Tender For Execution Of Works Supply And Repairing Of Necessary Materials To Be Used In Operating The Distribution Transformers And Related Other Damaged Equipment Installed (Preventive Maintenance) At Six Nos. 33/11 Kv Sub-StationS (Including The Requir, lucknow-Uttar Pradesh

Madhyanchal Vidut Vitran Nigam Limited has published Tender For Execution Of Works Supply And Repairing Of Necessary Materials To Be Used In Operating The Distribution Transformers And Related Other Damaged Equipment Installed (Preventive Maintenance) At Six Nos. 33/11 Kv Sub-StationS (Including The Requir. Submission Date for this Tender is 09-05-2024. Distribution Transformer Tenders in lucknow Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

43173472
Corrigendum : Tender For Execution Of Works Supply And Repairing Of Necessary Materials To Be Used In Operating The Distribution Transformers And Related Other Damaged Equipment Installed (Preventive Maintenance) At Six Nos. 33/11 Kv Sub-StationS (Including The Requir
Open Tender
Indian
Uttar Pradesh
lucknow
09-05-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Tender For Execution Of Works Supply And Repairing Of Necessary Materials To Be Used In Operating The Distribution Transformers And Related Other Damaged Equipment Installed ( Preventive Maintenance ) At Six Nos. 33 / 11 Kv Sub-StationS ( Including The Required Material As Indicated In Tender Specification ) Against O & M Head Under The Jurisdiction Of Eudd-Gomtinagar, Lesa, Lucknow

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 23-Apr-2024 Date- Date 30-04-2024
2 30-Apr-2024 Date--- Date 09-05-2024

Key Value

Document Fees
INR 3540 /-
EMD
INR 34140.0 /-
Tender Value
Refer document

Attachment

FileName File Description File Size
41a8fede-9a24-4a40-8f96-331dbcb3bc62.html Tender Notice 0 KB
BOQ_1593202.xls Tender Document 0 KB
Document.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

Name of Work: Execution of Works Supply and Repairing of necessary materials to be used in operating the distribution transformers and related other damaged equipment installed (Preventive Maintenance) at Six Nos. 33/11 KV Sub-station"s (Including the required material as indicated in Tender Specification) against O & M Head under the Jurisdiction of EUDD-Gomtinagar, LESA, Lucknow
Sl. No. Item Description
1Replacement of Old and Damaged H.T Busihing rod including Oil Seal/Gaskits etc.(160, 250, 400, 630 and 1000 KVA T/F)
2Removal of Old and damaged H.T Busing Rod from T/F and fixing of suitable size newH.T Busing rod made of Brass with all nuts and bolts etc. including replacement of all old/damaged Neoprene Oil seal/Gasket set by fixing suitable size New Neoprene Oil Seal/Gasket Set , Complete Job in all respect. (All material will be provided by the Contractor)
3T/F Size 25, 63 & 100 KVA
4T/F Size 250 & 400 KVA
5T/F Size 630 KVA
6Replacement of Old and Damaged L.T Bushingrod including Oil Seal/Gaskits etc. Removal of Old and damaged L.T Busing Rod from T/F and fixing of suitable size new L.T Bushing Rod
7Busing rod made of Brass with all nuts and bolts etc. including replacement of all old/damaged Neoprene Oil seal/Gasket set by fixing suitable size New Neoprene Oil Seal/Gasket Set & as per site requirement, Complete Job in all respect. (Cable shall be provided by the department.)
8T/F Size 25, 63 & 100 KVA
9T/F Size 250 & 400 KVA
10T/F Size 630 KVA
11Stopping Oil leakage from T/F
12Stopping of Major Oil leakage from T/F L.T/ H.T Side Bushing, Radiator, Conservator, Top Cover and Breather.Removing of all damaged oil Seal/Gasket Set/Cork sheet and fixing of suitable size new Neoprene Oil seal/Gasket set/Cork sheet and tightening of H.T/LT bushing rod Complete Job in all respect. ( All material will be provided by the contractor)
13T/F Size 25, 63 & 100 KVA
14T/F Size 250 & 400 KVA
15T/F Size 630 KVA
16Stopping of Minor Oil leakage from T/F fixing of suitable size new Neoprene Oil seal/Gasket set/Cork sheet and tightening
17T/F Size 25, 63 & 100 KVA
18T/F Size 250 & 400 KVA
19T/F Size 6300 & 1000 KVA
20Replacement of Old and Damaged LT PVC CABLE (All Material will be provided by department.)
21Replacement of LT Aluminum unarmored XLPE/PVC Cable of different sizes from TF to LT fuse Unit
22Replacement of LT Aluminum unarmored XLPE/PVC Cable of different sizes from LT fuse Unit to Pole
23Replacement of Old and Damaged Suitable capacity of Aluminum Lugs (All Material will be provided by Contractor).
24Supply and fixing of Aluminium Crimping Lugs(Made of 99.9% pure A grade Aluminium) suitable for 240sqmm cable, Wt 78gm. Old damaged lug removal and Proper lug crimping by crimping machine and suitable size Brass Nut and bolt to be provided by contractor.
25Supply and fixing of Aluminium Crimping Lugs(Made of 99.9% pure A grade Aluminium) suitable for 400sqmm cable, Wt 170gm. Old damaged lug removal and Proper lug crimping by crimping machine and suitable size Brass Nut and bolt to be provided by contractor.
26Supply and fixing of Aluminium Crimping Lugs(Made of 99.9% pure A grade Aluminium) suitable for 630sqmm cable, Wt 298gm. Old damaged lug removal and Proper lug crimping by crimping machine and suitable size Brass Nut and bolt to be provided by contractor.
27Repairing of Old and Damaged Distribution Box. (All Material will be provided by contractor)
28SMC L.T. Distribution Pillar box with one incomer and 3 sets of 300 Amps Kit Kat rewritabletype fuse unit for outgoing circuits complete, connected on 800A bus bar.
29Provision of fuse unit at LT side
30Supply and Errection of complete Henely Type Tailess LT fuse unit 300 Amp consisting of 6 Nos Brass backentry, 6 Nos U type copper spring contact, Brass coupling with porcelain fitted on GI Sheet of 16 SWG with arrangement of 1 No neutral
31Supply and Errection of complete Henely Type Tailess LT fuse unit 500 Amp consisting of 6 Nos Brass backentry, 6 Nos U type copper spring contact, Brass coupling with porcelain fitted on GI Sheet of 16 SWG with arrangement of 1 No neutral
32Provision of fuse unit at HT side
33To protect transformer by unbalancing and overloading, provision of fuse unit to be installed at HT side with suitable capacity of Fuse assembly ( All Material as fuse assembly, nut bolts etc. will be provided by contractor)
34160, 250 KVA KVA T/F
35400. 630 KVA and1000 KVA T/F
36Repair and Maintenance of Old and Damaged Transformer Earthing
37Maintenance and repair of Transformer Body and Neutral Earthing by replacing damaged GI Strip 40x6mm earth and welding connection properly and earth resistance should be less then 01ohm.(All Material Provide by contactor)
38Provision of Pipe earthing of body and neutral at two points
39Provision of pipe earthing of transformer body and neutral seperately with 1.5 inch dia 60fitpipe. Contactor to ensure that earth connection properly should be tight and earth resistance should be less then 01ohm.(All Material Provide by contactor)
40Maintenance & Repairing Of DamageT/F Plinth / L T Distribution box Plinth
41Construction/Repairing & Maintenance of T/F Plinth by Using Bricks ,ballast or sand and Cement. (All Material will be provided by Contactor.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail