| 1 | ?Providing and erection on existing foundation 20 meter high mast lighting system suitable to install upto 10 No. 2 x 250/ 400 w M.H/S.V/LED flood light and control gear with integral Power tool, weight 450 kg. comprising of 2 sections of hot dipped galvanized materials as per BSEN ISO 1461 thickness 3 mm & 4 mm, dia 150mm & 410mm for top and bottom respectively, stress fitting arrangement on site with 500mm overlap dynamic loading to withstand max wind pressure as per -IS 875 part III, parameters for structural & foundation design must be taken from wind tunnel test. Lightning protection of GI single spike 1200mm at top and at base inside compartment having double thickness 3 mm & 4 mm, dia 150mm & 410mm for top and bottom respectively, stress fitting arrangement on site with 500mm overlap dynamic loading to withstand max wind pressure as per -IS 875 part III, parameters for structural & foundation design must be taken from wind tunnel test. Lightning protection of GI single spike 1200mm at top and at base inside compartment having double internal lock with adequate size of MCB erected on PVC board complete with base plate of 25mm thick 570mm dia. 490 PCD, including accessories viz. (1) Lantern carriage of 50 NB ERW class-B, MS pipe covered with PVC sleeve suitable to carry 500kg. load and upto 10 fittings symmetrically. (2) Trailing copper cable 5x4.0 sq.mm, PVC insulated PVC sheathed (3) Double drum 750Kg Winch having gear 53:1, oil bath (SAE90/140) arrangement. (4) 2 nos. stainless steel wire ropes 6 mm dia (7/19) breaking load capacity 2350 kg. x 2, (5) Integral power tool 3-phase, 1HP 2m/min single speed .torque limiter upto 500 kg adjustable (6) 2 Nos. LED 300 nos. aviation light (7) Feeder pillar fabricated out of 14 SWG CRCA sheet and comprise of incoming MCB 63 A TPN switch, HRC fuses, single dial timer, suitable size of contactors for lighting and power tool, 2 nos. outgoing, reversing switch for motor. (8) Foundation drawing, test certificate and guarantee certificate shall be provided by manufacturer. (without fixture and lamp) |
| 2 | Providing and erection on existing foundation12.5 meter high mast lighting system suitable to install 6 No. 2 x 400 w M.H/S.V/LED flood light fitting and control gear with integral Power tool, weight 340 kg. comprising of 2 section of hot dipped galvanized materials as per BSEN ISO 1461 thickness 3 mm, dia 100mm & 360mm for top and bottom respectively, stress fitting arrangement on site with 350mm overlap dynamic loading to withstand max wind pressure asper -IS 875 part III, parameters for structural & foundation design must be taken from wind tunnel test. Lightning protection of GI single spike 800mm at top and at base inside compartment with double internal lock with adequate size of MCB erected on PVC board complete with base plate of 25mm thick 520mm dia. and foundation bolts having 4 nos. bolts of 24mm dia, 750mm long (EN8 grade), Anchor plate 445 PCD, including accessories viz.?(1) Lantern carriage of 50 NB ERW class-B, MS pipe covered with PVC sleeve suitable to carry 250kg. load and upto 6 fittings symmetrically. (2) Trailing copper cable 5x2.5 sq.mm,EPR insulated PCP sheathed. (3) Double drum/350kg winch having gear 53:1, oil bath (SAE90/140) arrangement. (4) 2 nos. stainless steel wire ropes 5mm dia (7/19) breaking load capacity 1450 kg.x 2. (5) Integral single speed.powertool 3-phase,0.75HP2m/min (6) Feeder pillar fabricated out of 14 SWG CRCA sheet and comprise of incoming MCB 32 A TPN switch, HRC fuses, single dial timer, suitable size of contactors for lighting and power tool, 2 nos. outgoing, reversing switch for motor. (7) Foundation drawing, test certificate and guarantee certificate shall be provided by manufacturer. (without fixture and lamp) |
| 3 | ?Earthing with copper earth plate 600mm X 600mm X 3mm thick including accessories and providing masonry encloser in cement mortar, cover plate having locking arrangement on the top and G.I. watering pipe 20mm dia 2.7 metre long etc. (but without charcoal or coke and salt) complete as required. |
| 4 | ?Add extra for using salt and charcoal/coke for G.I. plate or copper plate earth electrode as required including excavation and refilling the pit in all type of soil, murrum |
| 5 | Supply and laying 25mm X 5mm G.I. strip at 0.5 metre below ground level as strip earth electrode including jointing etc. as required. |
| 6 | Supply of XLPE insulated power cable(conforming IS-7098 Part-I) 1100 Volt grade, 1 core/2 core/3½ core/4 core ISI marked with alu. stranded /solid conductor \"3½ core armoured X 70 sq. mm\" |
| 7 | Supply of XLPE insulated power cable(conforming IS-7098 Part-I) 1100 Volt grade, 1 core/2 core/3½ core/4 core ISI marked with alu. stranded /solid conductor \"3½ core armoured X 35 sq. mm\" |
| 8 | Supplying and installing double wall corrugated pipes (DWC) of HDPE (IS 14930 Part II -marked) for cable laidunderground with necessary material and at required depth upto 90cm. below road/ground surface, includingexcavation, back filling with excavated material, ramming and making the surface good. \"63.00mm outside dia.\" |
| 9 | Laying of one number additional armoured / unarmoured power cable 1.1KV grade of size exceeding 25 sq. mm but not exceeding 120 sq. mm direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the pit etc. as required. |
| 10 | Supplying and fixing heavy duty cable gland for P.V.C. insulated armoured cable with brass washer, rubber ring complete erected with cable and lead connection etc. as per specification complete. \"Gland size 32 mm for 2/3, 3½, 4 x 25 sq. mm OR 2/3, 3½ x 35 sq. mm or 2/3/3½ x 50 sq. mm.\" |
| 11 | Supplying and fixing heavy duty cable gland for P.V.C. insulated armoured cable with brass washer, rubber ring complete erected with cable and lead connection etc. as per specification complete. \"Gland size 38 mm 3½ x 70 sq. mm, 3x95 sq. mm\" |
| 12 | ?Supplying and fixing crimping type alum. lugs as per I.S.S. specification suitable for following size of cable with alu./copper solid/stranded conductor evenly crimped with high/pressure tool and connected to switch gear/bus/M.C.C.B./M.C.B. etc. as required complete. \"35 sq. mm\" |
| 13 | ?Supplying and fixing crimping type alum. lugs as per I.S.S. specification suitable for following size of cable with alu./copper solid/stranded conductor evenly crimped with high/pressure tool and connected to switch gear/bus/M.C.C.B./M.C.B. etc. as required complete. \"70 sq. mm\" |
| 14 | Designing & casting of open raft shallow footing foundation with M-20 cement concrete suitable for 20meter high mast considering the safe soil bearing capacity at site as 10 T/sqm at 2meter depth including excavation, foundation nut bolts in an approved manner as per manufacturer drawing or engineer-incharge. |
| 15 | Designing & casting of open raft shallow footing foundation with M-20 cement concrete suitable for 12.5meter High Mast considering the safe soil bearing capacity at site as 10 T/sqm at 2meter depth including excavation, foundation nut bolts in an approved manner as per manufacturer drawing or Engineer-incharge. |
| 16 | NOTE: 1) Bidder shall quote BASIC UNIT RATE including 1% CESS in column no. 5 |