Directorate Of Lighthouses And Lightships-DGLL has published Tender For Provision Of Electrical Wiring Of Transit/Touring Staff Quarter At Tajpur Lighthouse, West-Bengal.. Submission Date for this Tender is 13-05-2024. Electrification Work Tenders in tajpur West Bengal. Bidders can get complete Tender details and download the document.
FileName | File Description | File Size |
581d571e-259f-4d34-9012-62fede87e7a3.html | Tender Notice | 0 KB |
Bid.pdf | Tender Document | 0 KB |
BOQ_845714.xls | Tender Document | 0 KB |
Tendernotice_1.pdf | Tender Document | 0 KB |
Sl. No. | Item Description |
1 | Supplying and fixing following size modules GI box/ PVC surface box along with modular base & cover plate for modular switches in recess/surface etc. as required. |
2 | 3 Module (100mm * 75mm) |
3 | 4 Module (125mm * 75mm) |
4 | 6Module (200mm * 75mm) |
5 | 8Module (200mm * 75mm) |
6 | 12Module (200mm * 150mm) |
7 | Supply and fixing metal box of following sizes on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required. |
8 | 100mm X 100mm X60mm deep |
9 | 200mm X 150mm X60mm deep |
10 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
11 | 10 Amp switch |
12 | 16/20 Amp switch |
13 | 3 pin 10 Amp socket outlet |
14 | 6 pin 16/20 Amp socket outlet |
15 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ PVC box including connections etc. as required. |
16 | Supplying & fixing pvc batten/ angle holder including connection etc as required. |
17 | Installation , testing, commissioning of wall bracket/ celling fittings of all sizes and shapes containing up to two GLS/CFL/LED bulkhead, surfacelamps, etc per fitting, complete with all accessories including connection etc as required. |
18 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
19 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
20 | Installation, testing and commissioning of pre-wired, fluorescent fitting / LED/compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
21 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
22 | Supplying and fixing of 25mm sizes of medium class PVC conduit /Casing capping along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required |
23 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
24 | 3 x 1.5 sq. mm (10 coil of 90 mtrs) |
25 | 3 x 2.5 sq. mm (5 coil of 90 mtrs) |
26 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted\ including earthing etc. as required. (But without MCB/RCCB/Isolator) |
27 | 8- way, Double door |
28 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
29 | Single pole 10A/16A/20A |
30 | Double pole 32A/40A |
31 | Laying of one number 4 sq mm PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering and end to end connection. |
32 | Earthing with G.I earth pipe 4.5 metre long, 40mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipeetc. with charcoal/ coke and salt as required. |
33 | Supply and laying 6 SWGdia GI wire at 0.50 meter below ground level for conductor earth electrode including connection / termination with GI thimble etc as required. |
34 | LED tube light batten, 20 watt, 4-feet. |
35 | LED lamp 12 watt. (B-22 holder). |
36 | 15 Watt LED bulkhead fitting for outdoor purpose |
37 | Ceiling Fan with Sweep 1200mm and Hight performance even at low voltage, |
38 | Supplyof 4.0 sq mm, 3-core, PVC copper armoured U.G cable with connection. |
39 | Insulation Tape 5 mtr roll. |
40 | Indicator 1-Modular. |
41 | PVC round junction box.1,2,3,4-way. 1-inch. (Each - 10 nos) |
42 | Fan rod of 3-feet with clamp. |
43 | GI fan box for concealed |
44 | PVC round pipe, 1-inch for concealed |
45 | Backlite sheet, 4mm, size- 6 inch X 8 inch |
46 | Labour charges for laying of pvc pipes with fan box at the time of roof slab casting. (slab area- approx. 65 sq mtr.) |