Paschimanchal Vidyut Vitran Nigam Limited has published Carrying Out The 04 Nos. Work In Head Construction Of 11 / 0.4 Kv Lt Substation At Various Places As Per Dpr S.No. 1, 2, 3, 4 And 04 Nos. Work In Head I / C Of 11 / 0.4 Kv Lt Substation At Various Places As Per Dpr S.No. 1, 2, 3, 4 In Area Of Eudsd-I / Iv. Submission Date for this Tender is 25-05-2024. Electrification Work Tenders in noida Uttar Pradesh. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 03-May-2024 | DATE EXTENSION | Date | 04-05-2024 |
2 | 04-May-2024 | DATE EXTENSION 2 | Date | 09-05-2024 |
3 | 09-May-2024 | DATE EXTENSION 3 | Date | 15-05-2024 |
4 | 15-May-2024 | DATE EXTENSION 4 | Date | 20-05-2024 |
5 | 20-May-2024 | Date Extension 5 | Date | 25-05-2024 |
FileName | File Description | File Size |
a3bf7286-e285-4b07-a846-52baffaebc7b.html | Tender Notice | 0 KB |
BOQ_1595070.xls | Tender Document | 0 KB |
DOC.pdf | Tender Document | 0 KB |
Tendernotice_1.pdf | Tender Document | 0 KB |
Sl. No. | Item Description |
1 | Cartage of following material from ESC Noida/Sahibabad/ Ghaziabad /Any other ESC of Meerut Discom to JE Store and from JE store to various points site of work including loading and unloading at both ends : - |
2 | ST Pole 11 Mtr. Long |
3 | PCC Pole 8.5 Mtr. Long |
4 | 11 KV Disc Insulator T&C Type |
5 | 11 KV Disc fitting |
6 | 11 KV Pin Insulator |
7 | 11 KV Pin with nuts |
8 | 11/0.4 KV T/F 250 KVA |
9 | 11 KV TPMO |
10 | 11 KV Fuse Set |
11 | LT PVC Cable Al. 1x400 Sq.mm. |
12 | LT XLPE Cable 3.5x400 Sq.mm. |
13 | ACSR Dog Conductor |
14 | Cable LT ABC (3x120+1x95+1x16) Sq.mm. |
15 | 3 Phase Distribution Box |
16 | MS channel (Dropper) 100x50x2028mm |
17 | MS channel (Top) 125x65x2240mm |
18 | MS channel for Fuse Set 100x50x2028mm |
19 | MS channel (T-Off) 125x65x1300mm |
20 | Earthing Complete |
21 | Stay Set Complete |
22 | Providing & fixing of following material of standard make / best quality for complete the work of pole structure at HT / LT line as per RESPO norms by the contractor at his own cost : - |
23 | Stone Pad 300x300x75mm |
24 | MS Holding Clamp |
25 | ST Pole clampwith nut & bolt |
26 | clamp with nut & bolt |
27 | Suspension clamp with I-Hook |
28 | Dead End clamp with I-Hook |
29 | LT piercing connector for size 120/95 Sq.mm. |
30 | Al. Crimping Lug 400 Sq.mm. |
31 | Al. Crimping Lug 240 Sq.mm. |
32 | Al. Long Barrel, Off Size (LS) |
33 | Dismantling of following item from various site of work and carriage from work site to J.E"s store / central store including loading & unloading at both ends. |
34 | 100 KVA 11/0.4 KV T/f Old & Used |
35 | ST Pole 11 Mtr. long old & used |
36 | Iron Scrap |
37 | 11/0.4 KV T/F 160 KVA |
38 | Laying and pulling of LT / 11 KV Cable DTs to ACBs to LT line, loop & riser complete in all respects. |
39 | Hoisting of cable on double pole structure through GI pipe 6 inch dia 3 mtr long fixed on pole structure including its jumpering complete with clamps, bolts and nuts. |
40 | The Excavation of foundation pit in CC road/ mix soil/ normal soil/ soft & hard rack by using heavy duty compressor and its back filling and leveling etc. The size of the pit will be 600x600x1800 mm for each pole and having a depth of 1/6 of the full length of the support. |
41 | Fabrication of MS channel / Angle as per site requirement complete in all respects. |
42 | Erection of S.T. pole 11 Mtr. including fitting of all reqired accessories of HT/LT line as per RESPO schedule. |
43 | Erection of PCC pole 8.5 Mtr. including fitting of all reqired accessories of HT/LT line as per RESPO schedule. |
44 | Grouting & concreting of each pole (In ratio of 1:4:8 in Cement, sand and Brick Ballast) in size 450mmx450mmx1800 mm as per RESPO schedule Complete in all respects. |
45 | Construction of Plinth in size 450x450x300 mm of each (0.880 Cu.m) pole above the ground level(In ratio of 1:3:6 in Cement, sand and Brick Ballast) as per RESPO schedule Complete in all respects. |
46 | Fixing of 11 KV TPMO. |
47 | Fixing of 11 KV Fuse Set. |
48 | Fixing of 3 Phase Distribution Box. |
49 | Grouting & concreting of stay rod 1800x16 mm & Fixing, Tighting & nozzling of stay wire 5 kg with the pole of required tension with clamps, bolt & nut. |
50 | Excavation of earth and driving of M.S. earthing rod of size 20x2500 mm in earth and jointing through G.I wire of 6 SWG between support and earth electrode by providing proper size of bolts and nuts etc. as per RESPO schedule Complete in all respects. |
51 | Laying, Lifting and final Binding, Sagging of ACSR Dog Conductor including fixing of all accessories as per RESPO schedule Complete in all respects. |
52 | Laying, Lifting and final Binding, Sagging of Cable LT ABC (3x120+1x95+1x16) Sq.mm. including fixing of all accessories as per RESPO schedule Complete in all respects. |
53 | Construction of new distribution 250 KVA T/F Plinth. The size of plinth shall be 2 Mtrs. long, 2 Mtrs. wide and height 1.5 Mtrs. from ground level with 15 CM thick top CC slab. The above work includes Excavation of earth, laying of bring ballast pad for foundation brick work, CC and plastering and proper curing complete with all respects as per RESPO schedule. |
54 | Construction of new distribution 250 KVA T/F Chair. The size of chair shall be 2 Mtrs. long, 2 Mtrs. wide and height 1.5 Mtrs. from ground level complete in all respects as per RESPO schedule. |
55 | Mounting, installation of 250 KVA T/F Transformer on above Plinth, Chair & existing plinth, alongwith double earthing of the same, complete in all respect as per RESPO schedule. |
56 | Providing and installation ofLT ACB630 Amp. with cabinet / structure (L&T, Schneider, ABB, Hevell"s, PVVNL approved make) as per following specification with all relevant certificate :- |
57 | 630 amp. 03 pole fixed manual ACB. |
58 | Red/yellow/blue light indication |
59 | ON & OFF Indication |
60 | Amp., Voltmeter& energy meter digital |
61 | Metering C.T 630/5A, |
62 | Panel fabrication of size 1250mm x 900mm x 600 mmmade of M.S sheet 14 gauge with powder coating with panel lock and key arrangement.(two nos). and additional locking arrangement seprately including providing hut type shape as per drg. |
63 | Fabrication ofaluminium bus-bar for each phases |
64 | Incoming size 425 mm x 50mmx12 mm (twin) |
65 | Out going size 720 mm x 50mm x 12 mm(twin) |
66 | Neutral size 900mmx50mmx12 mm. |
67 | Fabrication of pannel stand made of M.S Angle of size 900mm x 600mm x 500 mm as per drg. |
68 | Assembly of above ACB, Indicators, Meters, Metering CT & bus bar arrangment in the panel, fitting the panel on Stand with nut and boltswith wiringetc. & grouting inratio 1:4:8 with cement, coarse sand and brick blast. |
69 | Providing and fixing of aluminium bus bar of size 300mmx60mmx12 mm on L.T side of T/F. |
70 | Making all connections with ACB & Distribution T/F and commissioning the ACB complete in all respect. |
71 | WORK OF PROVIDING AND FIXING OF 6 NOS. NEW WIREMESH FENCING OF 11/0.4 KV L.T. SUB-STATION INSTALLED AT ABOVE PLACE AS PER FOLLOWING(All Material provided by contractor for above work.) :- |
72 | 1. Frames of size 12"X15"x6" for each fencing of LT Sub-stations. (All Material provided by contractor for above work.) 2. The fencing shall be fabricated out of MS angle iron of size 40x40x5 mm having 2 Nos. legs of 45 Cm. long in each frame duly welded and fixed with wire mesh of size 75mm 25mm, 10 SWG within the frame, pressed under MS flat of size 25x5 mm inside the angle iron on all four sides with the help of duly Welded along with cross bracing of 25x5 mm MS flat on every frame will be grouted in 1:2:4 cement mortar with cement, coarse sand 20 mm gauge stone ballast. 3. Every frame after Fabrication will be painted with one coat of red oxide and two coats of Green synthetic enamel paint of approved make after proper cleaning. 4. The above mentioned frame will be jointed with each other with 70 mm long MS flat of size 25x5mm by first class welding as per site. 5. Fabrication and providing of wire mesh fencing frame for gate of size 4’x6’. Fabricated as per above specifications with proper locking arrangement. |
73 | Construction of boundry / toe wall in bottom of fencing in brick work cement mortar 1:6 (1 cement : 6 coarse sand) for link in the size of 0.22mx0.60m (0.30m in earth, 0.30m above ground level) including plaster in cement mortar 1:4 and finishing with water proof cement paint. (Approx construction 12 Mtrs. boundry / toe wall for each fencing of LT Sub-stations.) (All Material provided by contractor for above work) |
74 | PROVIDING AND INSTALLATION OF CHEMICAL EARTHING FOR 250 KVA TRANSFORMERS (BODY & NEUTRAL) AND ACB (WITH ALL MATERIAL AND LABOUR) AFTER INSTALLATION RESISTANCE SHOULD BE LESS THAN ONE OHM. AS PER FOLLOWING (The all material and labour shall be provided by the contractor with 12 month guarantee for resistance value less than one OHM.) :- |
75 | Providing of earth elctrode for chemical earthing Pipe in pipe typeproper hot deep galvanization dia 50 mm length 3 mtr- 32mm x 6mmterminal connection hole dia 8mm The cavity between the pipe & pipe is filled with conductive mixture - for hermetically filling inside the cavity i.e. between secondary conductor & primary conductor, crystalline compound is to be injected in the electrode assembly. It is a combination of high conductivity metal alloys, copper & aluminum power, conductive carbon / cement and bonding material etc the electrode should be sealed from both the ends. The outer pipe of the elctrode should be galavanized the characteristics of this compound is highly cnductive, non magnetic & non corrosive in G.I. Including providing of backfill compound each elctrode should be supplied with bags of 25 kg x 2 bfc compound (ground resistance enhancement powder 50 kgs each CPRI tested for 250 KVA distribution t/f & ACB installed at Above 11/0.4 KV L.T. Substation. |
76 | Providing and fixing of GI strip of size 32 mm x 6 mm suitable for 250 KVA distribution t/f & ACB installed at Above 11/0.4 KV L.T. Substation. |
77 | Providing and fixing of PVC Pit covers for above earthing electrode terminals. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy