Tender For Repair Replacement And Maintenance Of External Distribution System Replacement Of Ug Cable Lt Panels And Other Connected Works Under Aor Of Age Em Ii Of Ge 865 Ews, Leh-Jammu And Kashmir

Military Engineer Services-MES has published Tender For Repair Replacement And Maintenance Of External Distribution System Replacement Of Ug Cable Lt Panels And Other Connected Works Under Aor Of Age Em Ii Of Ge 865 Ews. Submission Date for this Tender is 22-04-2024. Power Supply Unit Tenders in Leh Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

43085485
Tender For Repair Replacement And Maintenance Of External Distribution System Replacement Of Ug Cable Lt Panels And Other Connected Works Under Aor Of Age Em Ii Of Ge 865 Ews
Open Tender
Indian
Jammu And Kashmir
Leh
22-04-2024

Tender Details

Tender For Repair Replacement And Maintenance Of External Distribution System Replacement Of Ug Cable Lt Panels And Other Connected Works Under Aor Of Age Em Ii Of Ge 865 Ews

Key Value

Document Fees
INR 500 /-
EMD
INR 80000.0 /-
Tender Value
INR 40 Lakhs /-

BOQ Items

Name of Work: REPAIR/ REPLACEMENT AND MAINT OF EXTERNAL DISTRIBUTION SYSTEM , REPLACEMENT OF UG CABLE , LT PANELS AND OTHER CONNECTED WORKS UNDER AOR OF AGE E/M -II OF GE 865 EWS
Sl. No. Item Description
1Dismantling of ACSR or AAC conductors complete all as specified and directed by Engr-in-Charge
2M&L for Supply and installation,Over head, aluminium conductor, steel reinforced, weasel, including making connections and fixing on poles with all necessary arrangements, complete all as specified and as directed by Engineer-In-Charge. Note: Weight of ACSR or all aluminium conductors drawn for overhead lines is to be determined by measuring taut horizontal distance between centers of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra added for sag, jointing, jumpers, etc.
3Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting aside for re-use with in 50m complete all as specified and directed by Engr-in-Charge.
4M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint, complete all as specified and as directed by Engineer-In-Charge.
5Dismantling stay assembly complete all as specified and directed by Engr-in-Charge.
6M&L for Stay assembly complete with accessories as shown in electrical plate No. 1 (Excavation and concrete measured separately) Complete all as specified and directed by Engr-in-Charge.
7Taking down old unserviceable LT underground cable any type and any size complete all as specified and directed by Engr-in-Charge.
8Excavation in trenches not exc. 1.5m wide and not exc. 1.5m in depth, for foundation etc. or for shafts, welles cesspitsm, manholes, pier holes, etc. n exc 10 sqm on plan and n exc 1.5m in depthe in hard/dense soil and getting out , complete all as specified and as directed.
9Returning, filling in (soil), including spreading, leveling, watering and well ramming in layers not exc. 25m, complete all as specified and directed by Engr in Charge.
10Removing excavated material to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the stratingpoint, complete all as specified and directed by Engr in Charge.
11Sand cushioning to underground cables 8 cm below the cable before laying & 15 cm above the cable after laying, complete all as specified in clause 19.75 of SSR Par-I, complete all as specified and directed by Engr in Charge. Note :- Punned thickness shall be measured & paid
12Replacement of factory made, machine pressed, unreinforced, pre-cast concrete cable cover class LV type-I flate size 250 x 150x40mm , complete all as specified and directed by Engr in Charge.
13Supply and fixing cable route indicator made out cast iron and embedded LTCable on the plate of size 80 mm dia 5 mm thick and gouting lugg of suitable size including gouted in PCC foundation of suitable size complete all as directed and directed by Engr in Charge.
14Supply and fix in repair Indicator lamp LED type (Red,Yellow, green) moulded single piece suitable for LT Panels after taking out the Old U/S indicator lamp and directed by Engr in Charge.
15Supplying, laying, jointing and testing underground cable PVC XLPE insulated armoured and PVC sheathed LT 1100 volts grade (heavy duty) with aluminium conductor 2 core, 16 Sqmm, confirming to IS-1554, laid in ducts/through pipes, in floor, on poles, in trenches complete all as specified and directed by Engr in Charge. Note :- Clamps, GI pipes, excavation, earth work, sand cushioning and brick protection cover shall be measured and paid for separately.
16Description all as per sl item no 15 but of size 16 Sqmm 4 core.
17Descriptionall as per sl item no 15 but of size 25 Sqmm 3.5 core.
18Description all as per sl item no 15 but of size 35 Sqmm 3.5 core.
19Description all as per sl item no 15 but of size 50 Sqmm 3.5 core.
20Descriptionall as per sl item no 15 but of size 70 Sqmm 3.5 core.
21Description all as per sl item no 15 but of size 120 Sqmm 3.5 core.
22Description all as per sl item no 15 but of size 240 Sqmm 3.5 core.
23Dismantling / Taking down of Old broken LT Danger notice Plate of any size complete all as specified and directed.
24Supply and fixingDanger notice Plate of 1.6 mm thick mild steel sheet , vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS Clamps , bolts and nuts of approved size, for LT ,20x15 CM size and directed by Engr in Charge.
25Taking down Old U/S MCCB of any type and any capacity compplete all as specified and directed by Engr in Charge.
26Supply and fix in replacement MCCB 630 Amps current carrying capacity 50 KA, 3 pole AC, 415 Volts with thermal & adjustable magnetic setting complete all as specified and directed by Engr in Charge.
27Supply and fix in replacement MCCB 630 Amps current carrying capacity 50 KA, 4 pole AC, 415 Voltswith thermal & adjustable magnetic setting complete all as specifiedand directed by Engr in Charge.
28Supply and fix in replacement MCCB 500 Amps current carrying capacity 36 KA, 4 pole AC, 415 Volts with thermal & adjustable magnetic setting complete all as specifiedand directed by Engr in Charge.
29Supply and fix in replacement MCCB 400 Amps current carrying capacity 36 KA, 4 pole AC, 415 Volts with thermal & adjustable magnetic setting complete all as specified and directed by Engr in Charge.
30Supply and fix in replacementMCCB 350 Amp 4 Pole of rupturing capacity 36 KA complete all as specified and directed by Engr in Charge.
31Material and Labour for painting of LT Panels including cleaning of exposed surface with brush and empry paper including painting with smoke grey paint all as directed any size of LT Panels complete all as specified and directed by Engr in Charge.
32M&L for prepration of old Steel Surfaces and applying two coat of synthetic enamel white paint to LT Steel tubular /PCC Pole and upto 1 Mtr height from ground level alternative in Yellow and black or white and black strips of 30 CM height each including numbering of Pole No with black paint complete all as specified and directed by Engr in charge.
33Supplying & fixing in replacement mild steel galvanized pipe light grade 80 mm nominal bore for passing of cable fixed to poles/walls/laid under floor/roads complete with and including, fittings as requited all as specified and directed by Engr in charge.
34Supplying & fixing in replacement mild steel galvanized pipe light grade 50 mm nominal bore for passing of cable fixed to poles/walls/laid under floor/roads complete with and including, fittings as requited all as specified and directed by Engr in Charge.
35Supplying & fixing in replacement mild steel galvanized pipe light grade 40 mm nominal bore for passing of cable fixed to poles/walls/laid under floor/roads complete with and including, fittings as requited all as specified and directed by Engr in Charge.
36Dismantling insulators any type and any size complete all as specified and directed by Engr charge.
37M&L forPin type, porcelain,vitreous, white, green & brown insulator including one galvanised iron steel spindle, two galvanized iron washer and one galvanised iron nut, working pressure 1100 Volts and of size 65 mm dia and 100 mmheightISI marked complete all as specified and directed by Engr in charge.
38M&L for shackle type, porcelain,vitreous, white, green & brown insulator including one galvanised iron steel spindle, two galvanized iron washer and one galvanised iron nut, working pressure 1100 Volts and of size 115 mm dia and 100 mm height ISI marked complete all as specified and directed by Engr in charge.
39Material & labour for earthing with Galvanised Steel earth plate electrode 60cmx 60cm x 6.3mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer ofcharcoal dust and common salt filling in alternate layers and electrode connections by usingGalvanised Iron strip of 32 x 6mmas earthing lead(upto the body ofthe equipment) by means ofbolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40mm diaGI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6)type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type ofsoil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 ofSSR 2009 (Part-I)complete all as specified and directed.
40Supply and fix GI earthing strip of size 25x4 mm on PVC/Porcelain insulators at suitable distance with saddeles and fixing screws for roof/wall conductors and down conductors above ground all joints of GI strip should be brazed properly and directed by Engr in charge.
41M&L for Synthetic Insulating Mat for Electrical Instrument of size 2mx1mx10mm complete all as specified and directed by Engr in Charge.
42Supply and fix PVC Spacers 2/4 way for LT OH Line 1100 Volts grade with necessary screws nuts bolts etc complete all as specified and directed prevent the lines touching each other on heavy wind as a preventive arrangement to the existing system including removing the existing old/out lived spacers and directed by Engr in charge.
43Taking down Old U/S Change over switch of any size or any capacity complete all as specified and directed by Engr in Charge.
44Supply and replacement of ON Load Change over ( Front Handle) switch 415 Volt in sheet metal inclosure 4 Pole of capacity 1000 Amps with connecting acessories complete all as specified and directed by Engr in Charge.
45Supply and replacement of ON Load Change over ( Front Handle) switch 415 Volt in sheet metal inclosure 4 Pole of capacity 630 Amps with connecting acessories complete all as specified and directed by Engr in Charge.
46Supply and replacement of ON Load Change Change over (Front Handel) switch 415 Volt in sheet metal inclosure 4 Pole of capacity 400 Amps with connecting acessories complete all as specified and directed by Engr in Charge.
47Supply and replacement of ON Load Change over ( Front Handle) switch 415 Volt in sheet metal inclosure 4 Pole of capacity 125 Amps with connecting acessories complete all as specified and directed by Engr in Charge.
48Supply and replacement of ON Load Change over( Front Handle) switch 415 Volt in sheet metal inclosure 4 Pole of capacity 63 Amps with connecting acessories complete all as specified and directed by Engr in Charge.
49S&F in repalcementAluminium thimble of size 35/50/70/95 Sq mm complete all as spd and directed by Engr in Charge. .
50S&F in repalcement Aluminium thimble of size 120/150/185/240/400 Sq mm complete all as spd and directed by Engr in Charge.
51Supply and replacement of ON Load Change Change over ( Side Handel) switch 415 Volt in sheet metal inclosure 4 Pole of capacity 63 Amps with connecting acessories complete all as specified and directedby Engr in Charge.
52Supply and replacement of ON Load Change Change over ( Side Handel) switch 415 Volt in sheet metal inclosure 4 Pole of capacity 125 Amps with connecting acessories complete all as specified and directedby Engr in Charge.
53Supply and replacement of OFF Load Change Change over ( Side Handel) switch 415 Volt in sheet metal inclosure 4 Pole of capacity 125 Amps with connecting acessories complete all as specified and directedby Engr in Charge.
54Supply and replacement of OFF Load Change Change over ( Side Handel) switch 415 Volt in sheet metal inclosure 4 Pole of capacity 200 Amps with connecting acessories complete all as specified and directedby Engr in Charge.
55Supply and replacement of OFF Load Change Change over ( Side Handel) switch 415 Volt in sheet metal inclosure 4 Pole of capacity 320 Amps with connecting acessories complete all as specified and directedby Engr in Charge.
56Supply and replacement of OFF Load Change Change over ( Side Handel) switch 415 Volt in sheet metal inclosure 4 Pole of capacity 400 Amps with connecting acessories complete all as specified and directedby Engr in Charge.
57Supply and replacement of OFF Load Change over ( Side Handle) switch 415 Volt in sheet metal inclosure 4 Pole of capacity 630 Amps with connecting acessories complete all as specified and directed by Engr in Charge.
58Supply and replacement ofOFF LoadChange over ( Side Handle) switch 415 Volt in sheet metal inclosure 4 Pole of capacity 1000 Amps with connecting acessories complete all as specified and directed by Engr in Charge. .
59Supply and fix in replacement MCCB 63 Amp 4 Pole of rupturing capacity 25 KA complete all as specifiedand directed by Engr in Charge.
60Supply and fix inreplecement MCCB 100 Amp 4 Pole of rupturing capacity 16 KA complete all as specified and directed by Engr in Charge.
61Supply and fix inreplacement MCCB 125 Amp 4 Pole of rupturing capacity 16 KA complete all as specifiedand directed by Engr in Charge.
62Supply and fix in replacement MCCB 160 Amps current carrying capacity 36 KA, 4 pole AC, 415 Volts three pole with thermal & adjustable magnetic setting complete all as specifiedand directed by Engr in Charge.
63Supply and fix in replacement MCCB 200 Amps current carrying capacity 36 KA, 4 pole AC, 415 Volts three pole with thermal & adjustable magnetic setting complete all as specifiedand directed by Engr in Charge.
64M&L for PCC (1:3:6) type C-2 with 40 mm gradded stone aggregate for coping ofpoles Pedestal (PCC) or mass filling (CM 1:4) complete all as specified and directed by Engr in Charge.
65M & L for installing, testing and commissioning of factry made LT cubical panel board outdoor type free standing with double door made out of 3.15 mm thick CRCA sheet, dust and vermin proof , having locking arrangement at front and opening arrangement from front & rear both duly fitted with 600 Amp rated tinned copper busbar 4 strip covered with colour coded FRP with compression cable glands for entry & exit of cables, powder coated complete comprising of the following : - (A) INCOMING (i) MCCB 4 Pole 400 Amp, 50 Hz, 415 V with rupturing capacity 25 KA-01 No. (ii) On load Change over switch 4 pole, 250 Amp, open execution type - 01 No. (iii) Digital LED voltmeter 3 phase accuracy class 1 with selector switch - 01 Set. (iv) Digital LED ammeter 3 phase, 5 Amp accuracy class 1 with selector switch and 3 Nos CTs 400/5 Amp - 01 Set. (v) LED indicating lamps RYB- 01 set. (B) OUTGOING (I) MCCB 4 Pole 250 Amp, 50 Hz, 415 V with rupturing capacity 25 KA - 01 No. (ii) MCCB 4 Pole 160 Amp, 50 Hz, 415 V with rupturing capacity 25 KA - 01 No. (iii) MCCB 4 Pole 100 Amp, 50 Hz, 415 V with rupturing capacity 25 KA - 01 No. (iv) MCB SPN 20 Amp, 50 Hz, 230 V, "C" curve with rupturing capacity 10 KA - 01 No. (v) Space only for accomodating 4 pole MCCB upto 250 Amp 25 kA - 01 cubicle. (vi) Foundation for the panel should provided with PCC 1:4:6 at a depth of 150 mm below ground level and 100 mm above the ground level with slot openings fo I/C and O/G cables Note:-The structural and connection diagram of panel should be got approved by the AO before placing order to the panel manufacturer.
Disclaimer :