Tender For Repair / Replacement Of Unserviceable Ltunderground Cable, Maintenance Of Unserviceable Lt Equipment, Control Gear, Lt Panel And Other Connected Items Including Load Balancing Of Externa Electric Supplyin X Area Af Stn Gurgaon Under Ge(Af) Gurg, gurgaon-Haryana

Military Engineer Services-MES has published Tender For Repair / Replacement Of Unserviceable Ltunderground Cable, Maintenance Of Unserviceable Lt Equipment, Control Gear, Lt Panel And Other Connected Items Including Load Balancing Of Externa Electric Supplyin X Area Af Stn Gurgaon Under Ge(Af) Gurg. Submission Date for this Tender is 20-05-2024. Gear Product Tenders in gurgaon Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

43264041
Tender For Repair / Replacement Of Unserviceable Ltunderground Cable, Maintenance Of Unserviceable Lt Equipment, Control Gear, Lt Panel And Other Connected Items Including Load Balancing Of Externa Electric Supplyin X Area Af Stn Gurgaon Under Ge(Af) Gurg
Open Tender
Indian
Haryana
gurgaon
20-05-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Repair / Replacement Of Unserviceable Ltunderground Cable, Maintenance Of Unserviceable Lt Equipment, Control Gear, Lt Panel And Other Connected Items Including Load Balancing Of Externa Electric Supplyin X Area Af Stn Gurgaon Under Ge ( Af ) Gurgaon No 1

Key Value

Document Fees
INR 500 /-
EMD
INR 88000.0 /-
Tender Value
INR 44 Lakhs /-

Attachment

FileName File Description File Size
1cf26cc0-af84-4d30-9f53-4a657dc4b670.html Tender Notice 0 KB
BOQ_728991.xls Tender Document 0 KB
TenderDocuments06.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

Name of Work :REPAIR / REPLACEMENT OF UNSERVICEABLE LTUNDERGROUND CABLE, MAINTENANCE OF UNSERVICEABLE LT EQUIPMENT, CONTROL GEAR, LT PANEL AND OTHER CONNECTED ITEMS INCLUDING LOAD BALANCING OF EXTERNA ELECTRIC SUPPLYIN X AREA AF STN GURGAON UNDER GE(AF) GURGAON NO 1
Sl. No. Item Description
1Schedule of Works
2M&L for detecting of fault in 1100 Volt cable of any size upto 400 Sqmm 3.5 core laid in trenc fault locating machine comprising of surg generator pulse,ECHO fault locator with high frequency distance calculator etc and exposing the cable fault,removal of deteriated portion of cable , treating of cable and making the same ready for jointing work complete all as specified and directed by Engr-In-Charge. Note: In case of fault occured fault detection and rectification of joint shall be carried out within 8 hours otherwise recovery of Rs 1000/- per hour shall be recovered from the contractors dues as a panlity.
3M&Lin repair for heat shrinkable jointing kit including suitable size of connectorcomplete all as per directed by Engr-in-charge. Note : Cost of necessary excavation and earth work , labour, Jointing kit complete, fixing charges & T&P including removing of grass/shrubs nearby the fault location shall be deemed to include in quoted rates) forthe following sizes :-
4XLPE Cable of size 25 sqmm to 50 Sqmm x 3.5/4 core
5XLPE Cable of size 70 sqmm to 120 Sqmm x 3.5/4 core
6XLPE Cable of size 185 sqmm to 240 Sqmm x 3.5/4 core
7XLPE Cable of size 300 sqmm to 400Sqmm x 3.5 core
8Supply and fixing in replacement cable route indicator for LT UG cable of 1100 Volts 80mm dia , 2mm thick CI plate marked on LT cable bolted with 40X5mm flat iron member of height 0.50 Metre , embedded in PCC 1:2:4 type B-2 using 40mm graded crushed stone aggregate of size 20X20X30cm block complete all as specified and directed.
9M&L for drilling hole underhard standing /road in different location as per site requirement (between 03 mtr to 12mtr maximum) for laying ofpipe for protection of cable etc by means of mannual bookle and without disturbing the top surfaceand making good the disturbed surface if any complete as sepecifiedand directed by Engr-in-Charge.
10Supply and laying GI tube medium grade 80 mm bore, ISI marked complete as sepecifiedand directed by Engr-in-Charge.
11Supply and laying GI tube medium grade 50 mm bore, ISI marked complete as sepecifiedand directed by Engr-in-Charge.
12M&L for load balancing of Single/three phase system at LT Panel upto Distribution box of any size and capacity complete including disconnecting of existing cables and refixing the same as per load balance requirement including replacement of burnt/carbonized aluminium tube terminal of any size and capacityall as specified and as directed by Engr-in-charge.Note : (i) Necessary eqpt and safety mesures reqd for load balancing arranged by the contractor without any extra cost. (ii)Cost ofNew aluminium tube terminal of any size as per site reqmt change under the job deemed to be included in the quoted rate (iii) Contractor shall also submit the written record of phase wise electric load on panels/transformer duly signed by contractor, JE & AGE.
13Supplying , laying ,passing through pipe , connecting and testingUG cable XLPE insulated ,armoured heavy duty electric cable with aluminium conductor ,1100volts grade of Following size (Note:- Excavation & earthwork etc shall be measured and paid sepretaly)all as specified and as directed by Engr-in-charge:-
14XLPE Cable ofsize 10 Sqmm, 2 Core .
15XLPE Cable ofsize 25 Sqmm, 3½ Core .
16XLPE Cable ofsize 50 Sqmm, 3½ Core .
17XLPE Cable ofsize 70 Sqmm, 3½ Core .
18XLPE Cable ofsize 95 Sqmm, 3½ Core .
19XLPE Cable ofsize 120 Sqmm, 3½ Core .
20XLPE Cable ofsize 185 Sqmm, 3½ Core .
21XLPE Cable ofsize 240 Sqmm, 3½ Core .
22XLPE Cable ofsize 400 Sqmm, 3½ Core .
23Excavation in trenches in soft/loose soil , not.exc 1.5 mtr wide and not.exc 1.5 mtr deep and getting out in soft/loose soil for laying of cable/foundation of pole and stay etc in complete as sepecifiedand directed by Engr-in-Charge.
24Removing excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above ground level from starting point complete as sepecifiedand directed by Engr-in-Charge.
25Returning filling including spreading, levelling, watering and well ramming in layers n.exc 25 cm complete as sepecifiedand directed by Engr-in-Charge.
26M&L for sand cushioning in trenches for protection of LT under ground cable including punning and consolidation complete as sepecifiedand directed by Engr-in-Charge.
27Supply and laying well burnt sub class ‘B’ bricks, locally available in trenches for protection of underground cable complete as sepecifiedand directed by Engr-in-Charge.
28Taking out old serviceable /unserviceable under ground cable of following sizes from trenches/poles /pipe/floor complete all as specified and as directed:-
2910 Sqmm 2 core to 25 Sqmm 3.5 core
3050 Sqmm 3.5 core to 120sqmm 3.5 core
31185 Sqmm 3.5 core to 400 sqmm 3.5 core
32M&L forPCC 1:2:4Type B2(40mm graded aggregate ) in foundation / allaround the panel with includingearth work reqdcomplete all as specifiedand as directed by engr-in-charge
33M&L forPCC 1:2:4Type Bo(12.5 mm graded aggregate ) in foundation / allaround the panel omplete all as specifiedand as directed by engr-in-charge
34S&F in replacementLT volt meter (0-500)digitalsquire flush type of size96x96 mm including necessary addition/ alternationofpanel including cutting/welding of front side of panel board /feeder to match the existing panel board/feeder including taking out of unserviceable Volt meter complete as sepecifiedand directed by Engr-in-Charge.
35S&F in replacement 1100 Volts grade LT Ammeter(0 - 300 A) digital squire flush & CT type with CT"sincluding necessary addition/ alternationofpanel including cutting/welding of front side of panel board /feeder to match the existing panel board/feeder taking out of unserviceable Ammeter complete as sepecifiedand directed by Engr-in-Charge.
36S&F in replacement 1100 Volts grade LT Ammeter(0 - 500 A) digital squire flush & CT type with CT"sincluding necessary addition/ alternationofpanel including cutting/welding of front side of panel board /feeder to match the existing panel board/feeder taking out of unserviceable Ammeter complete as sepecifiedand directed by Engr-in-Charge.
37M&L for Spray painting to LT panel board with synthetic enamel high glow paintIst gradeincluding preparation/cleaningof steel surfaces. complete as sepecifiedand directed by Engr-in-Charge.
38Supply and spray Grass herbicide with the help of kishan sprayer for cleaning the grass of Substation and other installations in airforce station Gurgaon complete all as specified by Manufacturer instruction. Make - Roundup Herbicide (Note:- Contractor shall produce purchase voucher of chemical duly defaced by Engg-in-charge at the time of payment of RAR / Final Bill. Non submission can lead to non payment of item.)
39M&L for steel tubular swaged pole complete with cast iran base plate, finial taper plug, bolt, nut, screws as specified type 410- SP-31 (9mtr long), incl earth work and PCC 1:3:6in pole foundation and PCC 1:2:4 in coppingcomplete all as specified and directed by engineer in charge
40Supply and fixing aluminium thimble , cable glandand lux after disconnecting from panel and taking down burnt cable from panel of different location and cutting out the burnt portion of cable and extended the cable from cable loop, preparation of cable including necessary connection and testing complete (Note : (i)01 Job consisting of 04 Nos Lugs/thimble at one end of cable(ii) Rate of necessary earth work for opening of loop if requried at site are deemed to be included in the quoted rate.)of following sizes :-
4150 Sqmm 3.5 core 1100 volt grade
4295 Sqmm 3.5 core 1100 volt grade
43120 Sqmm 3.5 core 1100 volt grade
44240 Sqmm 3.5 core 1100 volt grade
45300 Sqmm 3.5 core 1100 volt grade
46400 Sqmm 3.5 core 1100 volt grade
47S&F in replacement of MCCBsfix thermal and fixed magetic setting including necessery fixing arrengement & testing completeas sepecifiedand directed by Engr-in-Charge of following sizes:-
48(a)100 Amps 4 Pole breaking capasity 35/36 KA .
49(b)125 Amps 3 Pole breaking capasity 35/36 KA .
50(c)160 Amps 4 Pole breaking capasity 35/36 KA .
51(d)160 Amps 3 Pole breaking capasity 35/36 KA .
52(e)200 Amps 4 Pole breaking capasity 35/36 KA .
53(f)200 Amps 3 Pole breaking capasity 35/36 KA .
54(g)250 Amps 4 Pole breaking capasity 35/36 KA .
55(h)250 Amps 3 Pole breaking capasity 35/36 KA .
56(j)400 Amps 4 Pole breaking capasity 35/36 KA .
57(k)400 Amps 3 Pole breaking capasity 35/36 KA .
58(l)630 Amps 4 Pole breaking capasity 50 KA .
59(m)630 Amps 3 Pole breaking capasity 50 KA .
60M&L for preparation of old painted surface of electric RCC pole by removing all dirt, dust etc and apply approved colour one coat of syhnthetic enemal paint upto 1.5 mtr height (Five layer 30 cm Blue and 30 cm White one over another) and one coat of synthetic enamel paint on steel surface such as cross arm including writing of identification No , etc complete all as specified and directed.
61All as per item No 25 herein beforebut one coat of aluminium paint on steel tubular pole.
62M&L for LT pin type porceline , vitreous, white , brown or green insulator including one galvanised mild steel spindal , washers , two galvanised iron washers and one galvanised iron nut100 mm height , 115 mm dia for 1100 voltscomplete all as specified and directed by Engr-in-Charge.
63Supply and fixing in replacement ofstay assembly complete with 16mm dia stay Rod including PCC 1:3:6 type C-2 complete all as specified and as directed by Engr-in-charge. Including excavation, earth work ,returning,filling and removal of surplus soil from site
64S&F danger notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white with letters,figures and conventional skull and bones in signal red colour and fixed with MS clamps,bolts and nuts of approved siz,for LT ,20X15 cm size complete all as specified and as directed.
65M&L for surface dressing and proper laying of XLPE electrical cable of any size and capacity nearby the LT Panel after disconnecting all incoming and outgoing connection complete including cleaning of grass nearby the LT Panel upto 2mtr all around , necessary earthwork as required all as specified and as directed by Engr-in-charge.(Note : Rate of necessary earthwork as required at site are deemed to be included in the quoted rate)
66Supply, laying/fixing, jointing and testing of 1100 volts grade heavy duty cable PVC insulated aluminium conductor , served with inner sheathing of PVC tape and overall PVC sheathed in service connection of size 10 Sqmm 2 core single stranded as in repair complete as sepecifiedand directed by Engr-in-Charge.
67M&L in repair for PCC pole , 9 mtr long, 102 mm x 172 mm at top and 12mm x 279 mm at bottom class 10 complete including excavation & earth work, PCC 1:4:8 type-D-2 in pole fdn & PCC 1:3:6 type C-1 in coping of pole complete as sepecifiedand directed by Engr-in-Charge.
68Supply only Synthetic insulating mat of size 2Mx1Mx10mm thick ISI marked complete as sepecifiedand directed by Engr-in-Charge.
69Supply only Synthetic insulating mat of size 2Mx1Mx12mm thick ISI marked complete as sepecifiedand directed by Engr-in-Charge.
70M&L formain switch Side handle of capacity 200 Amps , 415 Volts , 3 pole with sheet metal enclosure complete all as specified and directed by Engr-in-charge.
71M&L for re-stringing of ASCR conductor of any size/dia by removing sag in between the line including disconnecting ACSR conductor from both side to overhead line and rejoining after repair work complete all as specified and directed by Engr-in-Charge.
72M&L for providing PVC rigid spacer for 4 line LT overhead line complete all as specified and directed by Engr-in-charge.
73M&L for Change over switch of capacity 250 Amps , 415 Volts , 4 pole with sheet metal inclosure complete all as specified and directed by Engr-in-charge.
74M&L for Chang over switch of capacity 400 Amps , 415 Volts with sheet metal inclosure complete all as specified and directed by Engr-in-charge.
75M&L for Chang over switch of capacity 630 Amps , 415 Volts , 4 pole with sheet metal inclosure complete all as specified and directed by Engr-in-charge.
76M&L for Chang over switch of capacity 100 Amps , 415 Volts, 4 pole with sheet metal inclosure complete all as specified and directed by Engr-in-charge.
77Taking down existing old LT panel board/ LT feeder pillar box comprising of MCCB & switch fuse unit of any capacity and size includingbus bar ,ammeters, voltmeters etc after disconnectingall cable connection and removing from site complete all asdirected.
78Supply, installation, commissioning and testing in replacement of LT panel board double door outdoor type floor mounted of factory made powder coated made out of outside body of 3.15mm thick steel sheet and inside body 14 gauge steel sheet, locking arrangement, front side and rear side opening arrangement of suitable size, Includingmounted on Angle iron stand of size 50x50x6mm having minimum height 1.5 feet duly grouted or welded on floor. Aluminium bus bar TPN of 630 A for MCCB to all feeders to accommodate following items:-TheQuoted price of this Panel will also include following items and should accomodate in this panel: -(a) Incoming MCCB (Adjustable Thermal and fixed magnetic)400 Amp 35/36 KA 4pole-01 No. (b) Changeover Switch 400 Amp TPN- 01 No (c) Outgoing MCCB (Fixed thermal and fixed magnetic) 250 amp 35/36 KA 4pole -02 No.(c) Outgoing MCCB (Fixed thermal and fixed magnetic) 100 amp 35/36 KA 4pole -03 No. (d) RYB indicating lamp for each incoming & outgoing supplies-1set (e)Voltmeter, amp meter, with CT’s &selector switch-01 set.(f) Termination of all cables with suitable size thimble and gland-1job and all auxillary items required Note-This item also includes separate Steel Roof with four leg for panel whose leg should be grouted with RCC . Note- The panel should be installed on PCC plinth of height 1.5 feet above gronud level and and base should be proper depth and the making of plinth amount included in this item.
79Note:- The amount of Rs 2,67,735/- against Schedule of Credit on Page No 113 shall be deducted from the total amount quoted against Sch "A"while deriving the Contract Sum for Acceptance