Public Health Engineering Department-PHED has published Tender For Work Of Replacement Of Old And Damaged Pumping Machinery Under Sub Division Rajakhera Under Summer Contingency Plan 2024-25. Submission Date for this Tender is 30-04-2024. Pump Supply Tenders in dholpur Rajasthan. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | 2.15Supply & Installation of 3 phase ISI marked submersible motor pump set ofthree star or better rating of BEEand as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect. 2.15.5 9.3 KW (12.5 HP) & head up to 120 mtr. |
2 | 2.18Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB , fully automatic star-delta starter, over load relay,ampere meter with CTs, volt meter, phase preventer, suitable starting capacitors, phase indicators, lighting arrangement etc complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM).All these equipments shall be housed by panel box made out from 18 gauge M.S. Sheet with powder coating. Panel should be ofminimum size 900 x 600 x 450 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg s length 18and double door including in built locking system.The legs should be embedded in M-15 cement concrete plat form. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply. 2.18.2Above 10 HP and up to 15 HP |
3 | 2.19Supply & Fixing of ISI marked three core PVC flat submersible cableas per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980including making connection etc. 2.19.23 core 6.0 Sq.mm |
4 | 2.20Supply & Fixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. 2.20.110.0 Sq.mm, 4 core |
5 | 5.1Providing, installation, testing and commissioning of Centrifugal Monoblock pump set conforming to IS 9079 , 2 pole motor operating at syncronised speed of 3000 RPM with requisite MOC impeller, priming funnel, cock, suitable flanges at suction and delivery side. Pump shall have common shaft for pump and motor. Motor shall be suitable for working on 415 V 10%, 3 Ph, 50 Hz A.C. Supply. Motor shall be TEFC type and Pump set shall be suitable for working at various discharge and head requirements as per scope of work. Pump shall be erected onC.C. foundation / cross channels / RSJ frame block with suitable foundation bolts grouted in C.C. foundation block etc. complete in all respect as perspecification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. 5.1.1Centrifugal Monoblock Pump set (Single Stage) 5.1.1.47.5 KW (10 HP) |