New Delhi Municipal Council-NDMC has published Annual Rate Contract For Maintenance Of Acs, Water Coolers And Fridges Installed In Ndmc Buildings, South Of Rajpath, New Delhi.. Submission Date for this Tender is 09-05-2024. Air Conditioner Tenders in Delhi Delhi. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Supplying and charging of R-22 / R-32/ R-134(a)/R-410 A Non CFC refrigerant gas in the following capacity WTAC / STAC and Water Coolers after pressure testing with nitrogen gas, vacuuming etc. including providing capillary filter of suitable size etc. as required (Gas will be supplied by the contractor) |
2 | 1 TR Capacity Water Coolers |
3 | 1.5 Ton Capacity WTAC / STAC |
4 | 2 / 2.5 Ton Capacity WTAC / STAC |
5 | Fridge 160 to 300 ltrs capacity |
6 | Supplying, installation, testing and commissioningof following capacity of compressor in existing Split/Window type AC & Water Coolers installed at various locations in NDMC area on exchange basis including connection with suitable size of suction and discharge copper pipe, copper strainer, cappliery, nut-bolts, anti-vibration pad, connection, interconnection all the electrical wiring with thimbles cleaning and leakage/pressure testing with nitrogen gas for 24-Hrs., vacuuming, charging with R-22 gas, ( Gas will be supplied by the contractor) including dismantling of defective compressor etc. as required at site of work. |
7 | Capacity 1 TR Kirloskar Make reciprocating type for Water Cooler. |
8 | Capacity 1.5 TR Kirloskar makereciprocating typetype |
9 | Capacity 1.5 TR Kirlosker make rotary type. |
10 | Capacity 2 TR/2.5 TR Kirloskar make reciprocating type. |
11 | Capacity 2 Tr/2.5 TR Kirloskar make rotary type |
12 | Replacement of burnt compressor of fridge 1/6 or 1/8 HP on exchange basis with new company make including Gas charging, brazing of suction and discharge lines, supplying and replacement of capillary strainer, pressure testing, vaccumising etc. in fridges of capacity 165/286/300 ltr at various locations in NDMC area(old burnt motor retained by Contractor) |
13 | Replacement of condenser coil / cooling coil in ACs / Water Coolers excluding gas charging complete as reqd. |
14 | Rewinding, repairing, overhauling of condenser motor complete for water cooler and ACs as reqd. |
15 | Replacement of PCB circuit of window AC / split AC complete as required. |
16 | Replacement of split AC indoor blower and bush set complete as reqd. |
17 | Replacement of suction & discharge copper pipe for 1.5 TR / 2 TR capacity for split type AC including 3 core PVC insulated wire and PVC pipe for drainage complete as reqd at site. |
18 | Installation, testing and commissioning of 1.5/2 TR capacity STAC units complete with 4 No. brass heavy duty flair nut, includingP/F of suitable size of copper pipe up to 6 Mtr. length duly insulated with foam insulation in surface/recess in wall and covering with PVC channel of 4”x2” size or ½” dia PVC flexible pipe (whereas is required), P/F regid PVC pipe heavy duty 25 mm. dia complete with all accessories such as elbow, nipple, socket etc: Supplying, connection, interconnection with 3 Core PVC insulated and PVC sheathed copper conductor flexible wire of size 80/0.20 mm. dia (NS) with plug top (wherever is required), etc. as required at site of work. |
19 | Fabricating, supplying of seasoned teak wood frame made out of 2”x3” / 1.5”x4” (NS) teak wood, suitable for 1.5/2 TR capacity window type AC the work including making modification on frame with same material (teak wood) to suit the AC (the frame should be duly varnished) including providing 6 mm. thick ply wood and painted with enameled paint to suit the wall color around AC and providing packing to prevent the heat leakage from inside and outside the room including making connection of AC installation, testing and commissioning etc. as required. |
20 | Rewinding of blower motors of STAC units including dismantling from the machine, cutting the burnt copper wire, rewinding with suitable size of copper wire, varnishing, baking, testing includingreplacement of suitable ball bearing / GM bushes, shaft and re-installation etc. as required. |
21 | Replacement of old burnt unserviceable condenser fan motor with new condenser fan motor for ACs and Water Coolers. (old burnt motor retained by Contractor) |
22 | During preventive maintenance of Acs, Water Cooler & Fridges checking all electrical connection of Gas pressure , Leakage, Cleaning of filter, Water Leakage etc as required during the contract in the cases list of machine with location in attached. a.)Acs, Water Coolers and Fridges ( 609+185+79)=873 (1 job) |