Tender For Augmentation Of Electric Infrastructure At 14P And Su And Provision Of 50Kva Servo Stabilizer At Dcn Under Af Station Bamrauli, bamrauli-Uttar Pradesh

Military Engineer Services-MES has published Tender For Augmentation Of Electric Infrastructure At 14P And Su And Provision Of 50Kva Servo Stabilizer At Dcn Under Af Station Bamrauli. Submission Date for this Tender is 22-05-2024. Electrification Work Tenders in bamrauli Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

43274114
Corrigendum : Tender For Augmentation Of Electric Infrastructure At 14P And Su And Provision Of 50Kva Servo Stabilizer At Dcn Under Af Station Bamrauli
Open Tender
Indian
Uttar Pradesh
bamrauli
22-05-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Augmentation Of Electric Infrastructure At 14P And Su And Provision Of 50Kva Servo Stabilizer At Dcn Under Af Station Bamrauli

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 04-May-2024 Revised BOQ BOQ 15-05-2024
2 15-May-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 22-05-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 83000.0 /-
Tender Value
INR 41.50 Lakhs /-

Attachment

FileName File Description File Size
3089753f-7801-4c9f-b458-44aa5cacf041.html Tender Notice 0 KB
87350TD2ndcall.rar Tender Document 0 KB
BOQ_729544.xls Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

NAME OF WORK: AUGMENTATION OF ELECTRIC INFRASTRUCTURE AT 14P & SU AND PROVISION OF 50KVA SERVO STABILIZER AT DCN UNDER AF STATION BAMRAULI
Sl. No. Item Description
1Supply, installation, testing and commissioning of transformer suitable for 100 KVA step down floor mounted outdoor type 11/.433, 3 phase, 50 Hz AC, IS: 1180-2014 ISI marked BEE LEVEL-2, double wound core type copper wound, oil immersed, air naturally cooled with external cooling tubes, transformer delta connection on HV side and star connected on LV side in accordance with vector symbol Dyn-11 (vector group 4) with neutral brought out on LV side with for earthing and having tapping on HV side for constant out put so as to alter/vary secondary voltage by(Tapping range + 5 %to - 10% in equal step of 2.5 % ) changed by means of manualy operated " off load" taps changing gear. The voltage regulation shall be as per IS including first fill of transformer oil as per IS-335 and including all fittings/accessories as specified in SSR Part-I and IS-2026. The limit of temprature rise after continuousfull load run as specified in IS-2026 shall be suitably adjusted to suite the maximum ambient temprature of 55 degree centigrade as prevalent at Bamrauli.The transformer shall be complete with the following fittings and accessories :-
2(a) Oil conservator tank with fillings holes and cap filter type drain valve and oil level gauge. (b) Silicagel breather with connecting pipe, first fill of dehydrating agent. (c) Explosion relief mounted on tank with double diaphram and equalizer pipe connected to conservator air tank (pressure release valve) (d) Air release valve plug (e) One cable box on LV side (Secondary)Consisting of 04 Nos porcelain bushing with nuts, washers & bushing rods with 01 cable gland suitable for reception of taking out suitable size cable, including gland joint. (f) Explosive vent (g) 01 No 100 mm dial type thermometer vapour pressure type having range 0-120 degree centigrade with max temp indicator and resetting device incl max reading pointer washer etc. (h) Thermometer pocket on tank cover (j) 04 Nos plain solid CI detachable rollers (k) Two nos Earthing terminals marking plate.
3(l) Rating plate and terminal marking plate. (m) Extra bushing for neutral outside the cable box brought out on LV side. (n) First filling of oil conforming to IS and tested upto 60 KV dielectric strenght. (o) Lifting lugs (p) Oil drain valve with plug
4(q) One cable box on HV side (Primary) consisting of 01 cable gland suitable for reception of taking in HT cable including gland joints. (r ) Hand hole of sufficient size to assess interior of tank (s) Dehydrating breather with first filling of Dehydrating agent (t) Two earthing ofterminal on tank body to facilitate fixing of 32x6mm GI strip. (u) Rating plate with terminal marking plate (v) Inspection cover. (w) Extra bushing for neutral out side the LV side (x)PCC plateformshall be provided as per drg No CEAF/TD/EM/03, complete all as specified including XPM welded mesh fencing and doors including 75 x 40 mm channel. Note:- (i) Anything missed above but is required for efficient functioning of transformer is deemed to be included in the quoted rate (ii) Full load testing shall be done at site. The artificial load shall be arranged by contractor. This is included in above quoted rate.
5Supply, Install, Testing & commissioning ofServo Voltage stabilizer conforming to IS 9815, Part 1: 2004 (2nd revision) three phase, naturally oil cooled, out door operation & designed for automatic operation on unbalanced voltage and unbalanced load, input vairation between 380 V-480v (3 phase) with 3 phase output voltage stabilized at 415V +/-1 % (adjustable) , speed of correction 10V/sec min, efficiency not less than 95%, response time less than 10ms, suitable for ambient working temperature 0-50 degree celsius, relative humidity 90%, of capacity 50 KVA complete all as directed and specified along with the following features.
6(i) Regulator for sensing circuit to maintain constant output voltage even on DG set (ii) Min metering should be digital VIF meter for input and output voltage, out put current and frequency (iii) Protection : high/low voltage cut-off, singlephasing cut off, single phase sequence change cut off, over temperature cut off, spike/surge protection (iv)Surge protection device 8/20 micro sec as per IEC-61000-4-4/61000-4-5 (v) stabilizer by pass switch, Out put voltageprotection, Adujustable output under and over volt, Auto - manual switch
7Supply, installation, testing & commissioning of HT 11 KV, 3 Phase, 50 HZ, indoor type, totally enclosed / metal clad switch gear complete with three vaccum circuit beaker (VCB) panel with one incoming and two outgoing having rupturing capacity of 350 MVA of rating 630 Amp, overload, earth fault and shortcircuit protection,Voltmeter range (0-15 KV) and Ammeter (0-500 Amp), required battery bank with charging arrangement including additional adopter panel for fixing with the exisitng VCB complete of following specifications mentioned inIS/IEC 62271-201 incl latest amendments / additions (a)Motorised spring charging mechanism with 24 volt DC universal motor 200 watts and having charging time less than 10 seconds. (b) Earthing switch rated for full making capacity with provisin for safe & reliable position indicator. (c)(i)Assembly of Vaccum ciruit breaker shall be completely insulated as per the relevants IS/IEC. (ii)The rating of VCB shall be 11 KV, 630 Amps, 21 KA (for 3 sec), 50 Hz, 3 phase (iii)The vacuum interrupture bottle shall be of the same make of VCB.
8(iv)Electrically charged and electrically operated independent closing / tripping, trip free, operating mechanism including mannual closing / tripping push button and breaker close / open ption shall be provided. Make: ABB/Siemens/Schneider v) One bus Bar Chamber including a set of 3 phase 1000 Amps copper bus Bars to be provided for further extension in future, if necessary. vi) Strip Heaters with thermostat to be provided with the following specifications :- Power input 80 watts with Voltage rating 230 volts AC Single phase vii) Incomer :- Dual core dual ratio Current Transformer (CT) chamber comprising of 3 Nos, single phase resin cast / ring core CTs of 200-100 / 5+5, burden not less than 15 VA and accuracy class 0.5, for metering, having class SP10 for protection as per IS:2705 for each circuit breaker - 01 Sets. viii) Outgoing No-1 & 2 :- Current Transformer (CT) chamber comprising of 3 Nos, single phase resin cast / ring core CTs of 75-100 / 5+5, burden not less than 15 VA and accuracy class 1.0 for metering, having class SP10 for protection as per IS:2705 for each circuit breaker - 02 Sets.
9ix) 1 No. Potential Transformer (PT), 3 phase, dry type (resin cast) fixed type 11 KV / 110 Volts, Burden 100 VA, Accuracy class 0.5 with HT & LT HRC fuses /MCBfor primary and secondarycomplete all as specified and as directed as per IS: 3156 - 01 Set x) Incoming breakers :- SCADA compatibleself powered IDMT numerical relays L&T, over current & earth fault relay with high adjustablesetting, short circuit fault relayfor complete protection of HT ,11 KV,3 Phase feeder having facility to record fault current with MODBUS communication on RS 485 communication port - 01 No. including 1 No voltage monitoring relay for under voltage / over voltage protection.
10xi) Outgoing breakers :- SCADA compatibleself powered IDMT numerical relays L&T, over current & earth fault relay with high adjustablesetting, short circuit fault relayfor complete protection of HT ,11 KV,3 Phase feeder having facility to record fault current with MODBUS communicationon RS 485 communication port - 01 No. including 1 No voltage monitoring relay for under voltage / over voltage protection. xii) Digital SCADA compatible meter of accuracy class 1, as per IEC 62052-11 / IEC 62053-22 monitoring all electrical parameters likevoltage & current per phase and Watts, VA, VAR etc. Also to monitor all instanteneous integrated demand,parameters, neutral current, frequency,power factor, % load, % unbalance (V&I), phase angle, THD working on MODBUS protocol. xiii) One set of mechanical indicatior for ON / OFF indication for all LBS / VCB breaker. xiv) One set of capacitive voltage indication for R-Y-B xv) One set of battery and battery charger to provide suitable back up as per OEM"s instruction
11Note :- 1. Any auxillary fitting/fitments for protection and functioning shall be provided as per the relevant IS. 2.The contractor shall submit GA drawingsand techinical specifications of VCB to GE for his approvalbefore placing order.
12Fabrication, supply, installation, testing and commissioning in replacement CPRI approved electrical cubical control panel boardof size 900mm X 600mm X 450mm, factory assembled made outdoor type feeder pillar box double door type wheather and vermin proof fabricated of 3.15 mm CRCA MS Sheet of suitable size, 3 phase 4 wire 415 V AC 50Hz complete duly painted with powder coating complete with locking arrangement, earthing termimal with suitable rating copper strips for incoming/outgoing MCCB"s including and mounting measuring instrument such as Volt meter, Ammeter, selector switch, CTs phase indicator lamp with holder, toggle switches and backelite fuse cut outs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 90 cm long angle iron size 50x50x6mm welded on all four corner embedded in PCC (1:2:4) using 20mm graded upto 30cm complete all as specified and directed by the Engr-in-Charge (Feeder piller box shall be consisting the following:-
13(a) High conductivity aluminium busbar (Set of 4 strips), 4 Nos TPN of suitable for 400 Amps rating ,(RYB) for phase and 1 No for neutral mounted on DMC support with heat shrink sleeve-1 Set. (b) Phase indication lamp, LED type(set of 3) -1 Set (c) Ammeter digital type having measuring range (0-500) Amps with CTs etc including rotary switchto measureload of each phase. (d)Volt meter having measuring range (0-500) volt with rotary switch to measure voltage of phase LED R.Y.B. (e) Grouting of panel including earth work as required PCC (1:3:6) type D-2 using 20 mm gradeded stone & plastering with (1:4 )cement sandetc complete.
14(f)INCOMMING: MCCB 4 Pole 250 Amp 415 volt thermaladjustable ,type with 36 KA breaking capacity & spreader both side as Incomming cotrol device :01 Nos. (g) OUTGOING: MCCB 4 Pole 125 Amp 415 voltthermal adjustable ,type with 16 KA breaking capacity & spreader both side as outgoin cotrol device :02 Nos. (h)MCCB 4 Pole 63 Amp 415 voltthermal adjustable ,type with 16 KA breaking capacity & spreader both side as outgoin cotrol device :02 Nos. (i) ON load change over switch 415 Volt, 4 pole of capacity 100 Amp.=01 Nos
15Supply, Laying, Jointing and Testing of HT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts Earthed, grade cross sectional area 95 Sqmm 3 core laid in trenches/ducts/along poles/ through pipe under road etc complete all as specified and directed by Engr-in-Charge. Note :- (i) Excavation, earthwork, cable protection cover, cable joint, sand cushioning shall be measured and paid for separately under respective item of this schedule.
16Supply, Laying, Jointing and Testing of LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core laid in trenches/ducts/along poles/ through pipe under road etc complete all as specified and directed by Engr-in-Charge. Note :- (i) Excavation, earthwork, cable protection cover, cable joint, sand cushioning shall be measured and paid for separately under respective item of this schedule.
17Supply , Laying, Jointing and Testing of LT cable XLPE insulated ,screened PVC bedded , galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 Sqmm 3.5 Core laid in trenches/ducts/along poles/ through pipe under road etc complete all as specified and directed by Engr-in-Charge. Note :- (i) Excavation, earthwork, cable protection cover, cable joint, sand cushioning shall be measured and paid for separately under respective item of this schedule.
18Supply, Laying, Jointing and Testing of LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core laid in trenches/ducts/along poles/ through pipe under road etc complete all as specified and directed by Engr-in-Charge. Note :- (i) Excavation, earthwork, cable protection cover, cable joint, sand cushioning shall be measured and paid for separately under respective item of this schedule.
19Supply, Laying, Jointing and Testing of LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core laid in trenches/ducts/along poles/ through pipe under road etc complete all as specified and directed by Engr-in-Charge. Note :- (i) Excavation, earthwork, cable protection cover, cable joint, sand cushioning shall be measured and paid for separately under respective item of this schedule.
20Supply , laying, jointing and testing of LT cable XLPE insulated ,screened PVC bedded , galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sqmm4 Core laid in trenches/ducts/along poles/ through pipe under road etc complete all as specified and directed by Engr-in-Charge Note :- (i) Excavation, earthwork, cable protection cover, cable joint, sand cushioning shall be measured and paid for separately under respective item of this schedule.
21Supply, Laying, Jointing and Testing of LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 3.5 core laid in trenches/ducts/along poles/ through pipe under road etc complete all as specified and directed by Engr-in-Charge. Note :- (i) Excavation, earthwork, cable protection cover, cable joint, sand cushioning shall be measured and paid for separately under respective item of this schedule.
22Supply , laying, jointing and testing of LT cable XLPE insulated ,screened PVC bedded , galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 Sqmm 4 Core laid in trenches/ducts/along poles/ through pipe under road etc complete all as specified and directed by Engr-in-Charge. Note :- (i) Excavation, earthwork, cable protection cover, cable joint, sand cushioning shall be measured and paid for separately under respective item of this schedule.
23Supply, Laying, Jointing and Testing of LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core laid in trenches/ ducts/along poles / through pipe under road etc complete all as specified and directed by Engr-in-Charge. Note :- (i) Excavation, earthwork, cable protection cover, cable joint, sand cushioning shall be measured and paid for separately under respective item of this schedule.
24Supply, Jointingand testing of cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 70 to 95 sqmm,Indoor /Outdoor type complete all as specified and directed by Engr-in-Charge.
25Taking down carefully aluminium battenpoint, wiring for light/fan/socket/bell or power point including. All fittings i.e. switch, sockets, ceiling rose, regulators, batten holders, etc. Complete and making good disturbed surfaces of wall/floor to match with the surroundings of wall/ceiling/floor etc including taking down old light fittings. Note :- (i)Contractors quoted rate of this item deemed inclusive of unscrewing of the serviceable fittings and fixture as directed and deposit in MES store yard. (ii)Quoted rate also deem to be included cost of cutting chases for taking out concealed conduit and nitch for terminal box. (iii)Decision of GE shall be final and binding in respect of serviceability of fittings/fixture.
26M & L for Point wiring complete with 1.5 sqmm single core PVC insulated FRLSH cable 1100 volts grade with multi stranded copper conductor drawn through new PVC concealed conduit mediem grade, ISI markedand including provision of 1.5 sqmm PVC insulated copper cable FRLSH as earth continuty, fabricated branded modular metal flush box duly make embossed, concealed in walls with suitable modular inner and outer plate for housing switches , socket outlet and fan regulators etc, complete all as specified and as directed for the followings:-
27One light/fan/bellpoint controlled by one switch single pole one way
28one3 pin 6 amp switch socket out let independent .
29one 3 pin 6 amps socket outlet on the same board with other switch complete .
30M & L for Point wiring complete with 4.0 sqmm single core PVC insulated FRLSH cable 1100 volts grade with multi stranded copper conductor drawn through new PVC concealed conduit mediem grade, ISI markedand including provision of 4.0 sqmm PVC insulated copper cable FRLSH as earth continuty, fabricated branded modular metal flush box duly make embossed, concealed in walls with suitable modular inner and outer plate for housing switches , socket outlet and fan regulators etc,for for one 16 Amp switch socket outlet on independent board complete all as specified and as directed.
31Supply and fixing switch modular flush 6A single pole one way ISI marked complete all as specified and directed.
32Supply and fixing modular sockets 6 Amp 2 in 1 2/3 pin combined complete all as specified and directed.
33Supply and fixing switch modular flush type 15/16 Amp single pole one way 240 volt one module ISI marked complete all as specified and directed.
34Supply and fixing modular sockets 16Amp 2 in 1 3/5pin combined complete all as specified and directed.
35Supply and fixing Modular bell push flush type 5 Amps single pole 230 Volt white white finish complete all as specified and directed.
36Supply and fixing ceiling rose surface bakelite 60x25mm three terminal complete all as specified and directed.
37Supply and fixing electronic step type fan regulator 240 volt 50 Htz 120 watt (switch/sockets type in shape) modular type complete all as specified and directed.
38Supply and fixing in replacement white cover plate with frame one module for modular switchesand sockets complete all as specified and directed.
39Supply and fixing in replacement white cover plate with frame two module for modular switchesand sockets complete all as specified and directed.
40Supply and fixing in replacement white cover plate with frame three module for modular switchesand sockets complete all as specified and directed.
41Supply and fixing in replacement white cover plate with frame four module for modular switchesand sockets complete all as specified and directed.
42Supply and fixing in replacement white cover plate with frame six module for modular switchesand sockets complete all as specified and directed.
43Supply and fixing in replacement white cover plate with frame eight module for modular switchesand sockets complete all as specified and directed.
44Supply and fixing in replacement white cover plate with frame twelvemodule for modular switchesand sockets complete all as specified and directed.
45Supply and fixing in replacement white cover plate with frame sixteen module for modular switchesand sockets complete all as specified and directed.
46Supply and fixingin replacement metal flush box one module 1.6 mm for mounting modular switches and sockets complete all as specified and directed.
47Supply and fixingin replacement metal flush box two module 1.6 mm for mounting modular switches and sockets complete all as specified and directed.
48Supply and fixing in replacementmetal flush box three module 1.6 mm for mounting modular switches and sockets complete all as specified and directed.
49Supply and fixing in replacement metal flush box four module 1.6 mm for mounting modular switches and sockets complete all as specified and directed.
50Supply and fixingin replacement metal flush box six module 1.6 mm for mounting modular switches and sockets complete all as specified and directed.
51Supply and fixingin replacement metal flush box eight module 1.6 mm for mounting modular switches and sockets complete all as specified and directed.
52Supply and fixingin replacement metal flush box twelve module 1.6 mm for mounting modular switches and sockets complete all as specified and directed.
53Supply and fixingin replacement metal flush box sixteen module 1.6 mm for mounting modular switches and sockets complete all as specified and directed.
54Supply and fixing in replacement of Distribution boardMCB SPN 8 way, double door, IP-43, IK-09, Isolated Neutral Bar and fixed flush to wall and suitable for universal mounting completeall as specified and directed.
55Supply and fixing in replacement of Distribution boardMCB SPN 4 way, double door, IP-43, IK-09, Isolated Neutral Bar and fixed flush to wall and suitable for universal mounting complete all as specified and directed.
56Supply and fixing in replacement of MCB, single pole and neutral, 230 volts, 40 to 63 Amp rating, "C" series fixed in DBs catered here-in-before.
57Supply and fixing in replacement of MCB SP 6-32 Amps 240 volts 10 KA 50 HZ "C" curve complete all as specified and directed by Engineer in charge
58Supply and fixing calling bell AC buzzer complete all as specified and directed.
59Supply and fixing down rod for ceiling fan made out of galvanized iron pipe of size 15mm dia medium grade(ISI marked) of length 1.20 metre including threading, cutting, slotting, drilling including nut, bolt, clip, washer and rubber real complete all as specified and directed.
60Sub main wiring with 2 run of single core PVC insulated and PVC Unsheathed, multistranded copper condutor of nominal area 4 sqmm FRLSH, 1100 Volts gradecable drawn into and including rigid non metalic PVC Conduit of including all fittings and one run of PVC insulated and PVC unsheathed, multistranded copper conductor of nominal area 4 sqmm FRLSH 1100 volts grade cable continuous earth wire of green colour code complete including old taking down submain wiringallas specified and directed. Note:- (a) Two runs of4 sqmm cable and one run of 4 Sqmm cable as earth leadwith conduit shall be measured as one unit length for payment. (b) Quoted rate shall deem to be included cost of cutting chasses in wall for concealling conduit and making good to match with existing finish.
61Sub main wiring with 2 run of single core PVC insulated and PVC Unsheathed, multistranded copper condutor of nominal area 6 sqmm FRLSH, 1100 Volts gradecable drawn into and including rigid non metalic PVC Conduit of including all fittings and one run of PVC insulated and PVC unsheathed, multistranded copper conductor of nominal area 6 sqmm FRLSH 1100 volts grade cable continuous earth wire of green colour code complete including old taking down submain wiring allas specified and directed. Note:- (a) Two runs of6 sqmm cable and one run of 6 Sqmm cable as earth leadwith conduit shall be measured as one unit length for payment. (b) Quoted rate shall deem to be included cost of cutting chasses in wall for concealling conduit and making good to match with existing finish.
62Supply and fixing in replacement of sheet metal enclosure with socket and plug top and MCB single pole and neutral enclosure with two Pin and earth plug and socket complete with one single pole MCB, 240 V, 20 Amp completeallas specified and directed.
63Supply and fixingin replacement of LED lights fitting 1x 20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core 1.5sqmm flexible copper conductor cable of suitable size from ceiling rose completeallas specified and directed.
64Supply and fixing in replacement of LED Light fitting mirror type with high out put diffuser 2 feet ,10watt ,220 v AC decorative type with driver holder and LED lamp including connecting up with three core 1.50 sqmm flexible copper conductor cable of suitable size completeallas specified and directed.
65Supply and fixing in replacement of LED Light fitting 1x12 watt bulkhead luminaire including LED light driver holder connecting up with three core 1.50 sqmm flexible copper conductor cable of suitable size complete all as specified and directed.
66Supply and fixing in replacement of LED luminaire 600 mm x 600 mm, 40 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core 1.50sqmm flexible copper conductor cases of suitable size complete all as specified and directed.
67Supply and fixing in replacement of surface /recessed mounted, round/squareLEDdown light fittingwith die cast aluminium housing and system wattage of 15/18W,including connecting up with PVC sheathed 3 core 1.5 Sqmmcopper conductor flexible wire fixed completeall as specified and directed.
68Supply, fixing, connecting and testing in replacement of LED street light 35 watt 6000k/3000k new generation energy saving and environmental friendly long life led street light made up of pressure die cast aluminium housing with high efficient led as lighting source and PC cover having toP opening seperate driver compartment with IP66 protection and impact resistance of IK07 roadway luminaries with high power LED as light source and electronic driver complete with connection and accessories for fixing with with including grade 40mm dia GI pipe as bracket in appropriate length complete including taking down old light fitting complete all as specified and directed
69Supply and fixing in replacement bollard light9 watt with opal acrylic diffuser and IP-65 protection 240 volt 50 Htz including PCC work for foundation of 1:2:4 ratio complete function of light complete all as specified and directed
70Supply and fixingin replacement ceiling fansRobust and reliable inverter motor (brush less DC Motor) powered by ECM technology, BEE 5star rating for energy saving,AC single phase 230/240 V of size 1200 mm sweepincluding making connection with three core flexible, copper cable pvc insulated of suitable length incl taking down old & deposited to MES store yardcompleteallas specified and directed. Note : Cost of remote cell included in this item
71Supply and fixing wall mounted fan 400mm, 230 volts , 50 Hz 1420 RPM with 90 degree oscillation and having speed control by twopull cord system completeallas specified and directed.
72Supply and fixingingin replacement Ventilating Fan250mm sweep,non metallic resin body,single phase 240 volts AC 50 Hz including louvers,and copper cable 3 core of size 0.5 sqmm for connection from ceiling rose to fan complete all as specified and directed by Engineer-in-Charge. Note : Old material deposited to MES store Yard
73Supply and fixing exhaust fan, steel body AC single Phase. 230V of size 300m sweep heavy duty 1400 RPM with, blades, and frame and louvers complete with all accessories for hang and connecting with 3 run of 1.5 sqm, multicore, PVC insulated copper cable from ceiling rosecompleteallas specified and directed.
74Taking down carefully from existing place ceiling fan and removing to MES store yard Scraping, cleaninggreasing/oiling and refixing at site complete incl electric connection withthree core flexible wire 1.5 Sqmm and writing MES No completeallas specified and directed.
75Cutting the existing wall/removing existing steel bar to make a hole as per standerd size shape for fixing of ventilation/exhaust fan through packing of wooden ply to support the ventilating/ air circulating fan including necessary nut and bolts of suitable size incl making good of disturbed surface complete all as directed by Engr-in charge.
76Supply and fixing factory made epoxy powder coated Load line Distribution Board TPN-4 ways with metal door (IP-43 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including insulated 200 Amp copper bus bar, Isolated neutral bar, standard DIN rail, Earth bar and cable ties for cable management, top and bottom removeable gland plates with knockouts and suitable for one TPN- MCCB any capacity as incomer and 6 to 63 Amp SP MCBs outgoing and conforming to IS : 8623. complete all as specified & directed.
77Supply and fixing of MCCB 160 Amps, FP 415 volts 16 KA 50 HZ with thermal magnetic setting complete all as specified and directed by Engineer in charge.
78Material and labour for dismantling, shifting and refixing of split type Air Conditioner (Indoor and Outdoor units) of any make and any type after servicing and charging of gas (M410a/R134a/R-22/r32) by testing the leakage in system by filling of Nitrogen gas upto 300 PSIG and repairing of leaking spot/joints with gas welding work, cleaning and flushing out the complete system with gas, supply and replacing of drier/filter, making the complete system leak proof, vacuuming the systemas existing and testing etc complete all as specified & directed. Note :Quoted rate shall be deemed to include following :- (a)Drier capillary, copper tubing, refrigernt gas, Insulation and LDPE pipe. (b)Making hole and filling the hole on wall with PCC (1:2:4) type B0 (Using 12.5mm graded stone aggregade, 15mm thick rendereing in cement mortar (1:3) and makinggood the disturbed surface with existingschedule of finishes.
79Rigid non-metallic PVC conduit exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc.
80Supply and fixing in replacement 1.5 Sqmm FRLSH PVC insulated stranded copper conductor cable 1100 volts grade all as specified and directed.
81Supply and fixing in replacement 2.5 Sqmm FRLSH PVC insulated stranded copper conductor cable 1100 volts grade all as specified and directed.
82Supply and fixing in replacement 6.0 Sqmm FRLSH PVC insulated stranded copper conductor cable 1100 volts grade all as specified and directed.
83Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire complete all as specified and directed
84M & L for earthing complete with copper electrode plate electrode 600mm x 600mm x 3.15mm thick buried directly in ground (earth pit not less than 2.25 Mts deep below ground level with top edge of the plate not less than 1.50 Mtrs below ground level connected to glavanised copper strip of size 20mm x 3mm by means of bolts, nuts check nuts and washers of galvanised iron or steelconnected to earthing test point all as specified incl 40 mm GI tubing medium grade and necessary fitting for protection of GI wire incl laying of charcoal dust and common salt in alternate layer, PCC Pit (1:3:6) type C-1 using 20 mm graded stone aggregate, RCC cover 40mm thick (1:2:4) type B-0 using 12.5mm graded stone aggregate reinforced with 6 mm dia round bar @ 75mm C/C both ways with MS handle 8mm dia, plastering 15mm thick CM (1:6) externally upto 150mm below ground level , GI funnel with 20mm dia medium grade GI pipe for watering and wire mesh incl excavation and earth work and disposal of surplus soil complete all as specified and shown on electrical plate No 3 of SSR Part (2009) and connected to earth test point incl testing and marking Bldg Nos / Name of Equipments and writing Test Results on a 3.0mm thick painted M.S. earth pit marking Plate (200mm x 200mm) duly welded with a 450mm long 10mm dia round M.S. rod, fixed with the earth pit chamber by grouting complete all as specified and directed.
85Earthing complete with galvanised steel earth plate electrode 60cm x 60 cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron wire 4mm dia asearth lead wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in Electrical plate No. 3, MES SSR Part I- 2009 with 15 mm dia medium grade GI pipe as a protection to earthing lead and 20 mm dia medium grade GI pipe for watering purpose including excavation & earth work in any type of soil, funnel, wire mesh, RCC pit with cover, cast iron frame complete and connected to earthing test point all as specified or indicated including testing on completion. Notes(i)The concrete pit shall be PCC (1:3:6) type C-1, 40mm thick precast cover slab of RCC with suitable Mild steel handle in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I (ii) PCC pit shall be provide at least 500 mm away from the earth pit and not on just on the eath pit and extra cost of additional length of water pipes and fittings junction etc shall be deemed to be included in the rate. (iii) Item includes the cost of 7.5 metre earth lead wire andGI pipe for protection of earth wire. Any varriation in quantity shall be adjusted.
86M & L for earthing complete with galvanised steel plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mts deep below ground level with top edge of the plate not less than 1.50 Mtrs below ground level connected to glavanised MS strip of size32mm x 6mm by means of bolts, nuts check nuts and washers of galvanised iron or steelconnected to earthing test point all as specified incl 40 mm GI tubing medium grade and necessary fitting for protection of GI wire incl laying of charcoal dust and common salt in alternate layer, PCC Pit (1:3:6) type C-1 using 20 mm graded stone aggregate, RCC cover 40mm thick (1:2:4) type B-0 using 12.5mm graded stone aggregate reinforced with 6 mm dia round bar @ 75mm C/C both ways with MS handle 8mm dia, plastering 15mm thick CM (1:6) externally upto 150mm below ground level , GI funnel with 20mm dia medium grade GI pipe for watering and wire mesh incl excavation and earth work and disposal of surplus soil complete all as specified and shown on electrical plate No 3 of SSR Part (2009) and connected to earth test point incl testing and marking Bldg Nos / Name of Equipments and writing Test Results on a 3.0mm thick painted M.S. earth pit marking Plate (200mm x 200mm) duly welded with a 450mm long 10mm dia round M.S. rod, fixed with the earth pit chamber by grouting complete all as specified and directed.
87Surface excavation not exc 30 cm deep and averaging 15 cm deep and getting out in soft/loose of soil complete all as specified and directed
88Excavation not exceeding 1.5 m deep and getting out soft and dense soil as per specifications and drawingcomplete all as specified and directed
89Excavation in trenches in soft/loose soil n. exc 1.5 Mtr wide and not exc. 1.5 M deep and getting out including forming bottom surface for laying of pipes complete all as specified and directed.
90Returning filling in including spreading leveling watering and well ramming in layer not exceding 25 cm as in soil all as specified and dirceted all as specified and directed
91Removal of excavated material to a distance not exc 50 Meter and depositing wheredirected at a level not exc 1.5 M above the starting point complete all as specified and directed.
92Supply, laying and cushioning for cable protection in trenches 8 cm deep before laying cable and 15 cm deep over the cable including well punning complete all as specified and dierected
93Supply and laying sub class "B" bricks old size with axis of the bricks perpendicularto the axis of the cable as in cable protection complete all as specified and directed.
94Supply and laying reinforced precast concrete cable cover, class EHV, type 1 with peak, size 450mm x 230mm x 50mm for cable protection all as specified and directed
95Supply andLaying in trenches for road/plinth and fixing alongwith pole/wall GI Tube 40 mm light grade for protection of cable complete all as specified and directed
96Supply andLaying 80mm dia GI Pipe light grade in trenches for road/plinth and fixing alongwith pole/ wall for protection of cable complete all as specified and directed
97M & L for boring holes (manually) under road, hard standing without damaging surface for 80/50/40 mm dia GI pipe etc complete all as specified and directed
98M & L PCC 1:4:8 type D-2 using 12.5mm graded stone aggregate cement concrete as in foundations, filling and mass concrete complete all as specified and directed
99M & L for PCC 1:3:6 type C-0 using 12.5 mm granted stone aggregate asin hold fast/filling in pressed steel frame complete all as specified and directed.
100M & L 50 mm thick PCC 1:2:4 type B1 using 20 mm granted stone aggregate as in plinth protection complete all as specified and directed
101Hardcore of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface complete all as specified and directed
102Mild steel TMT bars 10mm dia and over, cut to length, bent to shape required, includingcranking, bending spirally for hooping for columns, hooking ends and bindingwith and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed
103Ditto above item , but TMT bar 6mm to 8mm dia complete all as specified and directed
104M & L RCC nominal mix foundations, type B1 (1:2:4) using 20mm graded stone aggregate as in rafts, footings, foundation beams; plinth beams; bases forcolumns, etc.; basement slabs, under-reamed piles and mass concrete complete all as specified and directed
105M &L RCC nominal mix foundations, type B1 (1:2:4) using 20mm graded stone aggregate as in Columns, pillars, piers, posts and struts complete all as specified and directed
106M&L RCC nominal mix foundations, type B1 (1:2:4) using 20mm graded stone aggregate as in Slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like complete all as specified and directed
107M & L RCC nominal mix foundations, type B1 (1:2:4) using 20mm graded stone aggregate as in Beams, cantilevers, bressummers, lintels over 1.5m span complete all as specified and directed
108Formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batter complete all as specified and directed
109Formwork to sides of pillars posts, struts, piers, columns and stanchions complete all as specified and directed
110M & L Formwork to sides and soffits of floor or roof beams, beam haunch ings, girders, bressummers, lintels, cantilevers, shelves including sup- ports, overhangs, etc. also splays between floors and beams, etc complete all as specified and directed.
111M & L Formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work; not exceeding 200mm thick (Horizontal or sloping) complete all as specified and directed
112M & L Formwork to edges of concrete flats, breaks in floors, openings in concrete walls, floors and roofs and sides of RCC/PCC bands in walls, horizontal or sloping, and similar work all exceeding 20cm wide complete all as specified and directed
113M & L for brickwork with sub class "B" bricks, straightor curved on plan exc 6m mean radius built in CM 1:6, complete all as specified and directed.
114M & L for 15mm thick rendering on faces of brick work or concrete surfaces finished even and smooth without using extra cement in CM 1:4, complete all as specified and directed
115M & L for 15mm thick rendering in CM 1:6 on fair faces of brick work, surfaces finished even and fair without using extra cement complete all as specified and directed
116M & L for 5mm thick renderingin CM 1:3 finish even and smooth without using extra cement in ceiling complete allspecified and directed.
117M & L preparation of new plastered ceiling surface and applying three coat of white wash of ceiling complete all as specified and directed.
118M & L preparation of new plastered wall surface and applying three coat of white wash of wall complete all as specified and directed.
119M & L preparation of new plastered surface cement base paint two coatfor new plaster surface over one coat primer of wall complete all as specified and directed.
120S & F of Steel ventilator with top hung shutter including hinges, steel peg stay etc as shown in TD Drg s include for painting with one shop coat of zinc chromate primer complete all as specified and directed
121M & L Framed work such as grills, gratings, etc.. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work con- forming to Fe.290.Gde-E-165 complete all as specified and directed
122Preparation of new surfaces of steel of any description over 10cm grith or width, not otherwise described withtwo coats of synthetic enamel paint over one coat of red oxide complete all as specified and directed
123Galvanised mild steel wire cloth, 0.56mm nominal dia of wire and average width ofaperture 1.18mm and fixed with tinned tacks, or galvanised wire staples complete all as specified and directed
124M & L Machine cut Kota stone 550X550 slab flooring 16 - 18 mm thick over cement screed base laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing, screed bed or bedding layer of mortar 20 mm thick for laying floor finished in CM 1:4 and jointed complete all as specified and directed.
125M & L Machine Kota stone slab 16-18mm thick in riser of steps, skirting, dado and pillar laid over cement screed screed bed laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing, screed bed or bedding layer of mortar 20 mm thick for laying floor finished in CM 1:4 and jointed complete all as specified and directed.
126M & L for coloured machine pressed precast concrete interlocking paver block any shape and size confirming to IS 15658-2006 of 80 mm thickness M-40 grade laid over including 30mm thick sand cushioning including filling of joints with sand complete all as specified and directed.
127M & L for pressed steel frames for doors with one or more rebates includinguding necessary fixing lugs, hinges, lock strike plate etc complete of size 125mm x 60mm complete all as specified and directed.
128S & F of Flush shutters 30mm thick, solid core construction, with block board core & plywood face panels, commercial type on both sides complete all as specified and directed.
129Preparation of new painted surfaces of wood and wood based materials of any description over 10 cm width or girthnot otherwise described and applying one coat of synthetic enammel paint complete all as specified and directed
130S & F of Aluminium anodised barrel tower bolts of extruded section of length of bolt 200mm complete all as specified and directed
131Supply & Fixing butt hinges, extruded aluminium alloy with galvanised mild steel hinge pin, anodised and fixed, type B-21 of size 100mm complete all as specified and directed
132S & F Aluminium handles, cast type, anodised of size 100mm complete all as specified and directed
133S & F Aluminium alloy, anodised, sliding door bolts with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts and sliding bolts of extruded sections or cast aluminium alloy and fixed of length of bolt 300mm complete all as specified and directed