Military Engineer Services-MES has published Tender For Provision Of Sewage Treatment Plant And Allied Work Services In Tech Area At Afs Bidar. Submission Date for this Tender is 03-06-2024. Sewage Treatment Plant Tenders in bidar Karnataka. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 07-May-2024 | Corrigendum No 01 | Other | 03-06-2024 |
2 | 07-May-2024 | Corrigendum No 01 | BOQ | 03-06-2024 |
3 | 10-May-2024 | Corrigendum No 02 | Other | 03-06-2024 |
FileName | File Description | File Size |
55db071f-4f76-4f4a-a13d-24c644e08eee.html | Tender Notice | 0 KB |
85614ALLDRAWINGS.pdf | Tender Document | 0 KB |
85614TENDER.pdf | Tender Document | 0 KB |
BOQ_729329.xls | Tender Document | 0 KB |
Tendernotice_1.pdf | Tender Document | 0 KB |
Sl. No. | Item Description |
1 | GENERAL SUMMARY NOTE : - Schedule "A" Part-I & Part-II are not prepriced by MES. Bidder shall insert their rates in Green coloured field under Column No 6 and Schedule ‘A’ Part III to VIII are prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 Only. |
2 | Lumpsum Price worked out by the contractor for “Sewage Treatment Plant” as listed in Schedule ‘A’Part–I and as Shown in Drawings. |
3 | Lumpsum Price worked out by the contractor for “Site Clearance and Area Development” as listed in Schedule ‘A’Part–II |
4 | Lumpsum Price worked out by the contractor for "Excavation and Earth Work” as listed in Schedule ‘A’Part–III |
5 | Lumpsum Price worked out by the contractor for “Treated Water Sump” as listed in Schedule ‘A’ Part – IV. |
6 | Lumpsum Price worked out by the contractor for “Path" as listed in Schedule ‘A’ Part V . |
7 | Lumpsum Price worked out by the contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part – VI. |
8 | Lumpsum Price worked out by the contractor for “EXTERNAL ELECTRIC SUPPLY” as listed in Schedule ‘A’ Part – VII |
9 | Lumpsum Price worked out by the contractor for “Sewage Disposal” as listed in Schedule ‘A’ Part-VIII |
10 | SCHEDULE "A"PART - IX MISC ITEMS : EXTERNAL WATER SUPPLY :- Pumping sets, centrifugal, electric driven, supplied and installed complete up to 15 WHP inclusive of starter and PCC foundation.(01 workng + 01 standby) complete all as specified and as directed |
11 | Supply and lay 80mm dia pipe galvanized, “Medium class”, including fittings complete all as specified and as directed . |
12 | Supply and fix 50mm dia Cast Iron Air Valves with single air Outlets, conforming to IS 14845 complete all as specified and as directed. |
13 | EXTERNAL ELECTRC SUPPLY :- Supply, Install, Test and commissioning LT panel board indoor type floor mounted made out of 2 mm thick CRCA sheet mounted on frame angle iron of suitable weather proof / vermin proof shutter type with locking arrangement of cubical type prewired with aluminium busbar 400 Amps for 03 phases and aluminium busbar 300 Amps for neutral including suitable CTs etc and powder coating painting, angle iron frame base 75 x 75 x 6mm with the necessary excavation, PCC etc complete comprising of the undermentioned MCCBs alongwith extendable bus bars for termination of cables to be connected to the following MCCB:- (STP Panel Bd) (a)MCCB 4 pole 250 Amps 35 KA -01 No ( incoming) (b)MCCB 4 pole 100 Amp25 KA- 04 Nos (02 for STP of 100 KLD Capacity + 01 for Sewage pumps LT Panel Board + 01 for Treated Water pump Panel) (c) MCCB 4 pole 32 Amps - 03 (For street lights + internal electrification + spare) (d) Time switches 415 V three Phase of 20 Amp rating with contactor fitted inside steel enclosure - 01 No (e)Digital type Ammeter 0-300 Amps capacity with CTs and rotator switch - 01 No (f) Digital type Voltmeter 0 - 500 volts capacity alongwith selector switch- 01 No (g) Indicating Lamps R, Y, B set of 03 Nos - 01 Set |
14 | Supply, Install, test and commissioning LT panel board indoor type floor mounted made out of 2 mm thick CRCA sheet mounted on frame angle iron of suitable weather proof / vermin proof shutter type with locking arrangement of cubical type prewired with aluminium busbar 200 Amps for 03 phases and aluminium busbar 200 Amps for neutral including suitable CTs etc and powder coating painting, angle iron frame base 75 x 75 x 6mm with the necessary excavation, PCC etc complete comprising of the undermentioned MCCBs alongwith extendable bus bars for termination of cables to be connected to the following MCCB:- (For Treated Water pump) (a)MCCB 4 pole 100 Amps 25 KA -01 No ( incoming) (b)MCCB TP 40 Amp25 KA- 02 Nos for treated water pumps (c)Star delta starter 15 HP- 02 Nos( for treated water pump) (d)Digital type Ammeter 0-60 Amps capacity with CTs and rotator switch - 01 No (e) Digital type Voltmeter 0 - 500 volts capacity alongwith selector switch- 01 No (f) Indicating Lamps R, Y, B set of 03 Nos - 01 Set |
15 | M&L 200mm DWC HDPE pipes with one collar per length of pipecomplete all as specified and as directed |