Tender For Repair Maintenance Of Lt Oh And Ug Network Of Haig Line And 01 Mw Solar Power Plant Under Ge Utility Ambala Cantt, ambala-Haryana

Military Engineer Services-MES has published Tender For Repair Maintenance Of Lt Oh And Ug Network Of Haig Line And 01 Mw Solar Power Plant Under Ge Utility Ambala Cantt. Submission Date for this Tender is 30-05-2024. Electrification Work Tenders in ambala Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

43273851
Corrigendum : Tender For Repair Maintenance Of Lt Oh And Ug Network Of Haig Line And 01 Mw Solar Power Plant Under Ge Utility Ambala Cantt
Open Tender
Indian
Haryana
ambala
30-05-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Tender For Repair Maintenance Of Lt Oh And Ug Network Of Haig Line And 01 Mw Solar Power Plant Under Ge Utility Ambala Cantt

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 23-May-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 30-05-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 96000.0 /-
Tender Value
INR 48 Lakhs /-

Attachment

FileName File Description File Size
8c840b3a-fb63-4dc0-9cc1-c13585cc2310.html Tender Notice 0 KB
BOQ_729572.xls Tender Document 0 KB
Tender.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

Name of Work : Repair/ Maint of LT OH & UG Network of Haig Line and 01 MW Solar Power Plant underGE (U) Ambala Cantt.
Sl. No. Item Description
1Supply and fix in replacement of solar photo voltaic modules panel 335watt, rated voltage 36.4 V, rated current 8.94 Amp, crystalline silicon PV moduleswith spare/parts required for smooth functioning, tightenining of electric connection complete and assembling and reconnecting all as per site requirmentcomplete all as specified & directed.
2Supply and fix in replacement of Copper strip 20x3 mm from earth electrode to test point complete all as specified and directed.
3Supply and fix in replacement of GI earth strip 25x4 mm from earth electrode to test point complete all as specified and directed.
4Material & Labour for Servicing and Cleaning of On grid inverter outdoor type, IP-65 protection, 60 KW capacity, AC nominal rating (array to inverter ratio 1:1), 3 P, 50 HZ,including making fresh connection as per existing complete all as per site requirment complete all as specified & directed.. Make: ABB Model : Solar inverter Trio-TM-60.0-480.
5Material & Labourfor spraying herbicide (Round up) on area to remove unwanted vegitation/grass at various locations complete all as specified & directed. (03 times per year)
6Supply and fixing in replacement of Surge protection Device (SPD) DC 1000 Volt in DC Distribution box in Solar Inverter complete all as specified & directed.
7Supply and fixing in replacement of DC Fuse 15 Amp in Surge protection Device (SPD) DC 1000 Volt in DC Distribution box in Solar Inverter complete all as specified & directed.
8Supply and fixing in replacement of Surge protection Device (SPD) AC in AC Distribution box in Solar Inverter complete all as specified & directed.
9Supply and fixing in replacement of PVC insulated Solar DC cable 6 sqmm 1.8 KV DC volt for solar plant copper cable complete all as specified & directed.
10Supply and fixing Rotational moulded polyethelene water storage tank triple layer ISI marked capacity 1000 ltr (cylinderical vertical with closed top) hoisted and fixed in position including making connection with existing pipeline complete all as specified & directed..
11Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation, shafts, man holes,for under ground cable / erection of poles, stays, locatingfault of LT cable and stay assembly etc not exceeding 10 square metre on plan and getting out in any type of soil including dressing/trimming of sides and leveling, grading and ramming of bottom of excavation complete all as specified and directed.
12All as per Ser item No 11.00 here in before but depth exceeding 1.5 metre and not exceeding 3.0 metre complete all as specified & directed.
13Returning, filling in, in soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick each layer complete all as specified and directed.
14Removing excavated material/soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
15Material & Labour sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cmsdeep after laying the cable (punned down to 18 cms depth after laying and stretching of cable) complete all as specified and directed.
16Supply and lay bricks, common burnt clay, sub class "B", old size, laid in vertical direction to cable as cable protection complete all as specified and directed.
17All as per Ser Item No 16.00 here in before but except bricks, complete all as specified & directed. Note:- Old bricks retrieved from Ser Item No 22 here in after shall be re-used.
18Material & Labour PCC 1:4:8 type D-2 using 40mm graded aggregate, mechanically crushed stone for mass filling in polepit and foundation etc. complete all as specified and directed.
19Material & Labour for cement concrete as coping to poles, PCC type B1, 1:2:4 using 20 mm graded stone agregate as foundations to poles complete all as specified & directed.
20Material & Labour cement concrete (1:3:6) type C-1using 20mm graded crushed stone aggregate as in coping of pole and strut, stayaround the poleetc complete all as specified and directed.
21Disconnecting & taking out defective underground cable from trenches, pole, pipe, floor, wall etc and locate the fault, rectify the defect and relaying the XLPE cable underground PVC insulated and overall sheathed aluminum conductor heavy duty 1100 volts including connecting and testing for any size complete all as specified & directed. (Excavation/earth work & sand cushioning, bricksandjoint shall be measured & paid for separately).
22Disconnecting & taking out defective underground cable any size and any type from trenches, pole, pipe, floor, wall etc complete all as specified & directed.
23Supply, laying, connecting and testing XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 10 sqmm 4.0 core including Al thimbles laid in trenches/on pole/road crossing or passing through existing/new pipe under road crossing clamping on wall etc complete all as specified and directed. Note : (i) Earth work, sand, bricks removing, returning filling will be paid seperately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates (iii)All equiments, machinery or tool if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
24All as per item ser No 23 here in before but for 4 core 16 Sqmm complete all as specified & directed.
25All as per item ser No 23 here in before but for 3.5 core 25 Sqmm complete all as specified & directed.
26All as per item ser No 23 here in before but for 3.5 core 35 Sqmm complete all as specified & directed.
27All as per item ser No 23 here in before but for 3.5 core 50 Sqmm complete all as specified & directed.
28All as per item ser No 23 here in before but for 3.5 core 70 Sqmm complete all as specified & directed.
29All as per item ser No 23 here in before but for 3.5 core 95 Sqmm complete all as specified & directed.
30All as per item ser No 23 here in before but for 3.5 core120 Sqmm complete all as specified & directed.
31All as per item ser No 23 here in before but for 3.5 core150 Sqmm complete all as specified & directed.
32All as per item ser No 23 here in before but for 3.5 core185 Sqmm complete all as specified & directed.
33All as per item ser No 23 here in before but for 3.5 core 240 Sqmm complete all as specified & directed.
34All as per item ser No 23 here in before but for 400 Sqmm, single core complete all as specified & directed.
35Supplying and fixing in replacement of 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of size 10 sqmm 2 core complete all as specified and directed.
36Supply and fixing in replacement or passing through PVC conduit pipe of 1100 volts grade heavy duty, PVC insulated round 3 core 1.0 sqmm copper cable including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed.
37Supply and fixing in replacement or passing through PVC conduit pipe of 1100 volts grade heavy duty, PVC insulated round 3 core 2.5 sqmm copper cable including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed.
38Supply and fixing in replacement or passing through PVC conduit pipe of single core PVC unsheathed multi stranded copper cable (FRLS) 1.5 Sqmm nominal cross sectional area 1100 volts conforming to IS 694 including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed.
39Supply and fixing in replacement or passing through PVC conduit pipe of single core PVC unsheathed multi stranded copper cable (FRLS) 2.5 Sqmm nominal cross sectional area 1100 volts conforming to IS 694 including electrical connection suitable size of lugs, nuts and boltscomplete all as specified and directed.
40Supply and fixing in replacement of rigid non-metallic PVC conduit of dia 20 mm exclusive of boxes (Junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified & directed. Note: PVC pipe will be clamped at three position on pole and cost of clamp, nut, bolts etc are incl in quoted rates complete all as specified and directed.
41Supplying and fixing in replacement oflight gradegalvanised mild steel pipe 80mm bore with all fittings, laid under roads, drain, paths, fixed to poles/walls with suitablemild steel clamps, bolts, nuts and washers complete all as specified & directed. Note:- Excavation & earth work shall be measured and paidfor separately under appropriate item of this schedule.
42All as per Item No 41.00 here-in-before but of size 50 mm bore complete all as specified & directed.
43Dismantling and taking down security light, street light, hanger light, flood light and high mast lights of any type at any height fittings such asHPSV/HPMV/MH/LED light of 48 Watt/ 60 watt / 70/72 watt/ 90 watt/ 120 watt/ 150 watt/ 200 watt and 300 watt of any make etc. AC 230 volts any wattage from pole/wall roof top/hanger roof including washing/cleaning of perplex cover inspection for location of faultand replacing of defective speare/parts required for smooth functioning, tighting of electric connection complete and assembling and reconnecting all as per site requirment complete all as specified & directed. Note: Defective spare/ part of relevant light fitting shall be measured and paid separately under relevant item as supply only.
44Supply only LED electronic driver/adaptor/SPDfor40-48 watt LEDsecurity light fitting of existing makecomplete all as specified & directed.
45Supply only LED electronic driver/adaptor/SPDfor60 watt LEDsecurity light fitting of existingmakecomplete all as specified & directed.
46Supply only LED electronic driver/adaptor/SPDfor70/72 watt LEDsecurity light fitting of existing makecomplete all as specified & directed..
47Supply only LED electronic driver/adaptor/SPDfor90 watt LEDsecurity light fitting of existing makecomplete all as specified & directed.
48Supply only LED electronic driver/adaptor/SPDfor120 watt LEDsecurity light fitting of existing makecomplete all as specified & directed.
49Supply only LED electronic driver/adaptor/SPDfor60-150 watt LEDflood light fitting of existing makecomplete all as specified & directed.
50Supply only LED electronic driver/adaptor/SPDfor200-300 watt LEDflood light fitting of existing makecomplete all as specified & directed.
51Dismantling and taking down old unsv Prestressed Concrete LT pole and Supply, fix and erection of Prestressed Concrete pole 9.0 mtr long in true vertical position 102x172 mm at top 102x279 mm at bottom class-10 incl providing black and white strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr including 2 bands of radium tape of 2" width greeen & red colour above the coping of pole starting with black strip complete all as specified & directed.. Note (i) Earth work and PCC shall be measured and paid seperately (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
52Dismantling and taking down old unsv Steel tublar LT pole and Supply, fix anderection of steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts,nuts and screws as specified type 410 SP-31, 09 meter long, providing synthetic enamel aluminium paint over one coat of red oxide and black and white strips with synthetic enamel paint 30 cm each alternatively upto 1.5 mtr including 2 bands of radium tape of 2" width greeen & red colour above the coping of pole starting with black strip, complete all as specified & directed. Note (i) Earth work and PCC shall be measured and paid seperately (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
53Supply and fixing in replacement ofstay assembly complete with all accessories, such as stay plate 230x230x6 mm, stay rod 215 cm long and 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc all as per electrical plate No 1 or SSR part 1 incl taking down old unsv complete all as specified & directed. Note- The quoted rate shall include the cost of loop type insulator, stay clamps, excavation, PCC, stay wire, stay bow, turn buckle, nuts etc. complete.
54Material and labour in replacement of Loop insulator Porcelain, vitreous white/brown/green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, large size with overall dimensions 90mmx 140mm, clearance of hole 25.5 mm, complete all as specified & directed.
55Material and labourin replacement for shackle type porcelain vitreous white or brown insulator including GI straps washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm hight, 90 mm dia, section of strip 30mmx3mm & dia of bolt 12 mm ccomplete all as specified & directed.
56Material and labour in replacement for pintype insulator porcelain vitreous white or brown 1100 volts grade100 mm hight and 65 mm dia with GI spindle two washer and one GI nut complete all as specified & directed.
57Dismantling and taking down old unserviceable ACSR conductor incl cutting, welding complete all as specified & directed.
58Material and labourforaluminium conductor steel reinforced (ACSR) conductor of size 6/1 x 2.59(Weasel) and6/1 x 2.11 (Squirrel) ISI marked for LT over head lines on poles including stretching, tightening of poles insulator with winding wire of suitable size with insulator/strechingof ACSR conductor complete all as specified & directed.
59Dismantling andtaking down old unserviceable cross-arms of M.S. channel or angle sections etc. incl cutting, welding complete all as specified & directed.
60Material and labourin replacement ofcross arms,bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape of size as indicated or directed and inclusive one primer coat, one under coat and one finishing coat of paint complete all as specified & directed.
61Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4.0 x 10-50 Sqmm complete all as specified & directed.
62Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-120 Sqmm ccomplete all as specified & directed.
63Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 150-300 Sqmm complete all as specified & directed.
64Supply and fixing straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4 x 25-50 Sqmm complete all as specified & directed.
65Supply and fixing straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-120 Sqmm complete all as specified & directed..
66Supply and fixing straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 150-300 Sqmm complete all as specified & directed.
67Dismantling andtaking down old u/searthing complete with galvanisedearth plate electrode 600mm x 600mmx 6.00mm thick surrounded by charcoal and salt, buried directly in ground vertically in a pit of depth not less than 2.25m belowground level with top edge of the earthplate not less than 1.5m belownormal groundlevel, connected to 25x4 mm GI strip earth lead by means of bolts, nuts, checks nut and washers made out of galvanized iron or steel, earth wire protected by galvanized steel pipe 40mm bore medium grade and connected to main switch or main control board all as shown in electrical plate No.3 of SSR Part-I & including necessary excavation and earth work. The rate also include charcoal & salt in alternate layers, 20mm bore GI pipe medium grade for watering and 40mm bore GIprotection pipe (light grade), funnel, wire mesh,cast iron cover andframe etc, complete, all as specified or indicated and as directed including testing on completion complete all as specified and directed. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with standgrouted in PCC. (iii) On testing after completion if the desired earth resistanceis more than 2?the earthing will be redone at no extra cost
68Dismantling andtaking down old u/s earthing andMaterial and labour for earthing complete with galvanized steel plate earth electrode 60cmx60cmx6mm thick surrounded by char coal and salt buried directly in ground vertically in pit of depth not less then 2.25 mtr below ground level with top edge of the earth plate at depth of not less than 1.5 mtr below ground level surrounded from all sides by char coal dust and common salt in alternate layers of 15 cm depth and earth plate electrode connected to galvanised earth lead wire of 4.0 mm dia by means of GI nuts bolts, check nuts and washers and connected to earthing test point drawn through 15 mm bore GI pipe medium grade for protection of GI earth lead wire including 20mm bore GI pipe medium grade for watering GI funnel PCC earth pit (1:3:6) type C-2 with CI frame and RCC cover all as shown in electrical Plate No 3 on SSR Part - I including testing complete all as specified and as directed. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with standgrouted in PCC. (iii) On testing after completion if the desired earth resistance is more than 2? the earthing will be redone at no extra cost
69Supply and fixing in replacement MCCB TPN 630 Amps, 415 Volts, 50 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type with microprocessor basedincl connection complete all as specified & directed.
70Supply and fixing in replacement MCCB TPN 400 Amps, 415 Volts, 36 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type microprocessor based incl connection complete all as specified & directed..
71Supply and fixing in replacement MCCB TPN 315 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type microprocessor based incl connection complete all as specified & directed.
72Supply and fixing in replacement MCCB TPN 250 Amps, 415 Volts, 16 KA,4 pole , Ics=100% Icu, incl connection complete all as specified & directed.
73Supply and fixing in replacement MCCB TPN 200 Amps, 415 Volts, 16 KA,4 pole , Ics=100% Icu,incl connection complete all as specified & directed.
74Supply and fixing in replacement MCCB TPN 160 Amps, 415 Volts, 16 KA,4 pole , Ics=100% Icu,incl connection complete all as specified & directed.
75Supply and fixing in replacement MCCB TPN 100 Amps, 415 Volts, 10 KA,4 pole , Ics=100% Icu, incl connection complete all as specified & directed.
76Material & Labour for Detecting of fault in cable HT/LT with fault locator equipment supplying of HT/LT electric supply (11 KV/430 Volts) to make the HT/LT cableserviceablewith Straight throughjoint of size 70-300 Sqmm complete all as specified & directed. Notes (a) The HT fault which is detected through cable fault locator will only be paid under this item including transportation charges demed to be included in the quoted rate. (b)Transportation charges of cable fault locator and DG set deemed to be included in the quoted rate. (c) Earth fault locator will be provided by the contractor for even single HT fault and no delay on this account will be acceptable otherwise penalty will levied Rs 500.00 per hour. (d)Straight through joint , 95 to 300 Sqmm, Labour charges, excavation and making joint deemed to be including in quoted rate.
77Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 4 line as per IS complete all as specified & directed.
78Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 3 line as per IS complete all as specified & directed.
79Re-streching of loose over head ACSR conductor of any type/GI wire and repair of the broken conductors andaddingnew length( if required) in placeof old and burnt conductor of any size on existing poles with proper sagging including winding with winding wire complete all as specified & directed. ( Old conductor shall be reused where required for repairing broken length of conductor). Note:- Each run of conductor will be measured and paid seperately
80Labour only for trimming and pruning of large tree branches OH lines of HT/LT & and boundary of solar plant to maintain approaching minimum clearance of 3 Mtrfrom branches. Proper shut down will be taken and maintained in the register complete all as specified and directed.
81Material and labour inreplacementofaluminium terminals (thimbles) after cutting the worn out/faulty cable end from LT pillar/panel box including necessary earth work for taking out the cable from loop line, returning, filling in and making cable lead by providing aluminium lugsincluding crimping with crimping tools in the existing LT cable 25 Sqmm 4 core upto 50 Sqmm including necessary connectioncomplete all as specified & directed.
82All as per item ser No 81 here in before but size of LT cable 70 Sqmm 3.5 core upto 120 Sqmm 3.5 core complete all as specified & directed.
83All as per item ser No 81 here in before but size of LT cable 150 Sqmm 3.5 core upto 300 Sqmm 3.5 core complete all as specified & directed.
84Material and labour for shifting heavy items / excavation / cleaning areas / cleaning site by providing crane/hydra/excavators/tractors/trolley etc as required at site complete all as specified and directed.
85Material & Labour for repair of LT panel of any type and anysize including replacement of old unsv items such as busbar, insulaor, CT/PT coils, insulating sleeves, front and rear doors, door hinges, gland, lugs volt meter, ammeter, indicator, locking arrangement and internal copper wiring after cleaning of surface including removing rusted particles removing dust tightening nut, bolts welding and painting on complete panel two coats of synthetic enamel aluminium paint over a coat of red oxide including stand complete all as specified & directed.. Note : (i)Cost of marking description on the front door as per direction of Engr-in-Charge is incl in quoted rate (ii)Cost of misc items like copper cable, lugs thimbles etc if required are included in quoted rates. (iii) Cost of welding works such ashinges, locking arrangement, door and angles are included in qouted rates.
86Material & Labour for surface cleaning of LTsteel tubular poles9 mtrs long including removing rusted particles painting withtwo coats of synthetic enamelaluminium paint over a coat of red oxide including stand cross arms, bracing, supports,clamps eye hooks, security light bracket clamps etc providing black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paints incl repairing and painting on coping with cement base white paint complete all as specified & directed.. Note : (i)The quoted rate shall includes making of numbers on self adhesive stickers on each LT pole as per direction of Engr-in-Charge.
87Material & Labour for cement base paint for Prestressed concrete pole 9 mtr includingblack & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint and painting with two coats of synthetic enamel aluminium paint over a coat of red oxide including cross arms bracing supports, clamps, eye hooks, security light bracket, clamp etcincl repairing and painting on coping with cement base white paint complete all as specified & directed. Note : (i)The quoted rate shall includes making of numberson self adhesive stickers on each LT pole as per direction of Engr-in-Charge.
88Supply only Chemical round Up for spraying herbicide (Round up) on area to remove unwanted vegitation/grass at various locations complete all as specified & directed.
89Supply and fixing in replacement of on load change over switch with sheet steel Enclosure 415 V, 4 pole, 100 Amps capacity fixed on walls for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified & directed.
90Supply and fixing in replacement of on load change over switch with sheet steel Enclosure 415 V, 4 pole, 200 Amps capacity fixed on walls/MS frame/pole/LT panel for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified & directed..
91Material & Labour Chemical spray (DC 2.26 contact cleaner) in container of 415 ml/300g for precision blended multipurpose product for prevents corrosion penetrates, lubricants, displaces and seals out moisture release rusted mechanisum cleanese etc complete all as specified & directed.
92Supply and fixing in replacement of fabrication of Kiosk box made out of fibre material complete with TPN ,aluminium bus and suitable for one number MCB (SP) including one No MCB (SP) 6 Amps 240 volts with glands for incoming & out going cable including fixing of flat iron clamps of size 20x4mm on PCC/Steel tubular pole complete all as specified & directed.. Make: Havells/Sintex.
93Supply and fix in replacement of MCB SP 6-32 Amps, 240 volt,10 KA "C" curveincluding all accessories complete all as specified and directed.
94Supply and fix in replacement of MCB DP 16-40 Amps, 240 volt,10 KA "C" curveincluding all accessories complete all as specified and directed.
95Material and labour for fabrication, supply, fixing and commissioning of box type display boards of size not less than 1.5M x 1.0M x 0.2M made out of ACP sheet of 3mm thickness with enlish alphabets and numerics cut out and designed out of 3mm thick acrylic sheet neatly pasted on the ACP board with flushed LED strips running along the sides of the acrylic letters to be fixed on wall with necessary fixing arrangement as per the site requirement on roof, wall etc complete all as specified & directed. Note:- (a) Beforefabrication of the display board, the contractor has to produce a paper printout detailing all documents and matter to be displayedso as to get it inspected and passed by Engr-in-charge. (b) Matter to be displayed, colour of the ACP sheet and colour of Retro Reflective sheet will be as specified and directed by Engr-in-Charge. (c) The quoted rate is deemed to be inclusive of cost of labour and materials required for fixing of the display board at the location including providing electrical connections complete all as specified & directed.
96Material and labour for fixing of Layout diagram of LT or HT lines/ flow chart/ shock treatment chart etc of size1.5M x 1.0Mfor power houses, sub stations and other E/M installations as per the requirement at various locations made out of pre laminated board with digital printing, pasting side beadings of decorative aluminium channel with proper fixing arrangement etc complete all as specified & directed.. Note:- (a) Before for fabrication of the display board, the contractor has to produce a paper printout detailing all documents and matter to be displayedso as to get it inspected and passed by Engr-in-charge. (b) Matter to be displayed, colour of the ACP sheet and colour of Retro Reflective sheet will be as specified and directed by Engr-in-Charge. (c) The quoted rate is deemed to be inclusive of cost of labour and materials required for fixing of the display board at the location including providing electrical connections complete all as specified & directed.
97Supply & fixing in replacementof Automatic Street Light Control Switch with Infrared Sensor based NATURE SWITCH & Voltage Monitoring System (VMS). Three phase, 25 Amps per phase, MCB rating 32 Amp, max load 8-12 kw incl circuit copper wire 10 sq.mm.Nature Switch operation should be based on Natural Light Lux level. Required Illuminance Level for Switching ON is = 60 Lux and for switching OFF = 10 Lux. The Sensor should also have part night operation facility of min. 4 to max. 12 hrs. VMS should have Adjustable Over & Under Voltage Trip level and Protection against Phase Loss, Neutral Loss & Phase Reverse. The Sensor & VMS along with suitable Power Contactor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Junction box conforming to IP54. The circuit should also have provision for Manual Operation (i.e. By-Pass Option for both Sensor (NS-02) and VMS) complete all as specified and directed. Note(i) S S Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii)The sensor must have the warranty of min of 2 years. (iii)The test certificate and warranty cirtificate must be provided by supplier.(iv)Cost of marking description on the box is incl quoted rate.
98Supply & fixing in replacementof Automatic Street Light Control Switch with Infrared Sensor based NATURE SWITCH & Voltage Monitoring System (VMS). single phase, 25 Amps per phase, MCB rating 40 Amp, max load 5-8 kw incl circuit copper wire 10 sq.mm.Nature Switch operation should be based on Natural Light Lux level. Required Illuminance Level for Switching ON is = 60 Lux and for switching OFF = 10 Lux. The Sensor should also have part night operation facility of min. 4 to max. 12 hrs. VMS should have Adjustable Over & Under Voltage Trip level and Protection against Phase Loss, Neutral Loss & Phase Reverse. The Sensor & VMS along with suitable Power Contactor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Junction box conforming to IP54. The circuit should also have provision for Manual Operation (i.e. By-Pass Option for both Sensor (NS-02) and VMS) complete all as specified and directed. Note(i) Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii)The sensor must have the warranty of min of 2 years. (iii)The test certificate and warranty certificate must be provided by supplier.(iv)Cost of marking description on the box is incl quoted rate.
99Supply and fix inreplacementof Lithium based Energy Efficient Integrated Solar Street Light of 32 Watt” in Single FRP body with duly Polyurethane coating (Camouflage color) , encases with Monocrystalline Solar PV Panel of 64/66Wp , Lithium Battery 11.1/12.8V, 33.0AH with inbuilt BMS, IP 65, High brightness W-LED(160-180lm/watt) lamp with Aluminum reflector for better light distribution , CRI >70, Color Temperature 5700°K - 6500°K, Microcontroller based charge controller cum driver, automatic dimming function (first four hours at full brightness & rest of the time at lower light level with PIR Motion Sensor), Dusk to Dawn Operation, suitable to working temperature: (-) 10°C to (+)55°C, weight not more than 16-18kg with adjustable MS clamp suitable for pole/wall mounting etc complete as required. Protections: Short Circuit, overload, Reverse polarity and battery protections. Firm should provide Vital Parameters Test report from NABL accredited lab and should be of made in India with CE & ROHS compliant including tubular pole 6 mtr height with bottom base plate 200x200x12 mm , outdoor dia not less than 65 mm with heavy duty GI pipe or steel thickness 3mm and suitable arrangement to mount solar light as directed on pole including foundation PCC 1:3:6 type C-1using 20mm graded crushed stone aggregate and erection as per manufacturer drawing, providing synthetic enamel aluminium paint over one coat of red oxide complete all as specified and directed.
100Supply & fixingin replacement of Integral LED Flood light Luminaries 80 Watts consisting of suitable number of LEDs andmounted on MCPCB high pressure die cast aluminium housing with sealed toughened glass cover with secondary optics lens,IP 66 protection suitable for mast light mounting, 5700K,LED efficiency >130 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV ,Confirm the tests from auth labs :LM79 & LM 80, incl proper fixing and testing of flood lights on 9/11 mtr long steel tubular pole and provide facility of power supply shall be provide as suitable for maint work of light fittings incl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as specified & directed.
101Supply & fixingin replacement of Integral LED Flood light Luminaries 150 Watts consisting of suitable number of LEDs andmounted on MCPCB high pressure die cast aluminium housing with sealed toughened glass cover with secondary optics lens,IP 66 protection suitable for mast light mounting, 5700K,LED efficiency >130 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV ,Confirm the tests from auth labs :LM79 & LM 80, incl proper fixing and testing of flood lights on 9/11 mtr long steel tubular pole and provide facility of power supply shall be provide as suitable for maint work of light fittings incl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as specified & directed.
102Supply & fixingin replacement of Integral LED Flood light Luminaries 200 Watts consisting of suitable number of LEDs andmounted on MCPCB high pressure die cast aluminium housing with sealed toughened glass cover with secondary optics lens,IP 66 protection suitable for mast light mounting, 5700K,LED efficiency >130 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV ,Confirm the tests from auth labs :LM79 & LM 80, incl proper fixing and testing of flood lights on 9/11 mtr long steel tubular pole and provide facility of power supply shall be provide as suitable for maint work of light fittings incl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as specified & directed.
103Supply & fixingin replacement ofLED street light fitting70 watts made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover/ toughened glass having TOP Opening seperate driver compartment with IP 66 protection and impact resistance of IK07 consisting of suitable number of LEDs with sealed toughened glass cover, 5700K,LED efficiency >110 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 140 V-270 V, Power factor> 0.95,mains current 0.270A, working temperature range-10ºC to 50ºC,built in surge protection of more than 10 kV, better optics for uniform distrubution with multiple LEDs not less than 2 watt each and having optical grade polycarbonate lens with all accessories , suitable for side entry, pole mounting with bracket arm OD 40 mm, recommended mounting height with suitable inground reinforcement is 8 mtrs, Confirm the safety test as per IS 15885 part-2 from auth labs :LM79 & LM 80, incl proper fixing and testing of street lights on 9/11 mtr long steel tubular poleincl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as specified & directed.. Note :-PVC heavy duty conduit pipe along with 3/1 run of 1.5/2.5 sqmm PVC insulated unsheathed/sheathed copper multistranded conductor from MCB box to streetshall be measured and paidfor separately.
104Supply & fixingin replacement ofLED street light fitting90 watts made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover/ toughened glass having TOP Opening seperate driver compartment with IP 66 protection and impact resistance of IK07 consisting of suitable number of LEDs with sealed toughened glass cover, 5700K,LED efficiency >110 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 140 V-270 V, Power factor> 0.95,mains current 0.270A, working temperature range-10ºC to 50ºC,built in surge protection of more than 10 kV, better optics for uniform distrubution with multiple LEDs not less than 2 watt each and having optical grade polycarbonate lens with all accessories , suitable for side entry, pole mounting with bracket arm OD 40 mm, recommended mounting height with suitable inground reinforcement is 8 mtrs, Confirm the safety test as per IS 15885 part-2 from auth labs :LM79 & LM 80, incl proper fixing and testing of street lights on 9/11 mtr long steel tubular poleincl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washercomplete all as specified & directed.. Note :-PVC heavy duty conduit pipe along with 3/1 run of 1.5/2.5 sqmm PVC insulated unsheathed/sheathed copper multistranded conductor from MCB box to streetshall be measured and paidfor separately.
105Supply, installing, testing & commissioning in replacement of outdoor type cubical panel board of size 1.5mX1.2mX.5m, outer shell made out of3.15 mm thick CRCA sheet and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform block type 60 cm above ground level and 30 cm grouting in ground,frame factory fabricated with front and back openable double door system and cable alley(Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open ablewith arrangement of pad locking on both doors incl 2 no. of pad locks of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, incl cupper bus bar of 600 A ,tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:61439/2011Part-1 andpart -2 type test certificate with not less thanIP-56and breaking capacity 65 KA comprising of the following :- (a) MCCB400 Amps, 36 KA 4 pole 415 Volts AC, adjustable type, Microprocessor with int release (incoming)-01 No. (b) MCCB250 Amp, 415 volt, 4 pole, breaking capacity 25 KA , (Outgoing)-01 Nos. (c) MCCB160 Amp, 415 volt, 4 pole, breaking capacity 16 KA , (Outgoing)-03 Nos. (d) MCCB100 Amp, 415 volt, 4 pole, breaking capacity 10 KA , (Outgoing)-02 Nos. (e) MCB32 Amp, 415 volt, TPN, breaking capacity 10 KA , (Outgoing)-02 Nos (f) RYB indication LED type, 22.5 mm dia, protected with MCB SP 2 Amp showing 3 phase supply -03 Nos (g) Digital Multifunction meter to measure Volt, amp, KWH load -01 Nos (j) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, glands etc complete are included in quoted rates.
106Supply, installing, testing & commissioning in replacement ofoutdoor type cubical panel board of size 1.4mX1.0mX.5m,outer shell made out of3.15 mm thick CRCA sheet and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm aboveand 45 cm below the ground level,frame factory fabricated with front and back openable double door system and cable alley(Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open ablewith arrangement of pad locking on both doors incl 2 no. of pad locks of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, incl cupper bus bar of 400 A , tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:61439/2011Part-1 andpart -2 type test certificate with not less thanIP-56and breaking capacity 65 KA comprising of the following :- (a) MCCB250 Amps, 25 KA 4 pole 415 Volts AC, adjustable type,(incoming)-01 No. (b) MCCB63 Amp, 415 volt, 4 pole, breaking capacity 10 KA , (Outgoing)-06 Nos (d) MCB32 Amp, 415 volt, TPN, (Outgoing)-01 Nos (e) RYB indication LED type, 22.5 mm dia, protected with MCB SP 2 Amp showing 3 phase supply -03 Nos (f) Digital Multifunction meter to measure Volt, amp, KWH load -01 Nos (h) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, glands etc complete are included in quoted rates.
107Supply, installing, testing & commissioning in replacement of outdoor type cubical LT feeder pillar panel box size 1.0Mx0.8Mx50Cm with double door type cubical panel board outer shell made out of3.15 mm thick CRCA sheet and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm aboveand 45 cm below the ground level,frame factory fabricated with front and rear openable double door system and cable alley(Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable by Keyshaving chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, incl cupper bus bar of 200 A , tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:61439/2011Part-1 andpart -2 type test certificate with not less thanIP-56and breaking capacity 65 KA comprising of the following :- (a) Incoming MCCB100 Amps, 16 KA 4 pole 415 Volts AC, adjustable type, -01 No. (b) Outgoing MCCB63 Amp, 10 KA, 4 pole 415 volt AC,-02 Nos. (c) Outgoing MCB32 Amp, 10 KA , TPN 415 voltAC -02 Nos (d) RYB indication LED type, 22.5 mm dia, protected with MCB SP 2 Amp showing 3 phase supply -03 Nos (e) Digital Multifunction meter to measure Volt, amp, KWH load -01 Nos (g) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, glands etc complete are included in quoted rates.
108Supply, installing, testing & commissioningin replacement of factory fabricated outdoor type feeder pillar board of size 700X600X500 mm , outer shell made out of3.15 mm thick CRCA sheet and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm aboveand 45 cm below the ground level,frame factory fabricated with front openable double door system and cable alley(Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open ablewith arrangement of pad locking on door01 no of pad lock of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coated painting after 7-tank pre treatement control & power wiring with suitable size of copper conductor along with suitable gasket to make it dust/vermin proof and general construction confirming to IS:61439/2011Part-1 andpart -2 type test certificate with not less thanIP-56and breaking capacity 65 KA comprising of the following :- (a) MCCB 125 Amps TPN, 25 KA -01 No (b) MCCB 40Amp TPN 4 pole - 04 Nos (c) Copper busbar of capacity 200 Amps with colour coated heat shrinkable sleeve and suitable hole for out going connection - Set of four. (d) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, glands etc complete are included in quoted rates
109Notes for item Sr No.105 to 108(i) The quoted rate shall include minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc. (ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming toIS-694. (iii) Panel drawing shall be got approved before placing of orderfrom Engr-in-Charge/GE. (iv) The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. (v) Cable will be entered in panles through gland.(vi) Cost of marking description and matter on the front door as specified and directed by Engr-in-Charge is incl in quoted rate.
110Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through heatshrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm incl taking down old unsv HT joint complete all as specified & directed.
111Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through heatshrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm incl taking down old unsv HT joint complete all as specified & directed.
112Material & Labour for cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPEcable 50-95 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as specified & directed.
113Material & Labour for cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPEcable 120-185 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as specified & directed.
114Material and labour in replacement of broken earth pit of size 300x300x300 mm madeof PCC 1:2:4 type B1 using 20 mm graded crushed stone aggregate, and earth pit cover made out of RCC 1:2:4 type B1, cover reinforced with 8 mm dia TMT bars @ 100 mm centre to centre both ways with handle made out of 8 mm dia bar, watering arrangement with funnel and wire mesh including reconnecting of earth lead of any type with new nuts, bolts and washers as required at site with testing result complete all as specified & directed.
115Material and labour in repairs of stay by tightening of stay wire after untying the conductor spans from the poles to make correct tensions and maintain verticality of poles, including re-jointing the conductors in position with new binding wire complete all as specified & directed.
116Material and labour for PCC 1:2:4 type B1, (using 20mm graded crushed stone aggregate) as in coping of LT/HT pole of size 600X600X300mm including form work and applying two coats of cement base paint including demolition of existing complete all as specified & directed.
117Taking down old unserviceable ammeter with selector switch and supply and fixing new rotary type ammeter with selector switch, three phase, 5 Amps, Ammeter 0-300 Amps including making electrical connection complete all as specified and directed.
118Taking down old unserviceable volt meter 0-500 volts with selector switch and supply and fixing new rotary type volt meter with voltage selector switch, three way, 2 Amps, 500 Volts including making electrical connection complete all as specified and directed.
119Taking down old unserviceable Indicator any type any colour and supply and fixing new Indicator red/yellow/green including making electrical connection with suitable size of copper lugs duly crimped complete all as specified and directed.
120Material & Labour for Brick work with subclass "B" bricks, straight or curved on plan exc 6m mean radius built in CM 1:6. complete all as specified and directed.
121Material & Labour for rendering 15mm thick on fair faces of brick work or concrete surfaces in CM 1:4 finishing the surface fair and even smooth without using extra cement complete all as specified & directed.
122Material & Labour for preparation and applying three coats of white wash on new plastered surface of wall complete all as specified directed.
123Material & Labour for replacement of steel nuts, bolts, washers of any size required at sitecomplete all as specified & directed.
124Supply and fixing in replacement of rolled mild steel plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk)forming holes, with riveted, bolted or welded attachmentFe-290 (Gde E- 165)for existing LT panel doors/gates complete all as specified and directed.
125Material & Labour for disconnecting and connecting of LT service wires and XLPE cables of any type and anysizefromLT panel, MCCBs, DBs, over head conductor, LT poles, street light timerincluding replacement of old unsv items such as nuts, bolts, thimbles, insulating seleaves and existing misc items etc, andafter cleaningand removing of carbon on cables end surface including removing rusted particles removing dust tightening nut, bolts complete all as specified and directed. Note : (i)Cost ofall tools and ladder required for maintenanne of LT service wires and XLPE cable end connection and disconnection is incl in quoted rate (ii)Cost of misc items like nuts, bolts, thimbles, insulating seleaves etc if required are included in quoted rates.
126Supply and fixing in replacement of nature switch operation should be based on natural light lux level, required illuanance level for switching on is <30 Lux and for switching off >10 lux , the sensor should also have part night operation facility of min 4 hrs to max 12 hrscomplete all as specified and directed.
127Supply and fixing in replacement of contactor 3 pole 18 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed.
128Supply and fixing in replacement of contactor two pole 25/40 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed.
129Supply and fixing in replacement ofcontactor coil (230V)for MU series 25/40 Amps 2 pole contactorscomplete all as specified and directed.
130Supply and fixing in replacement ofcontactor coil (240V)for freedom series 18 Amps 3 pole contactorscomplete all as specified and directed.
131Supply and fixing in replacement ofVMS (voltage monitoring series) in street light timer box, including all salient features such as selectabe under/over voltage trip levels, protection against phase loss & natural loss, protecotion against phase reversal and phase to phase unbalance (10%), voltage sensing principle and LED indications for power and fault conditions complate all as specified and directed.
132Supply and fix in replacement of danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled red, with letters, figures and conventional skull and bones in signal white colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as specified and directed
133Supplying and laying in replacement of synthetic rubber insulated mats 2.5 mm thick for voltage upto 11 kv forlectrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 10m x 1m complete all as specified and diercted.
134Supply and fix in replacement of cradles, hexagonal/rectangular, earth continuity wire for GOD/LAfabricated with galvanised steel wire 3.15/4 mm dia complete all as specified and directed.
135Supply and fixing in replacement of cable route indicator or cable joint mark for 1100 volts made out of mild steel 100mm dia 6mm thick plate welded to 40 x 40 x 6mm angle iron 60 cm long embeded in PCC 1:3:6 type C-2 (using 20mm graded stone aggregate) block of size of 150mm x 200mm x 200mm including applying two coats of synthetic enamel paint over a coat of redoxide primer on steel surfaces complete all as specified & directed.
136Material and labour for vibratory compactive,precast cement concrete rubber moulded, coloured ( except grey colour), interlocking designer paver blocksin Milano shape, comfirming to IS-15658-2006 of 60 mm thickness, M-35 grade, as in path, hardingstanding, etc laid over and including 25 mm compacted sand cushioning, including 75 mm thick PCC 1:4:8 type D-2 using 40mm graded crushed stone aggregate including surface excavationover area n. exc. 30 cm deep and averaging 15 cm deep and getting out in soft/loose soil and removing excavated soil exc. 50 mtr but n. exc. 250 mtr, complete all as specified & directed.
137Supply & Fixing in replacement of bracket made out of GI tubing single piece not welded, bended at proper angle of size 40mm dia, light grade 1.5 mtr long complete all as specified and directed.
138Supply & Fixing in replacement of MS clamp suitable for holding street light bracket on steel/PCC polemade out of 40 mm x6 mm thick flat iron with M.S nuts bolts 50 mm long 10 mm dia-3 Nos with flat washer 3mm thick -02 No complete all as specified and directed.
139Supply & Fixing in replacement of extended spreaders link should be installed both side with exisitng/new MCCBs 4P/3P of any capacity with existing LT panels complete all as specified & directed.
140Note:-Amount of credit ofRs. 138649.00 for retrieved materials is mentioned in Schedule of Credit of tender documents in PDF form which will be deducted offline while acceptance of tender.