}

Tender For Increasing Capacity Of 33/11 Kv Sub Station Fatehpur Tehsil From 2X5 Mva To 5+10 Mva Distt Barabanki, barabanki-Uttar Pradesh

Madhyanchal Vidut Vitran Nigam Limited has published Tender For Increasing Capacity Of 33/11 Kv Sub Station Fatehpur Tehsil From 2X5 Mva To 5+10 Mva Distt Barabanki. Submission Date for this Tender is 06-05-2024. Transmission Line Tenders in barabanki Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

43257874
Corrigendum : Tender For Increasing Capacity Of 33/11 Kv Sub Station Fatehpur Tehsil From 2X5 Mva To 5+10 Mva Distt Barabanki
Open Tender
Indian
Uttar Pradesh
barabanki
06-05-2024

Tender Details

Tender For Increasing Capacity Of 33 / 11 Kv Sub Station Fatehpur Tehsil From 2X5 Mva To 5+10 Mva Distt Barabanki

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 04-May-2024 Date E Date 06-05-2024

Key Value

Document Fees
INR 1180 /-
EMD
INR 5400.0 /-
Tender Value
INR 5.34 Lakhs /-

BOQ Items

Name of Work: INCREASING CAPACITY OF 33/11 KV SUB STATION FATEHPUR TEHSIL FROM 2X5 MVA TO 5+10 MVA DISTT BARABANKI
Sl. No. Item Description
1SafeLoading, Carriage and then safeunloading of the following material from Store Centres Under the jurisdiction of EEESD Ayodhaya to dump site proper stacking.
2Bus Isolator
333 KV Lightening Arrestor
411 KV Out going switch gear 200/100/5A0250MVA
5ACSR Dog Conductor
611 KV 3 Core Cable 3x300 mm XLPE
711 KV cable jointing kit indoor 3x300 sq.mm. XLPE
811 KV cable jointing kit outdoor 3x300 sq.mm. XLPE
911 KV Cable 3x185 sq. mm XLPE
1011 KV cable jointing kit indoor 3x185 sq.mm. XLPE
1111 KV cable jointing kit outdoor 3x 185 sq.mm. XLPE
12ST Pole 11Mtr
13M.S.Angle iron 65x65x6 bracing 2700 mm
1411 KV Top channel 100X50X2240 mm
15Dropper channel
1611 KV Polymer pin insulator
17Stay wire 7/10
186 SWGWire
19M.S. Channel 125x65 (for Structures)
20M.S. Angle 75x75x8 (for Structures)
21Opening of all the 33 KV Jumpers, Neutral connections, cable connections, opening of earth strips and then shifting of 5 MVA T/F from plinth to Other side(temrorary plinth) in yard.
22Shifting 33 KV Jumpers, from actual position to the new shifted place along with 11 KV cable and other accessories for maintaining & restoring the S/S supply
23Plinth of 10 MVA, 33/11 KV T/Fs Expansion of Plinth of size 3.46x3.46 Mtr for10 MVA T/F having 0.4 Mtr above ground level. The work includes Excavation of foundation, Base concreting in C.C. 1:6:12 ratio ( cement,fine sand and Brick ballast) 1ST Class bricks work in cement mortar of ratio 1:4 foundation, C.C. in 1:4:8 ratio( cement, fine sand and brick ballast) and RCC working ratio 1:2:4 ( cement, coarse sand and stone grit of 20 mm gauge) using MS Bars of 10 mm Dia (Tor) in reinforcement including its cutting, bending and binding in required shape. The work also includes laying of 2 Nos. 3.46 mts long each rail pieces complete with cutting, welding and proper fitting etc. The plinth will be made as per Drawing and shall be plastered/ finished on Top and Side of the plinth. (All the material will be supplied by the Contractor except rail Piece)
24H.T. Cable Laying Laying & dressing of 11 KV, 3x300 and 3X185 Sq.mm XLPE cable underground from 10 MVA T/F to 11 KV incoming switchgear in the trench 450mm wide, 900mm deep, providing 150mm fine sand cushion bench and 150mm fine sand cushion above the cable. The cable shall be duly protected by 1st class bricks two either side and third on top of the cables, laid in series one after the other, the work includes supplying offine sand and bricks, refillingand rammingof the left out soil, closing the trench and leveling. Spare cable shall be left and buried in the trench in the safe of rings at both ends. Cable laying work includes unrolling, cutting, meggering and sealing both end of the cable.(All the material will be supplied by the contractor)
25Erection and Installation of 33/11 KV 10 MVA Transformer Dragging of 33/11KV 10 MVA T/F from Dump site to road site and shifting of the T/F from road site to new constructed plinth distance about 150mtr ,along with loading, unloading and carriage, fixing and fitting of all the accessiories and filling of T/F oil to the desired level and insuring that there is no leakage. Erection and installation of 33/11 Kv, 10 MVA Transformer in a leveled position on the plinth.
26Installation of Lightening Arrestors Assembling and installation/ mounting of Lightening Arrestors on the L.A. structure/ complete with making earth connection ( Separate ) and line connections. The work includes fabrication for proper fixing if required.
27Installation of Switchgears in Control room Shifting carefully and safely 11 Kv incomingSwitchgear, 11 KV outgoing Switchgear and 11 KV Bus Coupler from out side of the switch gear room, as per direction of Engineer Incharge, Placing and fixing of switchgear on foundation providing nuts & bolt of proper size in proper position and alignment and mountting of P.T. on incoming S/G.
28Installation of Bus Isolators Assembling and installation of Bus isolator on the Isolator structure , adjusting of opening mechanism in proper alignment and grising and oilingso as to ensured smooth operation of the same. In case of line Isolator proper operation of earth links shall also be ensured. The work includes fabrication for proper fixing if required.
29Fixing and making Bus Bar connection in between I/C and O/Gswitchgears after cleaning and tapping with H.T. tape, Empire tape and PVC tape properly providing and fixing of 6mm thick bakelite seperators and plugging of all opening and holes with plastic compound. complete work including cost of all materialStrictly to the satisfaction of site incharge.
30Installation of Heat Shrinkable Type cable jointing kits indoor and O/D end Termination and S/T Joint suitable for 11KV 3X300 & 3X185 XLPE cable confirming to IS ESI-09-13-IS-13573 of 1992 amendment I&II VDE-0278 of latest version there of if any.
31Cable stand Structure Fabrication & erection of 11 KV Cable Stand made of 02 No. M.S chanel 125x65x6 mm 3 Mtr. Jointed to each other by M.S Channel horizontally and also jointed to each other by means of 05 No. M.S Strip (m.s flat) 50x6 mm of size 200 mm long each by welding at actual distance interval as per norms. And grouting in block of 300x300x700 completely providing 02 no. cable clamps also and eathing by G.I strip 50x6 mm size with the earth mat of switchyard both side of legs and provideing clamps , post/ pin insulator for holding cable. (All the materials will be arranged by the contractor such that clamps nut bolts and civil materials except M.S channel.)
32Construction of 11 KV Double pole Safe Dragging/ Loading - unloading from dump site to pit site and Fabrication & erection forDouble pole for 11 KV feederon 11.0 Mtr ST Pole with fitting of necessary clamp & other acessories like 1 No Top channel,Bracing angle 1 set., Disc insulator 3 No. as per norms. (Contractor shall provide , necessary clamps, Disc Fitting, Nut - Bolts etc.)
33Provding, fixing and mounting of following equipments(All the material will be supplied by the contractor)
3411 KV TPMO switch with holding clamps and proper size of fixing channel.
3511 KV Fuse set with holding clamps and proper size of fixing channel.
36Grouting of following structure by digging of pit 1.83 Mtr deep for 11 Mtr STP,with 1:4:8 Ratio cement, sand & first class brickballast0.285 cu mtr for 11 mtr STP, plinthing 0.3 Mtr above G/L and proper plastering.
37Providing and fixing of earth rod for earthing of support by G.I. Wire 6 SWG as per norms. (All materialwill be arranged by the contractorLike earth rod except 6 swg wire)
38Nozeling and grouting of stay set. (All the civil material and stay set will be arranged by the contractor except Stay wire)
39Painting of Structure Painting of 11 Mtr ST Pole with one coat of ready mixed primer and 2 coats of AL.Paint of good quality including cost of material, Labour and T&P complete in all respect.
40Neutral stand Fabrication and grouting of M.S Channel 125x65 mm L shape & in proper size and allignment to provide support for the two separate earthing strips for pwer T/F neutral including supply & fixing of two No.Flexible copper bonds for neutral earthing. (All the materials will be arranged by the contractor such that clamps nut bolts and civil materials except M.S channel.)
41Hoisting of 11 KV Cable on existing/erected support with provision of MS Pipe 150 mm dia 3 mtr long suitable for 3x185 sq mm cable fixing of proper support and its clamping , providing long barral lugs 6 nos and P.G. Clamps & "Y" shapejumpering properly and 02 nos. supporting angle 65X65X6, 2800 mm as per RESSPO Norms. (All material will be supplied by the contractor like MS Pipe , P.G. Clamps, Al. Lug And Supporting Angle 65X65X6, 2800 mm).
42Supply & Laying of 6x2.5 sq.mm. armoured. control cable from power T/F to controle board in the ground as per RESPO Norm with proper connection VCB, CT & Control Pannel with T/F to battery and battrey charger, Bucholz Relay, low higher and winding temperture protection alarm etc with including all the civil material. (All the material will be supplied by the contractor)
43Supply & Laying of 4x2.5 sq.mm. armoured control cable from power T/F to controle board in the ground as per RESPO Norm with proper connection VCB, CT & Control Pannel with T/F to battery and battrey charger, Bucholz Relay, low higher and winding temperture protection alarm etc with including all the civil material. (All the material will be supplied by the contractor)
44Supply & Laying of 2x2.5 sq.mm. armoured. control cable from power T/F to controle board in the ground as per RESPO Norm with proper connection VCB, CT & Control Pannel with T/F to battery and battrey charger, Bucholz Relay, low higher and winding temperture protection alarm etc with including all the civil material. (All the material will be supplied by the contractor)
45Special Earthing by way of boring and lowering of "B" class G.I. pipe 50 mm Dia 20mtr longfrom ground upto the water level andit will be connected to the G.I. strip 50X6 mm ( Providing & laying of G.S. strip including cutting, welding, bending etc.) for equipments(L.A,T/F,C.T., VCB.etc). The earth strip will be welded to the G.I. Pipe. The work also includes Cap & Clamps for pouring water, the cost of all material with all labour & T&P etc. Complete in all respect. (All the material will be supplied by the contractor)
46Construction of control cable trench of 200 mm wide and 300 mm deep with MS strip at a distance of 1mtr. With brick work 1:4:8 in foundation 12 mm thick plaster of 1:4 cement coarse sand for finishing along with MS strip. (All the material will be supplied by the contractor)
47Construction of trench cover of 600 mm long and 75 mm thick for cable trench Including cost of material, labour and T&P. (All the material will be supplied by the contractor)
48Painting ofAll switchyard Sub Station Structures (Old+New+fencing) with one coat of ready mixed primer and 2 coats of AL.Paint of good quality including cost of material, Labour and T&P complete in all respect.
4933 KV Bay Bus Bar & Stringing. Stringing of 33KV Bay Bus Bar by using and laying of ACSR Dog Conductor/panther including making Vertical/Horizontal (Y-shape) jumperconnection through PG clamps and connecting all the equipments ( Bus isolator, P.I. , C.T. , VCB, L.A & T/F) with each other through connecting clamps.(All the material will be supplied by the contractor)
50Delta type Earthing of Power T/F Neutral Earthing of Power T/F Neutral by providing 03 No. of "B" class G.I. pipe 50 mm Dia 20 feet longfrom ground upto the water level (Delta type) and Providing and laying G.S. strip 50 x 6 mm including cutting, welding, bending etc. complete in all respect.(All the material will be supplied by the contractor)
51Commissioning of 10 MVA T/F and its eqipments installed in switchyards and 11 KV Incoming and Outgoing Pannels complete in all respect upto energising
52Providing of Rubber matting one side chequered and other side plane size1800x900x12 mm
53providing of Hand gloves As per IS 4770 and tested potential 33 Kv.
54Providing and fixing of P.G clamp for dog and connector
55Breaking the concrete fencing/ Boundary wall in the switchyard of sub. Station for moving 10 MVA Transformer in switchyard after complition the work covered and restore the wall
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail