Tender For Hvac Work In Pod 1E 504, indore-Madhya Pradesh

Indian Institute Of Technology-IITB has published Tender For Hvac Work In Pod 1E 504. Submission Date for this Tender is 15-04-2024. Spare Part Tenders in indore Madhya Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

43110088
Tender For Hvac Work In Pod 1E 504
Open Tender
Indian
Madhya Pradesh
indore
15-04-2024

Tender Details

Tender For Hvac Work In Pod 1E 504; 1 Supply, Installation, Testing & Commissioning Of High Static Fcu Unit Made Of 25Mm Thick Panels Consisting Of Pre Plasticized G.I. Casing Of Thickness 0.8Mm Outside Layer And 0.8 Mm Inside Layer With Polyurethane Foam ( Puf ) Insulation Factory Injected Between Them By Injection Moulding Machine, Complete With Blower Section With Blower Suitable For Static Pressure As Required, Cooling Coil Section With Aluminum Finned Copper Tubes ( Tubes Thickness Not Less Than 0.5Mm ) , Filter Section With 50Mm Thick Metal Viscous / Washable Synthetic Type Air Prefilters, Belt Drive Package With Tefc Drive Motor With Efficiency Class Ie3 Or Eff1 Whichever Is More Efficient And Suitable For 415 ± 10% Volts, 50Hz, 3 Phase Ac Supply, Drain Connections, Stainless Steel ( 18G ) Drain Pan With Puf Insulation. 2 6 Tr ( 3000 Cfm ) 3 Providing & Fixing Valve Station For Fcu Including With Connected Piping And Adequately Supported As Per Specifications. 4 Supply & Installation Of Digital Thermostat For Fcu 5 Supply & Installation Of C Class 25Mm Pipe With Necessary Clamps, Vibration Isolators, Fittings And Support But Excluding Valves, Strainers, Gauges Etc. 6 Supply & Installation Of Tee 50Mmx50mmx25mm With Necessary Clamps, Vibration Isolators, Fittings And Support. 7 Supply & Installation Of Elbow 90 25Mm With Necessary Clamps, Vibration Isolators, Fittings And Support. 8 Supply & Installation Of Elbow 45 25Mm 9 Supply & Installation Of Socket 25Mm 10 Supply & Installation Of 2-Way Valve With Strainer 25Mm With Necessary Clamps, Fittings And Support. 11 Supply & Installation Of 25Mm Butterfly Valve With Necessary Clamps, Vibration Isolators, Fittings And Support. 12 Supply & Installation Of 25Mm Balancing Valve With Necessary Clamps, Vibration Isolators, Fittings And Support. 13 Supply & Installation Thermometer 14 Supply & Installation Of 25 Mm Ball Valve With Necessary Clamps, Vibration Isolators, Fittings And Support. 15 Providing & Fixing Offire Retardant Quality Expanded Polystrene Moulded Pipe Section Of Density 20 Kg / Cu.M After A Thick Coat Of Cold Setting Adhesive ( Cprx Compound ) Wrapping With 500G Polythene Faced Hessian And Finally Applying 0.63Mm Aluminum Sheet Cladding Complete With Type3 , Grade 1 Roofing Felt Strip ( As Per Is:1322 As Amended Up To Date ) At Joints Repairing Of Damage To Building Etc. As Per Specifications And As Required Complete In All Respect. 16 Shut Down Job Including Drain And Refilling Of Water And Required Civil Work.

Key Value

Document Fees
Refer document
EMD
INR 19940.0 /-
Tender Value
INR 9.97 Lakhs /-

BOQ Items

Name of Work: HVAC Work in POD 1E 504
Sl. No. Item Description
1Supply, Installation, Testing & Commissioning of HIGH STATIC FCU unit made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, cooling coil section with aluminum finned copper tubes (tubes thickness not less than 0.5mm) , filter section with 50mm thick metal viscous/ washable synthetic type air prefilters, belt drive package with TEFC drive motor with efficiency class IE3 or EFF1 whichever is more efficient and suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply, drain connections, stainless steel (18G) drain pan with PUF insulation.
26 TR (3000 CFM)
3Providing & fixing Valve station for FCU including with connected piping and adequately supported as per specifications.
4Supply & Installation of Digital Thermostat for FCU
5Supply & Installation of C Class 25mm Pipe with necessary clamps, vibration isolators, fittings and Support but excluding valves, strainers, gauges etc.
6Supply & Installation of Tee 50mmx50mmx25mm with necessary clamps, vibration isolators, fittings and Support.
7Supply & Installation of elbow 90 25mm with necessary clamps, vibration isolators, fittings and Support.
8supply & Installation of elbow 45 25mm
9Supply & Installation of Socket 25mm
10Supply & Installation of 2-way Valve with Strainer 25mm with necessary clamps, fittings and Support.
11Supply & Installation of 25mm butterfly valve with necessary clamps, vibration isolators, fittings and Support.
12Supply & Installation of 25mm Balancing valve with necessary clamps, vibration isolators, fittings and Support.
13Supply & Installation thermometer
14Supply & Installation of 25 mm Ball Valve with necessary clamps, vibration isolators, fittings and Support.
15Providing & fixing offire retardant quality expanded polystrene moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessian and finally applying 0.63mm aluminum sheet cladding complete with type3 , grade 1 roofing felt strip(as per IS:1322 as amended up to date ) at joints repairing of damage to building etc. as per specifications and as required complete in all respect.
16Shut down job including drain and refilling of water and required civil work.