Tender For Repair Maint And Improvement Of Lt Panel Incl Lt Switch Gear, Earthing, Timer Panel, Lt Poles, Pole Box, Outdoor Street Lights, Flood Lights, Area Lights, Lt Distr Network And Connected Items At Hq Central Command, Hq Mupsa, Kb Road, Th, lucknow-Uttar Pradesh

Military Engineer Services-MES has published Tender For Repair Maint And Improvement Of Lt Panel Incl Lt Switch Gear, Earthing, Timer Panel, Lt Poles, Pole Box, Outdoor Street Lights, Flood Lights, Area Lights, Lt Distr Network And Connected Items At Hq Central Command, Hq Mupsa, Kb Road, Th. Submission Date for this Tender is 30-04-2024. Electrical Maintenance Tenders in lucknow Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

43103809
Corrigendum : Tender For Repair Maint And Improvement Of Lt Panel Incl Lt Switch Gear, Earthing, Timer Panel, Lt Poles, Pole Box, Outdoor Street Lights, Flood Lights, Area Lights, Lt Distr Network And Connected Items At Hq Central Command, Hq Mupsa, Kb Road, Th
Open Tender
Indian
Uttar Pradesh
lucknow
30-04-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Repair Maintenance And Improvement Of Lt Panel Incl Lt Switch Gear, Earthing, Timer Panel, Lt Poles, Pole Box, Outdoor Street Lights, Flood Lights, Area Lights, Lt Distr Network And Connected Items At Hq Central Command, Hq Mupsa, Kb Road, Thimmaya Road

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 23-Apr-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 30-04-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 90000.0 /-
Tender Value
INR 45 Lakhs /-

Attachment

FileName File Description File Size
e4235d14-32d4-49d6-91bf-948c9407b2e8.html Tender Notice 0 KB
BOQ_726825.xls Tender Document 0 KB
Tender17.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

NAME OF WORK: REPAIR MAINTENANCE AND IMPROVEMENT OF LT PANEL INCLUDING LT SWITCH GEAR, EARTHING, TIMER PANEL, LT POLES, POLE BOX,OUTDOOR STREET LIGHTS, FLOOD LIGHTS, AREA LIGHTS, LT DISTRIBUTION NETWORKAND CONNECTED ITEMS ATHQ CENTRAL COMMAND, HQ MUPSA, KB ROAD, THIMMAYA MARG, HM MARG,SUBHASH MARG AND ADJOINING AREA OF AGE E/M EXT (ELECT) UNDER GE E/M LUCKNOW
Sl. No. Item Description
1Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft / loose soil for laying / taking up / taking down of cables and getting out and levelling of bottom suface to required level all as specified and directed by Engineer- in- Charge.
2Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.
3Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge.
4Material and labour for dry river sand, washed and screened dry for cushioning to under ground cable in trenches below and around under ground cable including spreading and levelling complete as specified and directed . Note :- Punned thickness shall only be considered for payment
5M&L for laying well burnt old sizebricks, sub class "B" bricks, straight or curved on plan , laid flat with width equal to length of brick, laid dry over electric cable for protection complete all as specified & directed by Engr-in-Charge.
6All as per srl item No 5 here-in-before but using old bricks obtained under srl item No1 here in before.
7M&L for demolition /cutting of road / path / hardstading / concrete in floor, etc for laying of cable complete all as directed at site by Engr-in-charge
8Material and labour for PCC 1:2:4 type B-2 using 40 mm graded stone aggregates for filling of cutting of roads / path / hardstanding etc complete all as specified and as directed by Engineer-in-Charge.
9Deployment of tools & manpower for Boring of hole under road / pavement / hard standing or any other situation by manual means suitable for passing of 40 to 80 mm bore pipe and making good both ends all specified and directed
10Supply and laying in trenches / Floor / road crossing or fixed to Pole / Wall GI pipe light grade ISI marked with fitting of size 40 mm bore for protection of cable including taking down existing pipe complete all as specified and directed by the Engineer-in-Charge.
11Supply and laying in trenches / Floor / road crossing or fixed to Pole / Wall GI pipe light grade ISI marked with fitting of size 50 mm bore for protection of cable including taking down existing pipe complete all as specified and directed by the Engineer-in-Charge.
12Supply and laying in trenches / Floor / road crossing or fixed to Pole / Wall GI pipe light grade ISI marked with fitting of size 80 mm bore for protection of cable including taking down existing pipe complete all as specified and directed by the Engineer-in-Charge.
13Material & Laying, jointing and testing in replacement ofLT under ground electric power cablecrossed linked polyethylene ( XLPE)insulated, galvanised steel strip or wire armoured,ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 10 sqmm cross sectional area, 2 core ,complete all as specified laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers complete all as specified and directed. Note :-Excavation, earth work, sand cushioning, protection bricks/ tiles/ block andpipe shall be measured and paid separately under appropriate items.
14All as per item No 13 above butLT UG Cable of size 16 Sqmm 2 core
15All as per item No 13 above but LT UG Cable of size 16 Sqmm 4 core
16All as per item No 13 above butLT UG Cable of size 25 Sqmm 4 core
17All as per item No 13 above butLT UG Cable of size 35 Sqmm 3.5 core
18All as per item No 13 abovebutLT UG Cable of size 50 Sqmm 3.5 core
19All as per item No 13 above butLT UG Cable of size 70 Sqmm 3.5 core
20All as per item No 13 above butLT UG Cable of size 95 Sqmm 3.5 core
21All as per item No 13 above butLT UG Cable of size 120 Sqmm 3.5 core
22All as per item No 13 above butLT UG Cable of size 185 Sqmm 3.5 core
23All as per item No 13 above butLT UG Cable of size 240 Sqmm 3.5 core
24Earthing in replacement complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by mean of GI wire 4 mm dia by means of bolts, nuts check nuts and washers of GI or steel and connecting to earthing test point, main switch board, testing on completion including PCC cover and frame, PCC (1:3:6) type C-2 as in earthing pit, MS funnel with wire mesh GI pipe 20 mm dia light grade for watering and GI pipe 15 mm dia light grade for the protection of GI wire from earth pit to earth point complete including necessary excavation and earth work in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50 m all as specified as shown in electrical plate No 5 SSR Part-I.PCC chamber shall be constructed at least one metre away from the earth pit and GI pipe fittings for watering shall be provided up to chamber and cost of the same is deemed to be included in the rate of earthing. Note :- Ifthe desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
25M&L Earthing in replacementcomplete with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end, GI earth strip encased inand including 40 mm dia GI "lightgrade" pipe from upper end of earth plate upto equipments,20 dia bore GI pipe "light grade" as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe andPCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS TMT bars 8mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as describedin electric plate of SSR Part I completeall as specified and directed and testing on completion. Note :- Ifthe desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
26M&L for disconnecting the existing cable from Panel / Pole, preparing the end for jointing including all earth work, Supply and fixing Cable end termination heat shrinkable joint including sleeves suitable for LT XLPE cable of size 3.5/4 core 10 to16 Sqmm
27All as per item No 26 abovebut suitable for LT XLPE cable of size 25 to 50 Sqmm
28All as per item No 26 abovebut suitable for LT XLPE cable of size 70 to 120 Sqmm
29All as per item No 26 abovebut suitable for LT XLPE cable of size 150 to 185 Sqmm
30All as per item No 26 above but suitable for LT XLPE cable of size 240 to 300 sqmm
31Disconnecting the existing cable from Panel / Pole, preparing the end for jointing including all earth work, Supply and fixing straight through heat shrinkable joint suitable for LT XLPE cable of size 3.5/4 core 10 to 16 sq mm
32All as per item No 31 above but size 25 to 50 Sqmm
33All as per item No 31 abovebut size 70 to 120 Sqmm
34All as per item No 31 abovebut size 150 to 185 Sqmm
35All as per item No 31 above but size 240 to 300 sqmm
36Supply & Fix in replacement twin core, 6 sqmm nominal cross sectional areamultistrandedaluminium conductor cable, over all PVC sheathed, 1100 Volts grade heavy dutycable PVC insulatedand PVC sheathedcomplete all as specified.
37Supply & Fix in replacement twin core, 10 sqmm nominal cross sectional areamultistrandedaluminium conductor cable, over all PVC sheathed, 1100 Volts grade heavy dutycable PVC insulatedand PVC sheathedcomplete all as specified.
38Supply, fixing, connecting andtesting in replacementMCCB 63 Amp 4 pole 25 KA 415 volts 50 Hzthermal magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed.
39Supply, fixing, connecting andtestingin replacement MCCB 100 Amp 4 pole 25 KA 415 volts 50 Hz thermal magnetic release with spreaderthermal magnetic release after taking down old existing unserviceableMCCB complete all as directed.
40Supply, fixing, connecting andtesting in replacement MCCB 125 Amp 4 pole 25 KA 415 volts 50 Hzthermal magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed.
41Supply, fixing, connecting andtesting in replacement MCCB 160 Amp 4 pole 25 KA 415 volts 50 Hz thermal magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed.
42Supply, fixing, connecting andtesting in replacementMCCB 200 Amp 4 pole 36 KA 415 volts 50 Hz thermal magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed.
43Supply, fixing, connecting andtestingin replacement MCCB 250 Amp 4 pole 36 KA 415 volts 50 Hz thermal magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed.
44Supply, fixing, connecting andtestingin replacement MCCB 400 Amp 4 pole 36 KA 415 volts 50 Hz thermal magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed.
45Supply, fixing, connecting andtestingin replacement MCCB 630 Amp 4 pole 50KA 415 volts 50 Hzthermal magnetic release with spreaderafter taking down old existing unserviceableMCCB complete all as directed.
46S&F in replacementon load change over switch open execution of capacity 400 Amps , 4 pole , 415 volt , 50 Hz fixed in any type of existing LT panel/Feeder piller including taking out old existing unserviceable change over from panels etc complete all as directed
47S&F in replacementon load change over switch open execution of capacity 250 Amps , 4 pole , 415 volt , 50 Hz fixed in any type of existing LT panel/Feeder piller including taking out old existing unserviceable change over from panels etc complete all as directed
48Supply and fixing in replacement MCCB FP 125 Amps, 25 kA, 415 Volt AC, 50 Hz, complete with sheet metal enclosure of 1.6 mm thick MS sheet factory made with powder coat paint including connecting with existing system with existing cablling network including making good disturbed surfaces complete all as specified and directed. Note : The cost of suitable size fastner/Nut bolts required at site for fixing of cubical is deemed to beincluded in the quoted rate by the contractor.
49Supply and fixing in replacement double pole sheet metal enclosure made of 1.6 mm thick MS sheet factory made with powder coat painting including 01x MCB20 Amps 10 kAcomplete all as directed Note : The cost of suitable size clamp/Nut bolts required at site for fixing of enclosure on garden light post/wall is deemed to beincluded in the quoted rate by the contractor.
50Supply drawing, connecting and testing in replacement3 core, 1.5 Sqmm PVC insulated and PVC round sheathed` copper conductor (flexible ) industurial cable, 1100 Volts conforming to IS 694 in steel tubular poles from Junction box to street light fitting including providing suitable copper lugs all as specified and directed by Engr-in-charge.
51S&F in replacementwheather proof pole mountingPVC junction box, base and door of junction boxmade out of SMC having outside dimention333x233x120mm, inside dimention300x200x105mm , single door front openable provided withhinged cover and locking arrangements with 4 Nos aluminium bas bar 63 Amps, mounted on porcelin insulatorincluding M&L for MCB SP10 Amp -1No, fixed on box in Din rail complete with electrical connection fixed to pole with suitable sizeFI clamp nut bolts and washer including embossing/painting of danger notice of size not less than 10cm x 7.5cm with letters, figures and conventional skull and bones in signal red colour on front face of junction box body Complete all as directed by Engr-in-Charge
52Supply & fixing in replacement GI brackets made of 40 mm nominal bore GI pipemedium grade of required length not less than 1.5 M long, mounting brackets made out of Mild steel FI 40x6 mm of required shape ( two Nos) duly fitted with Mild steel nuts, bolts and washers and painting with two coats of synthetic enamelled paint over one coat of red oxide Zn chrome primer and fixed to pole / walls etc complete all as specified & directed by Engr-in-Charge.
53Supply and fixingin replacement CRCA sheet for LT panel having thickness 3.15 mm powder coated finish over one coat of red oxide primer including all fixing acessories i.e. suitable size of hinge, nuts, bolts, washers, cutting and welding works etc complete all as directed by Engr -in-charge
54Supply and fix in replacement Digital VAF+PF meter with RS 485 CL1 in LT panel including taking out old existing unserviceable meter from panels etc complete all as directed
55Supply and fix in replacement of LED indication lampincluding taking down old unserviceable LED indication lamp from LT panel complete as specified and directed.
56Material & Labour for preparation old painted steel surface of LT tubular pole pole 9 meter long above coping, including MS clamp and applying two coat of aluminium paint, making of strip of 300 mm width (balck and yellow in alternate band) upto 1500 mm height with one synthetic enamel paint, rewriting pole No with stencil with white colour in black background with synthetic enamel paint, complete all as specifeid and directed.
57M&L for preparation of old painted surface of LT panel by scrapping, making good distrubed surfaces by applying putties on uneven surface to make it even and M&L for spray painting to LT panel of any size with two coat of synthetic enamel paint with desired colour complete all as specified and directed.
58Material and labour disconnecting faulty / burnt end or portion of cable from LT panel / LT pole / main switch / changeover etc by removing the cable from loop including necessary excavation & earth work, cleaning the surface area not less than 1 mtr surrounding the panel / pole, provision of suitable size of thimble, LT tap, relaying and reconnecting the cable by removing faulty / burnt portion of cable and preparing fresh terminals for 16 Sqmm 3.5/4 core to 240 Sqmm3.5 core of LT cable toLT Panel / pole / main switch / changeover complete all as directed.
59Supply and fix in replacement 15 Watt LEDPost Toplanterns housing made of Die-cast aluminum spigot for mounting LED driver and spun aluminum canopy, epoxy powder coated matt black finish after phosphochromate treatment, high quality polycarbonate cover is used over LED moudule to enhance the lumen output & clear acrylic diffuser is used to provide overall glare free light , Powered by electronic integral , isolated poted electronic LED driver in ABS housing with APFC (SMPS based constanct current supply) with lower THD , output short/open circuit protection , Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec-13 , IP 65 ,Lumen efficiency not less than 98 lumen per wattsystem efficency, power factor >0.95, THD<10% at Full load CRI> 70%
60All as per item No 59 above but 25 WattLED Post Toplanterns but Lumen efficiency not less than 100 lumen per wattsystem efficency
61Supplying and fixing in replacement8 Watt Bamboo LED bollard fitting of 1 meter heightnew generation , energy saving , enviornmental friendly , long life aesthetically designed aluminium landscape IP 65 luminaire for diffused lighting with high power LED as light souce housing made up of aluminium pipe UV protected pure polyester powder coated black after phosphochromate treatmentit consists of aluminum heat sink for effective thermal management , sturdiness & excellent corrosion resistantmounting flange of MS sand casting is used at bottomPC diffuser in opal finish is used for glare free uniform light distribution powered by built in , isolated , potted electronic LED driver in ABS housing with APFC (SMPS based constant current supply) with lower THD , output short/open circuit protection , over voltage protection , Surge voltage protectionLumen efficiency not less than 110 lumen per wattsystem efficency ,power factor >0.95, THD<10% at Full load CRI> 70%
62Supply, installing, testing and commissioning in replacementfactory made, CPRI approved LT Panel board (Dimention of Cubical / enclosure not less than 1200 mm x 900 mm x 500mm), confirming to IS 5039, cubical compartmentalized, out door type double door, plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 HzAC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain / SMC insulator. The panel shall be dust and vermin proofIP-54 class protection and outer shell made of of 3.15 mm CRCA MS sheet, inner shell made of 2.0 mm thick CRCA MS sheet , 50x50x6mm thick MS angle iron frame work, the cubical have bottom channel of size 75x40mm, panel shall be over all powder coated with zink metal coating, front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked,1100 volts grade of appropriate size ( but not less than 2.5 Sqmm)and comprising of the following:-
63(a) Incoming :- (i)MCCB 4 pole ,250Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos (ii) Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTsratio 250/5 A ,class 1, ISI marked -01 sets of three (iv)Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 500 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i)MCCB 4 pole ,100Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 04 Nos
64(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class "B", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The platform shall be such that it is of a height 45 cm above the nearest road level. Note :- (i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
65All as per item No62 above but comprising with following:- (a) Incoming :- (i)MCCB 4 pole , 250Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos (ii)Digital VAF+PF meter with RS 485 CL1 -01No (iii)CTsratio 250/5 A ,class 1, ISI marked -01 sets of three (iv) Indicating lamp- 01 set of three (v)Four Pole , Aluminium bus bar 500 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 160Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 01 Nos (ii)MCCB 4 pole , 125Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 02 Nos
66All as per item No62 above but comprising with following:- (a) Incoming :- (i) MCCB 4 pole , 250Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos (ii)On load change over switch open execution type , 250 Amps , 4 pole , 415 volt , 50 Hz-01 No (iii) Digital VAF+PF meter with RS 485 CL1 -01No (iv) CTsratio 250/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three (vi)Four Pole , Aluminium bus bar 500 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 125Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 03 Nos
67All as per item No62 above but comprising with following:- (a) Incoming :- (i)MCCB 4 pole , 400Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos (ii)Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTsratio 400/5 A ,class 1, ISI marked -01 sets of three (iv)Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 800 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i)MCCB 4 pole , 200Amps,50 Hz,415 Volts, 36 KA thermal magnetic release- 01 Nos (ii) MCCB 4 pole , 160Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 01 Nos (iii)MCCB 4 pole ,100 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 05 Nos
68Supply & fixing in replacementautomatic street light timer panel 12 KW / 40 Amp switch using Infrared Sensor basedfor automatic switching of street lights based on LUX level of natural light. Required illuminance for switching ON is < 30 Lux and for switching OFF > 10 Lux level. The sensor (nature switch) alongwith suitable power contactors, Input (supply) MCB and output (load) MCB(s), support terminals should be enclosed in pole/ wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR graded SMC junction box conforming to IP-54 degree of ingress three phase 8 KW lightening load capacity including mounting bracket, cable glands, openable doors with lock complete all as specified & directed by Engr-in-Charge.
69Supplying and fixing in replacement out door type busbar panel board (Dimention of Cubical / enclosure not less than 600 mm x 450 mm x 450 mm) made out of3.15 mm thick MS sheet and MS angle section 50x50x6 mm factory made suitable for 3 phase 4 wire 415 Volt, 50 Hz, powder coat painted comprising of the following:- (a)FP, Aluminium bus bar 500 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Incoming MCCB 160 Amps 25 KA, 415 Vots, 50 Hz, FP.– 1 No (c)LED Indicator lamp RYB - 01 set of three.
70(d) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class "B", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The platform shall be such that it is of a height 45 cm above the nearest road level. Note :- (i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
71Supplying and fix in replacement 3 pole power contractor AC 3 rating 40 Amp, 240 Volt AC complete all as specified and directed by Engr-in charge.
72Supplying and fixing in replacement Astronomical Digital Timer Switch240 V AC complete all as specified and directed by Engr-in charge
73S&F in replacement outdoor luminaries post made of50 mm bore mild steel galvanised pipe (medium grade with necessary accessories, including erect in vertical position complete all as specified and directed. Note Post hole &PCC in foundation shall be measured and paid in separately under respective item of schedule.
74Material and labour for PCC1:2:4 type B1 using 20 mm graded stone aggregates for making of foundation of post of oudoor luminaries complete all as specified and as directed by Engineer-in-Charge.
75Excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm complete.
76Deployment of manpower / tools / machinery etc for testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 1100 Volt LT cables of differentsizesfrom both ends, removal of Fault,Re-connections and testing of cables after removal of fault complete all as specified and directed.
77Note: (a)1100 Volt LT cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Retrieved old serviceable cable cover/brickswill be laid in trenches for cable protection. If extra PCC cover/bricks and sand required at site shall be measured and paid separately under respective items of BOQs. (c) Excavation and earth work will be measured and paid for seperately under respective items of schedule. (d) Note:-Contractor or his rep shall come to the site of breakdown within one hour of notification of breakdown .In case the rep or contractor shall not come to the site of breakdown and start attending breakdown within 1.00 hour a penalty of Rs 1000 per fault per hour will be imposed over contractor and will be deduct from his dues.
78Supply and fixing in replacement 60 W LED street light fitting with mandatory driver set having pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embaded PC cover /IP lens, street lightshould haveIP 66 protection, impact resistance ofIK 07 , Lumen efficiency of LED not less than 110 lumen per wattsystem efficency ,power factor >0.95, THD<10% at Full load CRI> 70% ,street light should have built in potted electronic LED driver with , lower THD, open circuit protection , over voltage protection , surge voltage protection ,andprovided with company LOGO ingraved on housing of the street lightcomplete including taking down of oldUNSV fittings all as specified and directed by Engr -in-Charge. Note :-The contractor shouldtake approval of techincal specification ofluminaries and driver from department before procurement .
79Supply and fixing in replacement of 200 W LED flood fitting having epoxy powder coated die cast aluminium housing ADC12 in grey finish with elegantly designed heat sink for efficient thermal management , sturdiness & excellent corrosion resistant. PG9 gland is used for cable entry and provision for loopin -loopout , PC lens/IP lens with narrow /wide beam distribution and toughened glass fixed to housing withscrews, floodlightshould haveIP 66 protectionand impact resistance ofIK 07 , Lumen efficiency of LED not less than 120 lumen per wattsystem efficency ,power factor >0.95, THD<10% at Full load CRI> 70% ,flood light should have built in pottedelectronic LED driver with , lower THD, open circuit protection , over voltage protection , surge voltage protection ,andprovided with company LOGO ingraved on housing of the floodlightcomplete including taking down of oldUNSV fittings all as specified and directed by Engr -in-Charge. Note :-The contractor should take approval of techincal specification ofluminaries and driver from department before procurement .
80All as per itemSer No75above but 120 Watt & system Lumen efficiency of light fitting not less than 110 lumen per watt.
81All as per itemSer No75above but 100 Watt & system Lumen efficiency of light fitting not less than 110 lumen per watt.
82All as per itemSer No75above but 50 Watt & system Lumen efficiency of light fitting not less than 110 lumen per watt.
83Supply and errectionin replacement07 mtr continuously tapered hot dip galvanised Octagonal cross sectional pole with single dipping method having bottom 130 mm A/F and top 70 mm A/F 3 mm thick confirming to ASTM A 572 Gr with yield 450mpa cut and folded to form an octagonal section and welded in accordance with AWS for wind loading as per IS 875 part 3 1987.Poles shall be provided with base plate of size 225x225x12 mm which shall be free from any lamination or incursion with no cutting or welding on the pole after hot dip galvanising with single arm 1000 mm long bracket tilted to 150 degree from horizontal toward vertices suitable for mounting on the octagonal pole, of company recommendationand one no TPN Connecton 3 phase 4 wire 100 Amps, and one number MCB SP 6 Amps. A triangular flat MS plat of 6mm thick duly coated with GI shall be welded between cap of the octagonal pole and bracket. Welding work shall be done 250mm on bracket and 150 mm on pole"s cap including all RCC work type (1:2:4) type B-1 including 04 Nos foundation nut bolt and plate as per pole manufacturer"s drawing and earth work all as per requirement complete all as specified and directed. Note Cost of construction of RCC foundation including construction material, necessary earth work and excavatonas per manufacturer design forabove polecompleteall as required at site and as directed by Engr-in-charge are deemed to be included in the quoted rate.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail