Tender For Construction Of Sdo (Civil) Complex At Kanina In Distt Mohindergarh. (Pdg. Substation And Dg Set Only), kanina-Haryana

Public Works Department-PWD has published Tender For Construction Of Sdo (Civil) Complex At Kanina In Distt Mohindergarh. (Pdg. Substation And Dg Set Only). Submission Date for this Tender is 09-05-2024. Diesel Generators Tenders in kanina Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

43134760
Corrigendum : Tender For Construction Of Sdo (Civil) Complex At Kanina In Distt Mohindergarh. (Pdg. Substation And Dg Set Only)
Open Tender
Indian
Haryana
kanina
09-05-2024

Tender Details

Construction Of Sdo (Civil) Complex At Kanina In Distt Mohindergarh. (Pdg. Substation And Dg Set Only)

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 18-Apr-2024 Date Date 09-05-2024
2 22-Apr-2024 Other Other 09-05-2024

Key Value

Document Fees
INR 5000 /-
EMD
INR 99126.0 /-
Tender Value
INR 49.56 Lakhs /-

BOQ Items

Name of Work: Construction of SDO (Civil) complex at kanina In Distt Mohindergarh. (Pdg. Substation and DG set only)
Sl. No. Item Description
1[13.18]Providing and fixing hard drawn steel wire fabric 75 mm X 25 mm rectangular mesh with 3.25 mm dia wire fixed on steel windows of standard rolled sections with 3 mm thick flat iron cover moulding of 12.5 mm width fixed with machine screws welded complete in all respect.
2[13.2]Providing and fixing angle iron frames for doors, windows and ventilators of mild steel Angle sections of size 35x35x5 mm, joints mitred and welded by angle iron 35x35x5 mm or 35x 5 mm flat pieces to the existing T-iron frame or to the wall with dash fastener,including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer, all complete as per the direction of Engineer-In-charge.
3[23.22.1.11]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.11. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 4 pole MCCB 200 to 250 amp, 25 KA
4[23.22.2.2]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 2.2. MCCB Enclosure made of Sheet Steel suitable for mounting MCCB of following ratings MCCB up to 250 A FP
5[23.22.8.2]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 8.2. SITC Four pole ON LOAD Manual change over switch in SS enclosureof following Ratings100 amp 415 volts
6[23.24.3.9]MS STAND, BUS BAR CHAMBER AND PANELS 3.9. Supply and erection of metal clad bus bar chamber made from 1.6 mm thick M.S. sheet and fixing with rag bolts on wall or on existing pedestal/angle iron frame including bonding, detachable top and bottom including painting and necessary connection etc. (Aluminium bars). 300 amp 4 bars of 100 cm each (cross section 51 mm x 6 mm) chamber over all size 1.10 m x 55 cm x 23 cm
7[23.26.1]SAFETY ITEMS 1. Supply and erection of Medium Voltage caution notice plate of size 200*150 mm in three languages.
8[23.26.2]SAFETY ITEMS 2. Supply and erection of High Tension Voltage caution notice plate of size 250*200 mm in three languages.
9[23.26.3]SAFETY ITEMS 3. Supply and erection of shock restoration chart in glass frame.
10[23.26.4]SAFETY ITEMS 4. Supply & Erection of mild steel bucket stand suitable for 6 Nos. fire buckets,(but without bucket) including the cost of welding and painting of complete stand will one coat of red oxide and 2 coats of approved paint of red colour with all labour and material required to complete the job in all respect up to the entireSatisfaction engineer in charge of the work (size 6x4 made of GI pipe 32mm dia).
11[24.1.10]EARTHING AND LIGHTENING ARRESTOR 10. Providing and fixing 25 mm x 5mm copper strip on surface or in recess for connections etc. as required with all labour and material.
12[24.1.3]EARTHING AND LIGHTENING ARRESTOR 3. Earthing with G.I. earth plate 600 mmx 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) complete as required.
13[24.1.4]EARTHING AND LIGHTENING ARRESTOR 4. Earthing with tinned copper earth plate 600mmx600mmx3mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but withoutcharcoal or coke and salt) etc. complete as required.
14[24.1.5]EARTHING AND LIGHTENING ARRESTOR 5. Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode.
15[24.1.7]EARTHING AND LIGHTENING ARRESTOR 7. Supplying and laying 25mm x 3 mm G.I. strip in 40 mm dia,GI pipe as/from earth electrode including soldering etc. as required.
16[24.1.8]EARTHING AND LIGHTENING ARRESTOR 8. Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material.
17[24.1.9]EARTHING AND LIGHTENING ARRESTOR 9. Providing and fixing 25 mm x5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required.
18[24.2.7.4]LT CABLE 7.4. Supply and erection ofsuitable compression type brass cable glands for underground Cable :- 70 sqmm to 95 sqmm Cable 3 to 3½ Core
19[24.2.8.8]LT CABLE 8.8. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 70 sqmm
20[24.2.8.9]LT CABLE 8.9. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 95 sqmm
21[24.3.3.1]HT CABLE 3.1. Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :70 to 120 sqmm
22[24.3.4.1]HT CABLE 4.1. Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :70 to 120 sqmm
23[24.5.2.5]MISCELLANEOUS ITEMS 2.5. S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Metre below ground level including digging and refilling of earth including cost of suitable size socket/coupler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work. DWC/HDPE pipe 120/105 mm outer dia/ inner dia
24[24.7.3]RCC FOUNDATIONS FOR DG SET 3. 100 KVA DG Set
25[24.7.5]RCC FOUNDATIONS FOR DG SET 5. 250 KVA DG Set
26Supply and erection of Rubber Mat 1mx2mx 3mm thick suitable for 11/33 KVA as per IS No. 15652C/M/L 3017739 as per approved by Chief Electrical inspector, Govt. of Haryana.
27Supply and erection of Fire Extinguishers duly hang on wall with necessary hook complete in all respect. Make( Make: Safex /Minimax / Cease Fire). CO2 type 4.5 Kg Capacity.
28S/Eof fire bucket of G.I. sheet of 24 gauge write with ` FIRE` as per fire specification.
29Supply and erection of Fire Extinguishers duly hang on wall with necessary hook complete in all respect. Make Make: Safex /Minimax / Cease Fire). ABC Dry Powder extinguisher 6 Kg Capacity.
30Supply Erection testing and Commissioning of 11 KV indoor HT metering panel complete with C.Ts P. Ts. Cubical and electronic meter with accurancy class as per requirment/approved by DHBVN at he time of installation, consisting of the following. Cubical panel free standing floor mounting type made out of sheet steel 14 SWG CRCA sheet with chanel iron base frame spray painted with strong synthetic light grey enamel paint as per size and design approved by the DHBVN 3 Nos. 11 KV CTS of ratio as approved by DHBVN for indoor installation of appd. Make of 1 Nos. 11 KV PTs 11000/110 Volts Oil filled suitable for indoor installation of approved make of DHBVN. Digital Electronic Meter 3 phase 4 wires recording in KWH and rating and accuracy as by DHBVN with push button display operating system of different kind of readings. The cubical panel will be complete in all respect including interconnection, internal wiring with PVC copper cable, its testing and approval of all item by DHBVN including cost of all testing/ approval charges of all items of DHBVNincluding cost of all labour and material required to complete the job in all respect upto the entire satisfaction of the engineer in charge of the work.(NS)
31Supply and Erection of 11 meter pole complete the job in all respect upto the entire satisfaction of Engineer-in-Charge.(NS)
32Supply and Erection of G.I. Half Clamps Wt. 1.47 kg. HVPN Drg. No. 2380 complete the job in all respect upto the entire satisfaction of Engineer-in-Charge. (NS)
33Supply and Erection of G.I. Full Clamps Wt. 2.325 kg. HVPN Drg. No. 2349 complete the job in all respect upto the entire satisfaction of Engineer-in-Charge. (NS)
34Supply and Erection of 11 KV pin insulator with pin complete the job in all respect upto the entire satisfaction of Engineer-in-Charge.(NS)
35Supply and Erection of G.I. Channel 100x50x6mm 2200mm for H pole, wt. 21.100 kg complete the job in all respect upto the entire satisfaction of Engineer-in-Charge.(NS)
36Supply and Erection of G.I. Angle iron 50x50x6mm 2400mm for earth wire, wt. 10.80 kg complete the job in all respect upto the entire satisfaction of Engineer-in-Charge. (NS)
37Supply and Erection of 11 KV GO switch complete with handle, pipe and supporting channel complete the job in all respect upto the entire satisfaction of Engineer-in-Charge. (NS)
38Supply and Erection of ACSR conductor 50mm2 (Rabbit) complete the job in all respect upto the entire satisfaction of Engineer-in-Charge.(NS)
39Supply and Erection of G.I. nut and bolt off sizes complete the job in all respect upto the entire satisfaction of Engineer-in-Charge. (NS)
40Supply and erection of HT 11KV XLPE under ground cable, loose in existing pipe or trenches complete with necessary connections.50 Sq. mm 3 Core Ard. Cable . (NS)
41S/E stay sets 8` long complete with X-Plat 460mm of Angie 65x65x6 Elbow and Rod Wt 13.80 kg (NS)
42Supply and Erection of Stay wire/GSS wire 7/8 SWG (4mm)complete the job in all respect upto the entire satisfaction of Engineer-in-Charge. (NS)
43Supply and Erection of Lightning arrestor 9KV, 5KA (3Nos.) complete the job in all respect upto the entire satisfaction of Engineer-in-Charge.
44Supply and Erection of G.I. Channel 75x40x6mm 2200mm for fuse unitcomplete the job in all respect upto the entire satisfaction of Engineer-in-Charge.(NS)
45Supply and erection of Three Phase 100 KVA, Diesel Generating Set having following specification. Diesel Engine shall be Liquid Cooled, electric start developing required B.H.P. at 1500 rpm suitable for alternator to deliver specified continuous KVA output at 0.8 lagging PF at NTP conditions (Rating shall be tested at Unity PF). The Diesel Engine should be capable of providing 10 % overload for one hour continuous running at full load after every 11 Hours continuous running. Diesel Engine should be fitted with Electronic Governor. The Diesel Engine shall be complete with the following accessories:- Engine instrument Panel consisting of starting switch/push button, Lube Oil and Pressure Gauges, Water Temperature Gauge, RPM indicator and Hour meter. Low lube oil pressure safety required in Engines, High Water temperature safety for water cooled Engines is required. The safety should include audio alarm and trip facility also to avoid damage to the engine. Radiator. Exhaust silencer of Residential type. 12V/24V starting system complete with starter motor, charging alternator and Cutout Lead Acid battery of suitable ratings with connecting cables. The batteries of 130AH shall be supplied in uncharged conditions and of Make : EXIDE/ STANDARD FURUKAWA/ AMARON/ TATA-GREEN/ AMCO/ LUMINOUS/ PACESETTER Diesel Engine of direct injection or Diesel Engine fitted with common Rail Direct Injection Pump shall be accepted. The Engine should confirm to applicable Emission Norms. The Diesel Engine shall be accepted only which conforms to latest BISALTERNATOR :- The Alternator shall be self – excited, self – regulated of specified KVA rating in three phase at 415 Volts, 50 Hz, 1500 RPM and 0.8 pf lagging (Rating shall be tested at Unity PF). The alternators shall be of brushless type only. The alternators shall be screen-protected drip proof with Min. IP-21 or improved degree of protection for outdoor installations. The class of insulation of the Alternator would be F/H. The rated voltage of Alternator will be 415 V for 3 phase. Make of Alternator : Kirloskar / Kirloskar Green/ Crompton – Greaves/ Leroy Somer / Trident/ Stamford/ Meccalte. AMF CONTROL PANEL:- Automatic mains failure (AMF) control panel shall be able to start up the DG set and can transfer the load on to D.G. set on mains failure without requiring any human intervention, similarly, on restoration of main supply, it shall be able to transfer the load to mains supply and switch off the D.G. Set automatically. The AMF panel enclosure should be with the IP-53 degree of protection and shall be fabricated from minimum 16 SWG thick steel sheet duly pre-treated and aesthetically finished and Power coated. The AMF Control Panel shall have the following instruments : a) Microprocessor based relay with composite/separate meter for digital display of : Generator voltage/AC Mains voltage. Generator Current. Load Current. Power Factor. Frequency. Energy. Three attempts engines start/ engines cranking relay. On delay timer for load change over. On delay timer for engine shut off. Mode selector switch for setting the panel on any one position such as off or auto or manual or test. Engine On-Off switch (Push button type) MCCB/Fuses of suitable rating shall be provided. Rectangular Aluminium Bus Bars (one number for each phase, neutral and Earthing terminal) of adequate ratings duly colour coded with heat shrinkable PVC Sleeves or Copper Cables. Two contactors/ACB of suitable rating (one for DG set and one for AC mains) with over load relay. UnderplusOver Voltage Relay. Automatic Battery charger with on-off switch, voltmeter and ammeter for charging the battery from mains. This will be addition to the battery charging alternator fitted on the engine. Instrument and Control Fuses/MCB. Four number indicating lamps to indicate ‘load on mains’ ‘set running’ ‘load on set’ and ‘battery charger on’. Audio visual alarm for ‘Low lubricating oil pressure’ High water temperature’ (for water cooled), ‘Start failure’, and ‘DG overload’ Any other switch, instrument, relay or contactor etc. essential for smooth and trouble free function of DG set with AMF Panel (to be specified by the tenderer in their offer with complete detail of the item). All Electro components/ parts such as MCCB/ MCB/FUSE/ Contactor/ Meters should be of LandT/ ABB/ SCHINEDIER/AE/ENERZON/GE/HAVELLS/ SIEMENS make. MANUAL CONTROL PANEL:- The Control Panel shall be made out of fabricated sheet 16 gauge (min) thick duly powder coated of suitable size for indoor/outdoor floor mounting installation. Aluminium Busbar/copper cables, internal wiring with suitable provision for / connection incoming/ outgoing leads. The Control Panel shall include following instruments:- Composite meter for digital display of i. Voltage ii. Current iii Frequency One MCB/MCCB/ACB of suitable Rating. Push Button switch for on off operation. Indication lamps. Automatic Battery charger with on-off switch, voltmeter and ammeter for charging the battery from mains. This will be addition to the battery charging alternator fitted on the engine. SOUND PROOF ENCLOSURE (CANOPY) The generator shall be in a sound proof (Acoustic) enclosure suitable for Diesel Generating Set complete in all respect having following specification/ Feature :- Fabricated as per standard specification of manufacturer, stuffing done with suitable Foam/ Rock wool. Rock wool supported with Tissue Paper or perforated sheets having holes. Residential type silencer provided to lower the noise of exhaust outlet. Canopy treated for antirust with powder coating. Should have fresh Air inflow and proper ventilation. Modular in construction and provided with lockable doors. The Sound proof enclosure shall be strictly as per CPCB -IV prevalent norms. The sheet thickness should be 18 gauge (min) as per manufacturer standard and as per CPCBIV rules.100 KVA DG set With AMF Panel
46Supply, installation, testing and commissioning of 11kV compact secondary substation outdoor type designed for natural cooling (K-10 class), having type tested equipments comprising of dry type CRT transformer and SF-6 insulated compact switchgear enclosed in robotically sealed stainless steel tank, low-voltage switchboard, interconnection between HT switchgear to transformer using Aluminium conductor Cables and transformer to LT-switchgear usingCopper busbars, factory built ready for connection type, internal GI earthing provided complete with other associated equipments etc. complete as required conforming to IEC 62271-202 only and relevant IS specifications, as regards to design, manufacturing, type-testing, routine-testing and general operator safety precautions (IAC AB 20kA/1-sec). The enclosure shall have modular construction using G.I. Sheet steel and shall be powder-coated from exterior, with all major equipment inside common enclosure. The Transformer compartment will have IP-23D ingress protection, whereas the transformer used shall be Cast Resin Type specially designed for low losses as per losses defined.( Make: ABB/Schneider/Siemens).RMU, LT Switchgear, Vacuum Interrupter shall be of same make as PSS OEM to ensure life cycle optimization . Also, System Integrator/Licencse partner make CSS shall not be acceptable . The compact substation shall primarily consist of : A) HT SWITCHGEAR having 01nos FIxed-Type Load break Switches and 02nos. Fixed-Type VCB (feeding into Transformer), enclosed in common tank( 2.5 mm thick ), made of robotically welded non-magnetic/non-ferritic Stainless Steel sheets, filled with SF6 gas acting as an excellent insulating medium, IP-67 tank design having leakage rate less than 0.1% per-annum, whereas it shall be Arc-Proof design with Internal Arc criteria of 20kA/1-sec individually. The Compact Switchgear shall be a front-flushed design with integrated spring-charging handle and associated Capacitive Voltage LED Indicators for arc-proof cable box, with associated Terminal Protector boots for mounting on site-replaceable cable bushings and front-facia semaphore mechanical indication for breaker ON/OFF/EARTH and associated Fault Passage Indicator for incoming Load break switch. The breaker will be provided with integrated Self-Powered 3OC plus 1EF relay with Low and High set for Over current and Earth Fault. Relay should have facility to display the maximum loaded phase current also.Relay shall record minimum 5 fault records with time stamping, and shall be operated via Resin cast RingCore Protection CTs of suitable ratio an burden.( Make: ABB/Schneider/Siemens) B) TRANSFORMER shall comprise of 200KVA 11KV/433V DYn11 Copper Wound Cast Resin Dry Type Transformer with Off load tap links ofplus 5% to -5% @2.5% with WTI scanner. Class of Insulation: H, Temperature rise limits 115 deg.C over ambient of 50 degrees. Losses (as per IS tol.) - No Load losses - 1000 W and Full load losses - 4000 W(Subject to IS Tol.) with WTI scanner and Surge arrestor on the HV side .(Make-ABB India Limited/Schneider/Siemens)
47Supply and erection of under ground cable, loose in existing pipe or trenches complete with necessary connections. 95 Sq. mm 3.5 Core Ard. Cable
48Supply and erection of under ground cable, loose in existing pipe or trenches complete with necessary connections. 70 Sq. mm 3.5 Core Ard. Cable