, And Install A 12.14 Cum Sectional Ms Tank On A Concrete Stand Complete With Inlet, Outlet, Overflow, Drain Connections, Access Ladder ( Outside ) With Protection, Access Cover, Air Vent, And Level Indicator, Complete As Detailed In Drawings. The Tank Dimensions Are 1.7M X 1.7M X 4.2M Constructed From Ms ( Is 2062 ) 8Mm Thick, One Baffle Plate 1.7Mx4.2M Constructed From Ms ( Is 2062 ) 8Mm Thick With Two Diffuser Plates Of 1.7Mx1.7M Each Made From Ms ( Is 2062 ) 5Mm Thick And Holes Of 8Mm Dia At 25Mm Pitch ( Or As Per Design ) . The Inlet And Outlet Connections Shall Be 200Mm Long, 150Mm Dia Flanged Connections To Be Placed As Indicated In Drawings. The Tank Shall Be Duly Primered And Epoxy Coated Inside. The Bottom Support ( Height 300 Mm ) Should Be Provided To Support The Tank, Maintain Stability, And Keep It Stationary As Per The Load Requirement. The Manhole And Drainpipe Should Be Provided As Per The Location Specified In The Drawing. , Supply, Fabricate, And Install 24.28 Cum Sectional Ms Tank On A Concrete Stand Complete With Inlet, Outlet, Overflow And Drain Connections, Access Ladder ( Outside ) With Protection, Access Cover, Air Vent, And Level Indicator, Complete As Detailed In Drawings. The Tank Dimensions Are 1.7Mx3.4Mx4.2M Constructed From Ms ( Is 2062 ) 8Mm Thick, Three Baffle Plates Of 1.7Mx4.2M Constructed From Ms ( Is 2062 ) 8Mm Thick With Two Diffuser Plates Of 1.7Mx3.4 M Each Made From Ms ( Is 2062 ) 5Mm Thick And Holes Of 8Mm Dia At 25Mm Pitch ( Or As Per Design ) . The Inlet And Outlet Connections Shall Be 200Mm Long, 150Mm Dia Flanged Connections To Be Placed As Indicated In Drawings. The Tank Shall Be Duly Primered And Epoxy Coated Inside. The Bottom Support ( Height 300 Mm ) Should Be Provided To Support The Tank, Maintain Stability, And Keep It Stationary As Per The Load Requirement. The Manhole And Drainpipe Should Be Provided As Per The Location Specified In The Drawing. , Supply, Installation, Testing, And Commissioning Of Insulation On Tanks With 100 Mm Thick Polyurethane Foam ( Puf ) Duly Finished With Uv Protection Cover With Heat-Resistant Adhesive On One Side. , Watertight Testing Of Ms Tanks. , Disinfection And Cleaning Of Structural Steel Tanks. , Pcm Tabs The Required Number Of Pcm Tabs Should Be Able To Store 150 Tr Capacity, Which Should Be Staggered In The Tanks. A 1 Cm Uniform Gap Should Be Provided Between Each Tab For Water Flow, And Staggering ( Vertical / Horizontal ) The Tabs Inside The Tank Without Any Damage Due To Staggered Weight Is Under The Contractor / Vendor Responsibility. , The Required Number Of Pcm Tabs Should Be Able To Store 150 Tr Capacity, Which Should Be Staggered In The Tanks. A 1 Cm Uniform Gap Should Be Provided Between Each Tab For Water Flow, And Staggering ( Vertical / Horizontal ) The Tabs Inside The Tank Without Any Damage Due To Staggered Weight Is Under The Contractor / Vendor Responsibility.