Tender For Internal And External Electrical Work Of New Iucaa-2 Building At Iucaa, Pune, pune-Maharashtra

Inter-University Centre For Astronomy And Astrophysics-ICFAA has published Tender For Internal And External Electrical Work Of New Iucaa-2 Building At Iucaa, Pune. Submission Date for this Tender is 15-05-2024. Electrical Maintenance Tenders in pune Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

43220178
Tender For Internal And External Electrical Work Of New Iucaa-2 Building At Iucaa, Pune
Open Tender
Indian
Maharashtra
pune
15-05-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Internal And External Electrical Work Of New Iucaa-2 Building At Iucaa, Pune

Key Value

Document Fees
Refer document
EMD
INR 1860000.0 /-
Tender Value
Refer document

Attachment

FileName File Description File Size
20e4846c-9d2e-4e8e-900b-93ac9dc2667e.html Tender Notice 0 KB
Annexure1_ComplianceSheet_1.pdf Tender Document 0 KB
Annexure2_ComplianceSheet_2.pdf Tender Document 0 KB
Annexure3_ComplianceSheet_3.pdf Tender Document 0 KB
Annexure4_Approved_Make_L_4.pdf Tender Document 0 KB
BOQ_845670.xls Tender Document 0 KB
BoQ_Note.pdf Tender Document 0 KB
Electrical_Tender_Drawings.rar Tender Document 0 KB
Enclosures_Technical_Spec_5.pdf Tender Document 0 KB
TechnicalBid_IUCAA_2_Elec_6.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

Name of Work: Internal And External Electrical Work of New IUCAA 2 Building At IUCAA, Pune
Sl. No. Item Description
1Point wiring for light/bell concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq. mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WGPW/CW
2Secondary point wiring for additional light/ bell point, concealed type in min 20 mm FRLS grade PVC conduit with 1.5 sq. mm. (2+1E) FRLSH grade copper wires with required accessories as per specification No: WG-PW/CW
3Wiring for plug on board with Switch socket surface/ concealed type, copper wiring and earthing and with modular accessories as per specification No : WG PW/CW
4TWO WAY Point wiring for light/bell concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq. mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WGPW/CW.
5Supplying and erecting HMS PVC conduit FRLS grade 20 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC
6Supplying and laying HMS PVC conduit FRLS grade 20 mm dia. with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
7Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC.
8Supplying and laying HMS PVC conduit FRLS grade 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
9Supplying and erecting HMS PVC conduit FRLS grade 32 mm dia. With necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC.
10Supplying and laying HMS PVC conduit FRLS grade 32 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
11Supplying and erecting mains with 3x2.5 sq.mm (P+N+E) FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW.
12Supplying and erecting mains with 3x4 sq.mm (P+N+E)FRLSH copper PVC insulated wire laid in provided conduit/ trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW(FOR PDB TO PP).
13Supplying and erecting modular type switch 16 / 20 A with indicator, duly erected on provided plate and box with wiring connections complete.
14Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
15Supplying and erecting modular type blanking plate one module, duly erected on provided plate & box.
16Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
17Supplying and erecting modular pop up Box 8 module erected with provided AV/ HDMI , RJ 45, 6 Amp electrical sockets and switch on provided table.
18Supplying, Erecting, Testing and Commissioning of 10 kW, 3x3.3 KW AC Electric Vehicle Charger suitable for 2 and 4 wheeler having minimum IK08/IP 54 Protection suitable for three phase, 415V AC, 50Hz incoming and 3 Nos. output as per IEC 62196 (Type 2) - 5 Wire cable with universal connector having capacity of output current of 16A,240V AC at Each output with 3.5" TFT touch screen for human interface & LED Light for status indication and metering for measurement of consumed energy having metering accuracy +/-1% including required billing software & hardware to Each output port, Communication : EVSE to Server - OCPP 1.6 and Cloud Connectivity - Wi-Fi, GSM, Ethernet, one hour battery backup for communication, emergency push stop button and having short circuit, over & under voltage, over current, over temperature, earth leakage protection, Earth disconnection and enclosure made of minimum 1.5 mm duly RAL7035 Coated M.S, Erected on iron/GI frame on provided cement concrete foundation complete with two year on site warranty, confirming to IS 17017 Series as per specification.
19Supplying and erecting LED square / circular Max. 18 W down lighter/ Panel Light having pressure die-cast aluminium housing, polystyrene diffuser having system lumens output of Min. 2000 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%,PF>0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty
20Supplying and erecting anodized aluminium corridor / passage light LED fitting (4 feet) Max. 22W with high transitivity diffuser with system lumens output of Minimum 2200 lumens , min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angle of 110 deg., Ripple <5%, THD<10%, PF> 0.95, operating range of 200-270V, surge protection of 2 kV, Life class of 50,000 Hrs. at L70B50, including driver, with end caps on provided PVC Block / wooden board with 3 years warranty.
21Supplying and erecting LED Panel Light (600mm X 600mm) Max. 30 Watt having CRCA powder coated housing, polystyrene diffuser having system lumens output of Min. 3600 Lumens, min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD 0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50 including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty.
22Supplying and erecting LED Strip light 5m Length Max. 45 W IP20 class having minimum lumens output of 800 Lumens/m, min. efficacy of 90 lumen/W, CRI>80, CCT upto 5000K, Beam Angle of 110 deg., THD0.95, operating range of 230-270V, Life class of 30,000 Hrs. at L70B50, including driver with two year warranty.
23Supplying and erecting Concealed type foot/step light Max. 5W having IP67. IK10 rated Pressure die cast housing having system lumens output of Min. 500 Lumens, min. efficacy of 100 lumen/W, CRI>80, CCT upto 5000K, Beam Angle of 110 deg., THD<10%, SDCM<5, p.f. >0.95, operating range of 230-270V, surge protection of 2.5 kV, Life class of 25,000 Hrs. at L70B50, including driver by making necessary arrangement/recess in wall to make it flush with surface with 2 Year warranty.
24Making suitable size recess in any type of false ceiling for erection of flush type down lighter and finishing the background to match the original surface upto 20W.
25Making suitable size of recess in any type of false ceiling for erection of flush type LED panel light 600mm x 600mm/1200 x 300 mm and finishing the background to match the original ceiling surface.
26Supplying and erecting anodized aluminium corridor / passage / mirror light LED fitting (2 feet) Max. 12W with high transitivity diffuser with min. system lumens output of 1200 lumens, min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angle of 110 deg., Ripple <5%, THD <10%, p.f. > 0.95, operating range of 200-270V, Surge protection of 2 kV, Life class of 50,000 Hrs. at L70B50, including driver with end caps on provided PVC Block / wooden board with 3 years warranty.
27Supplying and erecting bulk head LED fitting max. 10W with high transitivity diffuser with system lumens output of min. 1100 lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., THD <10%, p.f. > 0.95, operating range of 140-260V, in built Surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, IP66, IK09 rated on provided PVC Block / wooden board with 3 years warranty.
28Supplying and erecting double suspension heavy duty lacquered iron chain with hooks for erecting fluo. tube light fitting(for erecting various fixtures like FTL, LED, etc) with necessary shielded copper flexible wire three core of 1 sq. mm for connecting leads. (for measurements half of the actual length used)
29Supplying & erecting integral post top lantern fixtures (light house type) suitable upto LED 18 W Lamp consisting of combination of spun aluminium canopy & clear acrylic top cover, cast aluminium pole cap on provided pole/ bracket as per specification no. FG-ODF/PTL
30Supplying and erecting integrated LED Bollard Cylindrical/Cubical shaped 800mm 8W IP65 & IK10 class having extrusion aluminium housing with polycarbonate diffuser, having system lumens output of Min. 800 Lumens, min. efficacy of 100 lumen/W, CRI> 80, CCT upto 6500K, THD <10%, p.f. > 0.90, operating range of 140-240V, inbuilt surge protection of 2 kV, Life class of 25,000 Hrs. at L50B50, including driver complete with 2 Year warranty.
31Supplying and erecting integrated LED street light fitting 18 to 22W IP65 & IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 1800 Lumens, min. efficacy of 100 lumen/W, CRI >70, CCT upto 6500K, THD <10%, p.f. > 0.95, operating range of 140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50, including driver complete with 3 Years warranty
32Providing & erecting 4 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 130 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL
33Providing and erecting galvanised 1000 mm single arm sword type bracket with FRP dome and ball as per specification no. OH-PL/PBKT
34Making M- 20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity as 10 T/sq. m at 1.5 m depth including supply of steel, concrete, excavation, fixing provided nut bolts with the help of template, duly plastered as per design complete (for 3 to 5m octagonal / conical GI pole).
35Making cement concrete foundation in 1:3:6 cement concrete, (20 to 25) mm. stone metal duly plastered with necessary curing for complete. (pole muffing or any other purpose).
36Supplying & erecting three phase, 415V, street light control panel up to the max load of 6 kW, TPN MCB 40A, powder coated CRCA 14 SWG sheet, outdoor type, having IP54,IK10 protection, suitable rating contactor, 24 hrs. astronomical time switch with minimum 5 years battery back up, auto/manual selector switch, ON/OFF push buttons, indicator lamps, control wiring, metering device, etc. for automatic operation, with overcurrent, short circuit, earth fault protection on provided iron frame / CC foundation.
37Supplying & erecting G.I. pipe‘A’ class 40 mmdia.Erected forenclosing XLPE armoured cableonwall/pole asper specification no. CB-CE
38Making trench in soft soil / hard murum / BT road and laying of provided cables inside the trench, etc as per IS: 1255 having 0.9 m depth and minimum 0.3 m width for laying provided cables up to voltage level of 1.1kV complete As per specification. Excavating in all types of soil strata and making trench for laying cable/cables, providing sand bed for laying the cable, covering cable with specified material as per requirement and finishing the same by making the surface proper with crown on top of the trench.
39Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP.
40Supplying & erecting cast iron cable indicator plate buried along with route of cable for PVC / XLPE armoured cableas per specification no. CB-CIP
41Supplying, erecting, testing and commissioning 11 KV HT metering cubical (compact / vertical type) approved by MSEDCL fabricated with 2 mm (14 SWG) M.S. sheets with supporting angle, painted with powder coating / epoxy paint of required shade, copper bus bar size 25 x 6 mm, heavy duty mechanical lock, with counter meter for measuring no of times the opening of meter door, top side cover (CT, PT cover) interlock with meter door, epoxy casted 3 nos. CT having required ratio between 10/5A to 50/5A, VA10 or 15, Class 0.5S, epoxy casted 3 nos. PT having ratio 11000/V3/110/V3 VA 50, Class 0.5s suitable for provided trivector meter and provision for incoming and outgoing cables complete duly tested by licensee with necessary test certificates and erected on provided plinth/ cc foundation. Bidder shall arrange factory inspection of HT kiosk in coordination with MSEDCL Testing Engineer and Customer Engineer before dispatch.
42Supplying and erecting MSEDCL approved & tested HT CT multifunction DLMS compliance of accuracy of class 0.5 , 3x63.5V, 50 Hz with optical & RS 232 port, backlit LED/LCD, measures kWh, kVAh, V, I, kW, 6 months history of energy , load survey, & displays trivector energy, load survey, TOD, tamper detection & logging, power ON /OFF events, instantaneous parameters of rating 1/5 A with display in absence of power complete with zero adjustment & test certificate from manufacturer erected on provided M.S. box.
43Supplying, erecting, testing & commissioning 11kV, 630A, 21kA/3sec, 1 way outdoor, extensible motorised SCADA compatible RMU, internal arc tested consisting of 1 No. feeder with 1 LBS compliant to IEC 62271 -100, 200 and 102, as per specification no. SW-HTS/RMU SCADA
44Supplying, erecting, testing & commissioning 11kV, 630A, 21kA/3sec, 1 way outdoor, extensible motorised SCADA compatible RMU, internal arc tested consisting of 1 No. feeder with 1 VCB compliant to IEC 62271 -100, 200 and 102, as per givenspecifications and all necessary protection relays, sensors, measurement instruments/meters, Space heater with Thermostat, indication lamps etc. The panel shall be complete with all accessories & cable termination boxes for incoming and outgoing 11 kV XLPE Cables. The VCB should have all necessary transformer protections such as OTI, WTI alarm & trip, PRV & OSR trip, 8 Window Annunciation & Hooter with all necessary accessories & anti pumping relay. Potential free contact to be provided for HT trouble in breaker to be used for annunciation.
45Supplying, installing, testing & commissioning compact substation with 3 phase, 11/0.415, 50 Hz., 1000 kVA transformer, Tap position range +5% to -10% in step of 1.25%.Mineral oil immersed Copper wound, without gas cushioning , hermetically Sealed transformer having indoor type transformer bushings, with HT side (incoming side)load break switch of 630A capacity and LT side (outgoing side) ACB 1600A (4 pole) capacity, with inbuilt metering cubical, using type A winding insulation (kraft paper), standard accessories complete with test certificate with losses below 2790 Watts at 50% load, 7700 Watts at 100% load for transformer, as per IS:1180 (part 1) : 2014,with necessary permissions of Electrical Inspector & MSEDCL Engineers as per specification no SS- TRSL. Note : Statutory approvals from authorities like PWD, MSEDCL, CPCB, Electrical Inspector etc. for installation & commissioning process complete as required. The Bidder shall prepare and submit the necessary documents and drawings to the Authority for approval and clearance and submit the Commissioning Report to the IUCAA. Please note that any statutory payment to Government Departments will be paid separately by IUCAA on submission of receipt by the bidder.
46Supplying , erecting & terminating XLPE insulated, galvanised steel formed wire armoured (ROUND) MSEDCL approved cable 11 kV(E), 3 x 300 sq. mm. aluminium conductor laid in provided trench / pipe.(Cable length/route may vary as per MSEDCL engineer"s approval. Contractor to confirm before ordering cable.)
47ProvidinganderectingHeatshrinkable In/Outdoor (touchproof Indoor) termination kit (as per MSEDCL approved) for 11 kV ( E ) XLPE HT cable 3x 300 sq.mm. with necessarymaterial as perspecification
48Supplying & laying half round reinforced cement concrete pipe of IS 458:2003 NP-2 class of 150 mm internal diameter in proper line, level and slope including excavation 1.2 Meter depth below ground level andproviding and fixing collars in cement mortar 1:2 and curing etc. for cable laying complete as required.(Note : Contractor to confirmthe cable route as per MSEDCL"s engineer approval & or any other local body"s permissions & included in the item rates. Any charges of the local government body/organization for road or any excavation and restoration of road etc. shall be paid by the bidder and no payment shall be made separately to the bidder by IUCAA)
49Providing and making second class Burnt Brick masonry with conventional /I.S. type bricks in cement mortar 1:6 in foundation sand plinth of inner walls /in plinth external walls including bailing out water manually, striking joints on unexposed faces, raking out joints on exposed faces and watering etc. Complete. For LBS,MK,VCB ETC
50Supplying & laying reinforced cement concrete pipe of IS 458:2003 NP-2 class of 150 mm internal diameter including excavation 1.2 M depth below ground level in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete.
51Supplying and erecting GI sheet 1.6mm (16 SWG) caution board of size 250 x 200 mm duly painted with red oxide and enamel paint in Marathi, Hindi and English erected at position for HV/EHV (11000 Volts) installation with compliance to IS 2551-1982
52Supplying & erecting cast iron cable indicator plate buried along with route of cable for PVC / XLPE armoured cableas per specification no. CB-CIP
53Supplying and spreading stone metal 25 mm size for 100 mm depth above the ground level complete.
54Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 25 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
55Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 35 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
56Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 50 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
57Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 70 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
58Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 95 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
59Supplying, Erecting & Terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 120 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
60Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 150 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
61Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 185 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
62Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
63Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3 core 2.5 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
64Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3 core 4 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
65Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3 core 6 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
66Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
67Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
68Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
69Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
70Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 16 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU.
71Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM.(20KG=0.018 CU Meter)
72Supplying, installation & marking of surge arrestor / surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 100 kA for three phase and neutral with compliance to IEC 61643-11 as per specification no. CP-SPD
73Supplying, installation & marking of surge arrestor/ surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 50 kA for three phase and neutral with compliance to IEC 61643-11 as per specification no. CP-SPD
74Supplying, installation & marking of surge arrestor/ surge protection device at the sub main distribution board after the incoming breaker of type 2 tested for Imax 15 kA for three phase and neutral with compliance to IEC 61643-11 as per specification no. CP-SPD
75Supply, Installation, Testing & Commissioning of Hybrid APFCR Panels to maintain Unity Power Factor automatically irrespective of loadas per specifications - 1)Panel should be fabricated with CRCA sheets with 14/16 Gaugethickness, 2mm Load bearing and 1.6mm Non load bearing sections, 2.2mm Doors, 3mm Gland plate, Dust and vermin proof, Indoor Installation, IP4X, with minimum seven tank process powder coated with Siemens Gray 7035 shade, Floor mounted, Bottom Cable entry, 150 kVAr, 3 phase, 50 Hz. 415 V, IP42 Indoor Panel, Hybrid Power Factor compensation Panel. APFCR + Static Var Generator capacity (100 Kvar + 50 Kvar) 2) RTPFC Panel is with 525 V Capacitors, 7% detuned Reactor, Thyristor Switch, MCCBs,8 stage controller,Required switchgear, Protection,Indicating Lamps, selector Switches. 3) 50 KVAR SVG with HMI 4.3 inches monitor functioning for reactive power compensation, three phase unbalance compensation Input Voltage 415 V (-40% to + 20%), 50 Hz Panelmounted with grid structure 3P4W/3P3W,IGBT based inverter, three phase sensing, bidirectional correct both inductive (lag) and capacitive (lead) load, Suitable for HT sensing, monitoring using IoT with wi-Fi connectivity, RS485 / RJ45 network port , Response time <15ms, noise level <65db, stepless compensation, Abnormal frequency and voltage protection, Abnormal output current protection, Inverter short-circuit protection, Over temperature protection, Inverter over loaded protection etc. with four pole suitable rating MCCB as main incomer and four pole suitable rating MCCBs for Each branch protection.Factory tests before despatch & site tests for the unity PF have to be arranged by the bidder.
76Supplying, installation and testing of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete, and recording the results Specification no. EA-MOBI
77Supplying and erecting copper strip of required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with insulating and non-corrosive bond with required joints As per specification no. EA-EP.
78Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with insulating and non-corrosive bond with required joints As per specification no. EA-EP.
79Supplying & erecting conventional spike type air termination suitable to carry lightning stroke made up of heavy gauge 40 mm dia copper pipe of standard length with 5 Nos. copper spikes fixed on copper ball as air terminals duly threaded in copper pipe erected on provided foundation complete.
80Providing and back filling ground enhancing compound 25 kg bag complete.
81Supplying and erecting fencing of section having size 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete as per specification no SS-AS/FSG
82Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminium paint complete.
83Supplyinganderectingdoubleleafhingeddooreach1500 mminwidthx1850mminheightusingBclass,GIpipe with angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation, and painted complete as per specification no SS-AS/DLD
84Providing printed instruction chart for treating persons suffering from electric shock, printed in English & Marathi and duly laminated complete.
85Providing pair of duly tested rubber hand gloves as per IS:47705 suitable for working up to 22 kV supply complete.
86Supplying standard first aid box with necessary antiseptic cream, medicine for use on wounds due burn, crepe bandage, gauge bandage, medicated ready to use bandage (Band-Aid) adhesive tape for medicinal use, scissors, anti-septic solution, etc. (All above contents shall be of standard makes)
87Supplying and fixing PVC synthetic elastomer electrically insulating mat with class A insulation conforming to IS: 15652 – 2006 having 2 mm thickness up to 3.3 kV
88Supplying and fixing PVC synthetic elastomer electrically insulating mat with class B insulation conforming to IS: 15652 – 2006 having 2.5 mm thickness up to 11 kV
89Supplying shock proof leather safety shoes of electrical grade of standard size as IS :11226, 14544 duly tested, with necessary test certificate from manufacturer.
90Supplying SMC chequered plates of size 4ft x 2ft, hot press moulded from advanced composites of plastics namely sheet moulding compound of thickness 2.5 mm with insulation level up to 22 kV and fixing it to substation floor with SR-998 adhesive along with 5 mm thick E.P. foam complete.
91Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete.
92Supplying, erecting, testing and commissioning of 750 KVA diesel generating set as per CPCB IV+ norms with alternator of 750 kVA output continuous prime rating, 3 Phase, 415 V, 50c/s 0.8 p. f. A.C supply, a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours, along with standard accessories, self-excited, self-regulated, screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 1 %, with performance class G3 electronic governor and maximum fuel consumption 130 Litre/hr @75% loading. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA sheet, hospital grade silencer, sound absorbing material to restrict sound level up to 75 dB at 1.0 m, provided with first filling of oil, diesel tank capacity not less than 990 Litre etc. on provided M20 Grade CC Foundation and obtaining necessary approval from Electrical Inspector as per specification no. GEN-DG. Also the DG set shall be compliant CPCB IV+ norms to the latest MoEFCC"s notifications. Statutory approval from authorities like PWD, MSEDCL, CPCB, Electrical Inspector etc. for installation & commissioning process complete as required. Vendor to prepare & submit required documents & drawings to authorities for sanction & approval & submit the commissioning report to the IUCAA. Please note that any statutory payment to the Government Departments shall be paid by the IUCAA separately on submission of the receipt by Bidder.
93Supplying, erecting, testing and commissioning of microprocessor based AMF panel suitable for diesel generating set of2 X 750 kVA capacity Three phase, 415 Volts, 50Hz A.C. with all standard features, safeties etc as per specification no. GEN-AMF and SLD.
94Supplying, erecting, testing and commissioning of Microprocessor based Generator Control Unit (Synchronization panel) panel suitable for Diesel Generating Set of above 2 X 750 kVA capacity Three phase, 415 Volts, 50Hz A.C. with all standard features and safeties etc as per specification no. GEN-SYNC and SLD. Bidder has to prepare/design the GA drawings with all required accessories, controller, protection devices, sensors, wiring etc. and submit to the IUCAA for necessary approvals.
95Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes, panel boards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete including for Fuel tank 999 litres capacity.
96Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority including for fuel tank support.
97Supplying and erecting ON LOAD four pole automatic transfer switch, 415V, 160A, 50 Hz with enclosure, flexibility of neutral connection, line and load reversibility, changeover with phase barriers, source separator, terminal covers along with staggered termination for cable connection and ATS controller with provision of time delay protection of OV, UV, phase sequence changing, single phasing and event logging, connected with provided leads complete complying to IS/IEC 60947-3 Part-1/6
98Supplying and fixing tool-less IO (Ethernet) flush/surface type in provided modular box as per specification no. WG-NAS/IO
99Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background
100Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 6 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background
101Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.
102Supplying and erecting modular type 3 pin 6A multi socket with safety shutter, duly erected on provided plate and box with wiring connections
103Supplying and erecting 25 mm dia. corrugated flexible polypropylene conduit
104Supplying and erecting aluminium raceway 100X38X2 mm on floor/wall/ceiling using C type clamps for fixing the raceways properly. Further raceways shall be earthed with each other / junction box with suitable size cu pvc coat wire & lugs to form a continues earth connection. The edges of raceways shall be smoothed at the cut section by file to avoid any damage to the wires while laying in raceway to the satisfaction of the client /consultant.
105Supplying and erecting aluminium raceway 80X38X2mm on floor/wall/ceiling using C type clamps for fixing the raceways properly. Further raceways shall be earthed with each other / junction box with suitable size cu pvc coat wire & lugs to form a continues earth connection . The edges of raceways shall be smoothed at the cut section by file to avoid any damage to the wires while laying in raceway to the satisfaction of the client/consultant.
106Supplying and erecting aluminium raceway 40X38X2mm on floor/wall/ceiling using c type clamps for fixing the raceways properly. further raceways shall be earthed with each other / junction box with suitable size cu pvc coated wire & lugs to form a continues earth connection. The edges of raceways shall be smoothed at the cut section by file to avoid any damage to the wires while laying in raceway to the satisfaction of the client/ consultant.
107Supplying and erecting aluminium raceway 40X25X2mm on floor/wall/ceiling using c type clamps for fixing the raceways properly. further raceways shall be earthed with each other / junction box with suitable size cu pvc coated wire & lugs to form a continues earth connection. The edges of raceways shall be smoothed at the cut section by file to avoid any damage to the wires while laying in raceway to the satisfaction of the client/ consultant.
108Supplying and fixing CAT-6A LSZH cable suitable for LAN / WAN as per specification complete.
109Supplying, installing, testing and commissioning air circuit breaker electrical draw out type, 650V, 1600A rated at 50º C without deration, 12kV Impulse, 4 pole (100% Neutral Protection) 50 kA, (Ics=Icu=Icw for 1s), with standard accessories with ready to close, individual fault trip, alarm and trip indication, mechanical and electrical anti pumping, soft/hard rating plug (including hard rating plug CT) with Micro-processer based LCD display release with LSIG and temperature rise protection & with 4 C/O contacts for On-Off-Trip indication, min. 5 event and trip history on breaker display on provided iron frame as per specification.
110Supplying, installing, testing and commissioning air circuit breaker ELECTRICAL draw out type, 650V, up to 800A rated at 50º C without deration, 12kV Impulse, 4 pole (100% Neutral Protection), 50 kA (Ics=Icu=Icw for 1s),with standard accessories and with ready to close, individual fault trip, alarm and trip indication, mechanical and electrical anti pumping, soft/hard rating plug (including hard rating plug CT) with Micro-processer based LCD display release with LSIG and temperature rise protection & with 4 C/O contacts for On-OffTrip indication, min. 5 event and trip history on breaker display on provided iron frame as per specification no. SW-SWR/ACB
111Supplying, erecting & marking SPMCB 0.5A to 5A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB For I.L. in panel
112Supplying, erecting & marking SPMCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
113Supplying, erecting & marking SPMCB 6A to 32A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
114Supplying, erecting &marking DPMCB 6A to 32A,C-series (formotor/power)inprovideddistributionboardasper specification no. SW-SWR/MCB
115Supplying, erecting & marking TPMCB 6A to 32A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
116Supplying, erecting & marking TPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
117Supplying, erecting and marking triple pole isolators only switch version of miniature circuit breaker of 100A with required wiring connections and lugs etc. in provided distribution board.
118Supplying, erecting & marking FPMCB 6A to 32A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
119Supplying, erecting & marking FPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
120Supplying, erecting and marking four pole isolators only switch version of miniature circuit breakers of 80/100A in provided distribution board.
121Supplying & erecting CRCA sheet metal enclosures of 1.2mm thickness with 30 A, 3 pin plug & earth socket and 30A, 3 pin plug top with 30A triple pole MCB having rated short - circuit breaking capacity (Icn) 10kA complete erected on angle iron / GI frame.
122Providing & erecting 4 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB.
123Providing & erecting 4 Pole MCCB 415V, 125 A to 200A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB.
124Providing & erecting 4 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB.
125Providing & erecting 4 Pole MCCB 415V, 315 A to 400A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW-SWR/MCCB.
126Providing & erecting 4 Pole MCCB 415V, 800A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB.
127Supplying, erecting & commissioning 4 pole RCCB 40A, electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification
128Supplying, erecting & commissioning 4 pole RCCB 16/25A, electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB
129Supplying, erecting & commissioning 4 pole RCCB 63A, electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB
130Supplying, erecting & commissioning 2 pole RCCB 16/25A, electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB
131Supplying and erecting SS enclosure for MCCB suitable for above 250 A up to 800A MCCB for ups
132Supplying and erecting GI sheet 1.6 mm (16 SWG) caution board of size 200 x 150 mm duly painted with red oxide and enamel paint in Marathi, Hindi and English erected at position for medium voltage (415 Volt) installation with compliance to IS 2551-1982
133Supplying and erecting of any size electrolyte aluminium patti or bar in bus bar chamber / in panel or any other purpose, 500 V with require current capacity 99.9% aluminium purity with E91E Grade as per IS 5082 & Current Density 0.8 A per sq. mm. with fixing arrangement (like lug or bottle type lug) to both the end with high grade polyolefin insulation sleeve complete as per specification no. BCB-BB, Nut, bolts holding the lugs to bus bar shall be of bimetallic/ brass/ cadmium plated steel.
134Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 4 ways/phase (12 poles), with door, 1.2mm thickness, surface/flush mounted, IP 43 protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB
135Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 8 ways / phase (24 poles), with door, 1.2mm thickness surface/ flush mounted, IP 43 Protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB
136Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 12 ways /phase (36 poles), with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB
137Supplying and erecting single pole and neutral distribution board (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB
138Supplying and erecting single pole and neutral distribution board (SPNDB), with 2 ways for incoming and 10 ways (10 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB
139Supplying & erecting triple pole and neutral distribution board (TPNDB), SP/TP MCBs total 4 ways /12 Poles, with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB
140Supplying & erecting triple pole and neutral distribution board (TPNDB), SP/TP MCBs total 8 ways /24 poles, with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB
141Supplying & erecting triple pole and neutral distribution board (TPNDB), SP/TP MCBs total 12 ways /36 poles, with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB
142Supplying & erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame.
143Supplying and erecting blanking plate of suitable size on MCBDB.
144Supplying & erecting LED type indicating pilot lamp with LED colours red / yellow / green, 230 / 250V on provided box / panel with necessary material, wiring & connections etc.
145Supplying & erecting LED type indicating pilot lamp with LED colour blue, 230 / 250 V on provided box / panel with necessary material, wiring & connections etc.
146Supplying and erecting panel mounting type digital ammeter having three and half digit LED display, external CT operated, calibrated for suitable to operate on 500V, 0 to 2000A having accuracy class of 0.5, AC supply with necessary PVC wire leads and lugs and mounting hardware on provided panel complete with calibration certificate from manufacturer.
147Supplying and erecting LT current transformer with bar primary 50/5 to 1600/5 or 2000/5 ratio with 15 VA burden erected in provided CRCA box duly secured with insulating materials connected to the meter with test certificates.
148Supplying and erecting panel mounting type digital ammeter having three and half digit LED display, external CT operated, calibrated for suitable to operate on 500V, 0 to 1000A having accuracy class of 0.5, AC supply with necessary PVC wire leads and lugs and mounting hardware on provided panel complete with calibration certificate from manufacturer.
149Supplying and erecting LT current transformer with bar primary 50/5 to 1000/5 ratio with 15 VA burden erected in provided CRCA box duly secured with insulating materials connected to the meter with test certificates.
150Supplying and erecting panel mounting type digital voltmeter having three and half digit LED display, calibrated for 0 to 750V AC suitable to operate on 500V having accuracy class of 0.5, AC supply with necessary PVC wire leads and lugs and mounting hardware on provided panel complete with calibration certificate from manufacturer.
151Supplying and erecting selector switch suitable for voltmeter/ammeter for 3 phase AC supply 500V, 50Hz, on provided box / panel and duly connecting with necessary PVC wire leads and lugs.
152Supplying and erecting dual source intelligent flush mounted panel meter three phase four wire (IPM) 415V CT/ PT site programmable class I flush mounted (96 x 96 mm) meter with voltage, current, frequency, power factor, ON hrs, kWh, EB and DG set metering with LED display (excluding CT"S) complete with RS 485 communication protocol, class I accuracy and wiring connections and mounting hardware on provided panels complete with calibration certificate from manufacturer.
153Supplying and erecting Intelligent flush mounted panel meter three phase four wire (IPM) input voltage measurement range 50-550 V AC (P-P) 415V, aux. supply 90-300 V AC/DC, flush mounted (96 x 96 mm) meter constant Wh viewing in LCD multifunction meters in auto scroll mode with voltage, current, frequency, power factor kW, kVA, kVAR, kWh, kVAh, kVARh, phase angle, interrupts, THD, complete with RS 485 communication protocol, class 1 accuracy and wiring connections and mounting hardware on provided panels complete with calibration certificate from manufacturer.
154Providing & erecting hot dipped galvanised perforated/ ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware.
155Providing & erecting hot dipped galvanised perforated/ ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware.
156Providing & erecting hot dipped galvanised cover suitable for perforated type Cable tray manufactured from 18 SWG (1.2 mm thick) GI sheet of 150 mm width & 20 mm height complete with necessary hardware.
157Providing & erecting hot dipped galvanised cover suitable for perforated type Cable tray manufactured from 18 SWG (1.2 mm thick) GI sheet of 300 mm width & 20 mm height complete with necessary hardware.
158Excavating hard murum / stone metal road by chiselling for preparing pit for poles stay or earth plates or for laying cables, pipes & clearing the site by removing debris & making the site as required complete. (For Cable Chamber)
159Providing and making second class Burnt Brick masonry with conventional /I.S. type bricks in cement mortar 1:6 in foundation sand plinth of inner walls /in plinth external walls including bailing out water manually, striking joints on unexposed faces, raking out joints on exposed faces and watering etc. Complete.
160Providing and fixing reinforced cement concrete cover of size 60 cm x 45 cm with frame over inspection chamber etc. complete of medium duty.
161Excavation for foundation in hard murum including removing the excavated material upto distance of 50 metres beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. Lift upto 5 meter By Manual Means
162Providing soling for D.G. foundation using 80 mm size trap metal in 15 cm. layer including filling voids with Crushed sand/grit, ramming, watering etc. complete. SIZE:8.1x3.6x0.3 Meter.
163Providing and laying for D.G. foundation in situ /Ready Mix cement concrete M-20 of trap / granite /quartzite/ gneiss metal for R.C.C. work in foundations like raft, strip foundations, grillage and footings of R.C.C. columns and steel stanchions etc. including bailing out water, Steel centering formwork, laying/pumping cover blocks, compaction and curing roughening the surface if special finish is to be provided (Excluding reinforcement and structural steel) etc. complete, with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade). Size: 8x3.5x.0.75 Meter (two nos. for two DGs.)
164Providing and fixing in position TMT - FE - 500 bar reinforcement of various diameters for R.C.C. pile caps, footings, foundations, slabs, beams columns, canopies, staircase, newels, chajjas, lintels pardis, copings, fins, arches etc. as per detailed designs, drawings and schedules. including cutting, bending, hooking the bars, binding with wires or tack welding and supporting as required complete.
165Supplying and erecting modular type telephone socket one gang with safety shutter, duly erected on provided plate and box with wiring connections complete.
166Supplying & erecting 2 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit as per specification No. WG-TW
167Supplying & erecting 50 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit as perspecification No. WG-TW
168Supplying & erecting 10 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit as perspecification No. WG-TW
169Supplying, erecting & commissioning 50 pairs FR junction box with moulded plastic enclosure as per specification no. WG-TW
170Supplying, erecting & commissioning 10 pairs FR junction box with moulded plastic enclosure as per specification no. WG-TW
171Supplying & erecting 100 pair, 0.5 mm dia. jelly filled armoured telephone copper cable with poly-al laminate moisture barrier, polythene sheathed, G.S.Tape armoured polythene jacketed having laid in provided trench as per specification No. WG-TW
172Supplying & laying (including excavation) reinforced cement concrete pipe of IS 458:2003 NP-2 class of 150 mm internal diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete.
173Supplying & laying (including excavation) reinforced cement concrete pipe of IS 458:2003 NP-2 class of 250 mm internal diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete.
174Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes, panel boards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete.J.B.150x150x65
175Supplying, erecting & commissioning MDF Box 600x600 pairs made from min. 1.5mm thick MS sheet as per specification no. WG-TW
176Supplying, erecting & commissioning 10 pair module for connection & disconnection of telephone cable as per specification no. WG-TW
177Supplying & erecting over voltage protection magazine suitable for 10 pair as per specification no. WG-TW
178Supplying and erecting 25 mm dia. corrugated flexible polypropylene conduit
179Supplying, erecting & commissioning RTCC + OLTC FOR ABOVE 1 MVA, 11/0.415KV, hermetically sealed, TRANSFORMER, having Tap position range +5% to -10% in step of 1.25%. OLTC shall be fitted tothe transformer at the time of assembly of transformer by manufacturer. OLTC should be having motor & manual operated rotating mechanism. The OLTC panel"s voltage sensing relay should choose appropriate tap to maintain desired output voltage of transformer. The AVR relay inside RTCC panel should receive signals from OLTC tap & based on algorithm, it should be able to calculate the tap position as per desired output voltage. The RTCC should have two modes - auto & manual. In Auto mode, the tap position shall change automatically. In manual mode the tap position can be changed by pressing upward & downward switch at the RTCC panel.
180Supplying, erecting & commissioning 2 pole RCCB 63A, electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB
181Supplying LED concealed type foot / step light with aluminium body for indoor/outdoor application suitable for 4W-6W LED including driver and erecting by making necessary arrangement / recess in wall to make it flush with surface with 2 year warranty.
182Supplying, installing, testing and commissioning air circuit breakers, electrical draw out type, 650V, 2000A rated at 50º C without deration, 12kV Impulse, 4 pole (100% Neutral Protection) 50 kA, (Ics=Icu=Icw for 1s), with standard accessories with ready to close, individual fault trip, alarm and trip indication, mechanical and electrical anti pumping, soft/hard rating plug (including hard rating plug CT) with Micro-processer basedOLCD display release with LSIG and temperature rise protection & with 6no+6nc aux. contacts, On-Off-Trip indication, min. 5 event and trip history on breaker display, fault retention in case of power failure, communication port RS485,protocol of MODBUS/PROFIBUS &suitable provision for electrical & mechanical interlocking arrangement to use these two ACBs into auto/manual change over switch in provided enclosure & two nos. in DG panel as per details in SLD.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy