Military Engineer Services-MES has published Tender For Repair And Maintenance Of External Electric Lt Distribution System At Khanabal Under Ge 861 Ews. Submission Date for this Tender is 24-05-2024. Electrical Maintenance Tenders in Anantnag Jammu And Kashmir. Bidders can get complete Tender details and download the document.
FileName | File Description | File Size |
9f672d58-b71f-42c2-910d-6bcf03f2456f.html | Tender Notice | 0 KB |
BOQ_729412.xls | Tender Document | 0 KB |
Tender08-24-25.pdf | Tender Document | 0 KB |
Tendernotice_1.pdf | Tender Document | 0 KB |
Sl. No. | Item Description |
1 | M&L for excavation in trenches not exceeding 1.5 m wide and n.exc. 1.5 m deep for foundationof poles/stay/cable etc including getting out in loose/soft soil complete all as specified and directed by Engr-in-Charge. |
2 | Description all as per item No.1 above but depth exc 1.50m and n.exc 3mtr in depth complete all as specified and as directed by Engr-in -Charge |
3 | M&L for returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm all as specified and directed by Engr-in-charge |
4 | M&L for removing excavated material n.exc. 50m and depositing where directed at a level n.exc. 1.5 m above the starting point all as specified and directed by Engr-in-charge. |
5 | M&L for sand cushioning to cable with dry fine sand in trenches 8 cm below the cable and 15 cm above the cable after laying complete all as specified. Note : Punnedthickness 18 cm will be measured. |
6 | M&L for bricks laid in trenches flat with width equal to length of brick for cable protection well burnt sub class "B" laid across the cable complete all as specified directed by Engr-in-charge. |
7 | M&L for plain cement concrete 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete complete all as specified. |
8 | M&L for plain cement concrete 1:3:6 type C-1 (using20 mm graded aggregate) as in rounded and chamfered on edges complete all as specified. |
9 | Supply and fixing steel tubular swaged pole with cast iron base plate finial tapper plug, bolts nuts and screws and specified type 410-SP-31(9 mtr long) in truly vertical position 1.5 m length of pole above ground level shall be painted with two coats of synthetic enamel paint in strips of 30 cm width, black and yellow alternatively and painting with two coats of aluminum paint over a coat of red oxide primer on rest part of pole and its connected parts complete all as specified and directed by Engr-in-charge. |
10 | M&L for in replacement ofpin type insulator porcelain, vitreous, white/ brown or green insulators including one galvanised MS spindle, two galvanized iron washer, GI nut of size 100 mm height and 65mm dia 1100 volts grade complete all as specified |
11 | M&L for Cross arms, bracings, supports, clamps and back plate fabricated from structural steel section including nuts, bolts, washers, welding bending cold or hot, drilling holes for bolts in any shapes size as indicated or directed and inclusive of one primer coat, and one under coat and one finished coat of aluminium paint complete all as specified. |
12 | S&F in repair MCCB63 Amp rupturing capacity16 kA 4 pole 415 volts fixed type all as specified and directedby Engr-In- Charge |
13 | S&F in repair MCCB 100Amp rupturing capacity 16 kA 4 pole 415 volts fixed type all as specified and directedby Engr-In- Charge |
14 | S&F in repair MCCB160 Amp rupturing capacity 36 kA 4 pole 415 volts fixed type all as specified and directed by Engr-In- Charge |
15 | S&F in repair MCCB200 Amp rupturing capacity 36 kA 4 pole 415 volts fixed type all as specified and directed by Engr-In- Charge |
16 | S&F in repair MCCB250 Amp rupturing capacity 36 kA 4 pole 415 volts fixed type all as specified and directed by Engr-In- Charge |
17 | S&F in repair MCCB350 Amp rupturing capacity 36 kA 4 pole 415 volts fixed type all as specified and directed by Engr-In- Charge |
18 | S&F in repair MCCB400 Amp rupturing capacity 36 kA 4 pole 415 volts fixed type all as specified and directed by Engr-In- Charge |
19 | S & F in repair connecting and testing change over switch 4 pole 415 volts on load of rating 63 Amp and including sheet enclosures complete including taking out to old u/s switch complete all as specified. |
20 | S & F in repair connecting and testing change over switch 4 pole 415 volts on load of rating 100 Amp and including sheet enclosures complete including taking out to old u/s switch complete all as specified. |
21 | S & F in repair connecting and testing change over switch 4 pole 415 volts on load of rating 200 Amp and including sheet enclosures complete including taking out to old u/s switch complete all as specified. |
22 | S & F in repair including taking down 1100 volts grade service cable with PVCinsulated aluminium conductor 6 Sq mm nominal cross section 2 core complete all as specified and directed by Engr-in-charge. |
23 | All as per item No 22 above but size 10 Sqmm 2 core |
24 | All as per item No 22 above but size 16 Sqmm 2 core |
25 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 2 core complete all as specified and directed by Engr-in-charge. |
26 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core complete all as specified and directed by Engr-in-charge. |
27 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core complete all as specified and directed by Engr-in-charge. |
28 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core complete all as specified and directed by Engr-in-charge. |
29 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core complete all as specified and directed by Engr-in-charge. |
30 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95sq mm 3.5 core complete all as specified and directed by Engr-in-charge. |
31 | M&L for cable end heat shrink type jointing kit 1100 Volts for indoor/outdoor termination with jointing material and accessories suitable for 35 Sqmm to 50 Sqmm 3.5 core XLPE/PVC armoured aluminium conductor cablecomplete all as specified and directed by Engr-in-charge. |
32 | M&L for cable end heat shrink type jointing kit 1100 Volts for indoor/outdoor termination with jointing material and accessories suitable for 70 Sqmm to 95 Sqmm 3.5 core XLPE/PVC armoured aluminium conductor cablecomplete all as specified and directed by Engr-in-charge. |
33 | M&L for cable end heat shrink type jointing kit 1100 Volts for indoor/outdoor termination with jointing material and accessories suitable for 120 Sqmm to 185 Sqmm 3.5 core XLPE/PVC armoured aluminium conductor cablecomplete all as specified and directed by Engr-in-charge. |
34 | M&L for cable end heat shrink type jointing kit 1100 Volts for indoor/outdoor termination with jointing material and accessories suitable for 225 Sqmm to 300 Sqmm 3.5 core XLPE/PVC armoured aluminium conductor cablecomplete all as specified and directed by Engr-in-charge. |
35 | M&L for painting of LT iron pole with cros arm angle etc with silver colour waterfroof enamal paint including scrabing the old surface with emery paper to remove old paint and applying one cot of primer all as specified and directed by Engineer-in Charge. |
36 | Supply, laying, jointing and testingin trenches,galvanized iron water tubing medium gradeof 80 mm bore including provision of allnecessary steel fittings/ accessories complete all as specified and directed |
37 | Supply, laying, jointing and testingin trenches,galvanized iron water tubing medium gradeof 40 mm bore including provision of allnecessary steel fittings/ accessories complete all as specified and directed |
38 | S & F in repair including taking down old unserviceable1100 volt grade copper conductor cable single core 2.5 sq mmall as specified and directed |
39 | S & F in repair PVC conduit pipe 25 mm all as specified and directed by Engineer - in - Charge |
40 | S&F in repair street light junction / pole box of size 250x200x150 mm made of MS sheet1.6 mm thick front openable with fixing screw painted with two coat of synthetic enamelled paint over a coat of steel primer with and including two nos aluminium bus bar 20x 3 mm mounted on epoxy based post insulator and drilled holes for cable connection including one nos MCB SP 6 Amp fixing onsteel tubular pole with MS strip of size 20x3 mm with suitable size nuts,bolts and washers all as specified and directed by Engr-in-charge |
41 | S & F security light brackets of GI pipe medium grade upto 1.2 mtr long bend to shape at 100-120 degree including arrangement of fixing at pole/wal/anglel with the help of flat iron clamps and suitable nuts and bolts including all material required for fitting, including matching the surface with existing all as specified and directed by EIC. |
42 | Supply and fixing in replacement of galvanised strip 32x6mm with fixing arrangement etc complete all as specified and directed. |
43 | Supply and fixing LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete with including suitable wire 2.5 sqmm copper conductor from junction box to light fitting in non metallic PVC conduit complete all as specified and directed. |
44 | Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. |
45 | M&L for earthing complete with GI steel earthplateelectrode 600x600x6mm burrieddirectlyin groundnotless than2.25mtr deepbelow normal ground level with top edgeof earth plate not less than 1.5mtr below normal ground level connected to the Galvanised iron wire 4mm dia by meansof bolts, nuts, check nuts andwashers of galvanised steel all as shown on electrical plateNo 3 of MES Sch 2009 Part-I connected to earthing test point and testing on completion with and including necessary excavation and earthwork, earth electrode, earthing lead from electrode to eqpt/sub stn , adequated quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 using 20mm graded black trap/granite/basalt stone aggregate, 40mm thick cover reinforced with 8mm dia bar 4 Nos both way with 12mm dia round bar handle, GI light grade watering pipe 20mm bore with funnel and wiremesh and 15mm dia GI light grade earth lead protection pipe up to equipments max length 7.5 mtr complete all as specified and directed by Engr-in-Charge.Note:- On testing after completion if the desired resistenance is not obtained the contrator shall redo the earthing without any extra cost to the department . |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy