Border Security Force-BSF has published Tender For Renovation Up Gradation Of Ug Cables And Feeder Pillars Panel At 114 Bn Bsf Khajuwala Under Shq Bsf Bikaner. Submission Date for this Tender is 29-04-2024. Electrical Maintenance Tenders in khajuwala Rajasthan. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
2 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode includingconnection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
3 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required |
4 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
5 | i) Upto 35 sq. mm |
6 | ii)Above 35 sq. mm and upto 95 sq. mm |
7 | iii) Above 95 sq. mm and upto 185 sq. mm |
8 | iv) Above 185 sq. mm and upto 400 sq. mm |
9 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
10 | i) Upto 35 sq. mm |
11 | ii)Above 35 sq. mm and upto 95 sq. mm |
12 | iii) Above 95 sq. mm and upto 185 sq. mm |
13 | iv) Above 185 sq. mm and upto 400 sq. mm |
14 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. |
15 | i) Upto 35 sq. mm |
16 | ii)Above 35 sq. mm and upto 95 sq. mm |
17 | iii) Above 95 sq. mm and upto 185 sq. mm |
18 | iv) Above 185 sq. mm and upto 400 sq. mm |
19 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required |
20 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. |
21 | i) 3.5X 35 sqmm(32mm) |
22 | ii)3½ X 50 sq. mm (35mm) |
23 | iii)3½ X 70 sq. mm (38mm) |
24 | iv) 3.5X 95 sqmm(45mm) |
25 | v) 3.5X 120 sqmm(45mm) |
26 | vi) 3½ X 150 sq. mm (50mm) |
27 | vii) 3½ X 185 sq. mm (57mm) |
28 | viii) 3½ X 240 sq. mm (62mm) |
29 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. In the existing trench, complete as required . (REX Polyextrusion / Jain Irrigation / Duraline / Avadh Polytube/ Gemini make) |
30 | i) 90 mm dia (OD-90 mm & ID-76 mm nominal) |
31 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. Direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc complete as required. (REX Polyextrusion / Jain Irrigation / Duraline / Avadh Polytube/ Gemini make) |
32 | i) 63 mm dia (OD-63 mm & ID-51 mm nominal) |
33 | ii) 90 mm dia (OD-90 mm & ID-76 mm nominal) |
34 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc. as required ( Zenith/TATA/Jindal-hisar/Prakash- Surya make) (i) 100 mm dia nominal bore |
35 | Laying Charges for cable through Manual Boggi by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bituminfor road crossing as required. |
36 | S/I/T/C of cubical type out door joint box having size 600 mmx 600 mmx 400 mm deep having doors on both sidefabricated with 2.03 mm thick CRCA sheet mounted on 35 mm x 35 mm x 5 mm angle iron frame, having 600 mm long 04 nos leg stand erected in cement concrete 1 :3 :6 (1 cement :3 coarse sand : 6 graded stone 40 mm nominal size) foundation i/c excavation 30 Cm below the ground. The legs paint with primer and black paint as required and consisting of following accessories. 04 nos aluminium bus bar strip suitable for 300 Amp current carrying capacityhaving size and also suitable space for Incoming and outgoing cable.(area of Joint box is taken in sq mm face area) as per direction of Engg in-charge. |
37 | Desigining,Fabrication Supply/ installation/ testing and commissioning of compartmentalised type outdoor feeder piller, double door made out of 2.03 mm thick CRCA powdered coated sheethaving 300 amps, 04 nos insulated aluminium bus bars and to accommodate following accessories, front & back openable door with proper hinges, R-Y-B LED indicators and P & F of internal connection with suitable size of copper wires, following accessories & angle iron frame of size 500 mm x 200 mm with 600 mm long legs made out of 50 mm x 50 mm x 5 mm thick angle & grouting the same in suitable cement concrete foundation, arrangement for incoming & outgoing cables, cable termination, earthing, locking, interconnection etc. as required. (CPRI Approved builder). The feeder pillar should have Indicating lamp (LED type) 22.5 mm 230 volt AC Red, Yellow and blue make L&T/Havells/simens- 03 nos, CT Ratio (Amp) 100/05, accuracy class 1, burden 05 VA - makeL&T/AE/Trinity -03 nos, Digital Multifunction meter (VAF + PF) make L&T Cat no. WC411011OOOO or equivalent in AE/Siemns- 01 No,Earth studs on both side. The feeder pillar should have provision to acccomodate 250 Amp , 4 Pole MCCB-1 No as incomer, 125 Amp , 4 Pole MCCB-4 No, 100 Amp, 4 Pole MCCB-1 Nos in each feeder pillar. The design of the feeder pillar should got approved from Competent Technical authority before fabrication.(The Fp should be of approx size 1200 x 1000 x 400 mm deep =6 Nos and 1000 x 900 x 400 mm deep- 3 No) (area of Feeder pillar is taken in sq mm face area) as per direction of Engg in-charge. |
38 | Desigining,Fabrication Supply/ installation/ testing and commissioning of indoor type compartmentalized cubical panel of size suitable for 415 Volt, 3 phases, 50 Hz made out of 2mm thick CRCA sheet and depth up to 800 mm with required hardware duly painted with powder coated in an approved Siemens grey shade after 7 tank treatment processes. The panel having separate detachable gland plate, hinged door, with locking arrangement, earth bar/stud, 1000A/415V 4 strip aluminum bus bar duly PVC sleeved, including electrical mechanical interlocking, connection inter–connection for incoming/Outgoing cables with the required current capacity bus bar links (as per direction of Engg in charge), space for 800A 4 Pole Air Circuit Breakers, bus couplers for two transformers, MCCBs. The panel should be mounted on MS Base frame 75 mm x 40 mm x 5mm of suitable size and should have the provision of following instruments mounted and includingprovision of outgoing cable connections bus bar links of required current carrying capacity etc as required. (Indoor Panel should be as per design &drawing approved by Engg in charge and comprising of Instruments):-a) 0-500 Volts, Digital voltmeter of size 96 Sqmmx96 sqmm with Selector switch-02 Set b) 0-1000 Amps, Digital Ammeter of size 96Sqmmx96sqmm type with Selector switch -02 set c) LED Pilot light (22.5 MM dia) withprotection MCB’s-06Nos) d) Alarm System - 01 Nos e) Exhaust Fan for panel - 01Nos.(The Main LT Panel-1 should be ofsize-4000 x 1800 x 800 mm approx.) |
39 | Providing and fixing of following accessories in the above/existing cubical panel as mentioned in the existing/new panels i/c connection inter-connection with aluminum bus bar of required size and current carrying capacity etc as required as per direction of Engg in charge. Schneider/L&T/ABB/C&Sas per direction of Engg in-charge. |
40 | Desigining,Fabrication Supply/ installation/ testing and commissioning of indoor type compartmentalized Essential cubical panel of size suitable for 415 Volt, 3 phases, 50 Hz made out of 2mm thick CRCA sheet and depth up to 450 mm with required hardware duly painted with powder coated in an approved Siemens grey shade after 7 tank treatment processes. The panel having separate detachable gland plate, hinged door, with locking arrangement, earth bar/stud, 400 A/415V 4 strip aluminum bus bar duly PVC sleeved, including electrical mechanical interlocking, connection inter–connection for incoming/Outgoing cables with the required current capacity bus bar links (as per direction of Engg in charge), space forMCCBs and change over. The panel should be mounted on MS Base frame 75 mm x 40 mm x 5mm of suitable size and should have the provision of following instruments mounted and includingprovision of outgoing cable connections bus bar links of required current carrying capacityetc as required. (Indoor Panel should be as per design &drawing approved by Engg in charge and comprising of) Instruments Panel ) a) 0-500 Volts, Digital voltmeter of size 96 Sqmmx96 sqmm with Selector switch-01 Set b) 0-800 Amps, Digital Ammeter of size 96Sqmmx96sqmm type with Selector switch -01 set c) LED Pilot light (22.5 MM dia) withprotection MCB’s-03Nos) d) Alarm System - 01 Nos e) Exhaust Fan for panel - 01Nos. (TheEssential LT Panel should be ofsize-2300x 2000 x 800 mm Approx) |
41 | Providing and fixing of following accessories in the above/existing cubical panel as mentioned in the existing/new panels i/c connection inter-connection with aluminum bus bar of required size and current carrying capacity etc as required as per direction of Engg in charge. (In item No 20)-Schneider/L&T/ABB/C&S |
42 | 800A, Air circuit breaker breaking capacity 50 KA manual draw out type 4 Pole Microprocessor based ET trip systems with thermal memory Conforms to IS/ IEC 60947-2 & 3,Zone Selective Interlocking, Fully rated neutral with inbuilt protection, Pre trip alarm & individual fault indicating LEDs ACB/Bus bar coupler MVS08N3MW6L comprising of Overload, Short-circuit, Instantaneous & Earth-fault protections Schneideror equvilent make. |
43 | Providing and fixing of tape wound current transformer 1000/5 in the existing panel i/c connections with 1.5 sqmm pvc copper wirein the existing panel at SN 3 (AE/L&T/Scheinder make) or equivalent make and as per direction of Engg in-charge |
44 | Extended Rotary handle for 400 Amp TP MCCB |
45 | Extended Rotary handle for 250 Amp TP MCCB |
46 | Extended Rotary handle for 125 Amp TP MCCB |
47 | Alarm System - 01 Nos |
48 | Cooling Fan for panel |
49 | Providing and fixing of following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 80 A, 25 KA, 2 Pole MCCB.(Make Havells/C&S/L&T) or equvilent make. and as per direction of Engg in-charge. |
50 | Providing and fixing of following rating and breaking capacity and pole MCCB with thermomagnetic release in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 100 Amp, 18 KA, 4 Pole MCCB.(Make Havells/C&S/L&T) or equvilent make. and as per direction of Engg in-charge. |
51 | Providing and fixing of following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 200 Amp, 36 KA, 4 Pole MCCB.(Make Havells/C&S/L&T) or equvilent make. and as per direction of Engg in-charge. |
52 | Providing and fixing of following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 250 Amp, 36 KA, 4 Pole MCCB.(Make Havells/C&S/L&T) or equvilent make. and as per direction of Engg in-charge. |
53 | Providing and fixing following capacity 4 pole, 415 V, category AC-23A. On Load Change Over Switch,in open execution in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. ( Make:-L& T /Socomec / Legrand /ABB /Schneider/ Siemen) or equvilent make. and as per direction of Engg in-charge. |
54 | 400 Amp four pole |
55 | Providing and fixing of following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 400 Amp, 50 KA, 4 Pole MCCB.(Make Havells/C&S/L&T) or equvilent make. and as per direction of Engg in-charge. |
56 | Providing and fixing of following rating and breaking capacity and pole MCCB with thermomagnetic release in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 125 Amp, 30 KA, 4 Pole MCCB.(Make Havells/C&S/L&T) or equvilent make. and as per direction of Engg in-charge. |
57 | Painting of LT Panel anf junction box with one coat of primer and two coats of First quality synthetic enamel paint of approved colour and shade to give an even shade including cleaning of surface with sand paper, scrapping etc. and applying one coat of primer and numbering of Pole etc as required. paint first quality to be used of Berger / Asian paints / Nerolacas per direction of Engg in-charge. |
58 | Repair and functioning of APFC Panel and replacement of un-serviceable equipment in the existing APFC panel i.e dismantling of defective accessoriesand making connection etc as required. .(L&T/C&S/Schneider/ABB/Havells/ Simens) or equvilent make. and as per direction of Engg in-charge. |
59 | 1) Capacitor 440 Volt heavy duty 1 KVR, |
60 | 2) Capacitor 440 Volt heavy duty 2 KVR, |
61 | 3) Capacitor 440 Volt heavy duty 3 KVR, |
62 | 4) Capacitor 440 Volt heavy duty 4 KVR, |
63 | 5) Capacitor 440 Volt heavy duty 5 KVR, |
64 | 6) Capacitor 440 Volt heavy duty 7.5 KVR, |
65 | 7) Capacitor 440 Volt heavy duty 10 KVR, |
66 | 8) Capacitor 440 Volt heavy duty 12.5 KVR, |
67 | 9) Capacitor 440 Volt heavy duty 20 KVR, |
68 | 10) 12 step APFC relay having site selector secondry CT |
69 | 11) "C" curve MCB of rating 20/40 Amps Triple ploe 10KA breaking capacity |
70 | 12) Capacitor Duty Contactor 5 KVR |
71 | 13) Capacitor Duty Contactor 12.5 KVR |
72 | 14) CT (100/5A) in existing panel board including making connection etc as required. |
73 | 15) Supplying and fixing of Indicating Lights (Red-1,Yellow-1,Blue-1, Green-8 ) |
74 | 16) Supplying and fixing of Ammeter in the existing APFC panel |
75 | 17) Supplying and fixing of Voltmeter selector switch in the existing APFC panel ) |
76 | 18) Supplying and fixingsuitable sizes PVC channel,wiring with suitable size FRLS copper wires, copper lugs, ferrules, PVC sleeves in the existing APFC panel including dismantling ofall defectivematerials and Connection etc as required as per direction of engg in charge. |
77 | Add "GST" Difference Multification Factor (0.0633) on DSR-2022(E&M)Items |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail