| 1 | Disconnecting the existing LT UG cable of any size and taking out the damaged electric UG cable from trenches all as specified and directed by Engr-in-chargeNote : earth work shall be measure and paid separately. |
| 2 | Supply, lay andtesting XLPE, insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 sqmm, 2 core cross sectional area laid in trenches/ poles/ ducts/ pipes or through sleeves etc., including connecting/ jointing with lugs complete all as specified and directed by Engr-in-Charge. |
| 3 | Supply, lay andtesting XLPE, insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 16 sqmm, 2 core cross sectional area laid in trenches/ poles/ ducts/ pipes or through sleeves etc., including connecting/ jointing with lugs complete all as specified and directed by Engr-in-Charge. |
| 4 | Supply, lay andtesting XLPE, insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 16 sqmm, 4 core cross sectional area laid in trenches/ poles/ ducts/ pipes or through sleeves etc., including connecting/ jointing with lugs complete all as specified and directed by Engr-in-Charge. |
| 5 | Supply, lay andtesting XLPE, insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 sqmm, 4 core cross sectional area laid in trenches/ poles/ ducts/ pipes or through sleeves etc., including connecting/ jointing with lugs complete all as specified and directed by Engr-in-Charge. |
| 6 | Supply, lay andtesting XLPE, insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 sqmm, 3.5 core cross sectional area laid in trenches/ poles/ ducts/ pipes or through sleeves etc., including connecting/ jointing with lugs complete all as specified and directed by Engr-in-Charge. |
| 7 | Supply, lay andtesting XLPE, insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 70 sqmm, 3.5 core cross sectional area laid in trenches/ poles/ ducts/ pipes or through sleeves etc., including connecting/ jointing with lugs complete all as specified and directed by Engr-in-Charge. |
| 8 | Supply, lay andtesting XLPE, insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 95 sqmm, 3.5 core cross sectional area laid in trenches/ poles/ ducts/ pipes or through sleeves etc., including connecting/ jointing with lugs complete all as specified and directed by Engr-in-Charge. |
| 9 | Supply, lay andtesting XLPE, insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 120 sqmm, 3.5 core cross sectional area laid in trenches/ poles/ ducts/ pipes or through sleeves etc., including connecting/ jointing with lugs complete all as specified and directed by Engr-in-Charge. |
| 10 | Supply and fix road lighting (security light) luminaires, 90 watts high power LED with unique peanut lens for uniform distribution, higher spacing between poles, maintanance free system for long life ,fixing it in bracket and connecting it with pole mounted junction box or to the conductor with 6sqmm 2core aluminum conductor all as directed by Engr-in-Charge. |
| 11 | Supply & fix in repair FRP junction box Size,IP-65, weatherproof outside dimension 155x210x92 mm,IP65 protection alongwith suitable aluminium bus bar upto size of cable120sqmm , as incoming and outgoing provn for cable with MS angle/clamp , nut bolts suitable for pole or ground etc including PCC foundation all as specified and directed by Engr-in-Charge |
| 12 | Excavation in trenches in soft/loose soil not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth and getting out for laying of pipe cables etc,. and getting out complete all as specified and directed |
| 13 | Returing filling in, including spreading levelling, watering and well ramming in layers not exceeding 25cm thick withearth obtained from excavation complete all as specified and as directed. |
| 14 | Removal of surplus excavated soil to a distance n. exc. 50 m and depositing where directed at a level n. exc. 1.5 m above starting point complete, all as specified and directed by Engr-in-Charge. |
| 15 | Material and labour for dry river washed and screened dry sand for filling in trenches/ ground 8cm thick before laying of cable and 15 cm thock after laying of cable, stretching and testing the cable complete all as specified and directed. Note:- Punned thickness shall only be measured and paid. |
| 16 | Supplying and laying un-reinforced precast concrete cable cover, class LV , type 1 , size 250mm x 150mm x 40mm complete , all as specified and directed by Engr-in-charge. |
| 17 | Supply and fix light grade galvanisediron tube 40 mm bore with all fittings and fixed to walls / ceiling or laid in floor, pole or laid in trenches and road crossings including sealing ends with hession cloth impregnated with bituminous compound in ground and with teak wood bushes for ends fixed with walls / poles complete all as specified and as directed. |
| 18 | Supply and fix light grade galvanisediron tube 50 mm bore with all fittings and fixed to walls / ceiling or laid in floor, pole or laid in trenches and road crossings including sealing ends with hession cloth impregnated with bituminous compound in ground and with teak wood bushes for ends fixed with walls / poles complete all as specified and as directed. |
| 19 | Supply and fix light grade galvanisediron tube 80 mm bore with all fittings and fixed to walls / ceiling or laid in floor, pole or laid in trenches and road crossings including sealing ends with hession cloth impregnated with bituminous compound in ground and with teak wood bushes for ends fixed with walls / poles complete all as specified and as directed. |
| 20 | M and Labour for painting of Transformers, with one coat of epoxy coated paint suitable for all seasons, dismantling all cables before proceedings for work, cleaning all parts and refixing the same after the painting, connecting all cables with suitable lugs all as per required and directed by engr in charge. |
| 21 | Supply and fix feeder pillar sheet metal box outdoor type, aluminium bus bar with proper rating and incoming and outgoing arrangements, 500mmheight from ground, and suitable forconnecting 2/3.5/4 core aluminum conductor with proper grouting arrangement. |
| 22 | Supply and lay loose filling aggregate 40 mm size in installations ,after removing the vegetation from the area about 10cm below ground level and spraying one layer of crushed stone and sand mixture, including leveling of ground before laying and after laying of aggregate in layer all as specified and directed by Engr-in-Charge |
| 23 | Material and labour for providing earthing for steel tebular pole complete with galvanised steel earth pleate electrode 600x600x6mm thick buried directly in ground earth pit not less than 2.25 mtr deep below ground level with top edge of the plate not less than 1.5mtr below normal ground level) connected to galvanised iron earth strip 32x6mm as earthing lead by means of bolts, nuts, check nuts & washers of GI or steel and connecting to earth dolly all as shown in electrical plate No 3 connected to earth test point all as specified and indicated including testing on complete all as specified and directed.Note:- Earth continuity conductor and GI protection pipe beyond 7.5m shall be measured and paid under the respective items. |
| 24 | M & L for earth continuity conductor using GI strip 32 x 6 mm as earthing lead complete all as directed incl taking down the old unserviceable completeall as specified and directed. |
| 25 | Supply and fixin repairs MCCB, 4 pole, adjustable type, front operated with two suitable position, 200 amps, 50 Hz, 415 volts with rupturing capacity 35 KA. |
| 26 | Supply and fix in repairs MCCB, 4 pole, adjustable type, front operated with two suitable position, 100 amps, 50 Hz, 415 volts with rupturing capacity 35 KA. |
| 27 | M & L Shifting of floor mounted cubical type double door LT distribution panel board including all fittingwith any type repair/ damage if required within 900mtr distanceand install at site and allincoming and outgoing connection for electric supplywith PCC (1:4:8) type D2using 40mm graded crushed stone aggregate as in foundationfilling and mass concrete etc including excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and removal of surplus excavated soil to a distance n. exc 50m complete all as specified and directed by Engr-in-Charge. |
| 28 | Total contract sum shall be calculated after deduction of schedule of credit amount of Rs. 21,800.00 |