| Sl. No. | Item Description |
| 1 | Supply for New 33/11 KV Substation- SCADA Compatible asper technical specifications, scope of works and approved drawings |
| 2 | 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type PowerTransformer with off load tap charger ( completely field with oil) as per TS |
| 3 | 5 MVA Power Transformer |
| 4 | 10 MVA Power Transformer |
| 5 | 100 KVA, 11/0.415 kV, 3 ph, 50 Hz, ONAN,Aluminiumwound,(three star rated) CRGO core, outdoor typeStation Transformer Completely filled with transformer oil asper technical specifications. |
| 6 | MS Galvanised structures (all Type) made of joist / channel / angle / flat of different sections as per approved drawings. All structural steel members shall be galvanized after fabrication as per IS:4759 for all structural members. 3.5mm spring washers are to be used under each structural steel shall conform to IS 2026. All weld shall be 6mm filled weld unless specified otherwise.Anchor plat shall be of relevant IS |
| 7 | GI bolts & nuts, washers etc. (all Type) should be as per approved drawings & TS. All bolts & nuts, washers etc. shall be galvanizedas per IS:4759. 3.5mm spring washers are to be used under each nut shall conform to IS 2026.All nuts and bolts shall be of property class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063 and foundation bolts, shall be of relevant IS |
| 8 | 36kV, 1250A,25kA for 3 seconds, 3-ph, Outdoor typeVacuum Circuit breaker with marshalling box etc Complete in all respect along with support structure. |
| 9 | 36kV, 1-Phase, 25kA/3 seconds,800-400-200/1-1-1 Amps ( having 3 secondery, core), 1 set = 3 Nos outdoortype Current Transformers along with junction box (1 no junction box for 3 no of 1-phase CTs), as required as per technical specifications complete in all respect. |
| 10 | 36kV, indoor, Control & Relay panel alongwith E/F & O/C,Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other components etc. complete as per approved drawings & TS: |
| 11 | 33 kV feeder Panel (without diffirential relays) withDLMS(modem compactible ) Trivector Static Energy Meter complete |
| 12 | 33 kV Transformer Panel (withdiffirential relay and 5/1 A auxillary CT)withDLMS(modem compactible ) Trivector Static Energy Meter complete |
| 13 | 36kV, 800A, 25kA , 3-ph double break center rotating type (DBCR), Gang Operated,isolator alongwith Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete as per Technical Specifications. (with Earth Switch) |
| 14 | 36kV, 800A, 25kA , 3-ph double break center rotating type (DBCR), Gang Operated,isolator alongwith Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete as per technical specifications. (Without Earth Switch) |
| 15 | 30 kV, 10kA, 1-ph Station Class Lightening Arrester complete(1 set= 3 Nos.) |
| 16 | 9kV, 10kA, 1-ph Station Class LighteningArrester complete (1 Set = 3 Nos.) |
| 17 | 12 kV, 1250 A, 25kAfor 3 seconds, 3-ph, indoor typeVacuum Circuit BreakerforIncomer along with 12 kV, 1-Phase, 25kA, 600-300/5-5 A, 3 Nos indoor type Current Transformer 3 Core, Potential Transformer 11KV/110 V, indoor mounting type control panel for incoming breaker and required accessories, A-meter, volt-meter, 3-phase , withDLMS(modem compactible ) Tri Vector energy meter, Numerical Relays & accessories complete as per specifications for transformer breaker protectionwith earth fault, overcurrent . |
| 18 | 12 kV, 1250 A, 25kAfor 3 seconds, 3-ph, indoor typeVacuum Circuit Breakerforalong with 12 kV, 1-Phase, 25kA, 600-300/5-5 A,3 Nos indoor type Current Transformer, control panel for Bus couplar and required accessories, A-meter, Numerical Relays & accessories complete as per specifications for Bus Coupler protectionwith earth fault, overcurrent . |
| 19 | 12 KV 3 Ph 1250 A, 25kAfor 3 seconds, 3-ph, indoor typeVacuum Circuitbreaker along with 12 kV, 1-Phase, 25kA, 400-200/5-5 A,3 Nos indoor type CurrentTransformer,indoor mounting type control panel for feeder protection and required accessories, A-meter, Numerical Relay & accessories complete as perspecifications for feeder breaker protection & Protection for Earth fault and over current) with extensible arrangement for future |
| 20 | 24V, 150 AHPb(Lead) Acid battery, battery standmade of teakwood duly painted with anti acid resistive paint, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single coremulti strand cable, terminal connectors, Rubber mats & all other accessories and connectors as per technical specifications. |
| 21 | 24V, 150 AH.Float-cum-Boost Battery Charger with full wave rectification for230V,1 phase, 50 Hz AC Input Supply as per technical specifications. |
| 22 | 24V DCDB complete in all respect suitable for 20 nos.of DC circuit for smooth operation of DC supplyas per technical specifications. |
| 23 | 415V, ACDBalongwiththree phase-neutral voltmeter,three phase ammeter andSelector switches, 200 Amps TPNswitch fuse unit as incomer, 32 Amps TPN switches as outgoing feeders suited for number of control panels, nos of VCB kiosk panel, having20% spare outgoing feeders, mountingarrangements etc as pertechnical specifications. |
| 24 | ACSR Panther Conductor for Bus-Bars & Jumpers/Droppers/Terminations |
| 25 | Earthing & Grounding conductor as per Approved Electrical Layoutfor each sub- station with |
| 26 | 75 x 8 mm GI flat. |
| 27 | 50 x 6 mm GI flat. |
| 28 | 25 mm dia MS rod 6 m long for earth mat |
| 29 | 40 mm dia.,3000 mm long GI pipe earthelectrode as per Technical Specification |
| 30 | 33 KV and 11 KV Insulator - Pin, Post and Disc insulators along with G.I. Pin, Hardware & Accessories suitable for Panther conductors as per Technical secifications. |
| 31 | 33 KV Post Insulator (1 Set = 2 Nos of 22 KV) |
| 32 | 33 KV Disc InsulatorInsulator(1 Set = 4 Nos Disc Insulator 70 KN) |
| 33 | Hardware fitting for 33 KV Disc Insulator (B&S Type 70 KN) |
| 34 | 33 KV Polymer Pin Insulator with Pin |
| 35 | Bimetalic Clamps , Al. Connectors, Al. tape etc. complete in all respect as required. |
| 36 | Station Lighting System (External) 120 Watt, LEDwith proper illuminationcomplete for switchyard,main gate and sub-station boundry including all associated materials such as insulated wires, cables, boards, switches and fixing arrangements etc. all complte as per applicable TS and approved drawing. (minimum 8 nos on Lighting Poles & 8 nos on structure & control room ) |
| 37 | Station Lighting System (internal) with proper illumination complete forcontrol room building, Incharge room, Battery room, Store room, Washroom, Guard room, portico etc.including all associated materials such as insulated wires, cables, boards, switches and fixing arrangements etc.and Celling, wall Fan & exhast fan (Total 8 nos.) all complte as per applicable TS and approved drawing. |
| 38 | Tool & Plant: Gum Boot- 2 pair, Hand Gloves- 2 pair, Insulated Plier- 2 nos., D E spanner set- 2 sets, Slide range 8\" & 12\" 2 nos each, Torch (Flash Light) 4 cell- 2 nos, Earth megger- 1 no, Insulation Megger (hand operated) 1000 V-1 no, Tong Tester (Digital)- 1 no, Discharge Rod (1 Set=3 Nos)- 6 Sets, Rubber mat (1.25\" Thick) for laying in front of all panels in control room completely |
| 39 | Fire Fighting Equipment comprises of Dry Chemical Powder Type(6 Kg) for controlroom, CO 2 Type of 4.5Kg Capacity for Control Room,CO2 type Trolly mounted of 22.5 KG Capacity for Switch Yard, four nos.of fire buckets set including their stand as per technical specifications, scope of works and approved drawings |
| 40 | All types control cable and LT power cable required with all accessories complete for the commissioning of sub-station as per TS |
| 41 | LT power cable 3.5C x 95 sq. mm. |
| 42 | LT control cable 4X2.5 sqmm size Complete in all respect as per site requirement complete with lugs etc. |
| 43 | LT control cable 2X2.5 sqmm size Complete in all respect as per site requirement complete with lugs etc. |
| 44 | 11 kV, 3-ph, 200 A, 3 Pin type, Vertical Mounting type, Gang Operated,TPMO Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete asper technical specifications, scope of works and approved drawings |
| 45 | 36 kV, 1-Phase, 33kV/110 volt, Single coreoutdoor type Potential Transformer including accessories etc., complete as per technical specifications.( 1 set=3 no) |
| 46 | Design, engineering and supply of Fully automatic Capacitor bank with automatic control panel, isolator,indoor type suitable Vacuum Circuit Breaker, mounting structures, All types of cable (11 KV grade 185 sqmm, XLPE & control cable etc.) & its accessoriescomplete , earthing etc as required as per technical specifications, approved drawings, scope of the works of following capacities: |
| 47 | 1980 KVAR |
| 48 | 3960 KVAR |
| 49 | 11 KV, XLPE, Power cable, aluminiumconductor, stranded |
| 50 | 3Cx 400 sqmm (armoured) |
| 51 | 3Cx 185 sqmm (armoured) |
| 52 | 3Cx35 Sqmm (Un -armoured) |
| 53 | Cable termination kit suitable for termination in transformer cable box/breaker panel/ outdoor 11 KV terminals complete with all accessories etc. (1 Set= 1 Indoor+1 Outdoor) |
| 54 | 3Cx 400 sqmm |
| 55 | 3Cx 185 sqmm |
| 56 | 3Cx35 Sqmm |
| 57 | 11 KV TPMO as per technical specifications |
| 58 | Supply of 8.5 meter long /180 KG PCC Poles (PCC Pole as per state practice) |
| 59 | Supply of Pole accessories as per technical specification, approved drawing and scope of work |
| 60 | Supply of 11 KV danger board |
| 61 | Stone Pad(300x300x75mm) |
| 62 | Supply of GI Barbed wire 12 SWG |
| 63 | Supply of GI Earthing spike made of 20x2500mmsolid Rod |
| 64 | Supply of 8 SWG GI wire |
| 65 | Furniture items as required |
| 66 | Office table Godrej make |
| 67 | Office chair Godrej make |
| 68 | Godrej Storwel (Almirah) standard size. |
| 69 | Supply for New 33/11 KV Indoor GIS Type Substation- SCADA Compatible asper technical specifications, scope of works and approved drawings |
| 70 | Supply of 10 MVA 33/11 kV Transformer with all complete assesories as per TS |
| 71 | Supply of 33 KV GIS Panels with 2 line bays, 2 transformer bays, one bus coupler bay, Bus PT, all complete with numerical relays, facility for data transmission and remote control this includes PT raiser panel etc. if required. |
| 72 | Supply of 11 KV GIS Panels with 6 line bays, 2 transformer bays, 1 station transformer bay & one bus coupler bay, Bus PT, all complete with numerical relays, facility for data transmission and remote control this includes PT raiser panel etc. if required. PT required for each of the bus section. |
| 73 | Supply of 24 V, 150AH, Ni-Cd sealed type battery set and all other accessories complete. |
| 74 | Supply of Float-cum-boost battery charger (SMPS based ) with full wave , full control rectification, 50Hz input voltage for charging 24V, 150 AH Battery alongwith DCDB, connectors etc. complete and connection with 24 V , 80AH Battery set and single phase AC input supply. |
| 75 | Supply of 415V AC Distribution Board/Panel of sheet stealenclosed cubical floor mounting type for catering auxiliary power supply of the substaion etc. complete |
| 76 | Supply of 100KVA, 11 kV/0.415 kv Station Transformer alongwith allaccessories as per TS. |
| 77 | Supply of40mm dia 3000mm long GI Pipe (Medium Grade) earth electrodes & other accessories for treated earth erection is including of Excavation and other associated activities as per TS. |
| 78 | Supply of 60x8 mm Galvanized flat for raiser for earthing as per TS |
| 79 | Suplly of 30 KV, 1 Phase, 10KA LA with all accessories as per TS. |
| 80 | Suplly of 9 KV, 1 Phase, 10KA LA with all accessories as per TS. |
| 81 | Supllyof 3Cx300 sqmm. 33 KV cable (Panel to Transformer- 1 Run) with cable tray. |
| 82 | Supllyof 3Cx400 sqmm. 11 KV cable (Panel to Transformer- 2 Run) with cable tray. |
| 83 | Supllyof Control Cable of 2 core 2.5 sq. mm copper cable with cable tray and associated items |
| 84 | Supllyof Control Cable of 4 core 2.5 sq. mm copper cable with cable tray associated items |
| 85 | Supllyof Control Cable of 10 core 2.5 sq. mm copper cable with cable tray associated items |
| 86 | Supply of sand bucket stand with 4 Nos. buckets. |
| 87 | Supply of CO2 cylinder 4 nos of 4.5 kgs supply and fixing of CO2 type fire extinguishers capacity confirming to IS 2878 made ISI mark (1 set) |
| 88 | Supply of ISI make ABC Power MAP 2 kg Fire extinguisher Mono ammonium phosphate power 50, stored pressure type, complete with pressure guage and all accessories applicable on class A,B,C electrically started fier as per building SSR. |
| 89 | Supply of Synthetic Rubber mats as per IS 15652 in control room 2.5 mm thik |
| 90 | Supplyof 33 kV Silicon coated touchproof Indoor termination joint (Al) kit for XLPE 3 C X 300 sqmm |
| 91 | Supplyof 11 kV Silicon coated touchproof Indoor termination joint (Al) kit for XLPE 3 C X 400 sqmm(Incoming) |
| 92 | Supplyof 11KV XLPE Cable (3x400 Sq.mm.)outdoor Heat Shrinkable Termination kit boxes mounted with transformer. |
| 93 | Supplyof 11 kV Silicon coated touchproof Indoor termination joint (Al) kit for XLPE 3 C X 185 sqmm |
| 94 | Suplly of Complete lighting system for control room building,main gate and substation boundary including fans as per detailed Technical Specifications. |
| 95 | Supply for Augmentation/ Additional Power Transformers SCADA Compatible asper technical specifications, scope of works and approved drawings |
| 96 | 33/11 kV, 3 ph, 50 Hz, ONAN,Cu Wound, Outdoor Conventional type PowerTransformer with off load tap charger ( completely field with oil) as per TS |
| 97 | 10 MVA Power Transformer |
| 98 | 5 MVA Power Transformer |
| 99 | MS Galvanised structures (all Type) made of joist / channel / angle / flat of different sections as per approved drawings. All structural steel members shall be galvanized after fabrication as per IS:4759 for all structural members. 3.5mm spring washers are to be used under each structural steel shall conform to IS 2026. All weld shall be 6mm filled weld unless specified otherwise.Anchor plat shall be of relevant IS |
| 100 | GI bolts & nuts, washers etc. (all Type) should be as per approved drawings & TS. All bolts & nuts, washers etc. shall be galvanizedas per IS:4759. 3.5mm spring washers are to be used under each nut shall conform to IS 2026.All nuts and bolts shall be of property class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063 and foundation bolts, shall be of relevant IS |
| 101 | 36kV, 1250A,25kA for 3 seconds, 3-ph, Outdoor typeVacuum Circuit breaker with marshalling box etc Complete in all respect along with support structure. |
| 102 | 36kV, 1-Phase, 25kA/3 seconds,400-200/1-1 Amps ( having 3 secondery, core), 1 set = 3 Nos outdoortype Current Transformers along with junction box (1 no junction box for 3 no of 1-phase CTs), as required as per technical specifications. |
| 103 | SCADA Compatible, 36kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram, Voltmeter, Ammeter,Static Tri-Vector Energy Meter (DLMS modem compactible), With Differential Relay, 5/1 A Auxillary CT, Annunciation Windows with annunciation relays and other components etc as per approved drawings, specifications and scope of works : |
| 104 | 36kV,800 A, 25kA, 3-ph double break center rotating type (DBCR), Gang Operated,(Without Earth Switch)isolator along with Support Insulators, Operating Mechanism, With auxillary contact box, Base Channel down Pipe and all required accessories complete as per technical specifications, |
| 105 | 12 kV, 1250 A, 25kAfor 3 seconds, 3-ph, indoor typeVacuum Circuit BreakerforIncomer along with 12 kV, 1-Phase, 25kA, 600-300/5-5 A, 3 Nos indoor type 3 core Current Transformer, Potential Transformer 11KV/110 V, indoor mounting type control panel for incoming breaker and required accessories, A-meter, volt-meter, 3-phase , withDLMS(modem compactible ) Tri Vector energy meter, Numerical Relays & accessories complete as per specifications for transformer breaker protectionwith earth fault, overcurrent . |
| 106 | 12 KV, 3 Ph 1250 A, 25kAfor 3 seconds, 3-ph, indoor typeVacuum Circuitbreaker along with 12 kV, 1-Phase, 25kA, 400-200/5-5 A,3 Nos indoor type CurrentTransformer,indoor mounting type control panel for feeder protection and required accessories, A-meter, Numerical Relay & accessories complete as perspecifications for feeder breaker protection & Protection for Earth fault and over current) with extensible arrangement for future |
| 107 | 12 kV, 1250 A, 25kAfor 3 seconds, 3-ph, indoor typeVacuum Circuit Breakerforalong with 12 kV, 1-Phase, 25kA, 600-300/5-5 A,3 Nos indoor type Current Transformer, control panel for Bus couplar and required accessories, A-meter, Numerical Relays & accessories complete as per specifications for Bus Coupler protectionwith earth fault, overcurrent . |
| 108 | 30 kV, 10kA, 1-ph Station Class Lightening Arrester complete(1 set= 3 Nos.) |
| 109 | 9kV, 10kA, 1-ph Station Class LighteningArrester complete (1 Set = 3 Nos.) |
| 110 | ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardware fittings, hardware etc |
| 111 | Panther conductor |
| 112 | Earthing & Grounding conductor as per Approved Electrical Layoutfor each sub- station with |
| 113 | 75 x 8 mm GI flat. |
| 114 | 50 x 6 mm GI flat. |
| 115 | 25 mm dia MS rod 6 m long for earth mat |
| 116 | 1.1 KV Grade Control Cable 4x2.5 sq mm for commissioning of POWERtransformers with all associated Items complete |
| 117 | 1.1 KV Grade Control Cable 4x2.5 sq mm for commissioning of POWERtransformers with all associated Items complete |
| 118 | 11 kV, 3-ph, 200 A, 3 Pin type, Vertical Mounting type, Gang Operated,TPMO Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete asper technical specifications, scope of works and approved drawings |
| 119 | 11 KV, XLPE, Power cable, aluminiumconductor, stranded |
| 120 | 3Cx 400 sqmm (armoured) |
| 121 | 3Cx 185 sqmm (armoured) |
| 122 | Cable termination kit suitable for termination in transformer cable box/breaker panel/ outdoor 11 KV terminals complete with all accessories etc.(1 Set= 1 Indoor+1 Outdoor) |
| 123 | 3Cx 400 sqmm |
| 124 | 3Cx 185 sqmm |
| 125 | 33 and 11 KV Insulator - Pin, Post and Disc insulators along with Hardware & accessories suitable for Panther conductors as per Technical specifications. |
| 126 | 33 KV Post Insulator (1 Set = 2 Nos of 22 KV) |
| 127 | 33 KV Disc Insulator(1 Set = 4 Nos Disc Insulator 70 KN) |
| 128 | Hardware fitting for 33 KV Disc Insulator(B & S Type) |
| 129 | Bimetalic Clamps , Al. Connectors, Al. tape etc. complete in all respect as required. |
| 130 | Supply of 8.5 meter long /180 KG PCC Poles (PCC Pole as per state practice) |
| 131 | Supply of Pole accessories as per technical specification, approved drawing and scope of work |
| 132 | Supply of 11 KV danger board |
| 133 | Stone Pad(300x300x75mm) |
| 134 | Supply of GI Barbed wire 12 SWG |
| 135 | Supply of GI Earthing spike made of 20x2500mmsolid Rod |
| 136 | Supply of 8 SWG GI wire |
| 137 | Supply for New 33 KV Line asper technical specifications, scope of works and approved drawings |
| 138 | Supply of 9 m PCC Poles - (PCC Pole as per state practice) |
| 139 | Supply of 11 M long steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 140 | Supply of 13 M long steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 141 | Supply New Pre-fabricated hot dip galvanized steel item, for augmentation of 33 KV line, like V cross arm, top channel, top clamp, cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp,MS angle (65x65x6mm), MS flats (65x8mm) anti climbing device clamp etc of given sizes for over head structures as per technical specification, approved drawings and scope of work. |
| 142 | Supply of hot dip galvanized MS Nuts, Bolts with Washers and turn buckle for guarding as per technical specification, approved drawings and scope of work. |
| 143 | Supply of Pole accessories as per technical specification, approved drawing and scope of work |
| 144 | Supply of 33 KV danger board |
| 145 | Supply of GI Barbed wire 12 SWG |
| 146 | Supply for New 3 phase 33 kV line with following type of new ACSR conductor including jointing sleeves, binding material, aluminum tape and helical Preformed fittings etc as required as per technical specification, approved drawings and scope of work. |
| 147 | Supply of 6/4.72 mm+7/1.57 mm (100 mm² Al. Area) - Dog |
| 148 | Supply of 33 KV Under ground cable as per technical specification, approved drawings and scope of work. |
| 149 | Supply of 3CX300 Sqmm 33 KV XLPE Armored Cable |
| 150 | Supply ofof Heat Shrinkable Terminal Jointing Kit Outdoor for 33 KV 3x300 sq. mm XLPE Cable |
| 151 | Supply ofof Heat Shrinkable Jointing Straight Through Kitfor 33 KV 3x300 sq. mm XLPE Cable |
| 152 | Supply of 160 mm dia. HDPE pipe. |
| 153 | Supply of G.I. pipe 150mmwith clamp and nut & bolts |
| 154 | Supplyof new Insulator and hardware for Augmentation of33 kV line as per technical specification, approved drawings and scope of work |
| 155 | Supply of 33 KV 70 KN polymer Disc Insulator along with suitable hardware fittings |
| 156 | Supply of 33 KV 10 KN Polymer Pin Insulators |
| 157 | Supply of new Earthing arrangement for Augmentation of33 kV line as per technical specifications,approved drawings and scope of work. |
| 158 | 8 SWG GI Coil 115 turns (1.85 Kg) |
| 159 | Supply of new Stay Set (Galvanized) for 33 kV line with 50x8 mm stay clamp, 2 nos. guy insulator, anchor plate (300x300x8mm) , nut bolts, 1 no. turn-buckles, 1.8 m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work. |
| 160 | Supply of new GI wire for earthing and guarding for Augmentation of33 kV line as per technical specification, approved drawings and scope of work. |
| 161 | Supply of 6 SWG GI wire |
| 162 | Supply of 8 SWG GI wire |
| 163 | Supply of Conductor accessories as per technical specification, approved drawing and scope of work |
| 164 | Supply of PG Clamp for Dog to Dog conductor |
| 165 | 33 kV LINEFORUNDER GROUND RAILWAY CROSSING (300 Mtr) BY 2 Nos (INCLUDING ONE SPARE)3Cx300 Sqmm XLPE Armoured Cable USING 150MM DIA GI PIPES (grade A for underground laying and grade B for pole support), OUTDOOR HEAT SHRINKABLE CABLE JOINTING KITS,LUGS, 4 Nos GI 3-Meters LONG pipe, EARTHING, 8 SWG GI WIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING , AS REQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORK. |
| 166 | 33 kV LINEFORUNDER GROUND Highway CROSSING (200 Mtr) BY 2 Nos (INCLUDING ONE SPARE)3Cx300 Sqmm XLPE Armoured Cable USING 150MM DIA GI PIPES (grade A for underground laying and grade B for pole support), OUTDOOR HEAT SHRINKABLE CABLE JOINTING KITS,LUGS, 4 Nos GI 3-Meters LONG pipe, EARTHING, 8 SWG GI WIRES, CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING , AS REQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORK. |
| 167 | Supply For new 11 KV line asper technical specifications, scope of works and approved drawings |
| 168 | Supply of 8.5 meter long /180 KG PCC Poles (PCC Pole as per state practice) |
| 169 | Supply of 11 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 170 | Supply for Augmentation of 3 phase 11 kV line using new Pre-fabricated hot dip galvanized steel items like V cross arm, top channel, top clamp, Cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, MS angle, MS flats pole extension canal with welded plate, anti climbing device clamp, pole clamp etc of given sizes for over head structures as per technical specification, approved drawings and scope of work. |
| 171 | Supply of hot dip galvanized MS Nuts, Bolts with Washers and turn buckle for guarding as per technical specification, approved drawings and scope of work. |
| 172 | Supply of Pole accessories as per technical specification, approved drawing and scope of work |
| 173 | Supply of 11 KV danger board |
| 174 | Stone Pad(300x300x75mm) |
| 175 | Supply of GI Barbed wire 12 SWG |
| 176 | Supply for Augmentation of 3 phase 11 kV line replacing existing conductor with following type of new ACSR conductor including jointing sleeves, binding material and helicon formed fittings etc as required as per technical specification, approved drawings and scope of work. |
| 177 | Supply of 6/2.59 + 1/2.59 mm (30 mm² Al. Area) - Weasel |
| 178 | Supply of 6/3.35 + 1/3.35 mm (50 mm² Al. Area) - Rabbit |
| 179 | Supply of 6/4.72 mm+7/1.57 mm (100 mm² Al. Area) - Dog |
| 180 | Insulated covered Conductor (50 Sqmm) |
| 181 | Supply for New 3 phase 11 kV line using new Insulator and hardware as per technical specification, approved drawings and scope of work |
| 182 | Supply of 11 KV 45 KN polymer Disc insulator along with suitable hardware fittings |
| 183 | Supply of 11 KV 5 KN Polymer Pin Insulators with suitable hardware fittings |
| 184 | Supply for New 3 phase 11 kV line using new Earthing arrangement as per technical specifications,approved drawings and scope of work. |
| 185 | Supply of GI Earthing spike made of 20x2500mmsolid Rod |
| 186 | Supply of Stay Set (Galvanized) with 50x8 mm stay clamp, 1 no. guy insulator, anchor plate (200x200x6mm) , nut bolts, 1no. turn-buckles, 1.8 m long 16 mm diameter solid GI stay rod & 7/3.15 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work. |
| 187 | Supply for New of 3 phase 11 kV line using new GI wire for earthing and guarding as per technical specification, approved drawings and scope of work. |
| 188 | Supply of 6 SWG GI wire |
| 189 | Supply of 8 SWG GI wire |
| 190 | Supply of Conductor accessories as per technical specification, approved drawing and scope of work |
| 191 | Supply of PG Clamp for Weasel to Weasel conductor |
| 192 | Supply of PG Clamp for Dog to Dog conductor |
| 193 | Supply of PG Clamp for Rabbit to Rabbit conductor |
| 194 | Supply of 11 Kv Line on 3x70 sqmm XLPE Cable |
| 195 | cable Jointing kit for 11 kvLine 70 sqmm |
| 196 | Supply of 11 KV Lineunderground Cableensuring statutory clearances as required as per technical specification, approved drawings and scope of work |
| 197 | Supply of 3Cx185 Sqmm 11 KV XLPE Armored Cable |
| 198 | Supply of Heat Shrinkable Jointing Kit Outdoor for 11 KV 3x185 sq. mm XLPE Cable |
| 199 | Supply of Heat Shrinkable Jointing Kit Straight throughfor 11 KV 3x185 sq. mm XLPE Cable |
| 200 | Supply of 110 mm dia. HDPE pipe . |
| 201 | Supply of G.I. pipe 100 mm diawithclamps, Nut and Bolts. |
| 202 | Supply of 11 KV Lineunderground railway crossing ensuring statutory clearances as required as per technical specification, approved drawings and scope of work |
| 203 | Supply for 11 KV lineunder ground Railway crossing with 2 nos (Including one spare) 3Cx185 Sqmm XLPE Armored Cable (0.3 km each) using 150mm dia GI pipes (grade A for underground laying and grade B for pole support), Outdoor heat shrinkable cable jointing kit, 11 KV LIGHTENING ARRESTOR STATION CLASS 10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG pipe EARTHING, 6 SWG GI WIRES,CABLE MARKERS, BI METALLICK CLAMPS and JUMPERING etc AS REQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORK. |
| 204 | Supply of 11 LV Line underground Highway crossing ensuring statutory clearancesas required as per technical specification, approved drawings and scope of work |
| 205 | Supply of 11 KV LINEFORUNDER GROUND Highway CROSSING BY 2 Nos (INCLUDING ONE SPARE) 3Cx185 Sqmm XLPE Armored Cable (0.3 km each) USING 160 mm HDPE pipe at road crossing and 150MM DIA GI PIPES (gradeB for pole support), OUTDOOR HEAT SHRINKABLE CABLE JOINTING KITS, 11 KV LIGHTENING ARRESTOR STATION CLASS 10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG pipe EARTHING, 6 SWG GI WIRES, 7/20 GI wire, CABLE MARKERS, BI METALLICK CLAMPS and JUMPERING etc AS REQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORK. |
| 206 | Supply of New Distribution Transformers asper technical specifications, scope of works and approved drawings |
| 207 | Supply of 8.5m/180 kgs PCC Poles - (PCC Pole as per state practice) |
| 208 | Supply of 11 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 209 | Supply for distribution transformer mounting using new Pre-fabricated hot dip galvanized steel items like V cross arm, MS top channel, top clamp, Cross arm, Bracket, Clamps, cross bracings, bracings, strain plate, back clamp, MS angle, MS Channel, MS transformer base channel, MS flats pole extension channel with welded plate, anti climbing device clamp etc of given sizes for over head structures as per technical specification, approved drawings and scope of work. |
| 210 | Supply of hot dip galvanized MS Nuts, Bolts with Washersas per technical specification, approved drawings and scope of work. |
| 211 | Supply of Pole accessories as per technical specification, approved drawing and scope of work |
| 212 | Supply of 11 KV danger board |
| 213 | Supply of Stone Pad 300X300X75 |
| 214 | Supply of Stay Set (Galvanized) with 50x8 mm stay clamp, stay guy insulator (1 Nos.), anchor plate (200x200x6), nut bolts, 1 Nos turn-buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work. |
| 215 | Supply of Insulator and hardware as per technical specification, approved drawings and scope of work. |
| 216 | Supply of 11 KV45 KN polymer Disc insulator along with suitable hardware fittings |
| 217 | Supply of 11 KV 5 KN Polymer pin insulator with Pin |
| 218 | 9 KV 5 KA Distribution Class Lightening Arrester for DT as per technical specification, approved drawings and scope of work. |
| 219 | 11 kV, 3-ph, 200 A, 3 Pin type, Vertical Mounting type, Gang Operated,TPMO Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete asper technical specifications, scope of works and approved drawings |
| 220 | 11 kV, 200 Amp, 3-ph, Horn Gap fuse units (set of 3 units) along with Support Insulators, Base Channel, fuse barrel etc. complete asper technical specifications, scope of works and approved drawings |
| 221 | Supply of Earthing arrangement as per technical specifications,approved drawings and scope of work. |
| 222 | Supply of Spike Earthing 20mm X 2500 mm GI solidRod |
| 223 | Supply of Chemicalrod earthing including electrode, chemical, with 3000mm long, 40 mm diameterGI pipe, GI Strip of 24x3mm. |
| 224 | Supply of 6 SWG GI wire for earthing |
| 225 | New Distribution Transformer with all accessories as per as per technical specification, approved drawings and scope of work. |
| 226 | 11/0.4 KV Distribution Transformer 25 KVA 3 phase DTR |
| 227 | 11/0.4 KV Distribution Transformer 63 KVA 3 phase DTR |
| 228 | 11/0.4 KV Distribution Transformer 100 KVA 3 phaseDTR |
| 229 | 11/0.4 KV Distribution Transformer 250 KVA 3 phaseDTR |
| 230 | Outdoor mounting type Distribution box made of MS sheet of thickness not less than 18 SWG CRCA sheet by deep drawn method, dust and moisture vermin, weather proof with degree of protection with suitable bus bars, Modem Compatible DLMS Compliant LT Trivector Static Meter with suitable CTs, earthing bus, earthing terminals, box illumination, front door operated with proper locking arrangement, lugs, mounting channel frame, internal wiring with FRLS cables, danger plate, numbering, back clamps, hardware as per scope of the work, technical specifications and approved drawings, direction of Engineer in Charge suitable for following transformer: |
| 231 | 3 Ph 25 KVA transformer 40 A TPN MCCB (incomer) and 6 Nos. 25 A SP MCCB (outgoing) |
| 232 | 3 Ph 63 KVA Transformer having 200 A TPN isolator, 100 A HRC fuse (incomer) and 6 Nos. 60 A SP MCCB (outgoing) |
| 233 | 3 Ph 100 KVA Transformer having 200 A TPN isolator, 160A HRC fuse (incomer) and 6 Nos. 90 A SP MCCB (outgoing) |
| 234 | 3 Ph 250 KVA Transformer having 600 A TPN isolator, 315 A HRC fuse (incomer) and 9 Nos. 120 A SP MCCB (outgoing) |
| 235 | 1.1 KV XLPE Aluminium Conductor, Stranded, unarmoured cable for connection of transformer LV bushing to Distribution Box and Distribution box to overhead line as per Scope of work, technical specification and approved drawings: |
| 236 | 1CX35 sqmm aluminium conductor cable |
| 237 | 1Cx70 sqmm aluminium conductor cable |
| 238 | 1Cx150 sqmm aluminium conductor cable |
| 239 | 1Cx400 sqmm aluminium conductor cable |
| 240 | ACSR Rabbit Conductor for jumpering including PG Clamps, bi-metallic connectors, hardware etc as per technical specifications, approved drawings and scope of works. |
| 241 | Supply for Augmentation of existing Distribution transformer asper technical specifications, scope of works and approved drawings |
| 242 | 11/0.433 kV 25kVA Distribution Transformer |
| 243 | 11/0.433 kV 63kVA Distribution Transformer |
| 244 | 11/0.433 kV 100kVA Distribution Transformer |
| 245 | 11/0.433 kV 250kVA Distribution Transformer |
| 246 | 11/0.433 kV 400kVA Distribution Transformer |
| 247 | LT XLPE Cable 4x16 Sqmm |
| 248 | LT XLPE Cable 3.5x70 Sqmm |
| 249 | LT XLPE Cable 3.5x150 Sqmm |
| 250 | LT XLPE Cable 3.5x400 Sqmm |
| 251 | LT XLPE Cable 1x240 Sqmm |
| 252 | LT XLPE Cable 1x400 Sqmm |
| 253 | Supply of Stay Set (Galvanized) with 50x8 mm stay clamp, 1 no. guy insulator, anchor plate (200x200x6mm) , nut bolts, 1no. turn-buckles, 1.8 m long 16 mm diameter solid GI stay rod & 7/3.15 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work. |
| 254 | Earthing of pole by MS earthing rod of 20x2500 mm. and 6 SWG earthing wire etc. |
| 255 | Supply of Trolly Mounted DT- of 400KVA asper technical specifications, scope of works and approved drawings |
| 256 | 11/0.415 kV 400 KVA Distribution Transformer |
| 257 | Fabricated Trolley With 4 Tyre wheels to house Transformer with all fixing Arrangement along with fencing and locking mechanism. |
| 258 | 3x50 mm² 11KV class XLPE Cable. |
| 259 | Heat shrinkable Termination kits suitable for 3x50 mm²Xlpe Cable (out door) including bushing cap. |
| 260 | 400 Sq.mm., LT single core `XLPE insulatedun-armoured aluminium conductor cable |
| 261 | Supply of Protection of DT asper technical specifications, scope of works and approved drawings |
| 262 | Supply ofAB switch suitable for Distribution Transformer 100 KVA and above |
| 263 | Supply of DO Fuse set suitable for Distribution Transformer 100 KVA and above |
| 264 | Supply of LT ACB suitable for Distribution transformers having capacity 250 KVA and above |
| 265 | Supply of LT Distribution box suitablefor Distribution Transformer upto 250 KVA |
| 266 | Supply of LT Distribution box suitable for Distribution Transformer 400 KVA and above |
| 267 | Supply of DT Cable asper technical specifications, scope of works and approved drawings |
| 268 | LT XLPE Insulated Cable 1CX240 Sqmm |
| 269 | LT XLPE Insulated Cable 1CX400 Sqmm |
| 270 | LTXLPE Insulated Cable 1CX630 Sqmm |
| 271 | Supply of New LT Line asper technical specifications, scope of works and approved drawings |
| 272 | Supply of 8.5 m/180 kgs PCC Poles (PCC Pole as per state practice) |
| 273 | Supply of 9 M long steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 274 | Supply of 11 M long steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 275 | Galvanized Stay Set for LT line with anchor plate (200x200x6mm), 50x8mm stay clamp, 1 no. Stay guy insulator, nut bolts, 1 no. turn buckles, 1.8 m long, 16 mm diameter solid GS Stay rod & 7/3.15 mm Dia GI stranded wire etc as required as per technical specification, approved drawings and scope of work. |
| 276 | New LT lines using new Earthing as per approved drawings, technical specifications and scope of work |
| 277 | Supply of Spike Earthing made of 20mm X 2500 mm GI solid Rod |
| 278 | Supply of 8 SWG GI wire for earthing and guarding |
| 279 | Supply of following LT AB XLPE Cable for New AB XLPE Cable as required as per technical specification, approved drawings and scope of work: |
| 280 | Supply of Aerial bunchedXLPE cable 1x16 sqmm+1x25 sqmm |
| 281 | Supply of Aerial bunchedXLPE cable 3 X 50 sqmm+1x35 sqmm.(bare messenger wire)+1x16 sqmm. |
| 282 | Supply of Aerial bunchedXLPE cable 3 X 95 sqmm.+1x70 sqmm.(Bare messenger wire)+1x16 sqmm. |
| 283 | Supply of Aerial bunchedXLPE cable 3 X 120 sqmm. + 1x95 sqmm.(bare messenger wire) +1x16 sqmm. |
| 284 | Supplyof Aerial bunchedXLPE cable 3 X 150 sqmm. + 1x120 sqmm.(bare messenger wire) +1x16 sqmm. |
| 285 | Supply of Pole mounted LT Distribution box as per approved drawings, technical specifications and scope of work |
| 286 | Supply of Three phase SMC Distribution box with clamps |
| 287 | Supply of Single phase SMC Distribution box with clamps |
| 288 | Supply of XLPE insulated Al. cable for energisation of distribution box/ Kiosk as per approved drawings, technical specifications and scope of work |
| 289 | Suppply of 2Cx25 SQMM Stranded Unarmoured Cable (Al Conductor ) for chargingSingle Phase DB |
| 290 | Suppply of 4Cx35SQMM Stranded Unarmoured Cable (Al Conductor ) for chargingThreePhase DB |
| 291 | Supply of Stone pad (300x300x75) |
| 292 | Supply of Accessories for AB XLPE Cable as per approved drawings, technical specifications and scope of work |
| 293 | HDG LT Pole Clamp with nut & bolt for laying ABC |
| 294 | Dead end Clamp with I-Hook( Insulated) |
| 295 | Suspension Clamp with I-Hook ( Insulated) |
| 296 | PG Clamps 16-120 sq mm to 16-120 Sqmm (For line to line jumpering of massenger wire & energizing DB Neutral) |
| 297 | LT Insulation piercing connector 150-50 sqmm - 50-25 sqmm size (for energizing distribution box) |
| 298 | LT Insulation piercing connector 150-50 sqmm - 150-50 sqmm size (for line to line jumpering) |
| 299 | LT Insulation piercing connector 16 - 25sqmmsize suitable for street light connection |
| 300 | Pre-Insulated Compression connectors size 16 sqmm suitable for AB XLPE cable |
| 301 | Pre-Insulated Compression connectors size 50 sqmm suitable for AB XLPE cable |
| 302 | Pre-Insulated Compression connectors size 95 sqmm suitable for AB XLPE cable |
| 303 | Pre-Insulated Compression connectors size 120 sqmm suitable for AB XLPE cable |
| 304 | Pre-Insulated Compression connectors size 150 sqmm suitable for AB XLPE cable |
| 305 | Heat shrinkable type end cap for AB XLPE cable |
| 306 | Supply of Extra Circuits AB XLPE cableasper technical specifications, scope of works and approved drawings |
| 307 | Supply of 8.5 m/180 kgs PCC Poles (PCC Pole as per state practice) |
| 308 | Supply of 9 M long steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 309 | Supply of 11 M long steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 310 | Galvanized Stay Set for LT line with anchor plate (200x200x6mm), 50x8mm stay clamp, 1 no. Stay guy insulator, nut bolts, 1 no. turn buckles, 1.8 m long, 16 mm diameter solid GS Stay rod & 7/3.15 mm Dia GI stranded wire etc as required as per technical specification, approved drawings and scope of work. |
| 311 | Extra Circuits for LT lines using new Earthing as per approved drawings, technical specifications and scope of work |
| 312 | Supply of Spike Earthing made of 20mm X 2500 mm GI solid Rod |
| 313 | Supply of 8 SWG GI wire for earthing and guarding |
| 314 | Supply of following LT AB XLPE Cable for extra circuits as required as per technical specification, approved drawings and scope of work: |
| 315 | Supply of Aerial bunchedXLPE cable 3 X 50 sqmm+1x35 sqmm.(bare messenger wire)+1x16 sqmm. |
| 316 | Supply of Aerial bunchedXLPE cable 3 X 95 sqmm.+1x70 sqmm.(Bare messenger wire)+1x16 sqmm. |
| 317 | Supply of Aerial bunchedXLPE cable 3 X 120 sqmm. + 1x95 sqmm.(bare messenger wire) +1x16 sqmm. |
| 318 | Supplyof Aerial bunchedXLPE cable 3 X 150 sqmm. + 1x120 sqmm.(bare messenger wire) +1x16 sqmm. |
| 319 | Supply of Pole mounted LT Distribution box as per approved drawings, technical specifications and scope of work |
| 320 | Supply of Three phase SMC Distribution box with clamps |
| 321 | Supply of XLPE insulated Al. cable for energisation of distribution box/ Kiosk as per approved drawings, technical specifications and scope of work |
| 322 | Suppply of 4Cx35SQMM Stranded Unarmoured Cable (Al Conductor ) for chargingThreePhase DB |
| 323 | Supply of Stone pad (300x300x75) |
| 324 | Supply of Accessories for AB XLPE Cable as per approved drawings, technical specifications and scope of work |
| 325 | Stainless steel Strap |
| 326 | HDG LT Pole Clamp with nut & bolt for laying ABC |
| 327 | Dead end Clamp with I-Hook( Insulated) |
| 328 | Suspension Clamp with I-Hook ( Insulated) |
| 329 | PG Clamps 16-120 sq mm to 16-120 Sqmm (For line to line jumpering of massenger wire & energizing DB Neutral) |
| 330 | LT Insulation piercing connector 150-50 sqmm - 50-25 sqmm size (for energizing distribution box) |
| 331 | LT Insulation piercing connector 150-50 sqmm - 150-50 sqmm size (for line to line jumpering) |
| 332 | Pre-Insulated Compression connectors size 50 sqmm suitable for AB XLPE cable |
| 333 | Pre-Insulated Compression connectors size 95 sqmm suitable for AB XLPE cable |
| 334 | Pre-Insulated Compression connectors size 120 sqmm suitable for AB XLPE cable |
| 335 | Pre-Insulated Compression connectors size 150 sqmm suitable for AB XLPE cable |
| 336 | Heat shrinkable type end cap for AB XLPE cable |
| 337 | Supply of Augmentation of LT AB Cable (Increasing Capacity) as per approved drawings, technical specifications and scope of work |
| 338 | Supply of 8.5 m/180 kgs PCC Poles (PCC Pole as per state practice) |
| 339 | Supply of 9 M long steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 340 | Galvanized Stay Set for LT line with anchor plate (200x200x6mm), 50x8mm stay clamp, 1 no. Stay guy insulator, nut bolts, 1 no. turn buckles, 1.8 m long, 16 mm diameter solid GS Stay rod & 7/3.15 mm Dia GI stranded wire etc as required as per technical specification, approved drawings and scope of work. |
| 341 | Conversion of existing LT lines using new Earthing as per approved drawings, technical specifications and scope of work |
| 342 | Supply of Spike Earthing made of 20mm X 2500 mm GI solid Rod |
| 343 | Supply of 8 SWG GI wire for earthing and guarding |
| 344 | Supply of following LT AB XLPE Cable for Conversion of existing LT bare conductor line with AB XLPE Cable as required as per technical specification, approved drawings and scope of work: |
| 345 | Erection of Aerial bunchedXLPE cable 3 X 95 sqmm.+1x70 sqmm.(Bare messenger wire)+1x16 sqmm. |
| 346 | Erection of Aerial bunchedXLPE cable 3 X 120 sqmm. + 1x95 sqmm.(bare messenger wire) +1x16 sqmm. |
| 347 | Supply of Pole mounted LT Distribution box as per approved drawings, technical specifications and scope of work |
| 348 | Supply of Three phase SMC Distribution box with clamps |
| 349 | Supply of XLPE insulated Al. cable for energisation of distribution box/ Kiosk as per approved drawings, technical specifications and scope of work |
| 350 | Suppply of 4Cx35SQMM Stranded Unarmoured Cable (Al Conductor ) for chargingThreePhase DB |
| 351 | Supply of Stone pad (300x300x75) |
| 352 | Supply of Accessories for AB XLPE Cable as per approved drawings, technical specifications and scope of work |
| 353 | Stainless steel Strap |
| 354 | HDG LT Pole Clamp with nut & bolt for laying ABC |
| 355 | Dead end Clamp with I-Hook( Insulated) |
| 356 | Suspension Clamp with I-Hook ( Insulated) |
| 357 | PG Clamps 16 Sq mm .- 120 sq mm (For line to line jumpering of massenger wire & energizing DB Neutral) |
| 358 | LT Insulation piercing connector 120-50 sqmm - 50-35 sqmm size (for energizing distribution box) |
| 359 | LT Insulation piercing connector 120-50 sqmm - 120-50 sqmm size (for line to line jumpering) |
| 360 | Pre-Insulated Compression connectors size 95 sqmm suitable for AB XLPE cable |
| 361 | Pre-Insulated Compression connectors size 120 sqmm suitable for AB XLPE cable |
| 362 | Heat shrinkable type end cap for AB XLPE cable |
| 363 | Supply of Feeder Bifurcation (33KV Line) as per approved drawings, technical specifications and scope of work |
| 364 | 9m/400 kgs PCC Poles (PCC pole as per state practice) |
| 365 | 13 m longSTP SP72 |
| 366 | 11 m long steel tubular poles with welded steel base plate of designation 540 SP 55 (As per IS: 2713 , pt. I,II,III) |
| 367 | Concreting of poles as per specification |
| 368 | Stone Pad |
| 369 | Supply New Pre-fabricated hot dip galvanized steel item, for augmentation of 33 KV line, like V cross arm, top channel, top clamp, cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp,MS angle (65x65x6mm), MS flats (65x8mm) anti climbing device clamp etc of given sizes for over head structures as per technical specification, approved drawings and scope of work. |
| 370 | Supply of hot dip galvanized MS Nuts, Bolts with Washers and turn buckle for guarding as per technical specification, approved drawings and scope of work. |
| 371 | Danger Board with barbed wire including jumpher |
| 372 | Number Plate |
| 373 | Stay Set ( Galvanised) GI stay rod 20x1800 mm, stay wire 7/8 SWG GI wire, 50x8 mm stay clamp, stay insulator (2 nos.), anchor plate (300x300x8), nut bolts, 2 nos. turn buckles, 1.8 m long 20 mm dia. Solid GI Stay Rod, 7/4.0mm dia. GI stranded wire |
| 374 | Insulator and hardware as per technical specification, approved drawings and scope of work |
| 375 | 33 KV polymer Disc insulator 70 KNB&S along with suitable hardware fittings |
| 376 | 33 KV polymer Pin insulators with GI Pin & nuts |
| 377 | GI earthing Spike earthing 20x2500 mm solid rod & 6 SWG earthwire with nut and bolt |
| 378 | 6 SWGand 8 SWG GI wire, GI nuts, bolts & washers for guarding angle 2180 mm long 75x75x6 (Approx. 3 span per km.) |
| 379 | ACSR conductors of following sizes with jointing sleeves, binding materials,pG clamps, bi-metallic clamp, hardware etc for overhead line and jumpers as required as per technical specification,approved drawings and scope of work: |
| 380 | 6/4.72 + 7/1.57 mm (100 mm2 Al.area ) - Dog |
| 381 | Supply of 33 KV Lineunderground railway crossing ensuring statutory clearances as required as per technical specification, approved drawings and scope of work |
| 382 | Supply of 33 KV3Cx300 Sqmm XLPE Armored Cable (2 Nos including one spare) Accessories like 160mm dia HDPE pipes for road crossing and 150 mm dia GI pipegrade B for pole support outdoor heat shrinkable cable jointing kits, Lugs,CablePath markers, bi metallic clamps, 7/20 GI wire as per technical specification, approved drawing and scope of work |
| 383 | Supply for Feeder Bifurcation of 3 phase 11 kV line using additional supports matching with length and type of existing support asper technical specifications, scope of works and approved drawings |
| 384 | Supply of 8.5 meter long /180 KG PCC Poles (PCC Pole as per state practice) |
| 385 | Supply of 11 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 386 | Supply for Augmentation of 3 phase 11 kV line using new Pre-fabricated hot dip galvanized steel items like V cross arm, top channel, top clamp, Cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, MS angle, MS flats pole extension canal with welded plate, anti climbing device clamp etc of given sizes for over head structures as per technical specification, approved drawings and scope of work. |
| 387 | Supply of hot dip galvanized MS Nuts, Bolts with Washers and turn buckle for guarding as per technical specification, approved drawings and scope of work. |
| 388 | Supply of Pole accessories as per technical specification, approved drawing and scope of work |
| 389 | Supply of 11 KV danger board |
| 390 | Stone Pad(300x300x75mm) |
| 391 | Supply of GI Barbed wire 12 SWG |
| 392 | Supply for Augmentation of 3 phase 11 kV line replacing existing conductor with following type of new ACSR conductor including jointing sleeves, binding material and helicon formed fittings etc as required as per technical specification, approved drawings and scope of work. |
| 393 | Supply of 6/2.59 + 1/2.59 mm (30 mm² Al. Area) - Weasel conductor |
| 394 | Supply of 6/3.35 + 1/3.35 mm (50 mm² Al. Area) - Rabbitconductor |
| 395 | Supply of 6/4.72 mm+7/1.57 mm (100 mm² Al. Area) - Dog conductor |
| 396 | Supply for Augmentation of 3 phase 11 kV line using new Insulator and hardware as per technical specification, approved drawings and scope of work |
| 397 | Supply of 11 KV 45 KN polymer Disc insulator along with suitable hardware fittings |
| 398 | Supply of 11 KV 5 KN Polymer Pin Insulators with suitable hardware fittings |
| 399 | Supply for Augmentation of 3 phase 11 kV line using new Earthing arrangement as per technical specifications,approved drawings and scope of work. |
| 400 | Supply of GI Earthing spike made of 20x2500mmsolid Rod |
| 401 | Supply for Augmentation of 3 phase 11 kV line using new Stay Set (Galvanized) with 50x8 mm stay clamp, 1 no. guy insulator, anchor plate (200x200x6mm) , nut bolts, 1no. turn-buckles, 1.8 m long 16 mm diameter solid GI stay rod & 7/3.15 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work. |
| 402 | Supply for Augmentation of 3 phase 11 kV line using new GI wire for earthing and guarding as per technical specification, approved drawings and scope of work. |
| 403 | Supply of 6 SWG GI wire |
| 404 | Supply of 8 SWG GI wire |
| 405 | Supply of Conductor accessories as per technical specification, approved drawing and scope of work |
| 406 | Supply of PG Clamp for Weasel to Weasel conductor |
| 407 | Supply of PG Clamp for Dog to Dog conductor |
| 408 | Supply of PG Clamp for Rabbit to Rabbit conductor |
| 409 | Aluminium Jointing sleave for ACSR Rabbit |
| 410 | Aluminium Jointing sleave for ACSR Weasel |
| 411 | Aluminium Jointing sleave for ACSR DOG |
| 412 | Supply of 11 KV Lineunderground railway crossing ensuring statutory clearances as required as per technical specification, approved drawings and scope of work |
| 413 | Supply for 11 KV lineunder ground Railway crossing with 2 nos (Including one spare) 3Cx185 Sqmm XLPE Armored Cable (0.3 km each) using 150mm dia GI pipes (grade A for underground laying and grade B for pole support), Outdoor heat shrinkable cable jointing kit, 11 KV LIGHTENING ARRESTOR STATION CLASS 10KA (6 NOS.), LUGS, 4 Nos GI 3-Meters LONG pipe EARTHING, 6 SWG GI WIRES,CABLE MARKERS, BI METALLICK CLAMPS and JUMPERING etc AS REQUIRED AS PER TECHNICAL SPECIFICATIONS, DRAWINGS AND SCOPE OF THE WORK. |
| 414 | Supply of 12 KV 3ph Indoor type switch gear and 11 KV XLPE cable as per technical specifications, approved drawings and scope of works: |
| 415 | Supply of Indoor type 12 KV 3 Ph 1250 A VCB with control and protection system for out going feeder consisting ofCT, A-meter, volt-meter, Relays, energy meter (TVM) DLMS compliant & accessories complete as per specifications for feeder breaker |
| 416 | 11 KV 3X 185 sqmm XLPE armored Power cable, aluminum stranded conductor, including their termination materials like indoor and outdoor termination kit, glands, lugs, tagging, cable path marker etc as required as per technical specifications, approved drawings and scope of the works. |
| 417 | Supply of 11KVAgriculture Feeder Splitting due to overloading as per approved drawings, technical specifications and scope of work |
| 418 | Supply of 8.5 m/180 kgs PCC Poles (PCC Pole as per state practice) |
| 419 | Galvanized Stay Set for LT line with anchor plate (200x200x6mm), 50x8mm stay clamp, 1 no. Stay guy insulator, nut bolts, 1 no. turn buckles, 1.8 m long, 16 mm diameter solid GS Stay rod & 7/3.15 mm Dia GI stranded wire etc as required as per technical specification, approved drawings and scope of work. |
| 420 | New Earthing as per approved drawings, technical specifications and scope of work |
| 421 | Supply of Spike Earthing made of 20mm X 2500 mm GI solid Rod |
| 422 | Supply of 8 SWG GI wire for earthing and guarding |
| 423 | Supply of following LT AB XLPE Cable for New AB XLPE Cable as required as per technical specification, approved drawings and scope of work: |
| 424 | Supply of Aerial bunchedXLPE cable 3 X 50 sqmm+1x35 sqmm.(bare messenger wire)+1x16 sqmm. |
| 425 | Supply of Pole mounted LT Distribution box as per approved drawings, technical specifications and scope of work |
| 426 | Supply of Three phase SMC Distribution box with clamps |
| 427 | Supply of Single phase SMC Distribution box with clamps |
| 428 | Supply of XLPE insulated Al. cable for energisation of distribution box/ Kiosk as per approved drawings, technical specifications and scope of work |
| 429 | Suppply of 2Cx25 SQMM Stranded Unarmoured Cable (Al Conductor ) for chargingSingle Phase DB |
| 430 | Suppply of 4Cx35SQMM Stranded Unarmoured Cable (Al Conductor ) for chargingThreePhase DB |
| 431 | Supply of Stone pad (300x300x75) |
| 432 | Supply of Accessories for AB XLPE Cable as per approved drawings, technical specifications and scope of work |
| 433 | HDG LT Pole Clamp with nut & bolt for laying ABC |
| 434 | Dead end Clamp with I-Hook( Insulated) |
| 435 | Suspension Clamp with I-Hook ( Insulated) |
| 436 | PG Clamps 16 Sq mm .- 50 sq mm to 16-50 sqmm (For line to line jumpering of massenger wire & energizing DB Neutral) |
| 437 | LT insulation Piercing Connectors of 16-50 sqmm to 16-50 sqmm size for energizing distibution Kiosk/box |
| 438 | Pre-Insulated Compression connectors size 16 sqmm suitable for AB XLPE cable |
| 439 | Pre-Insulated Compression connectors size 50 sqmm suitable for AB XLPE cable |
| 440 | Heat shrinkable type end cap for AB XLPE cable |
| 441 | New Distribution Transformer with all accessories as per as per technical specification, approved drawings and scope of work. |
| 442 | 11 /0.433 KV 25 KVA T/F (BEE standard Three Star Self protected type) |
| 443 | Supply of 8.5m/180 kgs PCC Poles - (PCC Pole as per state practice) |
| 444 | Supply for distribution transformer mounting using new Pre-fabricated hot dip galvanized steel items like V cross arm, MS top channel, top clamp, Cross arm, Bracket, Clamps, cross bracings, bracings, strain plate, back clamp, MS angle, MS Channel, MS transformer base channel, MS flats pole extension channel with welded plate, anti climbing device clamp etc of given sizes for over head structures as per technical specification, approved drawings and scope of work. |
| 445 | Supply of hot dip galvanized MS Nuts, Bolts with Washersas per technical specification, approved drawings and scope of work. |
| 446 | Supply of 11 KV danger board |
| 447 | Supply of Stone Pad 300X300X75 |
| 448 | Supply of Stay Set (Galvanized) with 50x8 mm stay clamp, stay guy insulator (1 Nos.), anchor plate (200x200x6), nut bolts, 1 Nos turn-buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work. |
| 449 | Supply of Insulator and hardware as per technical specification, approved drawings and scope of work. |
| 450 | Supply of 11 KV45 KN polymer Disc insulator along with suitable hardware fittings |
| 451 | Supply of 11 KV 5 KN Polymer pin insulator with Pin |
| 452 | 9 KV 5 KA Distribution Class Lightening Arrester for DT as per technical specification, approved drawings and scope of work. |
| 453 | 11 kV, 3-ph, 200 A, 3 Pin type, Vertical Mounting type, Gang Operated,TPMO Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete asper technical specifications, scope of works and approved drawings |
| 454 | 11 kV, 200 Amp, 3-ph, Horn Gap fuse units (set of 3 units) along with Support Insulators, Base Channel, fuse barrel etc. complete asper technical specifications, scope of works and approved drawings |
| 455 | Supply of Earthing arrangement as per technical specifications,approved drawings and scope of work. |
| 456 | Supply of Spike Earthing 20mm X 2500 mm GI solidRod |
| 457 | Supply of Chemicalrod earthing including electrode, chemical, with 3000mm long, 40 mm diameterGI pipe, GI Strip of 24x3mm. |
| 458 | Supply of 6 SWG GI wire for earthing |
| 459 | Outdoor mounting type Distribution box made of MS sheet of thickness not less than 18 SWG CRCA sheet by deep drawn method, dust and moisture vermin, weather proof with degree of protection with suitable bus bars, Modem Compatible DLMS Compliant LT Trivector Static Meter with suitable CTs, earthing bus, earthing terminals, box illumination, front door operated with proper locking arrangement, lugs, mounting channel frame, internal wiring with FRLS cables, danger plate, numbering, back clamps, hardware as per scope of the work, technical specifications and approved drawings, direction of Engineer in Charge suitable for following transformer: |
| 460 | 3 Ph 25 KVA transformer 40 A TPN MCCB (incomer) and 6 Nos. 25 A SP MCCB (outgoing) |
| 461 | 1.1 KV XLPE Aluminium Conductor, Stranded, unarmoured cable for connection of transformer LV bushing to Distribution Box and Distribution box to overhead line as per Scope of work, technical specification and approved drawings: |
| 462 | 1CX35 sqmm aluminium conductor cable |
| 463 | ACSR Rabbit Conductor for jumpering including PG Clamps, bi-metallic connectors, hardware etc as per technical specifications, approved drawings and scope of works. |
| 464 | Supply for Augmentation of 3 phase 33 kV line using additional supports matching with length and type of existing support asper technical specifications, scope of works and approved drawings |
| 465 | Supply of 11 M long steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 466 | Supply of 9 m PCC Poles - (PCC Pole as per state practice) |
| 467 | Supply New Pre-fabricated hot dip galvanized steel item, for augmentation of 33 KV line, like V cross arm, top channel, top clamp, cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp,MS angle (65x65x6mm), MS flats (65x8mm) anti climbing device clamp etc of given sizes for over head structures as per technical specification, approved drawings and scope of work. |
| 468 | Supply of hot dip galvanized MS Nuts, Bolts with Washers and turn buckle for guarding as per technical specification, approved drawings and scope of work. |
| 469 | Supply of Pole accessories as per technical specification, approved drawing and scope of work |
| 470 | Supply of 33 KV danger board |
| 471 | Supply of GI Barbed wire 12 SWG |
| 472 | Supply for Augmentation of 3 phase 33 kV line replacing existing conductor with following type of new ACSR conductor including jointing sleeves, binding material, aluminum tape and helical Preformed fittings etc as required as per technical specification, approved drawings and scope of work. |
| 473 | Supply of 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther conductor |
| 474 | Supplyof new Insulator and hardware for Augmentation of33 kV line as per technical specification, approved drawings and scope of work |
| 475 | Supply of 33 KV 70 KN polymer Disc Insulator along with suitable hardware fittings |
| 476 | Supply of 33 KV 10 KN Polymer Pin Insulators |
| 477 | Supply of new Earthing arrangement for Augmentation of33 kV line as per technical specifications,approved drawings and scope of work. |
| 478 | 8 SWG GI Coil 115 turns (1.85 Kg) |
| 479 | Supply of new Stay Set (Galvanized) for 33 kV line with 50x8 mm stay clamp, 2 nos. guy insulator, anchor plate (300x300x8mm) , nut bolts, 1 no. turn-buckles, 1.8 m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work. |
| 480 | Supply of new GI wire for earthing and guarding for Augmentation of33 kV line as per technical specification, approved drawings and scope of work. |
| 481 | Supply of 6 SWG GI wire |
| 482 | Supply of 8 SWG GI wire |
| 483 | Supply of Conductor accessories as per technical specification, approved drawing and scope of work |
| 484 | Supply of PG Clamp for Panther to panther conductor |
| 485 | Supply of 11 kv Reconductoring of Feeder ( Older than 25 years ) as per approved drawings, technical specifications and scope of work |
| 486 | Supply of 8.5 meter long /180 KG PCC Poles (PCC Pole as per state practice) |
| 487 | Supply for Augmentation of 3 phase 11 kV line using new Pre-fabricated hot dip galvanized steel items like V cross arm, top channel, top clamp, Cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, MS angle, MS flats pole extension canal with welded plate, anti climbing device clamp etc of given sizes for over head structures as per technical specification, approved drawings and scope of work. |
| 488 | Supply of hot dip galvanized MS Nuts, Bolts with Washers and turn buckle for guarding as per technical specification, approved drawings and scope of work. |
| 489 | Supply of Pole accessories as per technical specification, approved drawing and scope of work |
| 490 | Supply of 11 KV danger board |
| 491 | Stone Pad(300x300x75mm) |
| 492 | Supply of GI Barbed wire 12 SWG |
| 493 | Supply for Augmentation of 3 phase 11 kV line replacing existing conductor with following type of new ACSR conductor including jointing sleeves, binding material and helicon formed fittings etc as required as per technical specification, approved drawings and scope of work. |
| 494 | Supply of 6/3.35 + 1/3.35 mm (50 mm² Al. Area) - Rabbit by replacing existing weasel/squirrel conductor- On 11 mtr STP |
| 495 | Supply of 6/4.72 mm+7/1.57 mm (100 mm² Al. Area) - Dog by replacing existing racoon/rabbit conductor on 11 Mtr STP |
| 496 | Supply for Augmentation of 3 phase 11 kV line using new Insulator and hardware as per technical specification, approved drawings and scope of work |
| 497 | Supply of 11 KV 45 KN polymer Disc insulator along with suitable hardware fittings |
| 498 | Supply of 11 KV 5 KN Polymer Pin Insulators with suitable hardware fittings |
| 499 | Supply for Augmentation of 3 phase 11 kV line using new Earthing arrangement as per technical specifications,approved drawings and scope of work. |
| 500 | Supply of GI Earthing spike made of 20x2500mmsolid Rod |
| 501 | Supply for Augmentation of 3 phase 11 kV line using new Stay Set (Galvanized) with 50x8 mm stay clamp, 1 no. guy insulator, anchor plate (200x200x6mm) , nut bolts, 1no. turn-buckles, 1.8 m long 16 mm diameter solid GI stay rod & 7/3.15 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work. |
| 502 | Supply for Augmentation of 3 phase 11 kV line using new GI wire for earthing and guarding as per technical specification, approved drawings and scope of work. |
| 503 | Supply of 6 SWG GI wire |
| 504 | Supply of 8 SWG GI wire |
| 505 | Supply of Conductor accessories as per technical specification, approved drawing and scope of work |
| 506 | Supply of PG Clamp for Dog to Dog conductor |
| 507 | Supply of PG Clamp for Rabbit to Rabbit conductor |
| 508 | Supply of Automatic Capacitor Bank as per approved drawings, technical specifications and scope of work (1.98 MVAr With APFC Panel) |
| 509 | 12.65 kV, 1980 kVAr, 3-Phase, 50 C/s, Outdoor Type , Capacitor bank having two variable step of 792 Kvar & one Variable steps of 396 kVAr. Bank shall be complete with Capacitor units of 264/132 kVAr,Aluminium busbars, Pin & Post insulators, Expulsion fuses etc.(1.98 MVAr HT Capacitor bank) |
| 510 | 0.52 kVAr for 792 kVAr step(1.98 MVAr HT Capacitor bank) |
| 511 | 0.25 kVAr for 396 kVAr step(1.98 MVAr HT Capacitor bank) |
| 512 | 11 kV, 3-Phase Oil-Cooled RVT(1.98 MVAr HT Capacitor bank) |
| 513 | 12 kV 3 Phase Indoor type metal enclosed Vacuum Capacitor switches.(1.98 MVAr HT Capacitor bank) |
| 514 | 11 kV, 400 Amp, Off Load Isolator with earth switch and mounting structure.(1.98 MVAr HT Capacitor bank) |
| 515 | 9 kV, 10 kA,Station Class, Lightning Arrestors(1.98 MVAr HT Capacitor bank) |
| 516 | Indoor Type Automatic Control Unit(1.98 MVAr HT Capacitor bank) |
| 517 | IP 55 , Outdoor CRCA cubicle Panel for accomdating capacitors,Series Reactor,Vacuum contactor,Surge arrestor,Fuses(1.98 MVAr HT Capacitor bank) |
| 518 | Control cables, lugs/thimble, Junction Box etc.(1.98 MVAr HT Capacitor bank) |
| 519 | 11 KV 3 Core Al. XLPE Insulated 3x120 mm sq. Cable(1.98 MVAr HT Capacitor bank) |
| 520 | 11KV XLPE Cable(3x185 sq.mm.) Heat Shrinkable Jointing kit Indoor(1.98 MVAr HT Capacitor bank) |
| 521 | 11KV XLPE Cable(3x185 sq.mm.) Heat Shrinkable Jointing kit Outdoor(1.98 MVAr HT Capacitor bank) |
| 522 | 11 KV VCB Switchgear with complete arangement for connection with existing 11 KV bus bar.(1.98 MVAr HT Capacitor bank) |
| 523 | Earthing for Panel and LA\"s by pipe in pipe earthing(1.98 MVAr HT Capacitor bank) |
| 524 | 3.96 MVAr With APFC Panel |
| 525 | 12.65 kV, 3960 kVAr, 3-Phase, 50 C/shoused in Outdoor Type CRCA Panel, Capacitor bank having two variable step of 792 Kvar & two Variable steps of 1188 kVAr. Bank shall be complete with Capacitor units of 396/264 kVAr,Aluminium busbars, Pin & Post insulators, HRC fuses,Surge arrestor etc.including structure for complete equipments (3.96 MVAr HT Capacitor bank) |
| 526 | 0.52 kVAr for 792 kVAr step(3.96 MVAr HT Capacitor bank) |
| 527 | 0.8 kVAr for 1188 kVAr step(3.96 MVAr HT Capacitor bank) |
| 528 | 11 kV, 3-Phase Dry Type RVT(3.96 MVAr HT Capacitor bank) |
| 529 | 12 kV 3 Phase Indoor type metal enclosed Vacuum Capacitor switches.(3.96 MVAr HT Capacitor bank) |
| 530 | 11 kV, 400 Amp, Off Load Isolator with earth switch and mounting structure.(3.96 MVAr HT Capacitor bank) |
| 531 | 9 kV, 10 kA,Station Class, Lightning Arrestors(3.96 MVAr HT Capacitor bank) |
| 532 | Indoor Type Automatic Control Unit(3.96 MVAr HT Capacitor bank) |
| 533 | IP 55 , Outdoor CRCA cubicle Panel for accomdating capacitors,Series Reactor,Vacuum contactor,Surge arrestor,Fuses(3.96 MVAr HT Capacitor bank) |
| 534 | Control cables, lugs/thimble, Junction Box etc.(3.96 MVAr HT Capacitor bank) |
| 535 | 11 KV 3 Core Al. XLPE Insulated 3x120 mm sq. Cable(3.96 MVAr HT Capacitor bank) |
| 536 | 11KV XLPE Cable(3x185 sq.mm.) Heat Shrinkable Jointing kit Indoor(3.96 MVAr HT Capacitor bank) |
| 537 | 11KV XLPE Cable(3x185 sq.mm.) Heat Shrinkable Jointing kit Outdoor(3.96 MVAr HT Capacitor bank) |
| 538 | 11 KV VCB Switchgear with complete arangement for connection with existing 11 KV bus bar.(3.96 MVAr HT Capacitor bank) |
| 539 | Earthing for Panel and LA\"s by pipe in pipe earthing(3.96 MVAr HT Capacitor bank) |
| 540 | Supply of Earthing of existing substation and Distribution Transformer |
| 541 | Supply of Spike Earthing 20mm X 2500 mm GI solidRod |
| 542 | Supply of Pipe rod earthing with 3000mm long, 40 mm diameterGI pipe, GI Strip of 24x3mm. |
| 543 | Supply of 8 SWG GI wire for earthing |
| 544 | Supply of Renovation and Modernization of Existing Substation, Battery Charger and Battery set |
| 545 | 24V, 150 AHPb(Lead) Acid battery, battery standmade of teakwood duly painted with anti acid resistive paint, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single coremulti strand cable, terminal connectors, Rubber mats & all other accessories and connectors as per technical specifications. |
| 546 | 24V, 150 AH.Float-cum-Boost Battery Charger with full wave rectification for230V,1 phase, 50 Hz AC Input Supply as per technical specifications. |
| 547 | MS Galvanised structures (all Type) made of joist / channel / angle / flat of different sections as per approved drawings. All structural steel members shall be galvanized after fabrication as per IS:4759 for all structural members. 3.5mm spring washers are to be used under each structural steel shall conform to IS 2026. All weld shall be 6mm filled weld unless specified otherwise.Anchor plat shall be of relevant IS |
| 548 | GI bolts & nuts, washers etc. (all Type) should be as per approved drawings & TS. All bolts & nuts, washers etc. shall be galvanizedas per IS:4759. 3.5mm spring washers are to be used under each nut shall conform to IS 2026.All nuts and bolts shall be of property class 5.6 of IS 1367. Plain washers shall be as per IS 2016 & spring washers shall be IS: 3063 and foundation bolts, shall be of relevant IS |
| 549 | 36kV, 1250A,25kA for 3 seconds, 3-ph, Outdoor typeVacuum Circuit breaker with marshalling box etc Complete in all respect along with support structure. |
| 550 | 36kV, 1-Phase, 25kA/3 seconds,800-400-200/1-1-1 Amps ( having 3 secondery, core), 1 set = 3 Nos outdoortype Current Transformers along with junction box (1 no junction box for 3 no of 1-phase CTs), as required as per technical specifications complete in all respect. |
| 551 | 36kV, 1-Phase, 25kA/3 seconds,33 Kv/110 V single core outdoortype Potential Transformers along with junction box, as required as per technical specifications complete in all respect. |
| 552 | 30 kV, 10kA, 1-ph Station Class Lightening Arrester complete(1 set= 3 Nos.) |
| 553 | 36kV, 800A, 25kA , 3-ph double break center rotating type (DBCR), Gang Operated,isolator alongwith Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete as per Technical Specifications. (with Earth Switch) |
| 554 | 33 kV feeder Panel (without diffirential relays) with arrangements for DLMS(modem compactible ) Trivector Static Energy Meter complete |
| 555 | 12 kV, 1250 A, 25kAfor 3 seconds, 3-ph, indoor typeVacuum Circuit BreakerforIncomer along with 12 kV, 1-Phase, 25kA, 600-300/5-5 A, 3 Nos indoor type Current Transformer 3 Core, Potential Transformer 11KV/110 V, indoor mounting type control panel for incoming breaker and required accessories, A-meter, volt-meter, 3-phase , withDLMS(modem compactible ) Tri Vector energy meter, Numerical Relays & accessories complete as per specifications for transformer breaker protectionwith earth fault, overcurrent . |
| 556 | 12 kV, 1250 A, 25kAfor 3 seconds, 3-ph, indoor typeVacuum Circuit Breakerforalong with 12 kV, 1-Phase, 25kA, 600-300/5-5 A,3 Nos indoor type Current Transformer, control panel for Bus couplar and required accessories, A-meter, Numerical Relays & accessories complete as per specifications for Bus Coupler protectionwith earth fault, overcurrent . |
| 557 | 12 KV 3 Ph 1250 A, 25kAfor 3 seconds, 3-ph, indoor typeVacuum Circuitbreaker along with 12 kV, 1-Phase, 25kA, 11 kv/110v,indoor type PotentialTransformer,indoor mounting type control panel and required accessories, A-meter, Numerical Relay & accessories complete as perspecifications for feeder breaker protection & Protection for Earth fault and over current) with extensible arrangement for future |
| 558 | 9kV, 10kA, 1-ph Station Class LighteningArrester complete (1 Set = 3 Nos.) |
| 559 | 12kV, 630 A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), Gang Operated,isolator along with Support Insulators, Operating Mechanism, Base Channel down Pipe and all required accessories complete as per technical specifications, scope of works and approved drawings . |
| 560 | 11 kv Bus-Coupler with all required accessories complete as per technical specifications, scope of works and approved drawings . |
| 561 | Supply of 3CX300 Sqmm 33 KV XLPE Armored Cable |
| 562 | Supply of 33 KV3Cx300 Sqmm XLPE Armored Cable (2 Nos including one spare) Accessories like 160mm dia HDPE pipes for road crossing and 150 mm dia GI pipegrade B for pole support outdoor heat shrinkable cable jointing kits, Lugs,CablePath markers, bi metallic clamps, 7/20 GI wire as per technical specification, approved drawing and scope of work |
| 563 | Supply of 3Cx185 Sqmm 11 KV XLPE Armored Cable |
| 564 | Supply of 11 KV3Cx185 Sqmm XLPE Armored Cable (2 Nos including one spare) Accessories like 160mm dia HDPE pipes for road crossing and 150 mm dia GI pipegrade B for pole support, GI Brackets, cable fixing U clamp with suitable nut & bolts, outdoor heat shrinkable cable jointing kits, Lugs,CablePath markers, bi metallic clamps, 7/20 GI wire as per technical specification, approved drawing and scope of work |
| 565 | Supply of DT Capacitor with Fitting as per Technical Specification, Approved Drawing and scope of work |
| 566 | Supply of LT Shunt capacitor 440 Volt 10 KVAr 3Phase 50Hz IP65 |
| 567 | Supply of LT Shunt capacitor 440 Volt 25 KVAr 3Phase 50Hz IP65 |
| 568 | LT Line with XLPE Armoured Cable in high loss area |
| 569 | 8.5 m/180 kgs PCC Poles (PCC Pole as per state practice) |
| 570 | 9 M long steel Tubular poles with welded steel base plate of Designation 410 SP 31 |
| 571 | Supply of Pole accessories as per technical specification, approved drawing and scope of work |
| 572 | Supply of Stone Pad 300X300X75 |
| 573 | Supply of Stay Set (Galvanized) with 50x8 mm stay clamp, stay guy insulator (1 Nos.), anchor plate (200x200x6), nut bolts, 1 Nos turn-buckles, 1.8 m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI strandedwire complete as per technical specification, approved drawings and scope of work. |
| 574 | Supply of Single core XLPE armoured cable as per technical specifications, approved drawings and scope of work. |
| 575 | 1.1 kV Single Core 25sqmm XLPE armoured cable (1Cx25 sqmm) |
| 576 | 1.1 kV Single Core 50sqmm XLPE armoured cable (1Cx50 sqmm) |
| 577 | 1.1 kV Single Core 95sqmm XLPE armoured cable (1Cx95 sqmm) |
| 578 | 1.1 kV Single Core 120sqmm XLPE armoured cable (1Cx120 sqmm) |
| 579 | LT cross arm arrangement angel (50x50x6mm) (50x8mm) (weight-9.41 kg)with Nuts and bolts |
| 580 | LT cross arm arrangement angel (75x75x8mm) (65x8mm) (weight-18.6 kg) with Nuts and bolts |
| 581 | C-Clamp with Nut & bolts |
| 582 | LT shakle insulator |
| 583 | Distribution tie for shakle insulator |
| 584 | Mid span joint 25sqmm |
| 585 | Mid span joint 50sqmm |
| 586 | Mid span joint 95sqmm |
| 587 | Mid span joint 120sqmm |
| 588 | Single phase 20SWG CRCA MS sheet by deep drawn/sheet bending processPole top distribution box with calmps (50x6 mm) and nut & bolts and lugs suitable for 25 sqmm armoured cable |
| 589 | Three phase 20SWG CRCA MS sheet by deep drawn/sheet bending processPole top distribution box with calmps (50x6 mm) and nut & bolts and lugs suitable for 50 sqmm armoured cable |
| 590 | Three phase 20SWG CRCA MS sheet by deep drawn/sheet bending processPole top distribution box with calmps (50x6 mm) and nut & bolts and lugs suitable for 95 sqmm armoured cable |
| 591 | Three phase 20SWG CRCA MS sheet by deep drawn/sheet bending processPole top distribution box with calmps (50x6 mm) and nut & bolts and lugs suitable for 120 sqmm armoured cable |
| 592 | Suppply of 2Cx25 SQMM Stranded Unarmoured Cable (Al Conductor ) for chargingSingle Phase DB |
| 593 | Suppply of 4Cx35SQMM Stranded Unarmoured Cable (Al Conductor ) for chargingThreePhase DB |
| 594 | Supply of Spike Earthing 20mm X 2500 mm GI solidRod |
| 595 | 8 SWG GI wire for pole,DB earthingwith GI nuts, bolts & washers |
| 596 | LT insulation Piercing Connectors of 16-150 sqmm size for energizing distibution Kiosk/box |
| 597 | Erection of new 33/11 KV Substation Works as per Scope of work, Approved Drawings and Technical Specifications |
| 598 | Civil works: Design, supply of all material, T&P, labour etc for the following civil works complete as per TS |
| 599 | Soil Investigation & Contour Survey of Substation areaas per Technical Specification |
| 600 | Earth Filling & Site Levelling |
| 601 | Earth work in PSS site with ordinary soil (vide classification of soil item - A) obtained from borrow pits free from logs, stumps, roots, rubbish or any other ingredients likely to deteriorate or affect the stability of the (1.00 meter filling considered size 60*40) site surface including breaking the clods maximum to 60 mm. cube, placing the earth in layers not exceeding 225 mm in loose thickness, rough dressing including cost of cutting and removing shrubs, roots falling in borrow area all complete as per approved design & technical specification and as per direction of Engineer in Charge (payment will be made as per actual requirement per cubic meter) |
| 602 | Antiweded treatment and stone spreading in switchyard area excluding road, Cable trench, Drainage etc (Stone Spreading 6 inches over 4 inches lean cement concrete layer as per technical specification, approved desgn and drawing and as per directon of Engineer in Charge. (payment will be made as per actual requirement per Square meter) |
| 603 | Construction of Boundary Wall including Barbed Wire Fencing on MS angle over the Boundary Walland one Gate per Substation, including Supply, Fabrication, Fixing, Painting all complete as per approved Drawing & Technical Specification and as per directon of Engineer in Charge in all 33/11 kV new sub-stations(payment will be made as per actual requirement per meter) |
| 604 | Security fencing along with one switchyard gate per Substation as per Technical specifications in all 33/11 kV new sub-stations - to isolate electrical yard and as per directon of Engineer in Charge in all 33/11 kV new sub-stations(payment will be made as per actual requirement per meter) |
| 605 | Design, engineering and construction of Control Room Building ( Hall of control room building -16 x 8 Mtr.(size may vary as per availability of land) and Guard room, store room, Battery room, Incharge room & Wash room etc.) including supply of T&P, Labour, Cement, Reinforcement Steel, Form Work, Excavation etc, all complete as per Technical Specification and Approved Drawing and as per directon of Engineer in Charge in all 33/11 kV new sub-stations(payment will be made as per actual requirement per Sq. meter plinth area) |
| 606 | Design, engineering and construction of Cable Trench of 0.75 Mtr wide , 1.0 Mtr. depth, precast RCC Trench Cover, Water stops, Brick Work wherever required includingsupply of T&P, Labour, Cement, Sand,Reinforcement Steel, Steel Angles, Flats, Form Work, Excavation and providingcement plaster (1:4) including floating coat of cement punning (1.5 MM) with clean pores sand etc, all complete as per Technical Specification, approved Drawing and as per directon of Engineer in Charge in all 33/11 kV new sub-stations(payment will be made as per actual requirement permeter) |
| 607 | Design, engineering and construction of Drainage System in the Substation premises includingsupply of T&P, Labour, Cement, , bricks, Form Work, Excavation etc, all complete as per design, Technical Specification and Tender Drawings in all 33/11 kV new sub-stationas as per directon of Engineer in Charge in all 33/11 kV new sub-stations(payment will be made as per actual requirement permeter) |
| 608 | Design, engineering and construction of PCC road, footpath including supply of T and P, labour, brick, stone and stonechips, earth,and excavation, compaction etc. all complete as per Technical specifications. |
| 609 | width of PCC road3.75 m- in M20, 200 mm Thick over compacted WBM in three layers (Grade-I-100 mm thick, Grade-II-75 mm thick, Grade - III - 75mm thick) etc as per PWD Specification and direction of Engineer In Charge. (payment will be made as per actual requirement per meter) |
| 610 | width of footpath 1.5 m-PCC in M15, 150 mm Thick over Brick on edge soling over 75 mm thick local sand filling etc as per PWD Specification and direction of Engineer In Charge. (payment will be made as per actual requirement per meter) |
| 611 | Stone pitching over sloping including supply of stone and surface preparation as per drawing and as per direction of Engineer in charge.(payment will be made as per actual requirement per Sq. meter) |
| 612 | Sinking of tube well and installation of motor operated submersible pump of suitable capacity with 1000 ltr. Sintex or reputed make water tank including GI Pipe(heavy duty) pipe line and sanitary fittings complete in all respect fortoilets , drinking water and providing water tap near the power transformer for watering the earth pit as per requirement. The depth of Tube-Well should be minimum 80 mtr. |
| 613 | Design, Engineering and construction of transformer foundation, erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power Transformer along with transformer oil, Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips with braided conductor on bushing end supported with insulators, OTI & WTI Indicators, Vent explosion plug, control wiring / cabling, cable supporting tray on the body, transformer wheels, bushing and extended copper connector made of 50x10 mm copper flat for connection of 11 KV side bushing with suitable bolts nuts and washers of Brassetcas required . 2 sets of body earthing with 50x8 mm GS Strip as per TS and as per direction of Engineer in Charge |
| 614 | 5 MVA with off load tap changer |
| 615 | 10 MVA with off load tap changer |
| 616 | Design, Engineering, providing and construction of transformer support/foundation, erection, testing and commissioning of 100 KVA, 11/0.415 kV, 3 ph, 50 Hz, ONAN, outdoor type (three star rated) Station Transformer on double pole structure alongwith HG Fuse set, AB Switch/ Isolator, LA, Earthing, etc complete to complete the erection testing & commissioning of SST as required as per specifications & drawings complete in all respect.as per direction of Engineer in Charge |
| 617 | Excavation, erection, cement concrete foundation, erection, testing and commissioning of all type of structures i.e. Gantry/Swing bus/isolator/CT/PT/PI/S.S.T structures etc. made of joist / channel / angle / flat of different sections as per approved drawings complete in all respect as per direction of Engineer in Charge |
| 618 | Design, Engineering and construction of foundation , erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor typeVacuum Circuit breakeralong with 36kV, 1-Phase, 25kA for 3 seconds, 800-400-200/1-1-1 Amp.or 800-400-200/1-1, Amps outdoor type Current Transformer along with junction box (1 no junction box for 3 no of 1-phase CTs)], Jumpers, earthing, supporting structures, maintenance platform, marshalling box, control & Power cabling between VCB and indoor control panel and required accessories complete as per approved drawings, technical specifications and scope of the work. as per direction of Engineer in Charge |
| 619 | Design, Engineering providing and installation of ISMC 75 channel on top of indoor trench, erection of panels on ISMC 75 channels, welding, testing and commissioning of 33kV indoor Control & Relay panel along with E/F & O/C relays, control and power supply cabling in trench between field equipment and panels, Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other components etc as per approved drawings, technical specifications and scope of the work for controlling complete in all respect |
| 620 | 33 kV feeder Panel (without diffirential relays) withDLMS(modem compactible ) Trivector Static Energy Meter complete |
| 621 | 33 kV Transformer Panel (withdiffirential relays) withDLMS(modem compactible ) Trivector Static Energy Meter complete |
| 622 | Design, Engineering and construction , Erection, testing and commissioning of 36kV, 800 A, 25kA , 3-ph double break center rotating type (DBCR), Gang Operated,isolator along with Support Insulators, Operating Mechanism, Base Channel down Pipe and all required accessories complete as per approved drawings, technical specifications and scope of the work,(with and without Earth Switch) |
| 623 | Design, Engineering , Erection, testing and Commissioning of 30 kV, 10kA, 1-ph Station Class Lightening Arresters with mounting on erected structures, jumpering from bus bar, earthing connection using 50x6mm GS flat, hardware etc as required, as per approved drawings, technical specifications and scope of the work complete in all respect(1 Set= 3 Nos) |
| 624 | Design, Engineering, Erection, testing and Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester with mounting on erected structure, jumpering from bus bar, earthing connection using 50x6mm GS flat, hardware, etc as required as per approved drawings, technical specifications and scope of the work.(1 Set=3 Nos) |
| 625 | Design, Engineering and construction , Erection, testing and Commissioning of 36 kV, 1-Phase, 33kV/110 volt, Single coreoutdoor type Potential transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including control and power supply cabling,earthing connection using 50x6mm GS flat and required accessories etc., complete as per as per approved drawings, technical specifications and scope of the work, |
| 626 | Design, Engineering and construction , erection, wiring, testing and commissioning of 12 kV, 1250 A/630 A , 25kA, 3-ph,indoor typeVacuum Circuit breakeralong with 12 kV, 1-Phase, 25kA for 3 seconds, 600-300-150/5-5 A and 1200-600-300/1-1-1 A CT , PT, andalong with control and relay panel consisting of Ammeter, volt-meter, E/F, O/C ,diff.Relay and 3 Phase Energy meter & accessories complete cabling between VCB and indoor control panel and required accessories complete as per approved drawings, technical specifications and scope of the work, |
| 627 | For Transformer Protection |
| 628 | For Feeder Protection |
| 629 | For Bus Coupler |
| 630 | Installation, initial charging, cabling, interconnection cabling, testing and commissioning of 30 V, 150 AHPb(Lead) Acid battery on battery stand made of teak wood duly painted with anti acid resistive paint, battery insulators, inter-battery wiring using 30 sqm copper single core multi strand cable, terminal connectors, & all other accessories and connectors as per as per approved drawings, technical specifications and scope of the work complete in all respect, |
| 631 | Design, engineering, construction , Installation, interconnection cabling, testing and commissioning of 24V, 150 Amp.Float-Cum-Boost Battery Charger with full wave rectification for230 V,1 phase, 50 Hz AC Input Supply with DCDB (as per supply schedule) as per approved drawings, technical specifications and scope of the work complete in all respect |
| 632 | Design, engineering, construction , Installation, interconnection cabling, testing and commissioning of 30V SupplyDCDB as per approved drawings, technical specifications and scope of the work & supply schedule complete in all respect. |
| 633 | Design, engineering, construction , Installation, interconnection cabling, testing and commissioning of 415 V, ACDB as per approved drawings, technical specifications and scope of the work, |
| 634 | Excavation, laying, welding, refilling, earthing & grounding of MS Flat as per Approveddrawing and erection of riser up to various equipment/structures as per scope of the work, specifications and approved drawings, |
| 635 | 75 x 8 mm MS flat for ground mat |
| 636 | 50 x 6 mm Galvanized GS flat (risers) |
| 637 | 25 mm dia MS Rod 3 m long for earth mat |
| 638 | Excavation, erection, testing and commissioning of 40 mm dia., 3000 mm long GI pipe earth electrode by providing test link, RCC pit, RCC cover, placedon GI frame, Charcoal & Salt in alternate layer as per REC Specification and other accessories complete as per approved drawings, technical specifications and scope of the work for power transformer neutral, station transformer neutral, lightening arresters direct earthing. |
| 639 | Erection, testing and commissioning of Bus Bar, jumpering and Dropper (Panther Conductor), by using all types of insulators, clamps and connectors etc. with all accessories complete in all respect. |
| 640 | Erection, testing and commissioning of Sub-Station Lighting System (External+Internal) with proper illumination levels complete for Switchyard, Control Room building, Main gate and Sub station boundary including all associated materials etc complete in all respect as per applicable TS and approved drawing. |
| 641 | Design, engineering,Erection, testing and commissioning ofFully automatic Capacitor bank with automatic control panel, isolator,indoor type suitable Vacuum Circuit Breaker, mounting structures, All types of cable (11 KV grade 185 sqmm, XLPE & control cable etc.) & its accessoriescomplete , earthing etc as required as per technical specifications, approved drawings, scope of the works of following capacities: (Banks in Muiltiple of 600 KVAR as per REC Specification) |
| 642 | 1980 KVAr |
| 643 | 3960 KVAr |
| 644 | Erection, testing and commissioning of 2x2.5 sqmm control cablefor the commissioning of sub-station |
| 645 | Erection, testing and commissioning of 4x2.5 sqmm control cable for the commissioning of sub-station |
| 646 | Erection, testing and commissioning of 3.5x 95 sqmm LT power cable required for the commissioning of sub-station |
| 647 | Laying & termination, Testing and commissioning of 11 KV grade, XLPE,power cable armored, aluminium conductor, stranded complete in all respectas per Technical Specification. |
| 648 | 3Cx 400 sqmm (armoured) |
| 649 | 3Cx 185 sqmm (armoured) |
| 650 | 3Cx35 Sqmm (Un -armoured) |
| 651 | Design, Engineering and construction , Erection, testing and commissioning of 12 kV, 630 A, 25 kA, 3-phGang Operated, TPMO along with Support Insulators, Operating Mechanism, Base Channel down Pipe and all required accessories complete as per approved drawings, technical specifications and scope of the work, (with and without earth Switch) |
| 652 | Erection, testing & commissioning of bus by using Panther conductor with all types of Clamps and Connectors and insulator as per TS & approved drawings (payment will be made as per actual requirement permeter) |
| 653 | Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scope of work, approved drawings and specifications: |
| 654 | 8.5 m/180 kgs PCC Poles - (PCC Pole as per state practice) |
| 655 | Erection of following types of poles for 11 KV double pole outgoing feeder line by installing danger plate, anti-climbing devices (barbed wire),pole numbering, earthing, including cement concrete foundation using 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) etc as per scope of work, approved drawings and specifications: |
| 656 | Erection of 8.5 m/180 Kgs PCC Poles withBase stone pad(state practices of PCC pole and base plate/stone to be used) |
| 657 | Erection of New 33/11 KV Indoor GIS Type Substation as per Scope of work, Approved Drawings and Technical Specifications |
| 658 | Installation & Commissioning of 10 MVA 33/11 kV Transformer with all complete assesories as per TS |
| 659 | Erection of 33 KV GIS Panels with 2 line bays, 2 transformer bays, one bus coupler bay, Bus PT, all complete with numerical relays, facility for data transmission and remote control this includes PT raiser panel etc. if required. |
| 660 | Erection of 11 KV GIS Panels with 6 line bays, 2 transformer bays, 1 station transformer bay & one bus coupler bay, Bus PT, all complete with numerical relays, facility for data transmission and remote control this includes PT raiser panel etc. if required. PT required for each of the bus section. |
| 661 | Erection of 24 V, 150AH, Ni-Cd sealed type battery set and all other accessories complete. |
| 662 | Erection of Float-cum-boost battery charger (SMPS based ) with full wave , full control rectification, 50Hz input voltage for charging 24V, 80 AH Battery alongwith DCDB, connectors etc. complete and connection with 24 V , 80AH Battery set and single phase AC input supply. |
| 663 | Erection of 415V AC Distribution Board/Panel of sheet stealenclosed cubical floor mounting type for catering auxiliary power supply of the substaion etc. complete |
| 664 | Erection of 100KVA, 11 kV/0.415 kv Station Transformer alongwith allaccessories as per TS. |
| 665 | Erection of40mm dia 3000mm long GI Pipe (Medium Grade) earth electrodes & other accessories for treated earth erection is including of Excavation and other associated activities as per TS. |
| 666 | Erection of 60x8 mm Galvanized flat for raiser for earthing as per TS |
| 667 | Erection of 30 KV, 1 Phase, 10KA LA with all accessories as per TS. |
| 668 | Erection of 9 KV, 1 Phase, 10KA LA with all accessories as per TS. |
| 669 | Suplly & Laying of 3Cx300 sqmm. 33 KV cable (Panel to Transformer- 1 Run) with cable tray. |
| 670 | Laying of 3Cx400 sqmm. 11 KV cable (Panel to Transformer- 2 Run) with cable tray. |
| 671 | Laying of Control Cable of 2 core 2.5 sq. mm copper cable with cable tray and associated items |
| 672 | Laying of Control Cable of 4 core 2.5 sq. mm copper cable with cable tray associated items |
| 673 | Laying of Control Cable of 10 core 2.5 sq. mm copper cable with cable tray associated items |
| 674 | Erection of 33 kV Silicon coated touchproof Indoor termination joint (Al) kit for XLPE 3 C X 300 sqmm |
| 675 | Erection of 11 kV Silicon coated touchproof Indoor termination joint (Al) kit for XLPE 3 C X 400 sqmm(Incoming) |
| 676 | Erection of 11KV XLPE Cable (3x400 Sq.mm.)outdoor Heat Shrinkable Termination kit boxes mounted with transformer. |
| 677 | Erection of 11 kV Silicon coated touchproof Indoor termination joint (Al) kit for XLPE 3 C X 185 sqmm |
| 678 | Erection of Complete lighting system for control room building,main gate and substation boundary including fans as per detailed Technical Specifications. |
| 679 | Design, engineering and construction of Control Room Building (including indoor cable trench) including supply of T&P, Labour, Cement, Reinforcement Steel, Form Work, Excavation etc. all complete other associated works as per Technical Specification and Drawing in 33/11 kV new GISsub-station. ( On As it is where it is basis) |
| 680 | Foundation for 10 MVA, 33/11 kV transformer including rail poles as per approved drawing as per TS( On As it is where it is basis) |
| 681 | Construction of Boundary Wall (including supply of all material) with fixing of MS angle & Barbed Wire fencing all along the boundary wall incuding supply and fixing of main gate - complete with painting etc all as per approved drawing & TS ( Measurement for this purpose will include length of gate along boundary wall).( On As it is where it is basis) |
| 682 | Construction of 3 meter wide RCC Approach Road (including supply of all material) all complete as per approved drawing & TS. |
| 683 | Construction (including supply of all material) of RCC cable Trench alongwith pre-cast RCC Trench Cover, Brick Work wherever required all complete as approved Drawing & TS outside the control room building 0.50 Mtrs. Wide Trench. |
| 684 | Erection for Augmentation/ Additional Power Transformers SCADA Compatible asper technical specifications, scope of works and approved drawings |
| 685 | Civil works: Design, supply of all material, T&P, labour etc for the following civil works complete as per TS |
| 686 | Earth Filling & Site Levelling |
| 687 | Gravel filling in switchyard area excluding road and footpath as per TS. |
| 688 | Design, engineering and construction of Cable Trench of 0.75 Mtr wide , 1.0 Mtr. depth, precast RCC Trench Cover, Water stops, Brick Work wherever required includingsupply of T&P, Labour, Cement, Sand,Reinforcement Steel, Steel Angles, Flats, Form Work, Excavation and providingcement plaster (1:4) including floating coat of cement punning (1.5 MM) with clean pores sand etc, all complete as per Technical Specification, approved Drawing and as per direction of Engineer in Charge. (Payment will be made as per actual requirement per Mtr.) |
| 689 | Design, engineering and construction of Drainage System in the Substation premises includingsupply of T&P, Labour, Cement, , bricks, Form Work, Excavation etc, all complete as per design, Technical Specification and Tender Drawings in all 33/11 kV new sub-station as per direction of Engineer in Charge. (Payment will be made as per actual requirement per Mtr.) |
| 690 | Substation works |
| 691 | Design, Engineering and construction of transformer foundation, erection, filtration, testing and commissioning of 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power Transformer along with transformer oil , Buchholtz relay, breather, OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2 sets of 50x8 mm GS Neutral Earthing strips with braided conductor on bushing end supported with insulators, OTI & WTI Indicators, Vent explosion plug, control wiring / cabling, cable supporting tray on the body, transformer wheels, bushing and extended copper connector made of 50x10 mm copper flat for connection of 11 KV side bushing with suitable bolts nuts and washers of Brassetcas required . 2 sets of body earthing with 50x8 mm GS Strip as per TS and as per direction of Engineer in Charge. |
| 692 | 5 MVA |
| 693 | 10 MVA |
| 694 | Dismantaling &Transportation from existing site to Store,Installation, Erection, Testing and Commisiioning of 5/8 MVAPower Transformerswithsuitable Clamps, Connectors, bolts nuts and washers of Brassetcas required with 2 sets each of body & neutral earthing with 50x8 mm GS Strip as per TS completely required for commissioning. |
| 695 | Modification of existing Power Transformer foundation required for installation and commissionig of augmented 5/10 MVA Power Transformers completely as per TS. (As per requirement) |
| 696 | Design, Engineering , erection, testing and commissioning of 36kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor typeVacuum Circuit breakeralong with 36kV, 1-Phase, 25kA for 3 seconds, 400-200/1-1-1 Amp.or 400-200/1-1, Amps outdoor type Current Transformer along with junction box (1 no junction box for 3 no of 1-phase CTs)], Jumpers, earthing, supporting structures, maintenance platform, marshalling box, control & Power cabling between VCB and indoor control panel and required accessories complete as per approved drawings, technical specifications, scope of the work and as per direction of Engineer in Charge. |
| 697 | Excavation, erection, cement concrete foundation, erection, testing and commissioning of all type of structures i.e. Swing bus/isolator/VCB/CT/PT/PI structure etc. made of joist / channel / angle / flat of different sections as per approved drawings |
| 698 | Design, Engineering providing and installation of ISMC 75 channel on top of indoor trench, erection of panels on ISMC 75 channels, welding, testing and commissioning of 33kV indoor Control & Relay panel along with E/F & O/C relays, control and power supply cabling in trench between field equipment and panels, Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other components etc as per approved drawings, technical specifications and scope of the work for controlling: |
| 699 | 33 kV Transformer VCB (with diffirential relays) |
| 700 | Design, Engineering and construction , Erection, testing and commissioning of 36kV,800 A, 25kA, 3-ph double break center rotating type (DBCR), Gang Operated,isolator along with Support Insulators, Operating Mechanism, Base Channel down Pipe and all required accessories complete as per approved drawings, technical specifications and scope of the work, (with and without Earth Switch) |
| 701 | Design, Engineering and construction , erection, testing and commissioning of 12kV, 1250A, 25kA for 3 seconds, 3-ph,Outdoor typeVacuum Circuit breakeralong with 12kV, 1-Phase, 25kA for 3 seconds, 600-300/1-1-1 Amp.(having 3 secondary core), outdoor type Current Transformer along with junction box (1 no junction box for 3 no of 1-phase CTs)], Jumpers, earthing, supporting structures, maintenance platform, marshalling box, control & Power cabling between VCB and indoor control panel and required accessories complete as per approved drawings, technical specifications and scope of the work. |
| 702 | 12 KV Control & Relay panel for12 KV VCB (suitable for 30 V DC tripping/closing coil and associated control Circuitry) alongwith, ElF & O/C relays, Static energy meter (class 0.5 with communication port) , Mimic Diagram, Voltmete, Ammeter, etc complete as per REC |
| 703 | Design, Engineering , Erection, testing and Commissioning of 30 kV, 10kA, 1-ph Station Class Lightening Arresters with mounting on erected structures, jumpering from bus bar, earthing connection using 50x6mm GS flat, hardware etc as required, as per approved drawings, technical specifications and scope of the work complete in all respect(1 Set= 3 Nos) |
| 704 | Design, Engineering, Erection, testing and Commissioning of 9kV, 10kA, 1-ph Station Class Lightening Arrester with mounting on erected structure, jumpering from bus bar, earthing connection using 50x6mm GS flat, hardware, etc as required as per approved drawings, technical specifications and scope of the work.(1 Set=3 Nos) |
| 705 | Excavation, laying, welding, refilling, earthing & grounding of conductor as perApprovedElectrical Layout for each sub station with ten no of treated 40mm dia, 3000 mm long GI pipe (Medium gauge) earth electode by providing test link, RCC pit, RCC cover, placedon GI frame,Charcoal & Salt in alternate layer as per REC Specification and other accessories complete as per approved drawings, technical specifications and scope of the work for power transformer neutral, station transformer neutral up to various equipment/structures as per scope of the work, specifications and approved drawings etc (treated earthing) |
| 706 | Erection, testing and commissioning of Bus Bar, jumpering and Dropper (Panther conductor), by using all types of insulators, clamps and connectors etc. with all accessories complete in all respect. |
| 707 | 11 kV, 3-ph, 200 A, 3 Pin type, Vertical Mounting type, Gang Operated,TPMO Switch along with Support Insulators, Base Channel, down Pipe, Arcing Horns etc. complete asper technical specifications, scope of works and approved drawings |
| 708 | Erection, testing and commissioning of 2x2.5 sqmm control cablefor the commissioning of sub-station |
| 709 | Erection, testing and commissioning of 4x2.5 sqmm control cable for the commissioning of sub-station |
| 710 | Dismentling of existing dismentled materials and devolution ofthe dismantled materialsincluding storage, handling, insurance, loading, unloading, transportation to store of Utility as per the direction of Engineer-in-charge with propoer accounting as per the inventory. |
| 711 | Excavation ofpole pit (of depth 1/6th of pole length) in normal soil as per scope of work, approved drawings and specifications: |
| 712 | 8.5 m/180 kgs PCC Poles - (PCC Pole as per state practice) |
| 713 | Erection of following types of poles for 11 KV double pole outgoing feeder line by installing danger plate, anti-climbing devices (barbed wire),pole numbering, earthing, including cement concrete foundation using 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) etc as per scope of work, approved drawings and specifications: |
| 714 | Erection of 8.5 m/180 Kgs PCC Poles withBase stone pad(state practices of PCC pole and base plate/stone to be used) |
| 715 | Erection for New 33 KV Line |
| 716 | Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scope of work, approved drawings and specifications: |
| 717 | Erection of 9 m PCC Poles - (PCC Pole as per state practice) |
| 718 | Erection of 11 M long steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 719 | Erection of 13 M long steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 720 | Erection of following types ofpoles by installing danger plate, anti-climbing devices (barbed wire), Painting with red oxide & aluminum paint including paint, pole numbering including cement concrete foundation using 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) etc as per scope of work, approved drawings and specifications: |
| 721 | Erection of 9 PCC Poles with Base pad including Cement concreting, (state practices of PCC pole, stone to be used) |
| 722 | 11 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 723 | 13 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 724 | Excavation of stay pit for 33 KV Stay in following type of soils,as per scope of work, approved drawings and specifications: |
| 725 | Normal soil |
| 726 | Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of stay wire, by providing Guy stay insulator and 0.3 cmt concreting 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) as per technical specifications, approved drawings and scope of works. |
| 727 | Erection, testing & commissioning of new Pre-fabricated HDG steel items like V cross arm, top clamp, cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats of given sizes for over head structures as per technical specification, approved drawings and scope of work. |
| 728 | Dismantling of existing overhead line conductor and fittings, depositing the dismantled material to employer\"s store and laying out & stringing of new ACSR conductor of following sizes by providing jointing sleeves, binding wire & tape & helical formed fittings etc as required as per technical specification, approved drawings and scope of work. |
| 729 | Erection of 6/4.72 mm+7/1.57 mm (100 mm² Al. Area) - Dog conductor |
| 730 | Digging of trench for laying of double circuit 33KV 3x300 sq.mm XLPE cable and making of trench for two nos cable with brick on both side, sand filling into the trench and finally trench will be covered with stone/Precast slab (\"PuVVNL 33 KV HT\" engraved) after laying of cable into the trench including providing and fixing cable route marker. |
| 731 | Laying of 3x300 Sq. mm 33KV XLPE insulated cable underground in cable trenchesand earth filling of trenches |
| 732 | Erection of Heat Shrinkable Jointing Kit Outdoor for 33 KV 3x300 sq. mm XLPE Cable |
| 733 | Erection of Heat Shrinkable Jointing Straight Through Kitfor 33 KV 3x300 sq. mm XLPE Cable |
| 734 | Laying of 160 mm dia. HDPE pipe by Horizontal drilling by HDD method as per site condition, for underground piping (trenchless) for road crossing. |
| 735 | Laying of 33 KV 3x300 Sqmm. XLPE Cable underground through HDPEPipe at 1050 mm below the ground surface.(by HDD method) for road crossing including providing and fixing cable route marker. |
| 736 | Laying of G.I. pipe 150 mm diawith clamp and nut & bolts |
| 737 | Digging of trench for laying of Single circuit 33KV 3x300 sq.mm XLPE cable and making of trench for two nos cable with brick on both side, sand filling into the trench and finally trench will be covered with stone/Precast slab (\"PuVVNL 33 KV HT\" engraved) after laying of cable into the trench including providing and fixing cable route marker. |
| 738 | Erection for Augmentation of 3 phase 33 kV line using new Insulator and hardware as per technical specification, approved drawings and scope of work |
| 739 | Erection of 33 KV 70 KN polymer Disc insulator along with suitable hardware fittings |
| 740 | Erection of 33 KV 10 KN Polymer Pin Insulators |
| 741 | Erection, testing & commissioning of earthing as per technical specifications,approved drawings and scope of work. |
| 742 | 8 SWG GI Coil 115 turns (1.85 kg) |
| 743 | Erection, testing & commissioning of new GI wire for earthing and guarding as per technical specification, approved drawings and scope of work. |
| 744 | Erection of 6 SWG GI wire |
| 745 | Erection of 8 SWG GI wire |
| 746 | Erection, testing & commissioning of 33 KV line for under ground railway crossing by2 Nos (including one spare) 3Cx 300 Sqmm XLPE Armored Cable (0.3 km each) , using 150MM dia GI pipes, outdoor heat shrinkable cable jointing kits, lugs,4 NosGI 3-meters long earthing pipe, 6 SWG GI wires, cable markers, clamps, jumpering and 11 KV station type lightening arrestors(6 NOS.), etc as required as per technical specifications, approved drawings and scope of he work. |
| 747 | Erection, testing & commissioning of 33 KV line for under ground highway crossing by2 Nos (including one spare) 3Cx300 Sqmm XLPE Armored Cable (0.2 km each) , using 160 mm HDPE pipe at road crossing, 150MM dia GI pipes for cable support, outdoor heat shrinkable cable jointing kits, lugs,4 NosGI 3-meters long earthing pipe, 6 SWG GI wires, 7/20 GI wire, cable markers, clamps, jumpering, 11 KV station type lightening arrestors(6 NOS.), etc as required as per technical specifications, approved drawings and scope of he work. |
| 748 | Erection for new 11 KV linesas per scope of work, approved drawings and specifications: |
| 749 | Excavation of pole pit (of depth 1/6th of pole length) in normal soil as per scope of work, approved drawings and specifications: |
| 750 | 8.5 m/180 kgs PCC Poles - (PCC Pole as per state practice) |
| 751 | 11 M long steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 752 | Erection of following types of poles for 11 KV overhead line by installing danger plate, anti-climbing devices (barbed wire),pole numbering including cement concrete foundation using 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) etc as per scope of work, approved drawings and specifications: |
| 753 | Erection of 8.5 m/180 Kgs PCC Poles withBase stone pad(state practices of PCC pole and base plate/stone to be used) |
| 754 | 11 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 755 | Excavation of stay pit in following type of soils,as per scope of work, approved drawings and specifications: |
| 756 | Normal soil |
| 757 | Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator and 0.2 cmt concreting 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) as per technical specifications, approved drawings and scope of works. |
| 758 | Erection, testing and commissioning of 11 kV insulator including their hardware fittings as per technical specification, approved drawings and scope of work. |
| 759 | Erection of 5 KN 11 kV Polymer Pin insulator |
| 760 | Erection of 45 KN 11 kV Polymer Disc insulator with strain hardware |
| 761 | Laying out, tensioning, binding of new conductor and tightening of stays and stringing, testing and commissioning of ACSRConductor of following sizes including jointing sleeves, helical formed fittings, jumpering and by providing & erecting PG Clamps etc as required as per approved drawings, scope of work and technical specifications |
| 762 | Stringing of 6/2.59 + 1/2.59 mm (30 mm² Al. Area) - Weasel |
| 763 | Stringing of 6/3.35 + 1/3.35 mm (50 mm² Al. Area) - Rabbit |
| 764 | Stringing of 6/4.72 mm+7/1.57 mm (100 mm² Al. Area) - Dog |
| 765 | Stringing of Insulated covered Conductor (50 Sqmm) |
| 766 | Stinging of 11 Kv Line on 3x70 sqmm XLPE Cable |
| 767 | Erection, testing & commissioning of pre-fabricated HDG steel items like V cross arm, top channel, top clamp, cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats of given sizes for over head structures and HDG MS nuts, bolts & washers as per technical specification, approved drawings and scope of work. |
| 768 | Providing and fixing of Danger Board IncludingMaterial and its Fabrication ,Painting ,Writing ,Logo and Scheme etc as Per RDSS Guidelines and T.S |
| 769 | Earthingand guarding arrangement as per technical specifications,approved drawings and scope of work. |
| 770 | Erection, testing & commissioning of Spike Earthing 20mm solid Rod |
| 771 | Erection of 6 SWG GI wire for earthing and guarding |
| 772 | Erection of 8 SWG GI wire for earthing and guarding |
| 773 | Digging of trench for laying of double circuit 11KV 3x185 sq.mm XLPE cable and making of trench for two nos cable with brick on both side, sand filling into the trench and finally trench will be covered with stone slab /Precast slab (\"PuVVNL 11 KV HT\" engraved) after laying of cable into the trench including providing and fixing cable route marker. |
| 774 | Laying of 3x185 Sq. mm 11KV XLPE insulated cable underground in cable trenchesand earth filling of trenches |
| 775 | Erection of Heat Shrinkable Jointing Kit Outdoor for 11 KV 3x185 sq. mm XLPE Cable |
| 776 | Erection of Heat Shrinkable Jointing Kit Straight throughfor 11 KV 3x185 sq. mm XLPE Cable |
| 777 | laying of 110 mm dia. HDPE pipe by Horizontal drilling by HDD method as per site condition, for underground piping (trenchless) |
| 778 | Laying of 11 KV 3Cx185 sq.mm XLPE Cable underground through HDPEPipe at 950 mm below the ground surface. (by HDD method) including providing and fixing cable route marker. |
| 779 | Digging of trench for laying of Single circuit 11KV 3x185 sq.mm XLPE cable and making of trench for one nos cable with brick on both side, sand filling into the trench and finally trench will be covered with stone slab after laying of cable into the trench. |
| 780 | Erection, testing & commissioning of 11 KV line for under ground railway crossing by2 Nos (including one spare) 3Cx185 Sqmm XLPE Armored Cable (0.3 km each) , using 150MM dia GI pipes, outdoor heat shrinkable cable jointing kits, lugs,4 NosGI 3-meters long earthing pipe, 6 SWG GI wires, cable markers, clamps, jumpering and 11 KV station type lightening arrestors(6 NOS.), etc as required as per technical specifications, approved drawings and scope of he work. |
| 781 | Erection, testing & commissioning of 11 KV line for under ground highway crossing by2 Nos (including one spare) 3Cx185 Sqmm XLPE Armored Cable (0.3 km each) , using 160 mm HDPE pipe at road crossing, 150MM dia GI pipes for cable support, outdoor heat shrinkable cable jointing kits, lugs,4 NosGI 3-meters long earthing pipe, 6 SWG GI wires, 7/20 GI wire, cable markers, clamps, jumpering, 11 KV station type lightening arrestors(6 NOS.), etc as required as per technical specifications, approved drawings and scope of he work. |
| 782 | Erection of Installation of new Distribution Transformer - 11/0.4 KV Three phase 25 KVA T/F |
| 783 | Erection for New Distribution Transformer accessories and supports as per technical specification, approved drawings and scope of work. |
| 784 | Survey, route alignment & pole spotting, preparation of survey report and uploading in the web portal after approval of Project Manager/Engineer in Charge |
| 785 | Erection of following types of poles for Distribution Sub Stations by providing and installing danger plate, anti-climbing devices (barbed wire), earthing material with and 8 SWG GI wire, red oxide & aluminium paint, pole numbering including Excavation of Pole Pit (of depth 1/6th of pole length), cement concrete foundation [For all types of Poles] using cement concreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) with top muffing (0.88 cmt/pole for STP Poles and 0.268 cmt/Pole for PCC Poles) etc as per scope of work, approved drawings and specifications: |
| 786 | Supply of 8.5m/180 kgs PCC Poles - (PCC Pole as per state practice) |
| 787 | Supply of 11 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 788 | Erection, testing, commissioning of Galvanized Pre-fabricated steel items like DC cross arm, back clamps, pole clamp, DO mounting channel, transformer mounting channel, transformer clamping set, transformer belting set and GI nuts, bolts & washers including painting by red oxide & aluminium as per technical specification, approved drawings and scope of work. |
| 789 | Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator (1 Nos.) and Excavation of Stay Pit, 0.2 cmt concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per technical specifications, approved drawings and scope of works. |
| 790 | Erection, testing and commissioning of 11 kV insulator including their hardware fittings as per technical specification, approved drawings and scope of work. |
| 791 | 11 kV Pin insulator with GI pin |
| 792 | 11 kV Disc insulator with strain hardware |
| 793 | Erection, testing and Commissioning of 11 KV, 200 A, 3-pole AB Switch for Distribution Transformer Substation as per Technical Specification, approved Drawing & Scope of works |
| 794 | Erection, testing and commissioning of 9 KV, 5 KA Distribution Class Lightening Arrester for DT as per technical specification, approved drawings and scope of work. |
| 795 | Erection, testing and commissioning of 11 kV, 200 Amp 3-ph, Horn Gap fuse units (set of 3 units) along with Support Insulators, Base Channel, fuse barrel etc. complete asper technical specifications, scope of works and approved drawings |
| 796 | Erection, Testing and Commissioning of Distribution Transformerwith all accessories as per scope of work, approved drawings and specifications: |
| 797 | 11/0.4 KV Distribution Transformer 25 KVA 3 phaseDTR |
| 798 | 11/0.4 KV Distribution Transformer 63 KVA 3 phaseDTR |
| 799 | 11/0.4 KV Distribution Transformer 100 KVA 3 phaseDTR |
| 800 | 11/0.4 KV Distribution Transformer 250 KVA 3 phaseDTR |
| 801 | Erection, testing and Commissioning of Outdoor mounting type Distribution box made of MS sheet of thickness not less than 18 SWG CRCA sheet by deep drawn method, dust and moisture vermin, weather proof with degree of protection with suitable bus bars, Modem Compatible DLMS Compliant LT Trivector Static Meter with suitable CTs, earthing bus, earthing terminals, box illumination, front door operated with proper locking arrangement, lugs, mounting channel frame, internal wiring with FRLS cables, danger plate, numbering, back clamps, hardware as per scope of the work, technical specifications and approved drawings, direction of Engineer in Charge suitable for following transformer: |
| 802 | 3 Ph 25 KVA transformer 40 A TPN MCCB (incomer) and 6 Nos. 25 A SP MCCB (outgoing) with metering |
| 803 | 3 Ph 63 KVA Transformer having 200 A TPN isolator, 100 A HRC fuse (incomer) and 6 Nos. 60 A SP MCCB (outgoing) |
| 804 | 3 Ph 100 KVA Transformer having 200 A TPN isolator, 160A HRC fuse (incomer) and 6 Nos. 90 A SP MCCB (outgoing) |
| 805 | 3 Ph 250 KVA Transformer having 600 A TPN isolator, 315 A HRC fuse (incomer) and 9 Nos. 120 A SP MCCB (outgoing) |
| 806 | Erection, testing and Commissioning of 2 Nos Spike Earthing 20x2000 mm and 1 Nos Chemical earthing 40x3000 mm , as per IS 1161, making earth grid using 6 SWG GI wire as per scope of work, approved drawings and technical specifications, |
| 807 | Erection, testing and Commissioning of 1.1 KV XLPE Aluminium Conductor, Stranded, unarmoured cable for connection of transformer LV bushing to Distribution Box and Distribution box to overhead line as per Scope of work, technical specification and approved drawings: |
| 808 | 1CX35 sqmm aluminium conductor cable |
| 809 | 1Cx70 sqmm aluminium conductor cable |
| 810 | 1Cx150 sqmm aluminium conductor cable |
| 811 | 1Cx400 sqmm aluminium conductor cable |
| 812 | Erection, testing and commissioning of ACSR Rabbit Conductor for jumpering including PG Clamps, bi-metallic connectors, hardware etc as per Technical Specification, approved Drawing & Scope of works |
| 813 | Erection of Augmentation of existing Distribution transformeras per scope of work, approved drawings and specifications: |
| 814 | Erection for augmentation of Distribution Transformers including cables, Stay & Earthing (2 Nos), with Lugs, copper L-clamp as required, bushing capsfrom 11/0.4 KV Substation/Double Pole/Plinth as per Technical Specifications, Scope of Work and Approved Drawings. |
| 815 | 11/0.433 kV 25kVA Distribution Transformer |
| 816 | 11/0.433 kV 63kVA Distribution Transformer |
| 817 | 11/0.433 kV 100kVA Distribution Transformer |
| 818 | 11/0.433 kV 250kVA Distribution Transformer |
| 819 | 11/0.433 kV 400kVA Distribution Transformer |
| 820 | Dismantling of old existing distribution transformer & Carriage of Dismantled Distribution Transformer and other accessories to Sub centre/Workshop including loading & Unloading at both End. |
| 821 | 11/0.433 kV 10kVA Distribution Transformer |
| 822 | 11/0.433 kV 16kVA Distribution Transformer |
| 823 | 11/0.433 kV 25kVA Distribution Transformer |
| 824 | 11/0.433 kV 63kVA Distribution Transformer |
| 825 | 11/0.433 kV 100kVA Distribution Transformer |
| 826 | 11/0.433 kV 160kVA Distribution Transformer |
| 827 | 11/0.433 kV 250kVA Distribution Transformer |
| 828 | Erection of Trolly Mounted DT as per scope of work, approved drawings and specifications: |
| 829 | Erection, Testing & Commisioning of 11/0.433 kV 400 KVA Distribution Transformer in Trolley along with fabrication of trolley with fencing and locking mechanism and all fixing arrangements and accessories. |
| 830 | Erection of Protection of DT as per scope of work, approved drawings and specifications: |
| 831 | Installation ofAB switch for Distribution Transformer 100 KVA and above |
| 832 | Installation of DO Fuse a for Distribution Transformer 100 KVA and above |
| 833 | Installation of LT ACB on DTs having capacity 250 KVA and above |
| 834 | Installation of LT Distribution boxfor Distribution Transformer upto 250 KVA |
| 835 | Installation of LT Distribution boxfor Distribution Transformer 400 KVA and above |
| 836 | Erection of DT Cable with lug and clamp as per scope of work, approved drawings and specifications: |
| 837 | LT Cable of DT 1C 240 Sqmm |
| 838 | LT Cable of DT 1C 400 Sqmm |
| 839 | LT Cable of DT 1C 630 Sqmm |
| 840 | Erection for New Circuits of LT lines with Aerial bunch XLPE cable as per scope of work, approved drawings and specifications: |
| 841 | Excavation of pole pit (of depth 1/6th of pole length) in normal soil of following pole as per scope of work, approved drawings and specifications: |
| 842 | 8.5 m/180 Kgs PCC Poles with Base pad including Cement concreting, (state practices of PCC pole, stone to be used) |
| 843 | 9 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 844 | 11 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 845 | Erection of following types of poles for LT overhead line with Stone pad, pole numbering by paint with cement concrete foundation using 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) etc as per scope of work, approved drawings and specifications: |
| 846 | Erection of 8.5 m/180 Kgs PCC Poles with Base pad including Cement concreting, (state practices of PCC pole, stone to be used) |
| 847 | 9 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 848 | Erection of 11 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 849 | Excavation of LT stay pit in following type of soils,as per scope of work, approved drawings and specifications: |
| 850 | Normal soil |
| 851 | Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator (1 no.) and 0.2 cmt concreting 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) as per technical specifications, approved drawings and scope of works. |
| 852 | Erection, testing & commissioning of new areal bunched XLPE cable, Fixing tension clamps for dead end, suspension clamps, clamps for neutral, piercing connectors type-I & type-II, Pre- insulated compression connectors, 16 mm dia MS nuts & bolts, pole clamps, stainless steel strap, Single and three phase pole mounted distribution board, energisation of distribution box through 2Cx25 sqmm anD 4Cx35 sq.mm XLPE cable fixing end cap etc. as required as per technical specification, approved drawings and scope of work: |
| 853 | Erection of Aerial bunchedXLPE cable 1x16 sqmm+1x25 sqmm |
| 854 | Erection of Aerial bunchedXLPE cable 3 X 50 sqmm+1x35 sqmm.(bare messenger wire)+1x16 sqmm. |
| 855 | Erection of Aerial bunchedXLPE cable 3 X 95 sqmm.+1x70 sqmm.(Bare messenger wire)+1x16 sqmm. |
| 856 | Erection of Aerial bunchedXLPE cable 3 X 120 sqmm. + 1x95 sqmm.(bare messenger wire) +1x16 sqmm. |
| 857 | Erectionof Aerial bunchedXLPE cable 3 X 150 sqmm. + 1x120 sqmm.(bare messenger wire) +1x16 sqmm. |
| 858 | Erection, testing & commissioning of earthing by inserting GI Earthing spike made of 20mm solid Rod as per approved drawings, scope of work and technical specifications |
| 859 | Erection of 8 SWG GI wire for earthing by providing GI nut, bolts & washers, turn buckle etc as per approved drawings, scope of work and technical specifications |
| 860 | Erection for Extra Circuits of LT lines with Aerial bunch XLPE cable |
| 861 | Excavation of pole pit (of depth 1/6th of pole length) in normal soil of following pole as per scope of work, approved drawings and specifications: |
| 862 | 8.5 m/180 Kgs PCC Poles with Base pad including Cement concreting, (state practices of PCC pole, stone to be used) |
| 863 | 9 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 864 | 11 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 865 | Erection of following types of poles for LT overhead line with Stone pad, pole numbering by paint with cement concrete foundation using 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) etc as per scope of work, approved drawings and specifications: |
| 866 | Erection of 8.5 m/180 Kgs PCC Poles with Base pad including Cement concreting, (state practices of PCC pole, stone to be used) |
| 867 | Erection of 9 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 868 | Erection of 11 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 869 | Excavation of LT stay pit in following type of soils,as per scope of work, approved drawings and specifications: |
| 870 | Normal soil |
| 871 | Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator (1 no.) and 0.2 cmt concreting 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) as per technical specifications, approved drawings and scope of works. |
| 872 | Erection, testing & commissioning of new areal bunched XLPE cable, Fixing tension clamps for dead end, suspension clamps, clamps for neutral, piercing connectors type-I & type-II, Pre- insulated compression connectors, 16 mm dia MS nuts & bolts, pole clamps, stainless steel strap, Single and three phase pole mounted distribution board, energisation of distribution box through 2Cx25 sqmm anD 4Cx35 sq.mm XLPE cable fixing end cap etc. as required as per technical specification, approved drawings and scope of work: |
| 873 | Erection of Aerial bunchedXLPE cable 3 X 50 sqmm+1x35 sqmm.(bare messenger wire)+1x16 sqmm. |
| 874 | Erection of Aerial bunchedXLPE cable 3 X 95 sqmm.+1x70 sqmm.(Bare messenger wire)+1x16 sqmm. |
| 875 | Erection of Aerial bunchedXLPE cable 3 X 120 sqmm. + 1x95 sqmm.(bare messenger wire) +1x16 sqmm. |
| 876 | Erectionof Aerial bunchedXLPE cable 3 X 150 sqmm. + 1x120 sqmm.(bare messenger wire) +1x16 sqmm. |
| 877 | Erection, testing & commissioning of earthing by inserting GI Earthing spike made of 20mm solid Rod as per approved drawings, scope of work and technical specifications |
| 878 | Erection of 8 SWG GI wire for earthing by providing GI nut, bolts & washers, turn buckle etc as per approved drawings, scope of work and technical specifications |
| 879 | Erection for Augmentation of LT lines with Aerial bunch XLPE cable |
| 880 | Excavation of additional pole pit (of depth 1/6th of pole length) in normal soil of following pole as per scope of work, approved drawings and specifications: |
| 881 | 8.5 m/180 Kgs PCC Poles with Base pad including Cement concreting, (state practices of PCC pole, stone to be used) |
| 882 | 9 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 883 | Erection of following types of poles for LT overhead line with Stone pad, pole numbering by paint with cement concrete foundation using 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) etc as per scope of work, approved drawings and specifications: |
| 884 | Erection of 8.5 m/180 Kgs PCC Poles with Base pad including Cement concreting, (state practices of PCC pole, stone to be used) |
| 885 | Erection of 9 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 886 | Excavation of LT stay pit in following type of soils,as per scope of work, approved drawings and specifications: |
| 887 | Normal soil |
| 888 | Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator (1 no.) and 0.2 cmt concreting 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) as per technical specifications, approved drawings and scope of works. |
| 889 | Erection, testing & commissioning of new areal bunched XLPE cable, Fixing tension clamps for dead end, suspension clamps, clamps for neutral, piercing connectors type-I & type-II, Pre- insulated compression connectors, 16 mm dia MS nuts & bolts, pole clamps, stainless steel strap, Single and three phase pole mounted distribution board, energisation of distribution box through 2Cx25 sqmm anD 4Cx35 sq.mm XLPE cable fixing end cap etc. as required as per technical specification, approved drawings and scope of work: |
| 890 | Erection of Aerial bunchedXLPE cable 3 X 95 sqmm.+1x70 sqmm.(Bare messenger wire)+1x16 sqmm. |
| 891 | Erection of Aerial bunchedXLPE cable 3 X 120 sqmm. + 1x95 sqmm.(bare messenger wire) +1x16 sqmm. |
| 892 | Erection, testing & commissioning of earthing by inserting GI Earthing spike made of 20mm solid Rod as per approved drawings, scope of work and technical specifications |
| 893 | Erection of 8 SWG GI wire for earthing by providing GI nut, bolts & washers, turn buckle etc as per approved drawings, scope of work and technical specifications |
| 894 | Erection of Feeder Bifurcation (33KV Line) |
| 895 | 9m/400 kgs PCC Poles (PCC pole as per state practice) |
| 896 | 13 m longSTP SP72 |
| 897 | 11 m long steel tubular poles with welded steel base plate of designation 540 SP 55 (As per IS: 2713 , pt. I,II,III) |
| 898 | Concreting of poles as per specification |
| 899 | Stone Pad |
| 900 | Pre fabricated Steel items including MS nuts, bolts with washer as per technical specification, approved drawings and scope of work,X arm angle 100x50x6 mm V-type 33 KV (18 nos /km), Cross Arm holding clamps with nuts & bolts(18 nos /km), F bracket for fitting Top insulator with nuts & bolts(18 nos /km), Channel Cross arms 125x65x3180 mm ( Top Channel)(1 nos /km), Angle Iron 65x65x6 mm 3180 mm long bracing set with nuts & bolts(1 nos /km), Clamp with nuts & bolts for Top channel(2 nos /km), E- bracket with nuts & bolts(3 nos /km) including MS nuts, bolts with washer as per technical specification, approved drawings and scope of work. |
| 901 | Danger Board with barbed wire including jumpher |
| 902 | Number Plate |
| 903 | Stay Set ( Galvanised) GI stay rod 20x1800 mm, stay wire 7/8 SWG GI wire, 50x8 mm stay clamp, stay insulator (2 nos.), anchor plate (300x300x8), nut bolts, 2 nos. turn buckles, 1.8 m long 20 mm dia. Solid GI Stay Rod, 7/4.0mm dia. GI stranded wire |
| 904 | Insulator and hardware as per technical specification, approved drawings and scope of work |
| 905 | 33 KV polymer Disc insulator 70 KNB&S along with suitable hardware fittings |
| 906 | 33 KV polymer Pin insulators with GI Pin & nuts |
| 907 | GI earthing Spike earthing 20x2500 mm solid rod & 6 SWG earthwire with nut and bolt |
| 908 | 6 SWGand 8 SWG GI wire, GI nuts, bolts & washers for guarding angle 2180 mm long 75x75x6 (Approx. 3 span per km.) |
| 909 | ACSR conductors of following sizes with jointing sleeves, binding materials,pG clamps, bi-metallic clamp, hardware etc for overhead line and jumpers as required as per technical specification,approved drawings and scope of work: |
| 910 | 6/4.72 + 7/1.57 mm (100 mm2 Al.area ) - Dog |
| 911 | Erection of 33 KV Lineunderground railway crossing ensuring statutory clearances as required as per technical specification, approved drawings and scope of work |
| 912 | Erection, testing & commissioning of 33 KV under ground railway crossing by2 Nos (including one spare) 3Cx 300 Sqmm XLPE Armored Cable (0.3 km each) , using 150MM dia GI pipes, outdoor heat shrinkable cable jointing kits, lugs,4 NosGI 3-meters long earthing pipe, 6 SWG GI wires, cable markers, clamps, jumpering and 11 KV station type lightening arrestors(6 NOS.), etc as required as per technical specifications, approved drawings and scope of he work. |
| 913 | Erection for Feeder Bifurcation of 3 phase 11 kV line using additional supports matching with length and type of existing support asper technical specifications, scope of works and approved drawings |
| 914 | Excavation of additional pole pit (of depth 1/6th of pole length) in normal soil as per scope of work, approved drawings and specifications: |
| 915 | 8.5 m/180 kgs PCC Poles - (PCC Pole as per state practice) |
| 916 | 11 M long steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 917 | Erection of following types of poles for 11 KV overhead line by installing danger plate, anti-climbing devices (barbed wire),pole numbering including cement concrete foundation using 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) etc as per scope of work, approved drawings and specifications: |
| 918 | Erection of 8.5 m/180 Kgs PCC Poles withBase stone pad(state practices of PCC pole and base plate/stone to be used) |
| 919 | 11 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 920 | Excavation of stay pit in following type of soils,as per scope of work, approved drawings and specifications: |
| 921 | Normal soil |
| 922 | Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator and 0.2 cmt concreting 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) as per technical specifications, approved drawings and scope of works. |
| 923 | Erection, testing and commissioning of 11 kV insulator including their hardware fittings as per technical specification, approved drawings and scope of work. |
| 924 | Erection of 5 KN 11 kV Polymer Pin insulator |
| 925 | Erection of 45 KN 11 kV Polymer Disc insulator with strain hardware |
| 926 | Laying out, tensioning, binding of new conductor and tightening of stays and stringing, testing and commissioning of ACSRConductor of following sizes including jointing sleeves, helical formed fittings, jumpering and by providing & erecting PG Clamps etc as required as per approved drawings, scope of work and technical specifications |
| 927 | Stringing of 6/2.59 + 1/2.59 mm (30 mm² Al. Area) - Weaselconductor |
| 928 | Stringing of 6/3.35 + 1/3.35 mm (50 mm² Al. Area) - Rabbitconductor |
| 929 | Stringing of 6/4.72 mm+7/1.57 mm (100 mm² Al. Area) - Dogconductor 8.5 Mtr 180 Kg PCC |
| 930 | Stringing of 6/4.72 mm+7/1.57 mm (100 mm² Al. Area) - Dogconductor 11 Mtr STP |
| 931 | Erection, testing & commissioning of pre-fabricated HDG steel items like V cross arm, top channel, top clamp, cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats of given sizes for over head structures and HDG MS nuts, bolts & washers as per technical specification, approved drawings and scope of work. |
| 932 | Providing and fixing of Danger Board IncludingMaterial and its Fabrication ,Painting ,Writing ,Logo and Scheme etc as Per RDSS Guidelines and T.S |
| 933 | Earthingand guarding arrangement as per technical specifications,approved drawings and scope of work. |
| 934 | Erection, testing & commissioning of Spike Earthing 20mm solid Rod |
| 935 | Erection of 6 SWG GI wire for earthing and guarding |
| 936 | Erection of 8 SWG GI wire for earthing and guarding |
| 937 | Erection, testing & commissioning of 11 KV line for under ground railway crossing by2 Nos (including one spare) 3Cx185 Sqmm XLPE Armored Cable (0.3 km each) , using 150MM dia GI pipes, outdoor heat shrinkable cable jointing kits, lugs,4 NosGI 3-meters long earthing pipe, 6 SWG GI wires, cable markers, clamps, jumpering and 11 KV station type lightening arrestors(6 NOS.), etc as required as per technical specifications, approved drawings and scope of he work. |
| 938 | Erection of 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor typeVacuum Circuit breaker with adopter panel for out going feeder by leveling, alignment and welding on existing cable trench in control room. Testing & commissioning of indoor VCB panel including 3 Nos indoor type Current Transformer,A-meter, volt-meter, Relay & accessories protection as per approved drawings, technical specifications and scope of the work.: |
| 939 | Providing and fixing of Sign Board IncludingMaterial and its Fabrication ,Painting ,Writing ,Logo and Scheme etc as Per RDSS Guidelines and T.S |
| 940 | Laying, erection, termination using indoor & outdoor termination kit, 11KV 3x 185 sqmm XLPEarmored Power cablesas per technical specifications, approved drawings and scope of works. : |
| 941 | Erection of 11KVAgriculture Feeder Splitting due to overloading |
| 942 | Excavation of pole pit (of depth 1/6th of pole length) in normal soil of following pole as per scope of work, approved drawings and specifications: |
| 943 | 8.5 m/180 Kgs PCC Poles with Base pad including Cement concreting, (state practices of PCC pole, stone to be used) |
| 944 | Erection of following types of poles for LT overhead line with Stone pad, pole numbering by paint with cement concrete foundation using 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) etc as per scope of work, approved drawings and specifications: |
| 945 | Erection of 8.5 m/180 Kgs PCC Poles with Base pad including Cement concreting, (state practices of PCC pole, stone to be used) |
| 946 | Excavation of LT stay pit in following type of soils,as per scope of work, approved drawings and specifications: |
| 947 | Normal soil |
| 948 | Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator (1 no.) and 0.2 cmt concreting 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) as per technical specifications, approved drawings and scope of works. |
| 949 | Erection, testing & commissioning of new areal bunched XLPE cable, Fixing tension clamps for dead end, suspension clamps, clamps for neutral, piercing connectors type-I & type-II, Pre- insulated compression connectors, 16 mm dia MS nuts & bolts, pole clamps, stainless steel strap, Single and three phase pole mounted distribution board, energisation of distribution box through 2Cx25 sqmm anD 4Cx35 sq.mm XLPE cable fixing end cap etc. as required as per technical specification, approved drawings and scope of work: |
| 950 | Erection of LT line on 8.5 mtr PCC pole with AB cable (3x50+1x35+1x16) |
| 951 | Erection, testing & commissioning of earthing by inserting GI Earthing spike made of 20mm solid Rod as per approved drawings, scope of work and technical specifications |
| 952 | Erection of 8 SWG GI wire for earthing by providing GI nut, bolts & washers, turn buckle etc as per approved drawings, scope of work and technical specifications |
| 953 | Erection of 6 SWG GI wire for earthing by providing GI nut, bolts & washers, turn buckle etc as per approved drawings, scope of work and technical specifications |
| 954 | Erection for New Distribution Transformer accessories and supports as per technical specification, approved drawings and scope of work. |
| 955 | Survey, route alignment & pole spotting, preparation of survey report and uploading in the web portal after approval of Project Manager/Engineer in Charge |
| 956 | Erection of following types of poles for Distribution Sub Stations by providing and installing danger plate, anti-climbing devices (barbed wire), earthing material with and 8 SWG GI wire, red oxide & aluminium paint, pole numbering including Excavation of Pole Pit (of depth 1/6th of pole length), cement concrete foundation [For all types of Poles] using cement concreting foundation 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) with top muffing (0.88 cmt/pole for STP Poles and 0.268 cmt/Pole for PCC Poles) etc as per scope of work, approved drawings and specifications: |
| 957 | Supply of 8.5m/180 kgs PCC Poles - (PCC Pole as per state practice) |
| 958 | Erection, testing, commissioning of Galvanized Pre-fabricated steel items like DC cross arm, back clamps, pole clamp, DO mounting channel, transformer mounting channel, transformer clamping set, transformer belting set and GI nuts, bolts & washers including painting by red oxide & aluminium as per technical specification, approved drawings and scope of work. |
| 959 | Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator (1 Nos.) and Excavation of Stay Pit, 0.2 cmt concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) as per technical specifications, approved drawings and scope of works. |
| 960 | Erection, testing and commissioning of 11 kV insulator including their hardware fittings as per technical specification, approved drawings and scope of work. |
| 961 | 11 kV Polymer Pin insulator with GI pin |
| 962 | 11 kV Polymer Disc insulator with strain hardware |
| 963 | Erection, testing and Commissioning of 11 KV, 200 A, 3-pole AB Switch for Distribution Transformer Substation as per Technical Specification, approved Drawing & Scope of works |
| 964 | Erection, testing and commissioning of 9 KV, 5 KA Distribution Class Lightening Arrester for DT as per technical specification, approved drawings and scope of work. |
| 965 | Erection, testing and commissioning of 11 kV, 200 Amp 3-ph, Horn Gap fuse units (set of 3 units) along with Support Insulators, Base Channel, fuse barrel etc. complete asper technical specifications, scope of works and approved drawings |
| 966 | Erection, Testing and Commissioning of Distribution Transformerwith all accessories as per scope of work, approved drawings and specifications: |
| 967 | 11/0.4 KV Distribution Transformer 25 KVA 3 phaseDTR |
| 968 | Erection, testing and Commissioning of Outdoor mounting type Distribution box made of MS sheet of thickness not less than 18 SWG CRCA sheet by deep drawn method, dust and moisture vermin, weather proof with degree of protection with suitable bus bars, Modem Compatible DLMS Compliant LT Trivector Static Meter with suitable CTs, earthing bus, earthing terminals, box illumination, front door operated with proper locking arrangement, lugs, mounting channel frame, internal wiring with FRLS cables, danger plate, numbering, back clamps, hardware as per scope of the work, technical specifications and approved drawings, direction of Engineer in Charge suitable for following transformer: |
| 969 | 3 Ph 25 KVA transformer 40 A TPN MCCB (incomer) and 6 Nos. 25 A SP MCCB (outgoing) with metering |
| 970 | Erection, testing and Commissioning of 2 Nos Spike Earthing 20x2000 mm and 1 Nos Chemical earthing 40x3000 mm , as per IS 1161, making earth grid using 6 SWG GI wire as per scope of work, approved drawings and technical specifications, |
| 971 | Erection, testing and Commissioning of 1.1 KV XLPE Aluminium Conductor, Stranded, unarmoured cable for connection of transformer LV bushing to Distribution Box and Distribution box to overhead line as per Scope of work, technical specification and approved drawings: |
| 972 | 1CX35 sqmm aluminium conductor cable |
| 973 | Erection, testing and commissioning of ACSR Rabbit Conductor for jumpering including PG Clamps, bi-metallic connectors, hardware etc as per Technical Specification, approved Drawing & Scope of works |
| 974 | Erection for Augmentation/Reconductoring of 33 KV Line (Older Than 25 Years) |
| 975 | Excavation ofpole pit (of depth 1/6th of pole length) in normal soil as per scope of work, approved drawings and specifications: |
| 976 | Erection of 11 M long steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) |
| 977 | Erection of 9 m PCC Poles - (PCC Pole as per state practice) |
| 978 | Erection of following types of additional poles matching with existing line supports by installing danger plate, anti-climbing devices (barbed wire), Painting with red oxide & aluminum paint including paint, pole numbering including cement concrete foundation using 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) etc as per scope of work, approved drawings and specifications: |
| 979 | Erection of 11 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 980 | Erection of 9 PCC Poles with Base pad including Cement concreting, (state practices of PCC pole, stone to be used) 0.268 cum Cement concreting+0.014 cmt (Muffing) |
| 981 | Excavation of stay pit for 33 KV Stay in following type of soils,as per scope of work, approved drawings and specifications: |
| 982 | Normal soil |
| 983 | Erection of complete stay set with GI stay wire (7x4.00 mm dia), binding of stay wire, by providing Guy stay insulator and 0.3 cmt concreting 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) as per technical specifications, approved drawings and scope of works. |
| 984 | Erection, testing & commissioning of new Pre-fabricated HDG steel items like V cross arm, top clamp, cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats of given sizes for over head structures as per technical specification, approved drawings and scope of work. |
| 985 | Dismantling of existing overhead line conductor and fittings, depositing the dismantled material to employer\"s store and laying out & stringing of new ACSR conductor of following sizes by providing jointing sleeves, binding wire & tape & helical formed fittings etc as required as per technical specification, approved drawings and scope of work. |
| 986 | Stringing of 30/3.00 + 7/3.00 mm (200 mm² Al. Area) - Panther replacing existing conductor |
| 987 | Erection for Augmentation of 3 phase 33 kV line using new Insulator and hardware as per technical specification, approved drawings and scope of work |
| 988 | Erection of 33 KV 70 KN polymer Disc insulator along with suitable hardware fittings |
| 989 | Erection of 33 KV 10 KN Polymer Pin Insulators |
| 990 | Erection, testing & commissioning of earthing as per technical specifications,approved drawings and scope of work. |
| 991 | 8 SWG GI Coil 115 turns (1.85 kg) |
| 992 | Erection, testing & commissioning of new GI wire for earthing and guarding as per technical specification, approved drawings and scope of work. |
| 993 | Erection of 6 SWG GI wire |
| 994 | Erection of 8 SWG GI wire |
| 995 | Erection for Augmentation/Reconductoring of 11 KV Line (Older Than 25 Years) asper technical specifications, scope of works and approved drawings |
| 996 | Excavation of additional pole pit (of depth 1/6th of pole length) in normal soil as per scope of work, approved drawings and specifications: |
| 997 | 8.5 m/180 kgs PCC Poles - (PCC Pole as per state practice) |
| 998 | Erection of following types of poles for 11 KV overhead line by installing danger plate, anti-climbing devices (barbed wire),pole numbering including cement concrete foundation using 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) etc as per scope of work, approved drawings and specifications: |
| 999 | Erection of 8.5 m/180 Kgs PCC Poles withBase stone pad(state practices of PCC pole and base plate/stone to be used) |
| 1000 | Excavation of stay pit in following type of soils,as per scope of work, approved drawings and specifications: |
| 1001 | Normal soil |
| 1002 | Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator and 0.2 cmt concreting 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) as per technical specifications, approved drawings and scope of works. |
| 1003 | Erection, testing and commissioning of 11 kV insulator including their hardware fittings as per technical specification, approved drawings and scope of work. |
| 1004 | Erection of 5 KN 11 kV Polymer Pin insulator |
| 1005 | Erection of 45 KN 11 kV Polymer Disc insulator with strain hardware |
| 1006 | Laying out, tensioning, binding of new conductor and tightening of stays and stringing, testing and commissioning of ACSRConductor of following sizes including jointing sleeves, helical formed fittings, jumpering and by providing & erecting PG Clamps etc as required as per approved drawings, scope of work and technical specifications |
| 1007 | Stringing of 6/3.35 + 1/3.35 mm (50 mm² Al. Area) - Rabbit by replacing existing weasel/squirrel conductor |
| 1008 | Stringing of 6/4.72 mm+7/1.57 mm (100 mm² Al. Area) - Dog by replacing existing racoon/rabbit conductor |
| 1009 | Erection, testing & commissioning of pre-fabricated HDG steel items like V cross arm, top channel, top clamp, cross arm, bracket, clamps, cross bracings, bracings, strain plate, guarding channels, back clamp, etc made of MS Channels, MS angle, MS flats of given sizes for over head structures and HDG MS nuts, bolts & washers as per technical specification, approved drawings and scope of work. |
| 1010 | Providing and fixing of Danger Board IncludingMaterial and its Fabrication ,Painting ,Writing ,Logo and Scheme etc as Per RDSS Guidelines and T.S |
| 1011 | Earthingand guarding arrangement as per technical specifications,approved drawings and scope of work. |
| 1012 | Erection, testing & commissioning of Spike Earthing 20mm solid Rod |
| 1013 | Erection of 6 SWG GI wire for earthing and guarding |
| 1014 | Erection of 8 SWG GI wire for earthing and guarding |
| 1015 | Erection of Automatic Capacitor Bank as per Technical specifications, Approved drawings & Scope of work. |
| 1016 | Erection, testing and commissioning of 12.65 kV, 1980 kVAr, 3-Phase, 50 C/s, Outdoor Type , Capacitor bank having two variable step of 792 Kvar & one Variable steps of 396 kVAr. Bank shall be complete with Capacitor units of 264/132 kVAr,Aluminium busbars, Pin & Post insulators, Expulsion fuses etc.(1.98 MVAr HT Capacitor bank) including capacitors, reactors, Vaccumm Capacitors switches, allied materials such as suitable size of aluminium busbars, Pin/Post insulators, Expulsion fuses etc. |
| 1017 | Erection, testing and commissioning of 12.65 kV, 3960 kVAr, 3-Phase, 50 C/shoused in Outdoor Type CRCA Panel, Capacitor bank having two variable step of 792 Kvar & two Variable steps of 1188 kVAr. Bank shall be complete with Capacitor units of 396/264 kVAr,Aluminium busbars, Pin & Post insulators, HRC fuses,Surge arrestor etc.including structure for complete equipments (3.96 MVAr HT Capacitor bank)including capacitors, reactors, Vaccumm Capacitors switches, allied materials such as suitable size of aluminium busbars, Pin/Post insulators, Expulsion fuses etc. |
| 1018 | Casting of Civil foundation(1.98 MVAr HT Capacitor bank) |
| 1019 | Cable trench for laying of power/control cables.(1.98 MVAr HT Capacitor bank) |
| 1020 | Casting of Civil foundation(3.96 MVAr HT Capacitor bank) |
| 1021 | Cable trench for laying of power/control cables.(3.96 MVAr HT Capacitor bank) |
| 1022 | Erection for earthing of existing substation and Distribution Transformer |
| 1023 | Erection, testing and Commissioning Spike Earthing 20x2000 mm, using 8 SWG GI wire as per scope of work, approved drawings and technical specifications, |
| 1024 | Erection, testing and Commissioning Pipe Earthing 40x3000 mm, using 8 SWG GI wire as per scope of work, approved drawings and technical specifications, |
| 1025 | Erection works for Renovation and modernization of existing substation, battery charger and battery set. |
| 1026 | Design, Engineering, erection, testing and commissioning of 24V, 150 AHPb(Lead) Acid battery, battery standmade of teakwood duly painted with anti acid resistive paint, battery insulators, inter-battery wiring using 30 sqm, 1.1 kv, copper single coremulti strand cable, terminal connectors, Rubber mats & all other accessories and connectors as per technical specifications. |
| 1027 | Design, Engineering, erection, testing and commissioning of 24V, 150 AH.Float-cum-Boost Battery Charger with full wave rectification for230V,1 phase, 50 Hz AC Input Supply as per technical specifications. |
| 1028 | Design, Engineering and construction of foundation , erection, testing and commissioning of 36kV, 1250A,25kA for 3 seconds, 3-ph, Outdoor typeVacuum Circuit breaker with marshalling box etc Complete in all respect along with support structure. |
| 1029 | Design, Engineering and construction of foundation , erection, testing and commissioning of 36kV, 1-Phase, 25kA/3 seconds,800-400-200/1-1-1 Amps ( having 3 secondery, core), 1 set = 3 Nos outdoortype Current Transformers along with junction box (1 no junction box for 3 no of 1-phase CTs), as required as per technical specifications complete in all respect. |
| 1030 | Design, Engineering and construction of foundation , erection, testing and commissioning of 36kV, 1-Phase, 25kA/3 seconds,33 Kv/110 V single core outdoortype Potential Transformers along with junction box, as required as per technical specifications complete in all respect. |
| 1031 | Design, Engineering and construction of foundation , erection, testing and commissioning of 30 kV, 10kA, 1-ph Station Class Lightening Arrester complete(1 set= 3 Nos.) |
| 1032 | Design, Engineering and construction of foundation , erection, testing and commissioning of 36kV, 800A, 25kA , 3-ph double break center rotating type (DBCR), Gang Operated,isolator alongwith Support Insulators, OperatingMechanism, Base Channel down Pipe and all required accessories complete as per Technical Specifications. (with Earth Switch) |
| 1033 | Design, Engineering and construction of foundation , erection, testing and commissioning of 33 kV feeder Panel (without diffirential relays) with arrangements for DLMS(modem compactible ) Trivector Static Energy Meter complete |
| 1034 | Design, Engineering and construction of foundation , erection, testing and commissioning of 12 kV, 1250 A, 25kAfor 3 seconds, 3-ph, indoor typeVacuum Circuit BreakerforIncomer along with 12 kV, 1-Phase, 25kA, 600-300/5-5 A, 3 Nos indoor type Current Transformer 3 Core, Potential Transformer 11KV/110 V, indoor mounting type control panel for incoming breaker and required accessories, A-meter, volt-meter, 3-phase , withDLMS(modem compactible ) Tri Vector energy meter, Numerical Relays & accessories complete as per specifications for transformer breaker protectionwith earth fault, overcurrent . |
| 1035 | Design, Engineering and construction of foundation , erection, testing and commissioning of 12 kV, 1250 A, 25kAfor 3 seconds, 3-ph, indoor typeVacuum Circuit Breakerforalong with 12 kV, 1-Phase, 25kA, 600-300/5-5 A,3 Nos indoor type Current Transformer, control panel for Bus couplar and required accessories, A-meter, Numerical Relays & accessories complete as per specifications for Bus Coupler protectionwith earth fault, overcurrent . |
| 1036 | Design, Engineering and construction of foundation , erection, testing and commissioning of 12 KV 3 Ph 1250 A, 25kAfor 3 seconds, 3-ph, indoor typeVacuum Circuitbreaker along with 12 kV, 1-Phase, 25kA, 11 kv/110v,indoor type PotentialTransformer,indoor mounting type control panel and required accessories, A-meter, Numerical Relay & accessories complete as perspecifications for feeder breaker protection & Protection for Earth fault and over current) with extensible arrangement for future |
| 1037 | Design, Engineering and construction of foundation , erection, testing and commissioning of 9kV, 10kA, 1-ph Station Class LighteningArrester complete (1 Set = 3 Nos.) |
| 1038 | Design, Engineering and construction of foundation , erection, testing and commissioning of 12kV, 630 A, 25kA for 3 seconds, 3-ph double break center rotating type (DBCR), Gang Operated,isolator along with Support Insulators, Operating Mechanism, Base Channel down Pipe and all required accessories complete as per technical specifications, scope of works and approved drawings . |
| 1039 | Design, Engineering and construction of foundation , erection, testing and commissioning of 11 kv Bus-Coupler with all required accessories complete as per technical specifications, scope of works and approved drawings . |
| 1040 | Supply of 3CX300 Sqmm 33 KV XLPE Armored Cable |
| 1041 | Erection, testing & commissioning of 33 KVunder ground Cable in underground by2 Nos (including one spare) 3Cx300 Sqmm XLPE Armored Cable, using 160 mm HDPE pipe at road crossing, 150mm dia GI pipes for cable support, outdoor heat shrinkable cable jointing kits, lugs, cable markers, clamps, jumpering, 7/20 GI wire etc as required as per technical specifications, approved drawings and scope of he work. |
| 1042 | Supply of 3Cx185 Sqmm 11 KV XLPE Armored Cable |
| 1043 | Erection, testing & commissioning of 11 KV line for under ground cabling in underground by2 Nos (including one spare) 3Cx185 Sqmm XLPE Armored Cable, using 150MM dia GI pipes, outdoor heat shrinkable cable jointing kits, lugs,4 NosGI 3-meters long earthing pipe, 6 SWG GI wires, cable markers, clamps, jumpering and 11 KV station type lightening arrestors(6 NOS.), etc as required as per technical specifications, approved drawings and scope of the work. |
| 1044 | Civil Worksfor Control room extension, Strengthning and Miscellaneous Works required as per Scope of work, Approved drawings and Technical Specifications. |
| 1045 | Control Room Extension Works |
| 1046 | Erection of 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor typeVacuum Circuit breaker with adopter panel for out going feeder by leveling, alignment and welding on existing cable trench in control room. Testing & commissioning of indoor VCB panel including 3 Nos indoor type Current Transformer,A-meter, volt-meter, Relay & accessories protection as per approved drawings, technical specifications and scope of the work.: |
| 1047 | Erection including Providing and fixing of Sign Board IncludingMaterial and its Fabrication ,Painting ,Writing ,Logo etc as Per RDSS Guidelines and T.S |
| 1048 | Laying, erection, termination using indoor & outdoor termination kit, 11KV 3x 185 sqmm XLPEarmored Power cablesas per technical specifications, approved drawings and scope of works. : |
| 1049 | Old Conrol Room Strengthning & Miscellaneous Construction Works required as per Scope of work, Approved Drawings and Technical Specifications |
| 1050 | Old Control room building strengthning (4 No\"s), Construction of boundary wall (200 mtr for each substation) (5 Nos) & Construction of Firewall (4 No\"s) as per Scope of work, approved drawings and Technical specifications. |
| 1051 | Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : |
| 1052 | Of area 3 sq. metres and below |
| 1053 | Dismantling old plaster or skirting raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping groundwithin 50 metres lead. |
| 1054 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. |
| 1055 | Nominal concrete 1:4:8 or leaner mix (i/c equivalent design mix) |
| 1056 | Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. |
| 1057 | In cement mortar |
| 1058 | Dismantling tile work in floors and roofs laid in cement mortar includingstacking material within 50 metres lead. |
| 1059 | For thickness of tiles 10 mm to 25 mm |
| 1060 | Dismantling G.I. pipes (external work) including excavation and refilling trenches after taking out the pipes, manually/ by mechanical means including stacking of pipes within 50 metres lead as per direction of Engineer-in-charge : |
| 1061 | 15 mm to 40 mm nominal bore |
| 1062 | Dismantling of flushing cistern of all types (C.I./PVC/Vitrious China) including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead. |
| 1063 | TILES WORK |
| 1064 | Erection including Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. |
| 1065 | Size of Tile 800x800 mm |
| 1066 | Erection including Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shadecomplete. |
| 1067 | Erection including Providing and laying Vitrified tiles in floor in different sizes (thickness tobe specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. |
| 1068 | Glazed Vitrified tiles Matt/Antiskid finish of size |
| 1069 | Size of Tile 600 x 600 mm |
| 1070 | PLASTERING & PAINTING |
| 1071 | 12 mm cement plaster of mix : |
| 1072 | 1:4 (1 cement: 4 fine sand) |
| 1073 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete. |
| 1074 | Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content. |
| 1075 | With water thinnable cement primer on wall surfacehaving VOC content less than 50 grams/litre |
| 1076 | Distempering with 1st quality acrylic distember (Ready mix) nhaving VOC content less than 50 grams/ litre of approved brand and manufacture to give an even shade : |
| 1077 | Old work (one or more coats) |
| 1078 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade: |
| 1079 | New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 1080 | Painting with synthetic enamel paint of approved brand andmanufacture of required colour to give an even shade : |
| 1081 | Two or more coats on new work over an under coat ofsuitable shade with ordinary paint of approved brand andmanufacture |
| 1082 | PLINTH & BRICK WORK |
| 1083 | Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone - III) : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth. |
| 1084 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. |
| 1085 | CONCRETE WORK |
| 1086 | Erection Including Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 1087 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) |
| 1088 | Erection Including Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. |
| 1089 | 100 mm nominal inner dia Pipes |
| 1090 | Erection of DT Capacitors atDTs |
| 1091 | Erection, Testing & Commissioning offollowing 440 Volt LT shunt Capacitor including mounting Structure and accessories as required as per technical specifications,approved drawings and scope of work. |
| 1092 | Erection of LT Shunt capacitor 440 Volt 10 KVAr 3Phase 50Hz IP65 |
| 1093 | Erection of LT Shunt capacitor 440 Volt 25 KVAr 3Phase 50Hz IP65 |
| 1094 | Erection for Armoured Cabling |
| 1095 | Excavation of pole pit (of depth 1/6th of pole length) in normal soil of following pole as per scope of work, approved drawings and specifications: |
| 1096 | 8.5 m/180 Kgs PCC Poles with Base pad including Cement concreting 0.268 Cum, (state practices of PCC pole, stone to be used) |
| 1097 | 9 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 1098 | Erection of following types of poles for LT overhead line with Stone pad, pole numbering by paint with cement concrete foundation using 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) etc as per scope of work, approved drawings and specifications: |
| 1099 | Erection of 8.5 m/180 Kgs PCC Poles with Base pad including Cement concreting, (state practices of PCC pole, stone to be used) |
| 1100 | 9 M long Steel Tubular poles with welded steel base plate of Designation 410 SP 55 (IS 2713, Pt I, II, III 1980) - Cement concreting 0.5 cmt + 0.014 cmt (Muffing) |
| 1101 | Excavation of LT stay pit in following type of soils,as per scope of work, approved drawings and specifications: |
| 1102 | Normal soil |
| 1103 | Erection of complete stay set with GI stay wire (7x3.15 mm dia), binding of stay wire, by providing Guy stay insulator (1 no.) and 0.2 cmt concreting 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate chips (1:2:4) as per technical specifications, approved drawings and scope of works. |
| 1104 | Erection, testing & commissioning of new single core armoured XLPE cable, Fixing of cross arm, piercing connectors, Pre- insulated compression connectors, MS nuts & bolts, pole clamps, insulation mastic tape, Single and three phase pole mounted distribution board, energisation of distribution box through armoured XLPE cable fixing end cap etc. as required as per technical specification, approved drawings and scope of work: |
| 1105 | 1.1 kV Single Core 25sqmm XLPE armoured cable (1Cx25 sqmm) |
| 1106 | 1.1 kV Single Core 50sqmm XLPE armoured cable (1Cx50 sqmm) |
| 1107 | 1.1 kV Single Core 95sqmm XLPE armoured cable (1Cx95 sqmm) |
| 1108 | 1.1 kV Single Core 120sqmm XLPE armoured cable (1Cx120 sqmm) |
| 1109 | Erection, testing & commissioning of earthing by inserting GI Earthing spike made of 20mm solid Rod as per approved drawings, scope of work and technical specifications |
| 1110 | Erection of 8 SWG GI wire for earthing by providing GI nut, bolts & washers, turn buckle etc as per approved drawings, scope of work and technical specifications |
| 1111 | Discount offered in % |
| 1112 | Words Final Quoted Price after Discount |