Madhyanchal Vidut Vitran Nigam Limited has published Tender For Increasing Capacity Of Distribution Transformer And Other Electrical Work Against Business Plan 2024-2025 Under Jurisdiction Of Edd, Cess-Ii, Lesa Cis Gomti-I, Lucknow. Submission Date for this Tender is 29-04-2024. Electrical Maintenance Tenders in lucknow Uttar Pradesh. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Safe Loading, Carriage & unloading of following Materials from Centre Store to Pit Site/J.E. Dump Store. |
2 | TF 250 KVA |
3 | TF 100 KVA |
4 | TF 63 KVA |
5 | TF 25 KVA |
6 | 11 KV Pin Insulator with pin |
7 | ABC 3x50/3x185/3x120 |
8 | ASCR Wesel Conductor |
9 | ST Pole 11 Mtr. Long |
10 | PCC Pole 8.5 Mtr.Long |
11 | Top Channel |
12 | Dropper Channel |
13 | S/S Base Angel |
14 | PVC Cable LT 1x400 sq.mm. |
15 | 11 KV X-Arm |
16 | Stay Set |
17 | Stay Wire |
18 | Earthing Rod |
19 | MS Chaneel |
20 | T-Off Channel |
21 | 11 KV Disc Insulator with fitting |
22 | 11 KV Xlpe cable 3x70/3x120/3x185 sq.mm |
23 | 11 KV OD 3x120 sq.mm |
24 | Dragging of ST/PCC Pole digging of pit erection of sub-station type double pole structure on ST/PCC Pole with fixing of necessary item such as Top Channel, along with grouting (As per RESPO Norms) Dropper Channel, 11 pin insulator with Pin & 11 KV Disc Insulator with fitting, DO Fuse set its ramming, as per RESPO Specification. Only Pole and insulator will be Provided by the Department. |
25 | Dragging of ST/PCC Pole to pit site, digging of pit erection and grouting (As per RESPO Norms) of 11 KV linewith fixingof necessary item, such as V-type X-arm, F-bracket, 11 KV Pin insulator, Guarding angle (1.8 mm 65x65x6) with Nut & boltsits ramming as per RESSPO Specification. Only Pole and insulator will be Provided by the Department. |
26 | Dragging of ST/PCC Pole from Dump Store to pit site, digging of pit erection and grouting (As per RESPO Norms) of LT support suitable for laying of ABC Line on 8.5 Mtr Long PCC Pole by providing of necessary eye hook/Lt Shackle insulator with Clamps and its accessories etc. as perRESSPO Specification.Only Pole will be Provided by the Department. |
27 | Grouting & Nuzzling of 11 KV stay set complete including fixing of necessary clamps. Accessories required including its grouting by civil material (Sand,Brick blast & cement). All material except stay wire shall be supplied by the contractor. |
28 | Ordinary earthing by 11 KV MS earth Rod 2500mm long as per RESPO Schedule. All material except earthing wire shall be supplied by the contractor. |
29 | Laying Stringing & sagging of 3 Phase 3 wire 11 KV New Line on ACSR Weasel/Raccoon conductor as per RESPO Specification and direction on E/I. All material except ACSR weasel/Raccoon conductor shall be supplied by the contractor. |
30 | Guarding of HT line by GI wire. GI wire shall be supplied by the department. |
31 | Proper laying & commissioning of (3x50/3x95/3x120 sq.mm) XLPE Aerial Bunched Conductor. Only ABC Provided by deptt. |
32 | Laying of LT PVC cable as per RESPO Norms. Only PVC cable will be provided by department. |
33 | Well type earthing of with 60 Fit Deep boring and providing GI Pipe 1.5" dia ("B" Class) and earthing must be joint by G.I. Strip of 32x5 mm thick long attached with nut & bolts and GI pipe cap. All material and labour shall be supplied the contractor. |
34 | Construction of T/F plinth of size 2x2x1.2 mtr with the help first class brick & masonry in the ratio 1:4 cement & sand coarse. Filling the structure completely per norms with RCC to 1:2:2 cement & stone grit with MS bar and MS channel for resting transformer. |
35 | Wiremess fencing of 11/0.4 KV S/S shall be made of rectangular of size as per site requirement not exceeding 3 meter fabrication 45x45x5 mm angel the frame is also have 1 no. Horizontal runner of MS flat 40x5 welded in middle to support of wire mesh. Rectangular welded type wire mess of size 50x25 made of 12 S.W.G. wire mess shall be welded all along the periphery of the frame as well as on horizontal runner to give extra strength of welding to wire mess welded on the frame. Diagonal bracing of all the frame panel will be welded with Ms flat of size 25x3mm to support as per RESPO specification & direction of E/I. |
36 | Construction ofmasonry/metallic type distribution pillar of size 1x1.5x2.5 mtr. with supply & fixing of fabricated 4 nos. doors (2ft.x4ft.) made of BP sheet of 18 SWG with locking arrangement, 2 Nos. Straight MS angle 50x50x6mm (1800 mm long) 2 nos. 500 Amp, 3 Nos. 300 Amp Henley Type Tailless Fuse Unit, 3 Nos copper bus bar of size 1000x50x6 mm and one No. Alum bursar 1000x50x6 mm including all civil material required for work. All material shall be supplied by contractor. |
37 | Fabrication, errection & commissioning of 250KVAT/F on Plinth with all accessories. All material except 250 KVA T/F shall be supplied by the Contractor. |
38 | Fabrication, errection & commissioning of 100 KVAT/F on DP with all accessories. All material except 100 KVA T/F shall be supplied by the Contractor. |
39 | Fabrication, errection & commissioning of 63 KVAT/F on DP with all accessories. All material except 63 KVA T/F shall be supplied by the Contractor. |
40 | Fabrication, errection & commissioning of 25 KVAT/F on DP with all accessories. All material except 25 KVA T/F shall be supplied by the Contractor. |
41 | Dismantling of 63 KVA T/F opening jumbers, LT cable and Other accessories of T/F including Safe loading, unloading Carriage from site to JE dump Store/Center Store. |
42 | Dismantling of 25/16/10 KVA T/F opening jumbers, LT cable and Other accessories of T/F including Safe loading, unloading Carriage from site to JE dump Store/Center Store. |
43 | Supply and fixing of L-Piece for 250 KVA T/F as per RESPO Norms |
44 | Supply and fixing of Allu. Lug 630 sq.mm as per RESPO Norms |
45 | Supply and fixing of Allu. Lug 120 sq.mm as per RESPO Norms |
46 | Digging of pit suitable for 3x70x3x135/3X185 sq.mm 11 KV XLPE cable laying. After 11 KV XLPE cable laying refilling by Bricks & sand as Per RESPO Norms. Only 11 KV XLPE cable supplied by Department. |
47 | Cable Hosting of 11 KV 3x70/3x135/3x185 sq. mm XLPE Cable at the following including jumpering etc complete with help of GI Pipe as PerRESPO Norms. GI pipe and other required material shall be supplied by contractor. |
48 | High pressure testing of 11 KV 3x70/3x120x3x185 XLPE cable along with arrangement of High Pressure equipment. |
49 | GST Extra as per Rules |