Tender For Preventive Maintenance Of Lt Distribution Transformer In The Area Of 33 11 Kv Substation Faizullaganj Daud Nagar Gsi And Priyadarshini Under Eudd Sitapur Road Transgomti Lesa Lucknow Under Se Eudc Vi Transgotmi Lesa Lucknow, For Preventive Main, sitapur-Uttar Pradesh

Madhyanchal Vidut Vitran Nigam Limited has published Tender For Preventive Maintenance Of Lt Distribution Transformer In The Area Of 33 11 Kv Substation Faizullaganj Daud Nagar Gsi And Priyadarshini Under Eudd Sitapur Road Transgomti Lesa Lucknow Under Se Eudc Vi Transgotmi Lesa Lucknow, For Preventive Main. Submission Date for this Tender is 28-05-2024. Distribution Transformer Tenders in sitapur Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

43270577
Corrigendum : Tender For Preventive Maintenance Of Lt Distribution Transformer In The Area Of 33 11 Kv Substation Faizullaganj Daud Nagar Gsi And Priyadarshini Under Eudd Sitapur Road Transgomti Lesa Lucknow Under Se Eudc Vi Transgotmi Lesa Lucknow, For Preventive Main
Open Tender
Indian
Uttar Pradesh
sitapur
28-05-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Tender For Preventive Maintenance Of Lt Distribution Transformer In The Area Of 33 11 Kv Substation Faizullaganj Daud Nagar Gsi And Priyadarshini Under Eudd Sitapur Road Transgomti Lesa Lucknow Under Se Eudc Vi Transgotmi Lesa Lucknow, For Preventive Maintenance Of Lt Distribution 25 / 63 / 100 / 250 / 400 / 630 Kva T / F In The Area Of 33 / 11 Kv S / S Faizullaganj, Daud Nagar, Gsi & Priyadarshini Under Eudd Sitapur Road, Transgomti Lesa Lucknow Under S.E. Eudc-Vi, Transgotmi Lesa, Lucknow.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 06-May-2024 Extention_T-01 Date 09-05-2024
2 10-May-2024 Extention_T-01-2024-25 Date 14-05-2024
3 15-May-2024 Extention_T-01-EUDCVI-24-25 Date 20-05-2024
4 21-May-2024 corridendum_T_01 Date 28-05-2024

Key Value

Document Fees
INR 1180 /-
EMD
INR 10000.0 /-
Tender Value
INR 9.83 Lakhs /-

Attachment

FileName File Description File Size
1f46d5e4-dc6d-4f70-94c7-8a7f01d7c78c.html Tender Notice 0 KB
BOQ_1595394.xls Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB
TENDERPROFARMA-01.pdf Tender Document 0 KB

BOQ Items

Name of Work: “For Preventive Maintenance of LT distribution 25/63/100/250/400/630 KVA T/F in the area of 33/11 KV S/S Faizullaganj, Daud Nagar, GSI & Priyadarshini under EUDD Sitapur road, Transgomti LESA Lucknow under S.E. EUDC-VI, Transgotmi LESA, Lucknow."
Sl. No. Item Description
1Replacement of Old and Damaged H.T Bushing rod including Oil Seal/Gaskets etc. ( 160, 250, 400, 630 and 1000 KVA T/F)
2Load measurement of distribution transformers & arresting of oil leakage wherever required. Opening of top cover & draining of transformer oil below. LV Bushing rod and Replacement of following damage parts as on site &refilling of TF Oil after work completion tighting of top cover, providing photograph before work and after work completion (All material provided by contractor)
3a) 250 KVA/400 KVA(i) LV bushing rod 20mm brass
4(ii) LV bushing M+F
5(iii) Gasket set
6(iv) LV Oil seal 20 mm
7b) 630 KVA(i) LV bushing rod 30mm brass
8(ii) LV bushing M+F
9(iii) Gasket set
10iv) LV Oil seal 30 mm
11c) 160-630 KVA HV Porcelain bushing
12d) 160-630 KVA HV bushing rod 12mm brass
13e) 160-630 KVA HV Oil seal 12 mm
14(i) Replacement of moist silica gel breather
15Replacement of gasket top cover sheet 900x600x6mm packing wherever required
16Replacement of Old and Damaged Suitable capacity of Aluminum Lugs (All Material will be provided by Contractor).
17Fixing of suitable capacity of lugs after removing old and damaged lugs from various capacity of PVC cable with using crimping tools.
18Provision of fuse unit at LT side:- To protect transformer by unbalancing and overloading, provision of fuse unit to be installed at LT side with suitable capacity of Fuse assembly ( All Material as fuse assembly, nut bolts etc. will be provided by contractor)
19160, 250 KVA KVA T/F
20400 and630 KVA T/F
21Provision of fuse unit at HT side:- To protect transformer by unbalancing and overloading, provision of DO fuse unit to be installed at HT side with suitable capacity of Fuse assembly ( All Material as fuse assembly, nut bolts etc. will be provided by contractor)
22160, 250 KVA KVA T/F
23400 and630 KVA T/F
24Repair and Maintenance of Old and Damaged Transformer Earthing:- Maintenance and repair of Transformer Body and Neutral Earthing PIPE/ROD are Damaged, in case of missing pole earthing, provision of M.S Rod Of 20x25mm and 6 SWGearthing wire .will be done by new one as per site requirement. Contactor to ensure that earth connection properly should be tight and earth resistance should be less than 01ohm.(All Material Provided by contactor) of 160 KVA to 250 KVA
25Provision of Pipe earthing of body and neutral at two points:- Provision of 7fit deep pipe earthing of transformer body and neutral separately with 1.5 inch dia 60fit pipe. Contactor to ensure that earth connection properly should be tight and earth resistance should be less then 01ohm.(All Material Provided by contactor)
26To protect 100 KVA transformer by unbalancing and overloading, provision of fuse unit to be installed at LT side with suitable capacity of Fuse assembly ( All Material as fuse assembly, nut bolts etc. will be provided by contractor) of 100 KVA
27Provision of fuse unit at HT side:- To protect 100 KVA transformer by unbalancing and overloading, provision of fuse unit to be installed at HT side with suitable capacity of Fuse assembly ( All Material as fuse assembly, nut bolts etc. will be provided by contractor) t/f 100 KVA T/F
28Repair and Maintenance of Old and Damaged Transformer Earthing:-Maintenance and repair of Transformer Body and Neutral Earthing PIPE/ROD are Damaged, in case of missing pole earthing, provision of M.S Rod Of 20x25mm and 6 SWGearthing wire will be done by new one as per site requirement. Contactor to ensure that earth connection properly should be tight and earth resistance should be less then 01ohm.(All Material Provide by contactor)
29GST will be paid extra as per rule.