| 1 | Supply,Fixing and Testing warm LED highbay light fitting of 150 Watt, Luminaire fittingof IP 66 protection comprises of Pressure die cast Aluminium housing powder coated, toughened glass,LED\"s provided with secondary lens optics,luminaire efficacy not less than 140 lm/w provided with SPD 10 KV included complete all as specified and directed.Make - Crompton /Philips/Wipro/Surya |
| 2 | Material and labour for sub main wiring with two single core PVC insulated (unsheathed) multi strand copper conductor FRLS cable of size 6 sqmm and one single core PVC insulated (unsheathed) multi strand copper conductor FRLS cable of size 4 sqmm as in continuous earth wiredrawn in existing conduit complete all as specified and as directed. |
| 3 | M & L for black stove enamelled rigid ERW steel conduit 25 mm dia fixing with suitable size MS clamp / saddles as per site requirement complete all as specified and directed by Engr In Charge.Make:- BEC/EMCO/ GARWARE /JINDAL/ WAVIN/FINOLEX. Note - (1) Quoted rate for conduit is deemed to be included for the taking down existing unserviceable conduit as per site requirement complete (2) New wiring portions for replacement of unserviceable wiring as required as per site requirement shall be measured and paid separately under relevant schedule item. |
| 4 | Supply, Fixingand TestingVTPN DB 12 way double door complete all as specified and directed. |
| 5 | Supply, Fixingand TestingMCCB 25 KA 200 Amp 4 Pole adjustable with thermal magnetic type complete all as specified and directed. |
| 6 | Taking down old / unserviceable light fittings of any type / wattage from existing positions inHangars at height upto 30 meter including necessary Boom lift / crane etc as per site requirement carefully, checking of fitting, dismantling unserviceable / burnt parts and replacement of parts as perrequirement and refixing in the location in hangar as directed complete all as specified and directed by Engr-in-charge.Note - (1) Quoted rate is deemed to be included the charges of Boom lift / Crane as required, T & P, labouretc complete as per site requirement. |
| 7 | Supply, install, testing and commissioning of motor of capacity 5 HP, 930 RPM with long shaft complete all as specified and directed by Engg-in-Charge.Note: 1. Necessary frame work for supporting and protectiong cover for motor from rain etc deemed to be included in the quoted rate2. Old unserviceable motor to be deposited to MES store |
| 8 | Supply & install Aluminum Motor Hub with blade for 5 HP motor of 160 TR Cooling Tower complete all as specified and directed by Engg-in-Charge. |
| 9 | Supply & install Sprinkler for 160 TR Cooling Tower complete all as specified and directed by Engg-in-Charge. |
| 10 | Supply and install PVC Branch Pipes & Drift Eliminators complete all as specified and directed by Engg-in-Charge. |
| 11 | Material and labour including fabrication MS Hand rails, supporting structure, etc fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint including embeding in concrete and screwing etc all as specified and as directed. |
| 12 | Taking down copper/aluminium point wiring (light,fan, socket or power) complete, including fixtures, PVC conduits and fittings such as switches, ceiling roses, pendents, regulators, sockets, light fittings etc. removing materials from wall/ceiling etc to store for keeping in safe custody or for taking credit and making good disturbed surfaces of wall, floors, etc. all as specified and as directed. |
| 13 | Material and labour for Point wiring with 1.5 sqmm (Nominal area) unsheathed FRLS multi-stranded copper conductor PVC insulated cable 1100 volts grade single core drawn into existingconcealedconduitthrough Wall/Ceiling/Flore along with FRLS 1.5 sqmm unsheathed multi stranded copper conductor cable PVC insulated 1100 volts grade as earth continuity conductor connected to common earth dolly and including 2 mm thick terminal boxes MS sheet flush mounted with 3 mm thick laminated hylem sheet fixed with camium plated iron screwsfor mountling switches, socket, fan regulators etc complete for for the following point wiring and making good disturbed surfaces matching with existing paint complete all as specified and as directed.Make of PVC copper conductor cable:- Finlex/Poly cab/ Havells. |
| 14 | One light/fan point controlled by one switch with cable 1.5 Sqmm size.. |
| 15 | All as per Ser Item No-13 above here in before but one 3 pin socket outlet 5 Amps, independentboardwith cables 2.5 Sqmm size. |
| 16 | All as per Ser Item No-13 above here in before but one 5 pin socket outlet 5/15 Amps, indipendentboardwith cables 4.0 Sqmm size. |
| 17 | Material and labour for Point wiring with 1.5 sqmm (Nominal area) unsheathed FRLS multi-stranded copper conductor PVC insulated cable 1100 volts grade single core drawn into and including non metallic rigid PVC conduitof minimum 20 mm dia concealed wiringthrough Walls andconcealed / surface wiring through Ceiling along with FRLS 1.5 sqmm unsheathed multi stranded copper conductor cable PVC insulated 1100 volts grade as earth continuity conductor connected to common earth dolly and including 2 mm thick terminal boxes MS sheet flush mounted with 3 mm thick laminated hylem sheet fixed with camium plated iron screwsfor mountling switches, socket, fan regulators etc complete for for the following point wiring and making good disturbed surfaces matching with existing paint complete all as specified and as directed.Note : Cutting work for concealed wiring is deemed to be included in the quoted rateMake of PVC copper conductor cable:- Finlex/Poly cab/ Asian.Make of PVC conduit /casing/capping : Avon plast/ Kon seal / Garware. |
| 18 | One Light/Fan point controlled by one switch. |
| 19 | One Bell/Buzzer point controlled by one push button with other switches on indipendent board with cable 1.5 Sqmm size. |
| 20 | One 3 pin socket outlet 5 Amps, sameboardwith cables 1.5 Sqmm size. |
| 21 | One 3 pin socket outlet 5 Amps, independentboardwith cables 2.5 Sqmm size. |
| 22 | All as per item No.2 above here in before but one 5 pin socket outlet 5/15 Amps, indipendentboardwith cables 4 Sqmm size. |
| 23 | Supply and fixing Modular switch one way 5/6 A white Active one module all as specified and as directed by the Engineer-in-Charge. Make: Havells(Crabtree)/Legrand/Plaza. |
| 24 | Supply and fixing Modular switch Bell push, flush type, 5 A white Active one module all as specified and as directed by the Engineer-in-Charge. Make: Havells(Crabtree)/Legrand/Plaza. |
| 25 | Supply and fixing in repair ofModular step type fan regulator,120 W white Active two module all as specified and as directed by the Engineer-in-Charge.Make: Havells(Crabtree)/Legrand/Plaza. |
| 26 | Supply and fixing Modular socket 5 Amp, 2/3 pin flush type Active white two module complete all as specified and as directed by the Engineer-in-Charge.Make: Havells(Crabtree)/Legrand/Plaza. |
| 27 | Supply and fixing Modular socket 16 A, 5 pin multi purpose Active white two module complete all as specified and as directed by the Engineer-in-Charge .Make: Havells(Crabtree)/Legrand/Plaza. |
| 28 | S&F Ceiling rose three terminals/ PVC/ polycarbonate, isolated bodycomplete all as specified and as directed by Engr-in-Charge Make: Anchor/ABB/Leader |
| 29 | Supply and fixing in repair of GI metal flush box suitable for mounting moduler plate of following modules:- |
| 30 | 3 Module |
| 31 | 6 Module |
| 32 | 8 Module |
| 33 | 12 Module |
| 34 | 16 Module |
| 35 | 18 Module |
| 36 | Supply and fixingin repair of combined both frame and cover plates fixing on mounting boxes for following modules:- |
| 37 | Cover plate with frame, 3 Module |
| 38 | Cover plate with frame, 6 Module |
| 39 | Cover plate with frame, 8 Module |
| 40 | Cover plate with frame, 12 Module |
| 41 | Cover plate with frame, 16 Module |
| 42 | Cover plate with frame, 18 Module |
| 43 | M&L for Cutting chases on brick walls/ concrete surfaces not exc10 cm girth and making good in cement mortar (1:3) the existing surfaceafter carryiing out the concealed wiring and making good disturbed surfaces matching with existing paint complete all as specified and as directed |
| 44 | Supply and fix high efficiency wall mounted LED light fitting 2 feet white, 10W, integrated LED driver etc. complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size including taking down old one and taken as credit complete all as specified and as directed. (Make:- Philps / Panasonic/ C&S) |
| 45 | Supply and fix high efficiency wall mounted LED light fitting 4 feet white, 20W, integrated LED driver etc. complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size including taking down old one and taken as credit complete all as specified and as directed.(Make:- Philps / Panasonic/ C&S) |
| 46 | Supply and high performance low wattage Street light not less than 25 Watts LED light fitting ,IP66 protection powder coated pressure die cast aluminium high power street light with heatresisant toughened glass with lens by providingGI pipe medium grade 25 mm dia 1.5 Mtrin length with suitable size MS Clamp two nos made out of 25x3 mm FI incl two coat of synthetic enamel paint over a coat of red oxide primer, prewired and including connecting up with 3 core flexible copper conductor cable of 1.5 Sqmm from ceiling rose to fitting and including taking down old u/s damagedall as specified. (Make : philips/Panasonic / C&S). |
| 47 | Taking down the old servicable 4 feet LED Tube light fitting and kept it in store for safe custody and refix it in orginal position including connecting up with 3 core flexible copper conductor cable of 1.5 Sqmm from ceiling rose to fitting complete all as specified and as directed by Engineer-in-Charge. |
| 48 | Taking down the Ceiling Fan/Wall Fan/Exhaust Fan, cleaning and greasing and refixing the sameand connecting up including provision of cable from ceiling rose with using 1.5/2.0 feet down rod as required in site after false ceiling all as directed by Engr-in-Charge |
| 49 | Supply and replacement of Metal clad socket single pole and neutral enclosure with a two pin and earth plug top and socket complete with one doble pole 20 Amps MCB C Type 230 Volts 2 all as directed. |
| 50 | S& F forDBOXX SRCD Protected Socket 20 A (With Steel Enclosure) Make: Havells/Legrand/ Siemens/Scheneider/ABB |
| 51 | Material and labour for Sub main wiring with Two run single core 4 sqmm for phase and neutral and one run single core 4 sqmm ass earth wire with multi stranded copper conductor (3 X 4 Sq mm)PVC insulated unsheathed FRLS cable 1100 volts grade confirming to IS-694 continuity conductor drawn into and including non-metallic rigid PVC conduit 20 mm dia concealed wiring through wall/ceiling/floor/roof etc including conduit accessories including taking down old sub main wiring with PVC conduit and taken as credit complete all as specified and as directed.Notes: (i) The disturbed surfaces shall be made good with existing surface including finishes as applicale. (i) Two different color wires shall be used for phase and neutral . (iii) Connections of cables with MCBs or bus bars shall be done through appropriate size brass/ copper thimbles .(iv) Three run of 4.0 Sqmm cable, and one run of PVC conduit will be measured as one unit.Make of cable:- Finlex/Poly cab/ Asian. Make of PVC conduit : Avon plast/ Kon seal / Garware. |
| 52 | All as per item ser no-2 above here in before but Two run single core 6 sqmm for phase and neutral and one run single core 6 sqmm as earth wire (3 X 6 Sq mm) |
| 53 | Supply and fix for MCCB 4 Pole, 415 V,adjustable Thermal &Fixed Magnetic setting typetype 150/160 Amps with breaking capacity 26 KA complete all as specified and as directed by Engr-in-charge.Make: Siemens/Scheneider/ABB, Note : Including taking down old unserviceable. |
| 54 | Supply and fix for MCB SPN 230 V, 32 Amps-40 Amps with breaking capacity 10KA C curve complete all as specified and as directed by Engr-in-charge.Make: Siemens/Scheneider/ABBNote : Including taking down old unserviceable. |
| 55 | Supply and fix for MCB SP 230 V, 6-32 Amps with breaking capacity 10KA C curve complete all as specified and as directed by Engr-in-chargeMake: Siemens/Scheneider/ABBNote : Including taking down old unserviceable. |
| 56 | S&F sheet metal enclosure VTPN MCCB DB 12 way double door with spreader terminals,insulating phase barrier and hardware, having IP 43 and IK 09 protection with neccesary arrangements Including taking down old u/s DB, MCCB and MCB\"s all as specified and directed Note :- (i) Including taking down old u/s DB and MCCB. Make: Legrand/Siemens/Scheneider/ABB. |
| 57 | S&F DB for MCB SPN 12 waydouble door DB with 200 amps rated copper bus barin SS enclosure double door type having IP 43 and IK 09 protection Including taking down old u/s DB and MCB\"s all as specified and directed . Note : MCB SPN/SP shall be measured and paid under the respective item of the schedule. Make: Legrand/Siemens/Scheneider/ABB. |
| 58 | S&F DB for MCB SPN 8 waydouble door DB with 200 amps rated copper bus barin SS enclosure double door type having IP 43 and IK 09 protection Including taking down old u/s DB and MCB\"s all as specified and directed . Note : MCB SPN/SP shall be measured and paid under the respective item of the schedule. Make: Legrand/Siemens/Scheneider/ABB. |
| 59 | Supply Fabricate, install, connect andtestindoor type distribution board of 2mm thick CRCA sheet powder coated painting fabrication and concealed in wall with all incomming outgoing cable connections provisions neutral and earth links for distribution with suitable insulation materials for fixing, suitable wiring from existing DB covered and as well as comprising followingswitch gear items mounted on suitable fibre sheet for for protectcting and fixing DB VTPN 12 way with locking arrangement complete including taking down old metal box and taken in to credit all as specified and as directed. |
| 60 | All as per Ser Item No-59 above here in before but for protecting and fixing DB SPN 12 way. |
| 61 | All as per Ser Item No-59 above here in before but for protecting and fixing DB SPN 8 way. |
| 62 | Material and labour for Earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick buried directly in ground vertically to a depth of not less than 2.25 mtr below ground level , with top edge of the earth plate at a depth of not less than 1.5 mtr below ground level connected with and incl GI strip earth 25 x 4 mm size including alternate 5 layersof charcoal, salt crystal and including 15 mm dia GI pipe light grade by means of nuts, bolts, washers and necessary earth work upto 7.5 mtr and connecting to test point, LT Switchgear etc as per site requirement including necessary excavation, earth work in any type of soil, PCC (1:3:6) type C-1 earth chamber, 40 mm thick RCC Cover with 6 mm dia MS bars 10 cm C/C on both ways as reinforcement complete all as shown in elecrical plate No 3 of SSR Pt- I including testing on completion complete all as specified and as directed. Notes:-The rates quoted is inclusive of galvanised earth lead strip 25x4mm conductor upto a length of 7.5m from the earth pit, necessary earth work PCC chamber, RCC cover, reinforcement, removal of surplus soil , site clearance etc. . |
| 63 | Supply and fix Heavy duty exhaust fan, steel body AC single Phase. 230V of size 300 mm sweep 1400 rpm with, blades, frame and metal mesh cover all as specified and as directed. Make: Almonard, Crompton, Havells.Note: Including taking down old unserviceable exhaust fans. |
| 64 | Supply and fix electric water heater, storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litre, BEE 4 Star rated complete with all accessories such as safety valve, thermostate, NRV, hot water steel pipe, cold water pvc pipe etc. all as specified and as directed. Make: Havells / VenusNote: Including taking down old unserviceable geysers |