Tender For Installation Of Spect Ct (3/8) At Gf,Rru Bldg,Actrec, kharghar-Maharashtra

Tata Memorial Centre has published Tender For Installation Of Spect Ct (3/8) At Gf,Rru Bldg,Actrec. Submission Date for this Tender is 14-05-2024. Uniform Tenders in kharghar Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

43225313
Tender For Installation Of Spect Ct (3/8) At Gf,Rru Bldg,Actrec
Open Tender
Indian
Maharashtra
kharghar
14-05-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Tender For Installation Of Spect Ct ( 3 / 8 ) At Gf, Rru Bldg, Actrec; 1 Civil & Interior Works 2 Demolition - Demolition And Removal Of Walls & Existing Flooring Tiles, Screed, Pcc Till Slab Finishing The Surface For New Flooring Works Without Causing Any Damage To Rcc Elementsand Removal Of Existing False Ceiling & Lights Without Causing Any Damage To Rcc Elements, Mgps, Hvac Or Any Other Services Which Need To Be Retained Wherever & Whenever Required During Execution. The Work Shall Include All Material, Labour, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debries From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 3 P.C.C. - Providing And Laying 100 - 150 Mm Thick M25 Grade Plain Cement Concrete In Spect Ct Gantry Room Forming An Even Surface Without Any Undulations And Approved Quality By Engineer In Charge. The Work Shall Include All Material, Fixing, Wastages, Labor, All Lead And Lifts At All Levels, Loading And Un Loading, Shuttering, Reinforcement, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debris From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 4 Brick Masonry ( 115 / 230 / 345 Mm Thick ) - Providing, Laying & Constructing 2Nd Class Red Brick Masonry 115 Mm Thick In Cm 1:4 Including Scaffolding, Raking Of Joints, Curing With Proper Finishing Of Mortar Joints Etc. Walls At All Heights And Levels Only & Providing Rcc Lintel Beams With1 :2: 4 Proportion 4 Nos Of 6 Mm Dia Reinforcementto Openings Wherever Necessary For Ac Vents, Doors, Windows And Any Other Services Also Providing Concrete 100 Mm Thick Bands At Every 4.The Work Shall Include All Material, Fixing, Wastages, Labor, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debris From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. ( For Partition Walls Between Battery Room, Ups Room And Equipment Room ) 5 Plaster ( Internal ) - Providing Internal Cement Plaster 12 Mm Thick For Walls & Ceiling In A Single Coats In Cement Mortar 1:4 To Concrete Or Brick Surfaces, In All Positions Including Scaffolding And Curing Complete. ( For Partition Walls Between Pet Ct, Battery Room, Ups Room & Equipment Room ) 6 Plaster ( External ) - Providing Sand Faced Plaster 25Mm Thick Externally In Cement Mortar Using Approved Screened Sand In All Positions Including Basecoat Of 15Mm Thick In 1:4 Using Water Proof Compound 1Kg Per Cement Bag Curing The Same For Not Less Than Two Days And Keeping The Surface Of Basecoat Rough To Receive The Sand Faced Treatment Of 6 To 8 Mm Thick In C.M. 1:4 Finishing The Surface Taking Out The Grains And Curing For Fourteen Days Including Including Fixing Of Chicken Mesh At Concrete Brickwork Junction, Glass Fiber Reinforcement [ Recron ] Scaffolding Etc. Complete. 7 P.O.P. Punning - Scraping Of Old Paint / Distemper Wherever Necessary From The Existing Walls, And Applying Of 3.0 To 6.0 Mm Thick Lime Punningover It To Give A Smooth Leveled Finish, The Final Coat Of Punning Tohave One Coat Of Oil Based Cement Primer. The Work Shall Include All Material, Fixing, Wastages, Labor, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debris From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. ( For Partition Walls Between Pet Ct, Battery Room, Ups Room & Equipment Room ) 8 Flooring, Dado, Skirting ( Vitrified Tiles ) - Providing And Fixing Vitrified Tiles 10 Mm Thick600 X 600 With Water Absorption Less Than 0.08% And Conforming To Is : 15622, On Up To 50 Mm Thick Cement Mortar Base 1:4. The Work Shall Include Cost Of Materials, Fixing Wastages, Labor, All Lead And Lift At All Levels, Loading And Unloading, Transportation, Curing, Joint Filling, ( With Cement Grout Matching The Color Of Tiles, Balendure ) , Removing Of Existing Tiles If Any, Cleaning After Fixing. Complete And All Other Incidental Charges Like Breakage In Transportation Or On Site Or While Fixing, As Directed By Engineer-In-Charge.Tiles To Be Used Strictly Which Have Been Used For Existing Flooring Or Approved Shade And Design. 9 Flooring ( Anti - Skid Tiles ) - Providing And Fixing Vitrified Tiles 10 Mm Thick300 X 300 With Water Absorption Less Than 0.08% And Conforming To Is : 15622, On Up To 50 Mm Thick Cement Mortar Base 1:4. The Work Shall Include Cost Of Materials, Fixing Wastages, Labor, All Lead And Lift At All Levels, Loading And Unloading, Transportation, Curing, Joint Filling, ( With Cement Grout Matching The Colour Of Tiles, Balendure ) , Removing Of Existing Tiles If Any, Cleaning After Fixing. Complete And All Other Incidental Charges Like Breakage In Transportation Or On Site Or While Fixing, As Directed By Engineer-In-Charge. 10 P.O.P. On Flooring - Providing And Applying Average 12Mm Thk. P.O.P. On Floor, On Plastic Sheet To Protect Floor From Physical Damage During Construction. 11 Core Cutting - Drilling With Core Cutting Machine ( 50 Mm - 300 Mm ) In Rcc Slabs, Walls Etc.Wherever Required In Buildings, Manholes, Ducts, Water Tanks, Pits Etc. For Laying Pipes, Sleeves And Making Good The Same To Give An Even Finish . The Rate Shall Include The Cost Of Drilling Core, Providing Epoxy Based Water Proofing Compound For Sealing The Joints Around The Pipes, Nominal Reinforcement Wherever Required, Scaffolding And Labor Charges For Working At All Levels , Leads And Heights . ( Maximum Thickness Of Rcc Members Shall Be 300Mm ) And As Directed By Engineer-In-Charge. 12 Micro Concrete - Drilling & Providing Encasement To Gantry Anchors, With Free Flow High Strength Non Shrink Micro Concrete M -35 Using Single Cement Micro Concrete Shrinkage Components Added With 100% By Weight Saturated Dry Stone Dust. The Water Cement Ratio Should Be Maintained As Per ManufacturerS Specifications To Achieve Dense Solid Mass. The Micro Concrete Shall Be Poured Properly In Slurry Tight Prefixed Holding Boards Formwork, Fixed Properly In Line, Level And In The Required Size / Shape And Well Oiled Etc. The Air Bubbles, If Any Shall Be Removed By Tapping The Boards And Removing The Same After 24 Hours, Curing The Micro-Concrete Thoroughly For 14 Days Etc. Complete. The Rate Shall Be Inclusive Of Shuttering, Strutting, Curing Etc. Including Cost Reinforcement Complete As Directed And Instructed. 13 Cable Trench - Providing Cable Trench And Cutout Of On Site Required Size In Flooring And Wall With Finishing Of All Edges With Pcc & Providing Plaster To Wall Cutouts With Paint & Specs As Mentioned In Boqand Providing 3 Mm Removable Cover Made Of Stainless Steel Matt Finish On Front Side For Cables, The Work Shall Include All Material, Fixing, Wastages, Labor, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debris From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 14 Internal Wall / Ceiling Paint - Providing And Applying Internal Wall Painting With Acrylic Paint Of Approved Shade Including Basepreparation Using Putty And Fillers As Specified And Directed All Complete. ( 2 Coat Lambi Putty + 2 Coat Primer + 2 Or More Coats Of Paint ) . The Work Shall Include All Material, Fixing, Wastages, Labor, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debris From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 15 Cemetacious Boardceiling - Providing & Fixing Cementacious Board Celling False Ceiling As Per Drawing.Using 12 Mm Thick Plain Gypsum Boards And Gypsum Verticals For Cove Lighting Of M / S. Saint Gobain Or Approved Equivalent, Fixed To The Suspended Grid, Fabricated And Fixed To The Soffit Of Roof / Beams And Wall Using - Gypsteel Ultra Ceiling Sections - Perimeter Channels Of Size 20 Mm X 28 Mm X 30 Mm Fixed To The Wall Using Metal Screws And Nylon Sleeves Recommended By The Manufacturer At A Spacing Not Exceeding 600 Mm C / C, Intermediate Channels Of Size 15 Mm X 45 Mm X 15 Mm At A Spacing Not Exceeding 1200 Mm C / C Suspended Using Ceiling Angles Of Size 25 Mm X 10 Mm And Appropriate Length, Fixed To The Soffit Of R.C.C Beams / Slabs Using G.I Soffit Cleats Of Size 27 Mm X 37Mm X 25 Mm X 1.6 Mm And Metal Expansion Fasteners Of 38 Mm X 12 Mm Diameter At A Spacing Not Exceeding 1200 Mm C / C, Ceiling Sections Of Size 80 Mm X 26 Mm X 51 Mm Provided Across The Intermediate Channel At A Spacing Of 475 Mm C / C, At Bottom Which Shall Be Fixed By G.I Connecting Clips Of 2.64 Mm Diameter At Junctions. The Ceiling Channels Shall Be Provided With A Minimum Overlap Of 50 Mm At Joints And Fixed To The Perimeter Channels Using Metal Screws At Ends. Specifications Using Cold Rolled Gypsteel Ultra Sections And Gypsum Boards Manufactured By Gypsum India Ltd. Or Approved Equivalent. Additional Perimeter Channels / Ceiling Sections Shall Be Provided Around The Cut Outs For Light Fittings A / C Diffusers Etc. Additional Support For Cut Outs To Be Provided At No Extra Cost. The Ceiling Boards Shall Be Fixed To The Underside Of The Suspended Grid Using 3.5 Mm X 25 Mm Self-Tapping Screws. The Joints Shall Be Finished With Joint Paper Tape And Jointing Compound Of Approved Make And Providing And Applying Plaster Of Paris Putty For Required Thickness. The Work Shall Include All Material, Fixing, Wastages, Labor, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debris From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 16 Metal Grid Ceiling - Providing & Fixing 600 Mm X 600 Mm Powdered Coated Metal Perforated / Non Perforated Plain Tiles With Beveled Edges And Integrated , False Ceiling With Metal Suspension Silout Grid ( To Match Existing False Ceiling Pattern ) System False Ceiling For Area Under Scope.Installation Shall Be Used As Per Manufacturers Specificationsgalvanized Section , Exposed Tee Will Be Powder Coated And Withsuspension System I.E.Anchor Fastener, Vertical Hanger, Hook Clip Etc. As Described. To Be Laid At All Heights Cut To All Shapes And Sizes. The Work Shall Include All Material, Fixing, Wastages, Labor, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debris From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 17 Skylight - ( Gantry Room ) - Providing And Fixing Of Skylight Of Translucent Acrylic Sheet Of Approved Print Design On Exposed Face ( 4 X 6 ) , With Box Frame Made With 18 Mm Ply Covered With Approved Laminate On All Exposed Edges And Shall Be Back Lit With Led Strips As Per Specifications And Drawings, With All Fitting, Wiring & Framing Accessories Necessary.The Work Shall Include All Material, Fixing, Wastages, Labor, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debris From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 18 Epoxy Self Levelling : Providing And Doing Epoxy Self Levelling Over Existing Flooring And Making Surface Clean And Clear To Receive Pvc Flooring As Per Manufacturers Specification, Including Cleaning The Flooring Dirt Free, Curing Etc. Complete As Directed And Instrustructed. 19 Vinyl Flooring - Supply And Fixing Of 2 Mm Thick Vinyl Of Approved Dual Colour By Architect And Customer Laid On Ips Flooring / Pcc With Plain Finish Inculuding Self Leveling Compound In Machine Room Without Any Undulation And Quality Check Approved By The Engineer.The Work Shall Include All Material, Fixing, Wastages, Labor, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debris From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 20 Roller Blinds - Providing And Fixing Of ( 100% Polyester Woven Fabric ( Acrylic Coated ) 168 Gsm Solid Panel: 0.4Mm± ) Openness Factor : 3% 4-5 Grade Tested In Accordance With Bs En Iso 105- B01:1999 ( Colour And Texture Will Be Provided By The Architect ) Control Unit: Blinds Mechanism Must Have The Control Clutch Drive Unit With Engineered Heavy Dutychain Drive Pulley Operating System Consisting Of Gear Clutch Housing And Locking Plug Containing At Least 6 Ribs And Inserted Into A Minimum Of 38Mm Dia. Roller Tube. Clutch Has To Be Self-Lubricating With Safety Pins For Secure Bracket Installation And Unlocking Pin For Quick Manual Removal. Provided Clutch System Must Allow Convenience In Operation For Large Windows To The Smallest Windows. The Control Unit Should Be Made Up Of Polypropylene Material Using Injection Moulding Method. Gearing Ratio: 1.75:1 To Reduce Operating Force For Larger Blinds. 24 Nos Sprocket For 38Mm Diameter Roller Tube. Control Unit Is Operated Directionally By The Use Of Beaded Endless Chain To Raise And Lower The Blind Smoothly. ( Colour And Texture Selection Will Be Done By The Architect And Customer ) The Work Shall Include All Material, Fixing, Wastages, Labor, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debris From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 21 Teak Wood Door Frame Providing Wood Work With C.P. Teak Wood In Frames For Doorswindows, Ventilators, Air-Condition Frames, Clear Story Window, False Ceiling And Partitions Etc.Wrought Framed And Fixedin Position Including Applying One Coat Of Approved Woodprimer To The Exposed Surfaces And Tow Coats Of Bitumasticpaint To The Surface Of Wood In Contact With Masonry / Concreteetc.Complete.In Frames Of Doors, Windows, Ventilators And Clearstorey Windows Etc. Fixed With M.S Hold Fast Of Size40x3mmx150mm Long Bend To Shape & Embeded Incement Concrete 1:2:4. Complete As Directed And Instructed 22 Wooden Door - Providing & Fixing On Flush Door, Single Or Double Panel Shall Be Of 35.0Mm Flush Door With 100 X 75Mm Second Class Teak Wood Frame , 1.0Mm Lamination On Both The Sides Of Approved Shade And Make ( Greenlam , Merino Or Royaletouch Only ) , With Two 1 Thick Vertical Metal Finish Laminate Lines On Both Sides Of Door To Be Fixed To Partition / Wall With 4 Heavy Duty 4 Ss Hinges, And Shall Have Cylindrical Lock With Heavy Duty Ss Tower Bolts. The Work Shall Include All Material, Fixing, Wastages, Labour, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debries From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. ( All Accesories To Be Used Of Godrej, Dorma Only ) 23 Lead Door Frame + Shutter- Providing And Fixing2mm Lead Lined Min 35Mm Thick Single Or Double Panel Block Door With Wooden Frame Covered With 1 Mm Thick Laminate Of Aproved Shade, Pasting 12 Mm Ply Over Lead Sheet On One Side Of Door And Frame, And 1 Mm Laminate On Both Side Of The Door And Frame With Heavy Duty Door Handle, Lock & Tower Bolts. The Work Shall Include All Material, Fixing, Wastages, Labour, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debries From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 24 Aluminium ( Anodized ) Door With Frame - Providing And Fixing Aluminium Door With Extruded Built Up Standard Tubular Sections / Appropriate Z Sections And Other Sections Of Approved Make Conforming To Is: 733 And Is: 1285, Fixing Withdash Fasteners Of Required Dia And Size, Indluding Necessary Filling Up The Gaps At Junctions, I.E. At Top. Bottom And Sides With Required Epdm Rubber / Neoprene Gasket Etc. Aluminium Sections Shall Be Smooth, Rust Free, Straight, Mitred And Jointed Mechanically Wherever Required Including Cleat Angle, Aluminium Snab Beading For Glazing / Panelling, C.P. Brass / Stainless Steel Screws, All Complete As Per Architectural Drawings And The Directions Of Engineer-In-Charge. ( Glazing, Panelling And Desh Fasteners To Be Paid For Separarely ) A ) For Fixed Portion:12 Guage. Powder Coated Aluminium ( Minium Thickness Of Powder Coating 50 Micron ) . B ) For Shutters Of Door 10 Guage Including Providing And Fixing Hinges / Pivots And Making Provision For Fixing Of Fittings Wherever Required Including The Cost Of Epdm Rubber / Neoprene Gasket Required ( Fittings Shall Be Paid For Separately ) Powder Coated Aluminium ( Minium Thickness Of Powder Coating 50 Micron ) .The Work Shall Include All Material, Fixing, Wastages, Labour, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debries From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 25 Lead Wooden Framing For Window - ( 6 X 3 ) On Site Fabricating Wooden Framing Forconsole Window, 3 Inch Thick Frame And Depth Depending On Wall Thickness ( Refer Layout & Consult Project Manager ) Made With 18 Mm Ply With 2 Mm Thick Lead Sheilding And All Exposed Surface With Approved Laminate. The Work Shall Include All Material, Fixing, Wastages, Labour, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debries From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 26 Workstation - On Site Fabricating - Providing & Fixing Workstation ( 700 Mm Wide X 750 Mm High ) In Any Required Room Of Pet Ct Premisis. To Be Made In 18 Mm Thick Marine Ply To Be Supported With 18Mm Marine Ply Is 710 Verticals At 5 C / C Or As Directed By Engineer Incharge. All The Exposed Surfaces 1.0Mm Thick Laminated Finish Of Approved Shadewith 450 Mm Wide Pedestals Having 4 Drawers Each With Ss Locking System. Providing Grommet With Cover At Each Vertical Partition.The Work Shall Include All Material, Fixing, Wastages, Labour, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debries From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 27 Wooden Cabinet- Fully Laminated: Providing & Fixing Cabinet Made Up Of 19 Mm. Commercialply Of Approved Make For Top, Bottom, Sides & Shelves &8Mm Commercial Ply Approved Make For Back Side Door Shutter Made Up Of 19Mm Thick Commercial Ply Andouter Surfaces And Top Of Shelves For Open Type Cabine Shouldbe Laminated With 1.5Mm Thick Approved Plastic Laminatesheet Of Required Colour Including All Brass Fittings Such Ashinges, Tower Bolts, Ball Catches, Stopper, Handle, Knosbs As Per Shown In Drawing Or Approved By Engineer-In-Charge Etc.And All Exposed Edges Lipping With 6Mm Thick T.W. Lipping Patti.Locking Arrangement With Heavy Duty Multipurposelock Etc. Allcomplete As Specified & Directed By Engineer-In-Charge. 28 Kaddappa Storage Unit - On Site Fabricating Open Storage Unit Made Up Of 25 Mm Thick Kadappa Stone 7 High With 3 Equal Horizontal Division 2.5 C / C The Work Shall Include All Material, Fixing, Wastages, Labour, Polishing, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debries From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 29 Granite Platform - On Site Fabricating 750 Mm Wide 18 Mm Thick Mirror Polished Machine Cut Steel Grey Granite Stone Platform On A Bed Of 12 Mm Average Thick Cement Mortar 1:3 ( With Coarse Sand ) To Make Up A Total Thickness Of 50 Mm Supported By Kadappa With Adequate C / C Support ( Max Vertical Support Distance 900 Mm C / C ) , Including Laying Slabs In Cement Slurry, Pigmented To Match The Shade Of Slabs, Grinding, Rubbing , Epoxy Touch Ups , Polishing , Curing And Making The Full Round Gola On Nosing Etc Complete At All Levels. 30 Office Chair - Providing And Arranging Office Chairs With Castors And Armrest.Heavy Duty Make -Mid Black Or Similar Cost Include Supply, Transport, Loading Unloading, Comple As Intructed By Engineer Incharge. 31 Soft Board / Notice Board - Providing And Fixing Of 1.5 X 2 Soft Board With Box Of Pins. The Work Shall Include All Material, Fixing, Wastages, Labour, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debries From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 32 Name Plate - Providing And Fixing Of Acrylic Name Boards Or Approved Design For Respective Rooms Of Pet C.T. Department ( 4 X 10 ) The Work Shall Include All Material, Fixing, Wastages, Labour, All Lead And Lifts At All Levels, Loading And Un Loading, Transportation And Other Incidental Charges, Cleaning After Completion, Removal Of Excess Material And Debries From Site To Nearest Waste Collection Etc., Complete As Directed By The Engineer-In-Charge. 33 Mirror - Supply And Installation Of 2 X 1.5 Mirrors With Ssstudds In Toilets As Directed By Engineer Incharge 34 Recliner Chairs - Supply And Installation Of Leatherite Finished Recliner Chairs In Post Dosage Waiting Room Of Approved Design, Size And Color By Architect / Customer. Complete As Directed & Instructed. 35 Radiographic Film Viewers - Supply And Installation Of 400 Mm X 1000 Mm Screen Radiographic Film Viewer. 36 Structural Steel Work ( Bulit Up Section & Hollow Sections ) : At All Levels Including Supplying Cutting Fabricating Welding Or Blotting Erecting And Fixing In Position Including Painting With A Primary Coat Of Approved Steel Primer, Including Cost Of Materials Labour With Chasing In Wall Or Embedding In Floor And Making Good The Same By Filling 1:2:4 Cement Concrete And Plastering If Necessary All As Specified And Directed By Engineer-In-Charge. 37 Electrical Sitc 38 Earthing & Safety Requirementsupply & Installationtesting And Commissioning 39 Sitc Of Tinned Copper Earth Plate Electrode 600 X 600 X 3.15 Mm Earth Station, 3 Mtr Below Ground Level As Per Drawing Complete With All Required Materials Like Cole, Charcoal, Salt, Brass Nut Bolts & Washers, Watering Arrangements, Gi Pipe ( B Class ) , Concrete Chamber, Heavy Duty Cast Iron Cover Plate & Excavation In All Types Of Soil In Ground Refilling & Removal Excess Earth Within A Radius Of 500 Mtr. Etc.Note:1.The Chamber Cover & Plate Shall Be Of Heavy-Duty Hinged Type & It Shall Weigh Approx. 65 To 75 Kgs. For 450 X 450 Mm Size & Shall Be Got Approved By Dept. ( 6 Mm Chequred Plate With 40 X 40 X 6 Mm Angle Iron Frame ) 2.Plastering Shall Be Done Both Inside & Out Side.3.The Measurement Of Resistance Of Earth Station & Resistance Of Complete Scheme Of Earthing Layout Shall Be Measured, Recorded & Got Approved By Engg-In-Charge.Drawing For Earthing Layout Atatched. Agency To Carry Out Earthing As Per Attached Drawing 40 Sitc Of Hot Dipped Gi Earth Plate Electrode 600 X 600 X 6.3 Mm Earth Station 3 Mtr Below The Ground Level --- Same As Above-- As Per Drawing & Specifications Complete With All Required Materials Like Coke / Charcoal, Salts , Brass Nut Bolts & Washers, Watering Arrangement, Gu Pipe ( B Class ) Concrete / Brick Chamber, Heavy Duty Cast Iron Cover Plate & Excavation In Ground, Refilling& Removing Of Excess Earth Within A Radius Of 500 Mtr.Etc. Scope Also Includes Dewatering, Shoring, & Consolidation Etc. Drawing For Earthing Layout Atatched. Agency To Carry Out Earthing As Per Attached Drawing 41 Sitc Of Gi Strip Of Size 25 X 6 Mm Including All Fixing Accessories, Pvcblack Colour Sleeves On Strip 42 Sitc Of 25Mm X 3Mm Thk Cu. Strip With Heat Shrinkpvc Sleeve For Ups And Electronicsearthing Including All Fixing Accessories, Pvcblack Colour Sleeves On Strip 43 Sitc Of 8 Swggibare Wire Including Lugs And All Fixing Accessories For Earthing Of All Metal Parts 44 Sitc Of Earthing Busbar Box With Acrylic Cover And Cu / Gi Strip On Suitable Insulator. Strip Shallbe Provided With Holes At Every 75 Mm With Nutbolts & Washers. 45 Sitc Of Earthing Busbar Box With 25 X 6 Mm Tinned Cu Strip 500 Mm Long On Suitable Insulator.Strip Shall Be Provided With 8Mm Holes At Every 75 Mm With Nutbolts & Washers. 46 Supply And Installation Of 1.1 Kv Grade Rubber Matting As Per Is Standard 5Mm Thick Inequipment Room & Battery Ups Room 47 Sitc Of 150Mm X 150Mm Enamel Type Danger High Voltage Board 48 M. V. Panels And Distribution Board.Supply & Installation Testing And Commissioning 49 Supply, Installation, Testing & Commissioning Of Mv Panel Boards Compartmental Cubicle Type Freestanding With Appropriate Cable Entries, Front Operating, Front Maintained Complete With Baseframe Etc As Required & As Per Is 8623Specifications Panel Has To Be Fabricated Out Of 16 / 18 Swg Crca Sheet, & Surface Quoted With Phosphate Seven Tank Process And Duly Painted ( Ral 7032 ) With Powder Coating Process. ( Refer Single Line Diagram For Switchgear & Other Details ) . 50 Sitc Of Main Panel 3Phase 415 Volt , For Pet-Ct As Per Sld In Tender Documents 51 Sitc Of Ups Distribution Panel Of Hvac Or Other Requirements As Per Sld In Tender Documents 52 Sitc Of Ups Distribution Board Flexi Db 4 Row 10 Module Each With63a Tpn Mcb As Main Incomer, 40 A Dp Rccb-30 Ma Si / Hi Sereis As Sub-Incomerand 20A Sp Mcb As Outgoing Qty 30 Nos .Ups Dbs ) All Mcb C Curve. The Work Also Includes Structural Steel Required For Base Frame Of Distribution Board Including Finishing Distribution Boards Supply, Installation, Testing & Commissioning Of 500V Distribution Boards As Speci- Fied, I ) Copper Busbars Together With Tapped Neutral Bar For Individual Phases. , Copper Earth Strip With Tapping For Eec, Interconnections And Earthing.Sheet Steel Enclosure Suitable For Recessed Or Surface Mounting With Hinged Lockable Doors Interlocked. Thikness Of 1.6 Mm , Phase To Phase Barriers In Case Of 3Ph Boards. , Vii ) Necessary Ms Support Frame & Painting, Labelling, Phase Indicating Lamps With Fuses Etc. Complete. 53 Sitc Of Flexi Db 4 Row 10Module Eachwith80a Tpn Mcb As Main Incomer, 63 A Dp Rccb-100Ma Si / Hi Sereis As Sub-Incomerand 20A Sp Mcb As Outgoing. Qty 30 Nos Lp Db ) All Mcb C Curvethe Work Also Includes Structural Steel Required For Base Frame Of Distribution Board Including Finishing Distribution Boards Supply, Installation, Testing & Commissioning Of 500V Distribution Boards As Speci- Fied, I ) Copper Busbars Together With Tapped Neutral Bar For Individual Phases. , Copper Earth Strip With Tapping For Eec, Interconnections And Earthing.Sheet Steel Enclosure Suitable For Recessed Or Surface Mounting With Hinged Lockable Doors Interlocked. Thikness Of 1.6 Mm , Phase To Phase Barriers In Case Of 3Ph Boards. , Vii ) Necessary Ms Support Frame & Painting, Labelling, Phase Indicating Lamps With Fuses Etc. Complete. 54 Supply, Fixing, Testing, Of Good Quality 20 Aindustrial Sockets With 20A McbSip 20 Metal Enclosure. Box Should Be Suitable To Terminate Cables / Wires Easily, Complete As Required. 4 For Ac Power Provision And 1 For Network Rack. 55 Supply And Installation Of Industrial 32 A 1 Ph. Plug & Socket Interlock Type With 32A Spmcb 3 Pin Type. 56 Sitc Of 250A 4 Pole Mccb With Enclosure Microprocessor , Lsi And Earth Fault Protection , Rotary Operating Handle Including All Fixing Accessories 57 Cablessupply & Installation Testing And Commissioning • All The Power Cables , Lighting Wirings Cable Tag To Be Provided.Cable Tag Specifications -D. Labelling: • Material: Stainless Steel, Zero Halogen, Or Halogen-Free• Thickness: 0.25 Mm Or 0.4 Mm• Width: 9.5 Mm Or 19 Mm• Height: 0.394 In• Printable Area Dimensions: 0.394 In H X 3.15 In W• Operating Temperature: -25 °C To +80 °C 58 Supply, Testing, Tagging, Laying And Commissioning Following Sizes Mentioned Below Of 1100 Volt Grade, Xlpe / Pvc Insulated Multistrand Al. / Cu. Conductor Armoured / Unarmoured Cables ( As Per Is 1554 & Is 7098 ) In Cable Trench , On Cable Trays / Ladders Etc. As. Required Complete With Clamps, Termination, Color Coding And Tagging. All Cable Glands To Be Double Compression Type And Lugs To Be As Per Specifications Mentioned In Tender Documents. Pvc Shroud To Be Provided On Each Glands Of Suitable Size. All Cable Tages To Be Ss Type And As Per Specifications In Tender Documents. 59 3.5C X 240 Sq.Mm. A2xfy Cable ( Al Cable ) .Armoured Cable Including Glanding , Lugging And All Fixing Accessories As Main Incomer Cable From Hospitalsbreaker 60 1C X 95 Sq.Mm. Fr Copper Flexible Cable. Including Glands , Lugs , End Connectionsand All Fixing Accessoriesfor Ups Input And Output Of Machine. 61 4C X 10 Sq.Mm Fr Copper Flexible 2Xfy Cableflexible Cable Including Glands , Lugs , End Connectionsand All Fixing Accessoriesfor Ups Db 62 4C X 16 Sq.Mm Fr Copper Flexible 2Xfy Cableincluding Glands , Lugs , End Connectionsand All Fixing Accessoriesfor 1 Lpdb 63 3C X 2.5 Sq.Mm. Fr Copper Sheathed Cableincluding Glands , Lugs , End Connectionsand All Fixing Accessoriesfor Workstations&Other Power Points. 64 1C X 95 Sq.Mm. Yy Cable. Flexible Including Glands , Lugs , End Connectionsand All Fixing Accessoriesfor Earthing 65 4C X 35 Sq.Mm Fr Copper Cable Armouredincluding Glands , Lugs , End Connectionsand All Fixing Accessories 66 Cable Tray Supply, Installation, Laying And Erection Of G.I. Perforated And Ladder Type Cable Tray With Reducer, Bends, Tees, Clamps And Couplers For Fixing Of Cable To Complete The Job. It Should Also Comply Load Testing Of Is 14927-1 ( 2001 ) .Scope Covers:1 ) Supply Of Pre-Fabricated Cable Trays As Per Approved Design By Consultant & Client.2 ) Delivery Of The Material At Site.3 ) Unloading Of Material & Storage At Site Store.4 ) Shifting Of Material From Site Store To Place Of Installation.5 ) Painting The Support Structure With Two Coats Of Red Oxide And Two Coats Of Enamel Colour Paint Of Approved Brands.6 ) All Material Shall Be Hot Dip Galvanised ( 86 Micron Zinc Thickness Min. ) As Per Is And Specifications.7 ) Max. Distance Between Two Structural Steel Supports Shall Not Exceed 1.2 Mtrs.8 ) Tying Of Cables With Cable Trays With Proper Dressing. 9 ) Max. No. Of Tier Of Cables On Cable Tray Mv Cables : 1 No.10 ) To Prepare Shop Drawing And To Take Approval Of Consultant & Client At Each Stage.11 ) To Prepare & Submit As-Built Drawing And Handing Over Document To End User. Structural Steel Required For Cable Tray Supportis In The Scope Of Agency. Rates To Be Quoted Accordingly 67 Sitc Of 100 Mm Perforated Tray ( 16 Swg ) . 68 Sitc Of 300 Mm Perforated Tray ( 14 Swg ) . 69 Sitc Of 100 Mm Perforated Tray Cover ( 18 Swg ) . 70 Sitc 300 Mm Perforated Tray Cover ( 18 Swg ) . 71 Sitc Of 300 X 100 Mmpvc Trunkingwith Cover 2Mm Thick For Db Wire / Cables Dressing Forldb / Pdb & Ups Db.& Console Room To Ct Machine 72 Sitc Of Cable Ladder - M.S Fabricated Cable Ladder For Rising Cables Upto Ceiling Level 73 Point Wiringsupply & Installationimportant Note : Refer Electrical Layout Provided By Architect For Better Understanding Of SbS • All The Lighting Circuits Switchboard Inside And Lighting Panel Inside Ferruling To Be Provided As Instructed By Eic Es. All The Wiringslight Side, Switch Side, Switch Socket Side , Lighting And Powerpanel Side Wire Ferrule Type Lug To Be Provided. 74 Sitc Of Wiring For Circuit / Submain Wiring Alongwith Earth Wire With The Following Sizes Of Frls Pvc Insulated Copper Conductor, Single Core Cable Including Surface / Recessed Heavy Class Pvc Conduitheavy ( Hms ) As Required. 2 X 2.5 Sq. Mm + 1 X 2.5 Sq. Mm Earth Wire From Main Distribution Board To Power Point Circuits And Lighting Switchboard. 75 Sitc Of Primary Point Wiring For Light Point / Fan Point / Exhaust Fan Point / Call Bell Point With 2 X 1.5Sqmm + 1 X 1.5Sqmm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Includingmedium Class Pvc Conduit Heavy ( Hms ) / Casing Capping , With Modular Switch , Modular Plate, Suitable Gi Box / Pvc Boxfor Concealled , Suitable Pvc Box For Surface, Ceiling Fan Rose, Pvc Junction Box And Earthing The Point With 1.5 Sq.Mm. Frls Pvc Insulated Copper Conductor Single Core Cable Etc As Required. 76 Sitcsecondary Point Wiring Light To Light Looping With 2 X 1.5Sqmm + 1 X 1.5Sqmm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Includingmedium Class Pvc Conduit Heavy ( Hms ) / Casing Capping , With Modular Switch, Modular Plate, Suitable Gi Box For Concealled , Suitable Gi Box / Pvc Box For Surface, Ceiling Fan Rose, Pvc Junction Box And Earthing The Point With 1.5 Sq.Mm. Frls Pvc Insulated Copper Conductor Single Core Cable Etc As Required. 77 Dm - Supply And Installation Of 4 Module Cat 6 Data Module Switch Board Modular Typeforcomputers. 78 Supplying And Fixing Following Size / Modules, Pvc / Gi Box Alongwith Modular Base & Cover Plate For Modular Switches In Recess Etc. As Required. • All The Power Socket Tagging To Be Provided , Pvc Tags To Be Provided.• All The Power Sockets Inside And Power Panel Insidewiring Ferruling To Be Done As Instructed By Eic Es 79 3 Module 80 6 Module 81 Supplying And Fixing Following Modular Switch / Socket On The Existing Modular Plate & Switch Box Including Connections But Excluding Modular Plate Etc. As Required. 82 Modular Switch 6A / 16A 83 Modular Socket 6A / 16A 84 Light Fixtures & Electrical Appliancessupply & Installationimportant Note : Refer Electrical Layout Provided By Architect For Better Understanding Of SbS 85 Supply, Installation, Testing And Commissioning Of Lighting Fixtures, Fans Including Necessaryaccessories. 86 Supply , Installation, Testing & Commisioning Of Led Shaped36 Watt Premium Range Recessed Downlighter Having Die Cast Aluminum Housing / Crca Housing 2 X 2 Lighting With In Built Driver- Non Dimmable -As Per The Make Approved By Engineer Incharge And Architect.The Material Should Be Of Premium Range Of Products With Reputed Make And Should Have Relevant Electrical Certification. Lumens More Than 100Lumens / Watt Pressure Die-Cast Aluminimum Housing With White Front Bottom Frame Suitable To Following Features. Led Fixture To Be Fixed Surface Or Concealed As Per Site Requirement.- Luminaires Suitable To Aluminium Metal Grid Ceiling Or Gypsum Or Pop, -Minimum System Lumen Output 3600 Lumens-In Built Electronic Led Pre Wired Driver, -Luminaire Shall Be With Special Translucent --High Surge Protection:-2.5Kv.-Highdiffuser>85%, -Provision Of Spring Loaded Mounting Clips.-Opal Translucent Cover / Poly Carbonate Reflector.-Cri>80, Thd<10%.-High Efficacy Gretaer Than Or Equal To 100 Lm / Watt, -Provide Uniform Low Glare Lighting Non Yellowing / Pmma Lens For Better Light Distribution, -Operatable Voltage - 220-240 V, 50 Hz, Pf>0.9, -Colour Temperature Gretaer Than Or Equal To 4500K To 5500K 87 Supply , Installation, Testing & Commisioning Of Led Shaped15 Watt Premium Range Recessed Downlighter Having Die Cast Aluminum Housing With In Built Driver- Non Dimmable -As Per The Make Approved By Engineer Incharge And Architect.The Material Should Be Of Premium Range Of Products With Reputed Make And Should Have Relevant Electrical Certification. Lumens More Than 100Lumens / Watt Pressure Die-Cast Aluminimum Housing With White Front Bottom Frame Suitable To Following Features. Led Fixture To Be Fixed Surface Or Concealed As Per Site Requirement. Led Round / Square As Approved - Luminaires Suitable To Aluminium Metal Grid Ceiling Or Gypsum Or Pop, -Minimum System Lumen Output 1500 Lumens-In Built Electronic Led Pre Wired Driver, -Luminaire Shall Be With Special Translucent --High Surge Protection:-2.5Kv.-Highdiffuser>85%, -Provision Of Spring Loaded Mounting Clips.-Opal Translucent Cover / Poly Carbonate Reflector.-Cri>80, Thd<10%.-High Efficacy Gretaer Than Or Equal To 100 Lm / Watt, -Provide Uniform Low Glare Lighting Non Yellowing / Pmma Lens For Better Light Distribution, -Operatable Voltage - 220-240 V, 50 Hz, Pf>0.9, -Colour Temperature Gretaer Than Or Equal To 4500K To 5500K 88 Sitc Of Led Batten Light - 24 W - 4 Feetwhite Including All Fixing Accessories 89 Sitc Of Led Strip / Ropelights 10Watt To 15Watt Per Meter, Colour Temp As Directed By Eic Es Led Strip Light - 22 W - 2700 K - 60- 90 Led Density Per Meter 90 Sitc Of Led Strip Light Drivers6a To 10A As Directed By Eis Es 91 Sitc Of Alluminium Profile Housing For Led Strip Lights As Directed By Eic Es 92 Sitc Of Led Cob Light - 15 W - 2700 K , The Light Crca Housing 93 Sitc Of Oscillation Wall Fan With Sweep Control - 400 Mm - Include Point Wiring And Switch - Location Tobe Decided On Site Of Turnkey Scope Only 94 Sitc Of Dehumidifier - 60 Liters ( Approved Make - Visumed ) 95 Sitc Of Red Led Bulb Including Angle Holder- Operation Theatre Light 96 Networking Works 97 Horizontal Cabling - Workstation Side 98 Sitc Of Cat 6 Lan Cable For Dataincluding 25Mm Pvc Conduit Supply , Installation, Testing & Commisioning Of Of Utp 23 Awg 4 Pair Cat 6 Lan Cableto Tia / Eia 568 B.2.1.In The Surface / Recessed Steel / Pvc Conduit As Required. 99 Network Rack Side 100 Sitc Of D Link 12 Port Network Switch 101 Network Rack & Server 102 Supply Installation Testing And Commissioning Of Supply & Installation Of 24U Closed Double Section Server Rack With Complete Accessories & Testing : Cbs350 24T 4G Cisco Make.Sitc Of It Rack -24Uwall Mounted Rack 24U ( Double Section Double Door Openable ) With Acrylic Glass Door With The Accessories - [ Two Fan Position Tray With Two 90 Cfm Fans ( Ac 230V ) , 3 Horizontal Cable Manager- 3Nos, Ac Power Panel Strip With 5 X 5 Amp / 15Ampsockets , Fuse And On / Off Switch, 1 Packet Mounting Hardware 103 Pvc & Other Miscellaneous Accessories. 104 Pvc Cable Ties, Velcrow Ties & Accessories 105 Telephone 106 Sitc Of Ip Telephone Instrument As Per Technical Specifications In Tender The Instrument To Be Compatible To Existing Epabx System Of Tadiran Make 107 Sitc Of Cat 6 Type I / O With Rj 45 Socket With Box, Faceplate And Fixing Screws, Having The Compliance / Certifications For Iso 9001:2015 & Rohs 108 Sitc Of Cat 6 Lan Cable For Dataincluding 25Mm Pvc Conduit Supply , Installation, Testing & Commisioning Of Of Utp 23 Awg 4 Pair Cat 6 Lan Cableto Tia / Eia 568 B.2.1.In The Surface / Recessed Steel / Pvc Conduit As Required. For Telephone 109 Novac System Design Supply Installation Testing And Commissioningall The Fire Alarm Related Work Proper Tagging , Glanding And Lugging To Be Provided.Agency Has To Submit Form A For Novac System , Fire System Installation Liasoning Works If Required For Fire Related Works Also In The Scope Of Agency. 110 Sitc Ofof 25 Bar Gas Suppression System ( Fk5112 ) L = 11M , W= 6.15M, C.V= 0.95M, R.V. = 2.950M 111 120 Lseamless Cylinder With Valve 112 Sapphire / Fk5112 Agent Per 1Kg 113 Supervisory Presure Switch - Standard ( Open On Fall ) 114 Pr. Swt, Dpst, Wp ( 2-3 / 4 OutlT ) , Lat. 115 1 / 4 Npt X 1 / 4 Bspp M Adpt 116 Male Elbow, 7 / 16-20 X 1 / 4 In. Npt 117 Male Tee 118 Act. Hose, Swl, Ss Br, 24, 1 / 4 Fml 119 Male Connector 7 / 16 - 20 X 1 / 4 Npt 120 Electrical Actuator - Ul Bridge Rectifier And Placement Switch ( Tlx-Us ) 121 2 Flexible Disc Hose 122 2 Check Valve 123 Local Manual Actuator 124 Pneumatic Actuator 125 Sapphire ( Fk-5-1-12 ) Door Caution Plate ( Less Than Noael - No Lock Off ) -English 126 Sapphire ( Fk-5-1-12 ) Manual Release Caution Plate - English 127 120 & 180 Litre 406Ø Container Bracket 128 Brass Nozzle - 360 Degree 129 Supply Of Ms Seamless Sch.40 Pipes Of 32Mm Dia., Forged Socket Fittings &All Accessories 130 Sitc Of Fire Detection System 131 Supply Of 2 Zone Conventional Gas Release Panel 132 Supply Ofmanual Abort Switch 133 Supply Of Manual Release Switch 134 Supply Of Conventional Smoke Detector With Base 135 Supply Of Response Indicator 136 Supply Of Conventional Hooter 137 Supply Of Conventional Hooter Cum Strobe 138 Supply Of 2 Core 1.5Sq Mm Frls Armouredcable 139 Installation Testing & Commissioning Novac And Fire Detection System Agency To Submit Form A For Installation All The Required Liasoning Work For Fire System Works Is In The Scope Of Agency. 140 Sitc Of New Fira Alarm System And Integration To Existing Fire Alarm System Bosch Make 141 Supply, Installation, Testing & Commissioning Ofphotoelectric Type Smoke Detector, Sensitivity Range Of 0.5% To 2.35% / Ft With Detector Base, Complete With Ms Powder Coated Junction Box For Mounting On Surface / On False Ceiling / Below False Floor. 142 Supply, Installation, Testing & Commissioning Of Ceiling Mounted / Wall Addressaablesounders / Hooter With Strobe Flasher 110 Cd 143 Supply Installation Of Detection Loop And Signal Cable : 2 Core X 1.5 Mm, Multistranded Copper, Frls, Armoured Cable, Red In Colour.The Cable Shall Belaid On Surface With Gi Saddle-Spacers Every 0.3 Meters. Complete With Gi Junction Box, Lugs, Cable Compression Glands, Cable Tags And Ferruling. 144 Supply, Installation Of Isi Mark Fire Extinguisher On Floor With Stand. Ceasefire Naf-50With Radium Sticker On Wall At Each Location ( 2 Kg ) Abc 145 Integration Of The System To Existing Fire Alarm System Of Bosch Make 146 Hvac Works 147 Design, Supply, Installation, Balancing And Commissioning Of Factory Fabricated Gss Sheet Metal Rectangular / Round Ducting Complete With Neoprene Rubber Gaskets, Elbows, Splitter Dampers, Vanes, Hangers, Supports Etc. As Per Approved Drawings And Specifications And As Per Smacna Standard Of Following Sheet Thickness Complete As Required. Hot Dipped Galvanised With 120Gsm Zinc Coatingthe Price Shall Include Necessary Scaffolding Required For Working At Required Height. 148 Thickness: 0.63 Mmsheet 149 Thickness: 0.8 Mmsheet 150 Supplying And Fixing Of 19Mm Thickness Duly Laminated Aluminum Foil Of Mat Finish Closed Cell Nitrile Rubber ( Class O ) Insulation On Existing Duct After Applying Suitable Adhesive For Nitrile Rubber. The Joints Shall Be Sealed With 50 Mm Wide And 3 Mm Thick Self Adhesive Nitrile Rubber Tape Insulation Complete As Per Specifications And As Required. Silver Tap To Be Provided For Final Finishing Of The Duct Insulation As Per Instructed And As Directed By Oic-Es. 151 Sitc Of Extruded Aluminium Powder Coated Diffuser / Grillwith Volume Control Damper With All Necessary Supports As Per Directed And As Instructed By Oic-Es 152 Sitc Of Extruded Aluminium Powder Coated Diffuser / Grillwithout Volume Control Damper With All Necessary Supports As Per Directed And As Instructed By Oic-Es 153 Supply, Installation, Testing And Commissioning Of Gi Volume Control Duct Damper / Non Return Damper 18 Guage Gi. Frame & 20 Guage Gi Blades Complete With Neoprene Rubber Gaskets, Nuts, Bolts, Screws Linkages, Flanges Etc, As Per Specifications. 154 Sitc Ofduct Mounted Finned Tubular Heaters With Low Watt Density ( 24 Kw In Threestepcontrol ) Withairflowswitch, Digitalhumidistat, Safety, Winterand Monsoon Selector Switch, Thermostat, Control Box ( Heater Panel ) , Controllers, Relays, Contactors And All Other Safety Accessories To Be Placed In The Plenum Box As Per Instructed And As Directed By Oic-Es. Note:- Cost Include With All The Cable Realted To The Above Unit. 155 Dismatling Of Existing Duct As Per Instructed And As Directed By Oic-Es. 156 Dismatling Of Src Unit With All Accessories I.E. Copper Pipe , Cable , Electrical Panel, Drain Etc As Per Instructed And As Directed By Oic-Es. 157 Installation And Commissioning Of Src Units As Mentioned In Sr. No 8 Items With All Respect As Per Instructed And As Directed By Oic-Es. Note:- Item Include Of All The Copper Pipe, Cable , Electric Panel, Gas Charging Etc. Incase Any Additional Item Require For Commissioning Of The Unit To Be Consider No Cost Given For The Same. 158 Supply, Installation, Testing And Commissioning Of Pvc ( Minimum 15Kg / Sqcm Pressure Rated ) Drain Water Piping Complete With Fittings ( Elbows, Tees, Reducers, Sockets, U Trap Etc. ) Supports, Jointinginsulated With Xlpe Class O Tubular Insulation And Any Other Item Required To Make The System Complete. Nominal Diameters Of Pipein Mms As Indicated Below: 159 25 Mm Dia Pipe, Insulation Thickness - 6 Mm 160 Sitc Of Drain Pump Fir Src Units As Per Instracted And As Directed By Oic-Es. 161 Supply And Installtion Of Dually Insulated Drain Protection Tray Below The Chilled Water Pipe As Per Instructed And As Directed By Oic-Es. 162 Sitc Of Portable Type Dehumidifier With Capacity Of 70 Lpd As Per Instructed And As Directed By Oic-Es. 163 Dismatling And Re-Installtion Of Fire Fighting Piping As Per Design Approved. Desogn In The Scope Of Contractor. Note:- Incase Any Additional Material Require For Complete The Job Is In The Scope Of Contractor No Additional Cost Given Fore The Same. 164 Mgps 165 Supply, Installation, Testing, Commissioing Of Medical Gas Isolation Valvesbare On Line, Nfpa 99 Compliant, High Tensile Bronze / Brass 4 Bolt Bronze Body Double Seal Union Ball Type With Tfe / Viton Seal 400 Psig Isolation Valves With K Type Pipe Stubs-Medical Grade Copper Pipe For Fixing In The Floor Local Zone Valve Box, Area Valve Boxes, Bare For Wards Asper Instructed And As Directed By Oic-Es. 166 15 Mm 167 22Mm 168 Supply, Installation, Testing, Commissioing Ofas Per Nfpa 99 Level 6020 Medical Grade Gas Distribution Pipingmanufactured From Phophorpus Deoxidized Non Arsenical Copper To Bs En 1412:1996 Grade Cw024a Manufactured To Metric Outside Diameters Having Mechanical Properties In Accordance With Bs En 13348:2008-R250 Half Hard For Sizes Up To 54 Mm Or Bsen 133348:2008-R290 Fro Larger Sizes In Ready Made Built Up Trenches As Per Applicable Standard, Open Execution On Internal / External Walls, In Vertical Shafts, Above False Ceilings As Also Inside Removable Trunking, In Walls By Chasing Cuttingcompelete With Factory Made Fittings Such As Tee / Elbow / Crossover / Wall Sleeves Etc., Complete With Vertical & Horizontal Supports And Termination At Both Ends, Colour Coded Painting Etc. 169 12Mm Id X 0.7 Mm Thick 170 15 Mm Id X 0.9 Mm Thick 171 22Mm Id X 0.9 Mm Thick 172 Supply, Installation, Testing, Commissioing Ofmedical Gas Specificterminal Outlets ( Tender Make Only ) , Nfpa 99 Compliant, Geometric Quick Fix Type For Breathing Air / Surgical Air / Medicall Vacuum / Medical Oxygen Complying & Matching With Correct Medical Gas Probe According To The Gas Service Outlets To Be Fitted In Bed Head Panels.As Per Tender Specifications 173 Medical Oxygen 174 Medical Vaccum 175 Supply, Installation, Testing, Commissioing Ofvacuum Unit Complying With Iso100793 :2000 For Ward Areas Consisting Of 0-760 Mbar Vaccum Regulator, Vaccum Filter & 1000 Ml Vacuum Collection Jar Made From Polycarbonate / Polysulphone Material 176 Supply, Installation, Testing, Commissioing Of Oxygen Flow Meters With Humidifier Bottle Complying With Iso 15002:2008 Range Of 0-15 Lpm, 3-5 Psig Humidifier Setting

Key Value

Document Fees
Refer document
EMD
INR 155000.0 /-
Tender Value
INR 77.50 Lakhs /-

Attachment

FileName File Description File Size
6c8e2bab-e9c2-4370-9c3b-6fedcf0315c2.html Tender Notice 0 KB
AnnexureForm.xls Tender Document 0 KB
BOQ_845796.xls Tender Document 0 KB
Earthinglayouts.pdf Tender Document 0 KB
TD.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

Name of Work:
Sl. No. Item Description
1Civil & Interior works
2Demolition - Demolition and removal of walls & existing flooring tiles, screed, PCC till slab finishing the surface for new flooring works without causing any damage to RCC elementsand removal of existing false ceiling & lights without causing any damage to RCC elements, MGPS, HVAC or any other services which need to be retained wherever & whenever required during execution. The work shall include all material, labour, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debries from site to nearest waste collection etc.,complete as directed by the Engineer-in-charge.
3P.C.C. - Providing and laying 100 - 150 mm thick M25 Grade Plain Cement Concrete in Spect CT gantry Room forming an even surface without any undulations and approved quality by engineer in charge. The work shall include all material, fixing, wastages, labor, all lead and lifts at all levels, loading and un loading, shuttering, reinforcement, transportation and other incidental charges, cleaning after completion, removal of excess material and debris from site to nearest waste collection etc., complete as directed by the Engineer-in-charge.
4Brick Masonry ( 115/230/345 MM thick ) - Providing, laying & constructing 2nd class Red Brick Masonry 115 mm thick in CM 1:4 including scaffolding, raking of joints, curing with proper finishing of mortar joints etc. walls at all heights and levels only & providing RCC lintel beams with1 :2: 4 proportion 4 nos of 6 mm dia reinforcementto openings wherever necessary for AC vents, doors, windows and any other services also providing concrete 100 mm thick bands at every 4".The work shall include all material, fixing, wastages, labor, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debris from site to nearest waste collection etc., complete as directed by the Engineer-in-charge. ( For Partition walls between Battery Room, UPS Room and Equipment room )
5Plaster ( Internal ) - Providing internal cement plaster 12 mm thick for walls & Ceiling in a single coats in cement mortar 1:4 to concrete or brick surfaces, in all positions including scaffolding and curing complete.( For Partition walls between PET CT, Battery Room, UPS Room & Equipment room )
6Plaster ( External ) - Providing sand faced plaster 25mm thick externally in cement mortar using approved screened sand in all positions including basecoat of 15mm thick in 1:4 using water proof compound 1kg per cement bag curing the same for not less than two days and keeping the surface of basecoat rough to receive the sand faced treatment of 6 to 8 mm thick in C.M. 1:4 finishing the surface taking out the grains and curing for fourteen days including including fixing of chicken mesh at concrete brickwork junction, glass fiber reinforcement [recron]scaffolding etc. complete.
7P.O.P. Punning - Scraping of old paint/ distemper wherever necessary from the existing walls, and applying of 3.0 to 6.0 mm thick lime punning over it to give a smooth leveled finish, the final coat of punning to have one coat of oil based Cement primer. The work shall include all material, fixing, wastages, labor, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debris from site to nearest waste collection etc., complete as directed by the Engineer-in-charge.( For Partition walls between PET CT, Battery Room, UPS Room & Equipment room )
8Flooring, Dado, Skirting ( Vitrified Tiles ) - Providing and Fixing Vitrified Tiles 10 mm thick600 x 600 with water absorption less than 0.08% and conforming to IS : 15622, on up to 50 mm thick cement mortar base 1:4. The work shall include cost of materials, fixing wastages, labor, all lead and lift at all levels, loading and unloading, transportation, curing, joint filling, (with cement grout matching the color of tiles, balendure), removing of existing tiles if any, cleaning after fixing. complete and all other incidental charges like breakage in transportation or on site or while fixing, as directed by Engineer-in-charge.Tiles to be used strictly which have been used for existing flooring or approved shade and design.
9Flooring ( Anti - Skid Tiles ) - Providing and Fixing Vitrified Tiles 10 mm thick300 x 300 with water absorption less than 0.08% and conforming to IS : 15622, on up to 50 mm thick cement mortar base 1:4. The work shall include cost of materials, fixing wastages, labor, all lead and lift at all levels, loading and unloading, transportation, curing, joint filling, (with cement grout matching the colour of tiles, balendure), removing of existing tiles if any, cleaning after fixing. complete and all other incidental charges like breakage in transportation or on site or while fixing, as directed by Engineer-in-charge.
10P.O.P. On Flooring - Providing and Applying average 12mm thk. P.O.P. on floor, on plastic sheet to protect floor from physical damage during construction.
11Core Cutting - Drilling with core cutting machine ( 50 mm - 300 mm ) in RCC slabs, walls etc.wherever required in buildings, manholes, ducts, water tanks, pits etc. for laying pipes, sleeves and making good the same to give an even finish . The rate shall include the cost of drilling core, providing EPOXY based water proofing compound for sealing the joints around the pipes, nominal reinforcement wherever required, scaffolding and labor charges for working at all levels ,leads and heights . (Maximum thickness of RCC members shall be 300mm) and as directed by Engineer-In-Charge.
12Micro Concrete - Drilling & Providing encasement to Gantry anchors, with free flow high strength non shrink micro concrete M -35 using single cement micro concrete shrinkage components added with 100% by weight saturated dry stone dust. The water cement ratio should be maintained as per manufacturer"s specifications to achieve dense solid mass. The Micro concrete shall be poured properly in slurry tight prefixed holding boards formwork, fixed properly in line, level and in the required size/shape and well oiled etc. The air bubbles, if any shall be removed by tapping the boards and removing the same after 24 hours, curing the micro-concrete thoroughly for 14 Days etc. complete. The rate shall be inclusive of shuttering, strutting, curing etc. including cost reinforcement complete as directed and instructed.
13Cable Trench - Providing Cable trench and cutout of on site required size in flooring and wall with finishing of all edges with PCC & providing plaster to wall cutouts with paint & specs as mentioned in BOQand providing 3 mm removable cover made of Stainless steel matt finish on front side for cables, The work shall include all material, fixing, wastages, labor, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debris from site to nearest waste collection etc., complete as directed by the Engineer-in-charge.
14Internal Wall/Ceiling Paint - Providing and Applying Internal wall painting with Acrylic paint of approved shade including basepreparation using putty and fillers as specified and directed all complete. ( 2 coat lambi putty + 2 coat primer + 2 or more coats of paint ). The work shall include all material, fixing, wastages, labor, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debris from site to nearest waste collection etc., complete as directed by the Engineer-in-charge.
15Cemetacious BoardCeiling - Providing & fixing Cementacious board celling false ceiling as per drawing.using 12 mm thick plain gypsum boards and gypsum verticals for cove lighting of M/s. Saint Gobain or approved equivalent, fixed to the suspended grid, fabricated and fixed to the soffit of roof / beams and wall using - Gypsteel Ultra ceiling sections - perimeter channels of size 20 mm x 28 mm x 30 mm fixed to the wall using metal screws and nylon sleeves recommended by the manufacturer at a spacing not exceeding 600 mm c/c, intermediate channels of size 15 mm x 45 mm x 15 mm at a spacing not exceeding 1200 mm c/c suspended using ceiling angles of size 25 mm x 10 mm and appropriate length, fixed to the soffit of R.C.C beams / slabs using G.I soffit cleats of size 27 mm x 37mm x 25 mm x 1.6 mm and metal expansion fasteners of 38 mm x 12 mm diameter at a spacing not exceeding 1200 mm c/c, ceiling sections of size 80 mm x 26 mm x 51 mm provided across the intermediate channel at a spacing of 475 mm c/c, at bottom which shall be fixed by G.I connecting clips of 2.64 mm diameter at junctions. The ceiling channels shall be provided with a minimum overlap of 50 mm at joints and fixed to the perimeter channels using metal screws at ends. Specifications using cold rolled Gypsteel Ultra sections and Gypsum boards manufactured by Gypsum India Ltd. or approved equivalent. Additional perimeter channels / ceiling sections shall be provided around the cut outs for light fittings A/C diffusers etc. Additional support for cut outs to be provided at no extra cost. The ceiling boards shall be fixed to the underside of the suspended grid using 3.5 mm x 25 mm self-tapping screws. The joints shall be finished with joint paper tape and jointing compound of approved make and providing and applying plaster of Paris putty for required thickness. The work shall include all material, fixing, wastages, labor, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debris from site to nearest waste collection etc., complete as directed by the Engineer-in-charge.
16Metal Grid Ceiling - Providing & fixing 600 mm x 600 mm powdered coated metal perforated / non perforated plain tiles with beveled edges and integrated , false ceiling with metal suspension silout grid (to match existing false ceiling pattern) system false ceiling for area under scope.Installation shall be used as per Manufacturers specificationsgalvanized section ,exposed tee will be powder coated and withsuspension system i.e.anchor fastener, vertical hanger, hook clip etc. as described. To be laid at all heights cut to all shapes and sizes. The work shall include all material, fixing, wastages, labor, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debris from site to nearest waste collection etc., complete as directed by the Engineer-in-charge.
17Skylight - ( Gantry Room ) - Providing and fixing of Skylight of translucent acrylic sheet of approved print design on exposed face ( 4" x 6" ), with box frame made with 18 mm ply covered with approved laminate on all exposed edges and shall be back lit with LED strips as per specifications and drawings, with all fitting, wiring & framing accessories necessary.The work shall include all material, fixing, wastages, labor, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debris from site to nearest waste collection etc., complete as directed by the Engineer-in-charge.
18Epoxy Self levelling : Providing and doing epoxy self levelling over existing flooring and making surface clean and clear to receive PVC flooring as per manufacturers specification, including cleaning the flooring dirt free, curing etc. complete as directed and instrustructed.
19Vinyl Flooring - Supply and fixing of 2 mm thick vinyl of approved dual colour by architect and customer laid on IPS Flooring / PCC with plain finish inculuding self leveling compound in machine room without any undulation and quality check approved by the engineer.The work shall include all material, fixing, wastages, labor, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debris from site to nearest waste collection etc., complete as directed by the Engineer-in-charge.
20Roller Blinds - Providing and fixing of( 100% Polyester Woven Fabric (Acrylic coated) 168 GSM Solid panel: 0.4mm± ) Openness Factor : 3% 4-5 Grade tested in accordance with BS EN ISO 105- B01:1999 ( colour and texture will be provided by the architect ) Control Unit: Blinds mechanism must have the control clutch drive unit with engineered heavy duty chain drive pulley operating system consisting of gear clutch housing and locking plug containing at least 6 ribs and inserted into a minimum of 38mm dia. roller tube. Clutch has to be self-lubricating with safety pins for secure bracket installation and unlocking pin for quick manual removal. Provided clutch system must allow convenience in operation for large windows to the smallest windows. The control unit should be made up of polypropylene material using injection moulding method. Gearing Ratio: 1.75:1 to reduce operating force for larger blinds. 24 nos Sprocket for 38mm diameter roller tube. Control unit is operated directionally by the use of beaded endless chain to raise and lower the blind smoothly. ( colour and texture selection will be done by the architect and customer ) The work shall include all material, fixing, wastages, labor, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debris from site to nearest waste collection etc., complete as directed by the Engineer-in-charge.
21TEAK WOOD DOOR FRAME Providing wood work with C.P. teak wood in frames for doorswindows, ventilators, Air-condition frames, clear story window,false ceiling and partitions etc.wrought framed and fixedin position including applying one coat of approved woodprimer to the exposed surfaces and tow coats of bitumasticpaint to the surface of wood in contact with masonry/ concreteetc.complete.In frames of doors, windows, ventilators and clearstorey windows etc. fixed with M.S hold fast of size40x3mmx150mm long bend to shape & embeded incement concrete 1:2:4. complete as directed and instructed
22Wooden Door - Providing & fixing on Flush door, single or double panel shall be of 35.0mm flush door with 100 x 75mm second class teak wood Frame ,1.0mm lamination on both the sides of approved shade and make( greenlam , merino or royaletouch only ), with two 1 " thick vertical metal finish laminate lines on both sides of door to be fixed to partition /wall with 4 heavy duty 4" SS hinges, and shall have cylindrical lock with Heavy duty SS Tower bolts. The work shall include all material, fixing, wastages, labour, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debries from site to nearest waste collection etc.,complete as directed by the Engineer-in-charge. ( all accesories to be used of godrej, dorma only )
23Lead Door frame + shutter- Providing and fixing2mm Lead lined min 35mm thick single or double panel block door with wooden frame covered with 1 mm thick laminate of aproved shade, pasting 12 mm ply over lead sheet on one side of door and frame, and 1 mm laminate on both side of the door and frame with heavy duty door handle, lock & tower bolts. The work shall include all material, fixing, wastages, labour, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debries from site to nearest waste collection etc.,complete as directed by the Engineer-in-charge.
24Aluminium (anodized) Door with frame - Providing and fixing aluminium door with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, indluding necessary filling up the gaps at junctions, i.e. at top. bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snab beading for glazing / panelling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, panelling and desh fasteners to be paid for separarely) a) for fixed portion:12 Guage. Powder coated aluminium (minium thickness of powder coating 50 micron). b) For shutters of door 10 Guage including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minium thickness of powder coating 50 micron).The work shall include all material, fixing, wastages, labour, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debries from site to nearest waste collection etc.,complete as directed by the Engineer-in-charge."
25Lead Wooden Framing for window - (6" X 3")On Site Fabricating wooden framing forconsole window, 3 inch thick frame and depth depending on wall thickness ( refer layout & consult project manager )made with 18 mm ply with 2 mm thick lead sheilding and all exposed surface with approved laminate. The work shall include all material, fixing, wastages, labour, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debries from site to nearest waste collection etc.,complete as directed by the Engineer-in-charge.
26Workstation - On site Fabricating - Providing & fixing workstation ( 700 mm Wide x 750 mm High ) in any required room of PET CT Premisis. to be made in 18 mm thick Marine Ply to be supported with 18mm Marine Ply IS 710 verticals AT 5" c/c or as directed by engineer incharge. All the exposed surfaces 1.0mm thick laminated finish of approved shadewith 450 mm wide pedestals having 4 drawers each with SS locking system. providing grommet with cover at each vertical partition.The work shall include all material, fixing, wastages, labour, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debries from site to nearest waste collection etc.,complete as directed by the Engineer-in-charge.
27WOODEN CABINET- FULLY LAMINATED: Providing & fixing cabinet made up of 19 mm. Commercialply of approved make for top, bottom, sides & shelves &8mm commercial ply approved make for back side Door shutter made up of 19mm thick commercial ply andouter surfaces and top of shelves for open type cabine shouldbe laminated with 1.5mm thick approved plastic laminatesheet of required colour including all brass fittings such ashinges, tower bolts, ball catches, stopper, handle, kNosbs as per shown in drawing or approved by Engineer-In-Charge etc.and all exposed edges lipping with 6mm Thick T.W. lipping patti.locking arrangement with heavy duty multipurposelock etc. allcomplete as specified & directed by Engineer-In-Charge.
28Kaddappa Storage Unit - On Site fabricating open storage unit made up of 25 mm Thick Kadappa stone 7" high with 3 equal horizontal division 2.5" c/c The work shall include all material, fixing, wastages, labour, polishing, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debries from site to nearest waste collection etc.,complete as directed by the Engineer-in-charge.
29Granite platform - On site fabricating 750 mm wide 18 mm thick mirror polished machine cut Steel grey Granite stone platform on a bed of 12 mm average thick cement mortar 1:3 (with coarse sand) to make up a total thickness of 50 mm supported by kadappa with adequate C/C support (max vertical support distance 900 mm c/c), including laying slabs in cement slurry, pigmented to match the shade of slabs, grinding, rubbing ,epoxy touch ups , polishing , curing and making the full round gola on nosing etc complete at all levels.
30Office Chair - Providing and arranging office chairs with castors and armrest. heavy duty Make -mid black or similar cost include supply, transport, loading unloading, comple as intructed by engineer incharge.
31Soft Board / Notice Board - Providing and fixing of 1.5 " x 2 " soft board with box of pins. The work shall include all material, fixing, wastages, labour, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debries from site to nearest waste collection etc.,complete as directed by the Engineer-in-charge.
32Name plate - Providing and Fixing of Acrylic Name Boards or approved design for respective rooms of PET C.T. Department ( 4" x 10" ) The work shall include all material, fixing, wastages, labour, all lead and lifts at all levels, loading and un loading, transportation and other incidental charges, cleaning after completion, removal of excess material and debries from site to nearest waste collection etc.,complete as directed by the Engineer-in-charge.
33Mirror - Supply and installation of 2" x 1.5" Mirrors with SSstudds in toilets as directed by engineer incharge
34Recliner Chairs - Supply and installation of leatherite finished recliner chairs in post dosage waiting room of approved design, size and color by architect / customer. Complete as directed & instructed.
35Radiographic film viewers - Supply and installation of 400 mm x 1000 mm screen Radiographic film viewer.
36STRUCTURAL STEEL WORK (bulit up section & hollow sections) : At all levels including supplying cutting fabricating welding or blotting erecting and fixing in position including painting with a primary coat of approved steel primer, including cost of materials labour with chasing in wall or embedding in floor and making good the same by filling 1:2:4 cement concrete and plastering if necessary all as specified and directed by Engineer-in-Charge.
37Electrical SITC
38Earthing & Safety requirement Supply & InstallationTesting and commissioning
39SITC of Tinned copper earth plate electrode 600 x 600 x 3.15 mm earth station, 3 mtr below ground level as per drawing complete with all required materials like Cole, charcoal, salt, brass nut bolts & washers, watering arrangements, GI pipe (B class), concrete chamber, heavy duty cast iron cover plate & excavation in all types of soil in ground refilling & removal excess earth within a radius of 500 mtr. Etc.Note:1.The chamber cover & plate shall be of heavy-duty hinged type & it shall weigh approx. 65 to 75 Kgs. For 450 x 450 mm size & shall be got approved by dept. (6 mm chequred plate with 40 x 40 x 6 mm angle iron frame)2.Plastering shall be done both inside & out side.3.The measurement of resistance of earth station & resistance of complete scheme of earthing layout shall be measured, recorded & got approved by Engg-in-charge.Drawing for earthing layout atatched. Agency to carry out earthing as per attached drawing
40SITC of Hot dipped GI earth plate electrode 600 x 600 x 6.3 mm earth station 3 mtr below the ground level --- Same as above-- as per drawing & specifications complete with all required materials like coke/charcoal, salts , brass nut bolts & washers, watering arrangement, GU pipe (B class) concrete/brick chamber, heavy duty cast iron cover plate & excavation in ground, refilling& removing of excess earth within a radius of 500 mtr.etc. scope also includes dewatering, shoring, & consolidation etc. Drawing for earthing layout atatched. Agency to carry out earthing as per attached drawing
41SITC of GI strip of size 25 x 6 mm including all fixing accessories, PVCblack colour sleeves on strip
42SITC of 25mm X 3mm thk Cu. Strip with Heat shrinkPVC sleeve for UPS and electronics earthing including all fixing accessories, PVCblack colour sleeves on strip
43SITC of 8 SWGGIbare wire including lugs and all fixing accessories for earthing of all metal parts
44SITC of Earthing Busbar Box with acrylic cover and Cu/GI strip on suitable insulator. Strip shall be provided with holes at every 75 mm with nutbolts & washers.
45SITC of Earthing Busbar Box with 25 x 6 mm tinned cu strip 500 mm long on suitable insulator. Strip shall be provided with 8mm holes at every 75 mm with nutbolts & washers.
46Supply and installation of 1.1 kV grade Rubber matting as per IS standard 5mm thick in equipment room & battery UPS Room
47SITC of 150mm x 150mm enamel type " DANGER HIGH VOLTAGE " board
48M. V. Panels and Distribution Board. Supply & Installation Testing and commissioning
49Supply, Installation, testing & commissioning of MV panel boards compartmental cubicle type freestanding with appropriate cable entries, front operating, front maintained complete with baseframe etc as required & as per IS 8623specifications panel has to be fabricated out of 16/18 SWG CRCA sheet, & surface quoted with phosphate seven tank process and duly painted (RAL 7032) with powder coating process. (Refer Single Line Diagram for Switchgear & other details).
50SITC of MAIN PANEL 3phase 415 volt , FOR PET-CT as per SLD in tender documents
51SITC of UPS DISTRIBUTION PANEL OF HVAC OR OTHER REQUIREMENTS as per SLD in tender documents
52SITC of UPS Distribution board Flexi DB 4 Row 10 Module each with63A TPN MCB as Main Incomer, 40 A DP RCCB-30 mA Si / Hi sereis as Sub-incomerand 20A SP MCB as outgoing Qty 30 Nos .UPS DBs) All MCB C Curve. The work also includes structural steel required for base frame of distribution board including finishing DISTRIBUTION BOARDS Supply, installation, testing & commissioning of 500V Distribution Boards as speci- fied, "i) Copper busbars together with tapped neutral bar for individual phases. , copper earth strip with tapping for EEC, Interconnections and earthing.Sheet steel enclosure suitable for recessed or surface mounting with hinged lockable doors interlocked. Thikness of 1.6 mm , Phase to phase barriers in case of 3Ph boards. , "vii) Necessary MS support frame & painting, labelling, phase indicating lamps with fuses etc. complete.
53SITC of Flexi DB 4 Row 10Module eachwith80A TPN MCB as Main Incomer, 63 A DP RCCB-100mA Si / Hi sereis as Sub-incomerand 20A SP MCB as outgoing. Qty 30 Nos LP DB)All MCB C CurveThe work also includes structural steel required for base frame of distribution board including finishing DISTRIBUTION BOARDS Supply, installation, testing & commissioning of 500V Distribution Boards as speci- fied, "i) Copper busbars together with tapped neutral bar for individual phases. , copper earth strip with tapping for EEC, Interconnections and earthing.Sheet steel enclosure suitable for recessed or surface mounting with hinged lockable doors interlocked. Thikness of 1.6 mm , Phase to phase barriers in case of 3Ph boards. , "vii) Necessary MS support frame & painting, labelling, phase indicating lamps with fuses etc. complete.
54Supply, fixing, testing,of good quality 20 Aindustrial sockets with 20A MCB"sIP 20 metal enclosure. Box should be suitable to terminate cables / wires easily, complete as required. 4 For AC power provision and 1 for Network Rack.
55Supply and Installation of Industrial 32 A 1 PH. Plug & socket Interlock type with 32A SP MCB 3 pin type.
56SITC of 250A 4 Pole MCCB with enclosure microprocessor , LSI and earth fault protection , rotary operating handle including all fixing accessories
57Cables Supply & Installation testing and commissioning • All the power cables , lighting wirings cable tag to be provided. Cable Tag Specifications -D. Labelling: • Material: Stainless steel, zero halogen, or halogen-free • Thickness: 0.25 mm or 0.4 mm • Width: 9.5 mm or 19 mm • Height: 0.394 in • Printable area dimensions: 0.394 in H x 3.15 in W • Operating temperature: -25 °C to +80 °C
58Supply, testing, tagging, laying and commissioning following sizes mentioned below of 1100 Volt grade, XLPE / PVC insulated multistrand Al. / Cu. Conductor armoured / unarmoured cables (As Per IS 1554 & IS 7098)in cable trench , on cable trays / ladders etc. as. required complete with clamps, termination, color coding and tagging. All cable glands to be double compression type and lugs to be as per specifications mentioned in tender documents. PVC Shroud to be provided on each glands of suitable size. All cable tages to be SS type and as per specifications in tender documents.
593.5C X 240 Sq.mm. A2XFY cable ( AL cable ).Armoured cable including glanding , lugging and all fixing accessories As main incomer cable from Hospitalsbreaker
601C X 95 Sq.mm. FR Copper flexible cable. Including glands , lugs , end connectionsand all fixing accessories For UPS Input and Output of Machine.
614C X 10 Sq.mm FR Copper flexible 2XFY cableflexible cable Including glands , lugs , end connectionsand all fixing accessories For UPS DB
624C X 16 Sq.mm FR Copper flexible 2XFY cableIncluding glands , lugs , end connectionsand all fixing accessories For 1 LPDB
633C x 2.5 Sq.mm. FR Copper Sheathed cableIncluding glands , lugs , end connectionsand all fixing accessories For Workstations&other power points.
641C x 95 Sq.mm. YY cable. flexible Including glands , lugs , end connectionsand all fixing accessories For earthing
654C X 35 Sq.mm FR Copper Cable armouredIncluding glands , lugs , end connectionsand all fixing accessories
66CABLE TRAY Supply, Installation, laying and erection of G.I. Perforated and Ladder Type cable tray with reducer, bends, tees, clamps and couplers for fixing of cable to complete the job. It should also comply load testing of IS 14927-1 (2001).Scope covers:1)Supply of pre-fabricated cable trays as per approved design by consultant & client.2)Delivery of the material at site.3)Unloading of material & storage at site store.4)Shifting of material from site store to place of installation.5)Painting the support structure with two coats of red oxide and two coats of enamel colour paint of approved brands.6)All material shall be Hot dip galvanised (86 micron Zinc thickness min.) as per IS and specifications.7)Max. distance between two structural steel supports shall not exceed 1.2 Mtrs.8)Tying of cables with cable trays with proper dressing. 9)Max. no. of tier of cables on cable tray MV cables : 1 No. 10)To prepare shop drawing and to take approval of consultant & client at each stage.11)To prepare & submit as-built drawing and handing over document to end user. Structural steel required for cable tray supportis in the scope of agency. Rates to be quoted accordingly
67SITC of 100 mm perforated tray (16 SWG).
68SITC of 300 mm perforated tray (14 SWG).
69SITC of 100 mm perforated tray Cover (18 SWG).
70SITC 300 mm perforated tray Cover (18 SWG).
71SITC of 300 x 100 mmPVC TRUNKINGwith cover 2mm thick for DB wire/ cables dressing for LDB/ PDB & UPS DB.& CONSOLE ROOM TO CT MACHINE
72SITC of Cable Ladder - M.S Fabricated cable ladder for rising cables upto ceiling level
73Point Wiring Supply & Installation Important Note : Refer Electrical layout provided by architect for better understanding of SB"s • All the lighting circuits switchboard inside and lighting panel inside ferruling to be provided as instructed by EIC ES. All the wiringslight side, switch side, switch socket side ,lighting and powerpanel side wire ferrule type lug to be provided.
74SITC of Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable including surface/ recessed Heavy class PVC conduitHeavy(HMS) as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire from main distribution board to power point circuits and lighting switchboard.
75SITC of Primary point wiring for light point/ fan point/ exhaust fan point/ call bell point with 2 x 1.5sqmm + 1 x 1.5sqmm FRLS PVC insulated copper conductor single core cable in surface / recessed includingmedium class PVC conduit Heavy(HMS) / casing capping , with modular switch , modular plate,suitable GI box / PVC Boxfor concealled , suitable PVC box for surface, ceiling fan rose, PVC junction box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
76SITCSecondary point wiring light to light looping with 2 x 1.5sqmm + 1 x 1.5sqmm FRLS PVC insulated copper conductor single core cable in surface / recessed includingmedium class PVC conduit Heavy(HMS) / casing capping , with modular switch, modular plate,suitable GI box for concealled , suitable GI Box / PVC box for surface, ceiling fan rose, PVC junction box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
77DM - Supply and installation of 4 module CAT 6 Data module switch board modular typefor computers.
78Supplying and fixing following size/ modules, PVC / GI box alongwith modular base & cover plate for modular switches in recess etc. as required. • All the power socket tagging to be provided , PVC tags to be provided. • All the power sockets inside and power panel insidewiring ferruling to be done as instructed by EIC ES
793 Module
806 Module
81Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
82Modular switch 6A/16A
83Modular Socket 6A/16A
84Light Fixtures & Electrical Appliances Supply & Installation Important Note : Refer Electrical layout provided by architect for better understanding of SB"s
85Supply, Installation, testing and commissioning of lighting fixtures, fans including necessary accessories.
86Supply ,Installation,Testing & Commisioning of LED shaped36 Watt Premium Range Recessed Downlighter having die cast aluminum housing/ CRCA Housing 2 x 2 lighting with in built driver- Non Dimmable -as per the make approved by engineer incharge and architect.The material should be of premium range of products with reputed make and should have relevant electrical certification. Lumens more than 100Lumens/watt pressure die-cast aluminimum housing with white front bottom frame suitable to following features. LED fixture to be fixed surface or concealed as per site requirement. - Luminaires suitable to Aluminium metal grid ceiling or Gypsum or POP, -Minimum System Lumen output 3600 lumens -In built electronic LED pre wired driver, -Luminaire shall be with special translucent --High Surge Protection:-2.5kV. -Highdiffuser>85%, -Provision of Spring loaded Mounting clips. -Opal Translucent cover/Poly Carbonate reflector. -CRI>80,THD<10%. -High Efficacy gretaer than or equal to 100 lm/watt, -Provide Uniform low glare lighting non yellowing/PMMA lens for better light distribution, -Operatable voltage - 220-240 V,50 Hz, PF>0.9, -Colour Temperature gretaer than or equal to 4500K to 5500K
87Supply ,Installation,Testing & Commisioning of LED shaped15 Watt Premium Range Recessed Downlighter having die cast aluminum housing with in built driver- Non Dimmable -as per the make approved by engineer incharge and architect.The material should be of premium range of products with reputed make and should have relevant electrical certification. Lumens more than 100Lumens/watt pressure die-cast aluminimum housing with white front bottom frame suitable to following features. LED fixture to be fixed surface or concealed as per site requirement. LED Round / Square as approved - Luminaires suitable to Aluminium metal grid ceiling or Gypsum or POP, -Minimum System Lumen output 1500 lumens -In built electronic LED pre wired driver, -Luminaire shall be with special translucent --High Surge Protection:-2.5kV. -Highdiffuser>85%, -Provision of Spring loaded Mounting clips. -Opal Translucent cover/Poly Carbonate reflector. -CRI>80,THD<10%. -High Efficacy gretaer than or equal to 100 lm/watt, -Provide Uniform low glare lighting non yellowing/PMMA lens for better light distribution, -Operatable voltage - 220-240 V,50 Hz, PF>0.9, -Colour Temperature gretaer than or equal to 4500K to 5500K
88SITC of LED Batten Light - 24 W - 4 feetWhite including all fixing accessories
89SITC of LED strip / ropelights 10watt to 15watt per meter, colour temp as directed by EIC ES LED Strip Light - 22 W - 2700 K - 60- 90 LED Density Per meter
90SITC of LED strip light drivers6A to 10A as directed by EIS ES
91SITC of alluminium profile housing for LED strip lights as directed by EIC ES
92SITC of LED COB Light - 15 W - 2700 K , the light CRCA Housing
93SITC of Oscillation Wall Fan with sweep control - 400 MM - include point wiring and switch - location to be decided on site of turnkey scope only
94SITC of Dehumidifier - 60 Liters ( Approved Make - visumed )
95SITC of RED LED Bulb including angle holder- Operation Theatre Light
96Networking Works
97Horizontal Cabling - Workstation Side
98SITC of CAT 6 LAN cable for DATAincluding 25mm PVC Conduit Supply ,Installation,Testing & Commisioning of of UTP 23 AWG 4 pair CAT 6 LAN Cableto TIA/ EIA 568 B.2.1.in the surface/ recessed steel/ PVC conduit as required.
99Network Rack Side
100SITC of D link 12 Port Network switch
101Network Rack & Server
102Supply Installation testing and commissioning of Supply & installation of 24U Closed double section Server Rack with complete accessories & testing : CBS350 24T 4G cisco make.SITC of IT rack -24UWall mounted rack 24U(double section double door openable )with acrylic glass door with the accessories -[Two Fan position tray with two 90 CFM fans(AC 230V),3 Horizontal cable manager- 3nos, AC power panel strip with 5 X 5 AMP /15Ampsockets ,fuse and on/off switch, 1 packet mounting hardware
103PVC & Other Miscellaneous Accessories.
104PVC Cable Ties, Velcrow Ties & Accessories
105Telephone
106SITC of IP telephone Instrument as per technical specifications in tender The instrument to be compatible to existing EPABX system of Tadiran Make
107SITC of Cat 6 type I/O with RJ 45 socket with Box, faceplate and fixing screws, having the compliance/certifications for ISO 9001:2015 & ROHS
108SITC of CAT 6 LAN cable for DATAincluding 25mm PVC Conduit Supply ,Installation,Testing & Commisioning of of UTP 23 AWG 4 pair CAT 6 LAN Cableto TIA/ EIA 568 B.2.1.in the surface/ recessed steel/ PVC conduit as required. For telephone
109NOVAC SYSTEM Design Supply Installation Testing and commissioningAll the fire alarm related work proper tagging , glanding and lugging to be provided.Agency has to submit Form A for NOVAC system , fire system installation Liasoning works if required for fire related works also in the scope of agency.
110SITC ofof 25 BAR GAS SUPPRESSION SYSTEM (FK5112) L = 11m , W= 6.15m, C.V= 0.95m, R.V. = 2.950m
111120 LSeamless Cylinder with Valve
112SAPPHIRE/FK5112 AGENT PER 1KG
113Supervisory presure switch - standard (open on fall)
114Pr. SWT, DPST, WP (2-3/4"" outl"t), Lat.
1151/4 NPT X 1/4 BSPP M ADPT
116Male Elbow, 7/16-20 x 1/4 in. NPT
117Male Tee
118Act. Hose, SWL, SS BR, 24"", 1/4"" FML
119Male Connector 7/16 - 20 x 1/4"" NPT
120Electrical Actuator - UL Bridge Rectifier and Placement Switch (TLX-US)
1212" FLEXIBLE DISC HOSE
1222" CHECK VALVE
123LOCAL MANUAL ACTUATOR
124PNEUMATIC ACTUATOR
125SAPPHIRE (FK-5-1-12) door caution plate (less than NOAEL - no lock off) - English
126SAPPHIRE (FK-5-1-12) manual release caution plate - English
127120 & 180 litre 406Ø container bracket
128Brass nozzle - 360 degree
129Supply of MS Seamless Sch.40 Pipes of 32mm dia., Forged socket fittings & all Accessories
130SITC of Fire Detection System
131Supply of 2 zone Conventional Gas release Panel
132Supply ofManual Abort Switch
133Supply of Manual Release Switch
134Supply of Conventional Smoke detector with base
135Supply of Response Indicator
136Supply of Conventional Hooter
137Supply of Conventional Hooter cum strobe
138Supply of 2 core 1.5Sq mm FRLS armouredcable
139Installation Testing & Commissioning NOVAC and Fire detection system Agency to submit FORM A for installation all the required liasoning work for fire system works is in the scope of agency.
140SITC of New Fira Alarm system and integration to Existing Fire Alarm System BOSCH make
141Supply, Installation, Testing & Commissioning ofphotoelectric type Smoke Detector, sensitivity range of 0.5% to 2.35% /ft with Detector base, complete with MS Powder coated Junction Box for mounting on Surface / on False Ceiling / Below False Floor.
142Supply, Installation, Testing & Commissioning of Ceiling mounted / wall Addressaable Sounders/ Hooter with Strobe flasher 110 Cd
143Supply installation of Detection Loop and Signal cable : 2 Core x 1.5 mm, Multistranded Copper, FRLS, Armoured cable, RED in Colour. The cable shall belaid on surface with GI saddle-spacers every 0.3 meters. Complete with GI Junction Box, lugs, cable compression glands, cable tags and Ferruling.
144Supply, Installation of ISI mark fire Extinguisher on floor with stand. CeaseFire NAF-50 with radium sticker on wall at each location ( 2 Kg ) ABC
145Integration of the system to existing fire alarm system of BOSCH make
146HVAC WORKS
147Design, Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications and as per SMACNA standard of following sheet thickness complete as required. Hot dipped Galvanised with 120GSM Zinc coatingThe price shall include necessary scaffolding required for working at required height.
148Thickness: 0.63 mmSheet
149Thickness: 0.8 mmSheet
150Supplying and fixing of 19mm thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class "O") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. Silver tap to be provided for final finishing of the duct insulation as per instructed and as directed by OIC-ES.
151SITC of Extruded aluminium powder coated diffuser/ Grillwith volume control damper with all necessary supports as per directed and as instructed by OIC-ES
152SITC of Extruded aluminium powder coated diffuser/ Grillwithout volume control damper with all necessary supports as per directed and as instructed by OIC-ES
153Supply, installation, testing and commissioning of GI volume control duct damper/Non Return damper 18 guage GI. frame & 20 guage GI blades complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications.
154SITC ofduct mounted finned tubular heaters with low watt density (24 kW in threestepcontrol)withairflowswitch,digitalhumidistat,safety,winterand monsoon selector switch, thermostat, control box (Heater panel), controllers, relays, contactors and all other safety accessories to be placed in the plenum box as per instructed and as directed by OIC-ES. Note:- Cost include with All the cable realted to the above unit.
155Dismatling of existing duct as per instructed and as directed by OIC-ES.
156Dismatling of SRC unit with all accessories i.e. copper pipe , cable , electrical panel, drain etc as per instructed and as directed by Oic-ES.
157Installation and commissioning of SRC Units as mentioned in sr. no 8 items with all respect as per instructed and as directed by OIC-ES. Note:- Item include of all the copper pipe, cable , electric panel, gas charging etc. incase any additional item require for commissioning of the unit to be consider no cost given for the same.
158Supply, Installation, Testing and commissioning of PVC (minimum 15kg/sqcm pressure rated) drain water piping complete with fittings(elbows, tees, reducers,sockets,u trap etc.) supports, jointinginsulated with XLPE class O tubular insulation and any other item required to make the system complete. Nominal diameters of pipein mms as indicated below:
15925 mm dia pipe, Insulation thickness - 6 mm
160SITC of Drain pump fir SRC units as per instracted and as directed by OIC-ES.
161Supply and Installtion of Dually insulated drain protection tray below the chilled water pipe as per instructed and as directed by OIC-ES.
162SITC of Portable type dehumidifier with capacity of 70 LPD as per instructed and as directed by OIC-ES.
163Dismatling and re-installtion of fire fighting piping as per design approved. Desogn in the scope of contractor. NoTe:- Incase any additional material require for complete the job is in the scope of contractor no additional cost given fore the same.
164MGPS
165Supply, Installation, Testing, Commissioing of Medical Gas Isolation valvesbare on line, NFPA 99 compliant, High tensile bronze/ brass 4 bolt bronze body double seal union ball type with TFE/ Viton seal 400 psig isolation valves with K type pipe stubs-Medical Grade Copper pipe for fixing in the Floor Local Zone Valve box,Area Valve Boxes, Bare for wards asper instructed and as directed by OIC-ES.
16615 mm
16722mm
168Supply, Installation, Testing, Commissioing ofas per NFPA 99 Level 6020 Medical Grade Gas distribution pipingmanufactured from phophorpus deoxidized non arsenical copper to BS EN 1412:1996 grade CW024A manufactured to metric outside diameters having mechanical properties in accordance with BS EN 13348:2008-R250 half hard for sizes up to 54 mm or BSEN 133348:2008-R290 fro larger sizes in ready made built up trenches as per applicable standard, open execution on internal / external walls, in vertical shafts, above false ceilings as also inside removable trunking, in walls by chasing cuttingcompelete with factory made fittings such as tee/ elbow/ crossover/ wall sleeves etc., complete with vertical & horizontal supports and termination at both ends, colour coded painting etc.
16912mm ID x 0.7 mm thick
17015 mm ID x 0.9 mm thick
17122mm ID x 0.9 mm thick
172Supply, Installation, Testing, Commissioing ofMedical Gas specificterminal Outlets (tender make only) , NFPA 99 compliant,geometric quick fix type for breathing air/surgical air/medicall vacuum/medical oxygen complying & matching with correct medical gas probe according to the gas service outlets to be fitted in bed head panels. As per tender specifications
173Medical Oxygen
174Medical Vaccum
175Supply, Installation, Testing, Commissioing ofVacuum Unit complying with ISO100793 :2000 for ward areas consisting of 0-760 mbar vaccum regulator, vaccum filter & 1000 ml vacuum collection jar made from polycarbonate/ polysulphone material
176Supply, Installation, Testing, Commissioing of Oxygen flow meters with humidifier bottle complying with ISO 15002:2008 range of 0-15 LPM, 3-5 psig humidifier setting
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy