Tender For Repair And Maintenance Of Dg Sets, Amf Panels, Apfc Panel And Connected Allied Works And Repair/Replacement And Maintenance Of Lt Distribution System Lt Panel, Lt Cables And Connected Allied Works Under Age E/M No 1 Of Ge (U) Secunderabad, secunderabad-Telangana

Military Engineer Services-MES has published Tender For Repair And Maintenance Of Dg Sets, Amf Panels, Apfc Panel And Connected Allied Works And Repair/Replacement And Maintenance Of Lt Distribution System Lt Panel, Lt Cables And Connected Allied Works Under Age E/M No 1 Of Ge (U) Secunderabad. Submission Date for this Tender is 22-04-2024. LT Cable Tenders in secunderabad Telangana. Bidders can get complete Tender details and download the document.




Tender Notice

43079064
Corrigendum : Tender For Repair And Maintenance Of Dg Sets, Amf Panels, Apfc Panel And Connected Allied Works And Repair/Replacement And Maintenance Of Lt Distribution System Lt Panel, Lt Cables And Connected Allied Works Under Age E/M No 1 Of Ge (U) Secunderabad
Open Tender
Indian
Telangana
secunderabad
22-04-2024

Tender Details

Repair And Maintenance Of Dg Sets, Amf Panels, Apfc Panel And Connected Allied Works And Repair / Replacement And Maintenance Of Lt Distribution System Lt Panel, Lt Cables And Connected Allied Works Under Age E / M No 1 Of Ge ( U ) Secunderabad

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 10-Apr-2024 AMENDMENT Date 22-04-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 98000.0 /-
Tender Value
INR 49 Lakhs /-

BOQ Items

Name of Work: REPAIR AND MAINTENANCE OF DG SETS, AMF PANELS, APFC PANEL AND CONNECTED ALLIED WORKS UNDER AGE E/M NO 1 OF GE (U) SECUNDERABAD
Sl. No. Item Description
1M&L for Maintenance of DG set and carrying out ‘B’ check and replacement of ‘B’ check kit filters such as Oil filter, by pass filter, fuel filter,CR element and CR plates complete with ‘O’ rings and draining of Engine oil and topping up with the new engine oil complete testing all as specified and directed by the Engr-in-Charge for the following capacity DG sets:- Note :-(i) Engine oil shall be measured and paid separately (ii) Labour & transportation shall be arranged by contractor,quoted rate deemed to be inclusive in the unit rate. Make: KIRLOSKER/ CUMMINS /GREAVES/ GREAVES COTTON/ASIATIC/ RUSTON (a)up to 35 KVA DG Set
2125 KVA DG Set
3200 KVA to 250 KVA DG Set
4Attending thebreakdown of any capacity/make DG Sets, AMF Panels, by Technician & helper for checking all components and rectifythe fault and give report to concern JE complete all as directed by Engr-in-charge. Note :- Spare Parts for rectify the fault is measured and paid seperately.
5M&L for Renewal/ repairs of unserviceable automatic voltage regulator (AVR) upto 125 KVA DG set including all spares, testing all as specified and directed by Engr-in-Charge. Make:- As per OEM approved make.
6M&L for Renewal/ repairs of unserviceable automatic voltage regulator (AVR) above 125KVA and upto 250 KVA DG set including all spares, testing all as specified and directed by Engr-in-Charge. Make:- As per OEM approved make.
7M&L for Dismantling of exhaust pipe of the DG set by unscrewing nuts and bolts and taking down the pipe with muffler removing the burnt out asbestos rope and well wrapping with new aluminium metal cladding with glass wool including cleaning the silencer, and fixing the same in its original position complete all as directed by Engr- in- Charge for the following capacity DG Sets. (a)up to 125KVA
8Above 125 KVA to 250 KVA DG set.
9M&L for Disconnecting all electrical connections from the unserviceable self starter of any make/ capacity model 24 volts and taking down the self starter and transporting to civil workshop for carrying out repairs, complete overhauling the system including replacing the unserviceable parts like bearings, carbon brushes, clutch plates etc & assemblingincluding after repair refixing the self starter in its original position,making all connection as per DG Set OEM recomendation, testing and commissioning complete all as directed by Engr-in-charge. Note:- Supply only Armature coil, field coil shall be measured and paid separately under relevant items of this Schedule.
10Supply only Armature coil for self starter of any make, any capacity and any model 24 Volts including testing complete all as directed by Engr-in-charge
11Rewinding of field coil for self starter of 24 volts with fine enamelled copper conductor of same gauge with "F" class insullation, size twins and weight with necessary insulating materials, guage of conductor suitablef any make, any capacity and any modelcomplete all as directed by Engr-in-charge.
12M&L for Disconnecting all electrical connections from the unserviceable self starter of any make/ capacity model 12 volts and taking down the self starter and transporting to civil workshop for carrying out repairs, complete overhauling the system including replacing the unserviceable parts like bearings, carbon brushes, clutch plates etc & assemblingincluding after repair refixing the self starter in its original position,making all connection as per DG Set OEM recomendation, testing and commissioning complete all as directed by Engr-in-charge. Note:- Supply only Armature coil, field coil shall be measured and paid separately under relevant items of this Schedule.
13Supply only Armature coil for self starter of any make, any capacity and any model 12 Volts, 180/200 AH complete all as directed by Engr-in-charge
14Rewinding of field coil for self starter of 12 volts with fine enamelled copper conductor of same gauge with "F" class insullation, size twins and weight with necessary insulating materials, guage of conductor suitablef any make, any capacity and any modelcomplete all as directed by Engr-in-charge.
15M&L for Disconnecting the oil cooler of capacity up to 125 KVA DG set of any make/ model from the existing locations duly removing of all mechanical connections and taking down the same for complete servicing opening the parts and cleaning thoroughly by using suitable cleaning material and acid and reassembling and refixing in its original position, testing and commissioning complete all as directed by Engr-in-charge
16M&L for Disconnecting the oil cooler of capacity above 125kVA to 250KVA DG set of any make/ model from the existing locations duly removing of all mechanical connections and taking down the same for complete servicing opening the parts and cleaning thoroughly by using suitable cleaning material and acid and reassembling and refixing in its original position, testing and commissioning complete all as directed by Engr-in-charge
17M&L for Renewal/ replacement of existing unserviceable air cleaning element inner and outer with necessary ‘O’ rings for the DG sets of following capacities as that of existing make and model complete all as directed by Engr-in-charge: - Make for item No.10 to 10.04:OEM recomended (a) Upto 125 KVA DG Set
18Above 125 KVA and up to 250 KVA DG Set
19M&L for Disconnecting all the incoming and outgoing rubber hoses and draining out the water from the choked radiator assembly of the existing make and model and various capacities of DG sets and taking down the radiator assembly by unscrewing all mechanical/electrical connections from the existing mounting, transporting the same to civil workshop for carrying out servicing, opening the top and bottom covers ofradiator assembly cleaning thoroughly the chocked pipe of the radiator by using chemical detergent, lime caustic soda, cotton etc., cleaning of all the deposited sediments in the pipes/tubes including arresting of leakage by means of soldering, brazing and transporting back to site and refixing the same in its original position with suitable size nuts, bolts and washers and Anti vibrating mounting(AVM) pads as required as per OEM recomendation etc., for the following DG sets all as specified and directed by Engr-in-Charge: (a) Upto 125 KVA DG Set
20Above 125 KVA and up to 250 KVADG Set
21M&L for Renewal of battery cable leads of copper conductor and with brass lugs terminal, for the 12V, 150/180 /200 AHbatteries to self stater as that of existing size and length complete all as directed by Engr-in-charge
22S&FAutomatic cut off type Battery Charger suitable for 12 V,up to 10 Amp Battery complete all as directed by Engr-in-charge. Make SMPS/ Phonix
23S&F Automatic cut off type Battery Charger suitable for 24 V, up to 10 Amp Battery complete all as directed by Engr-in-charge. Make SMPS/ Phonix
24M&L for Renewal/replacement of "V" belts for the following capacity DG sets as perexisting size and model complete all as directed by Engr-in-charge. Make:- FENNER/ DUNLOP (a) Upto 125 KVA DG Set
25Above 125 KVA and up to 250 KVADG Set
26M&L for Renewal/replacement of fan belts for the following capacity DG sets as perexisting size and model complete all as directed by Engr-in-charge. Make:- As per OEM Recommendation (a) Upto 125 KVA DG Set
27Above 125 KVA and up to 250 KVADG Set
28M&L for Renewal/replacement of Dynamo belts for the following capacity DG sets as perexisting size and model complete all as directed by Engr-in-charge. Make:- As per OEM Recomendation(a) Upto 125 KVA DG Set
29Above 125 KVA and up to 250 KVADG Set
30M&L disconnecting & removingthe unservicable DC wiring from DG set of any type/any make/any model/any capacity and rewiring withthe same with suitable new copper wire to existing guage wire by providing flexible pipe including making all electrical connections as per OEM recomendation for satisfactory completion of job & checking of electrical/electronic spares working condtion and testingetc complete all as specified and directed.Note: (i) The rate quoted deemed to be inclusive of new copper wire cost in the unit rate.
31M&L for replacement of existing unserviceable water temperature gauge with new water temperature gauge for the DG set of any description inclduing making necessary electrical /mechanical connections and taking down old unserviceable one complete all as directed by Engr-in-charge. Make: OEM recomended make
32M&L for replaceemnt of existing unserviceable lubricant oil temperature gauge with new lubricant oil temperature gauge for the DG set of any capacityinclduing making necessary electrical /mechanical connections and taking down old unserviceable one complete all as directed by Engr-in-charge. Make: OEM recomended make
33M&L for replacement of existing unserviceable oil pressure gauge with new oil pressure gauge for the DG SET of any capacityinclduing making necessary electrical /mechanical connections and taking down old unserviceable one complete all as directed by Engr-in-charge. Make: OEM recomended make
34M&L for replacement of unserviceablesolenoid switch with new solenoid switch 12voltsfor DG set of any make and any capacityinclduing making necessary electrical /mechanical connections and taking down old unserviceable one complete all as directed by Engr-in-charge. Make :-OEM recomended
35M&L for replacement of unserviceablesolenoid switch with new solenoid switch 24voltsfor DG set of any make and any capacityinclduing making necessary electrical /mechanical connections and taking down old unserviceable one complete all as directed by Engr-in-charge. Make :- OEM recommended
36S&F in repairs the following spare parts for any type/make of DG sets, as and when required by the department complete all as specified and directed. Make for item no 28 to 28.10:- OEM recommended
37Starting/Ignition - key/button
38Volt Meter 0-500V
39S.D Valve assembly
40Oil safety control
41Water safety control
42Water separator bowl 3247715
43Radiator Metal Pipes
44Supply and filling the new engine oil 20W/40 for toping up upto the required level complete all as directed by Engr-in-chargeMake :- CASTROL/ INDIAN OIL/ SERVO
45Supply and filling the new engine oil 15W/40 for toping up upto the required level complete all as directed by Engr-in-chargeMake :- CASTROL/ INDIAN OIL/ SERVO
46S&F in replacement of Line Voltage Monitors (LVMS) of existing make to DG set of 30 KVA to 250 KVA capacity listed parameters including testing complete all as specified and as directed. Make :- OEM recommended
47Drain out the fuel from the fuel tank of DG set of capacity 400 Ltrs and above and keeping it in separate container safely, disconnecting all the fuel lines and other mechanical connections and taking out the fuel tank for cleaning, internally and externally by removing all the accumulated dirt/ sediment, leak testing the tank and welding/ brazing including one coat ofsynthetic enamel paint, refixing the tank in its original position, replacing the drain plug and PVC pipe, calibrating the fuel tank, refilling the drained out fuel back into the tank and marking of liters in gauge and provision of locking arrangements complete all as directed by Engr-in-charge.
48Description all as per item No. 32 above but upto 250 Ltrs complete all as directed by Engr-in-charge.
49M&L for Removing of defective engine oil control pressure switch supply & fix new engine oil control pressure switch suitable for above 30 KVA to 250 KVADG setcomplete all as directed by Engr-in-charge.Make as per OEM Recommendation.
50M&L disconnecting & removingthe unservicable AC wiring from AMF panel ofDG set of any type/any make/any model/any capacity and rewiring withthe same with suitable new copper wire to existing guage wire by providing flexible pipe including making all electrical connections as per OEM recomendation for satisfactory completion of job & replacement of electrical/electronic spares and testingetc complete all as specified and directed. Note: (i) The rate quoted deemed to be inclusive of new copper wire cost in the unit rate.(ii) Electrical/Electrnoc spares shall be measured & paid separately under relevant items.
51Supply only following spare parts:- Push buttons.
52AMF Panel Hooter
53Earth fault relay.Make: OEM recomeded
54Over load relay.Make: OEM recomeded
55Over/Under voltage relay.Make: OEM recomeded
56Auxilary relays 12v/6Amps Make: OEM recomeded
57Single phase preventer,make:minilec/GIC
58Auxiliary Relays 24Volts / 6A Make: OEM recomeded
59PLC based AMF relay unit Make: OEM recomeded
60Low lube oil safety switch Make: OEM recomeded
61Booster Relay 24Volts / 10A Make: OEM recomeded
62Coolant temparature sensor Make: OEM recomeded
63M&L for Removing the defective charging dynamo of capacity 24 Volt DC any make, model, any capacity and opening it, by removing all nuts and bolts, cleaning with necessary cleaning agent and overhauling lubricating of therewinding the damaged winding of field coilswith super enameled copper wire suitable tosame existing size/guage & reconnecting the same, refixing back, in original position including making all necessary electrical/mechanical connectionstesting and commissioning complete all as directed by Engr-in-charge.
64M&L for Removing the defective charging dynamo of capacity 12 Volt DC any make, model, any capacity and opening it, by removing all nuts and bolts, cleaning with necessary cleaning agent and overhauling lubricating of therewinding the damaged winding of field coilswith super enameled copper wire suitable tosame existing size/guage & reconnecting the same, refixing back, in original position including making all necessary electrical/mechanical connectionstesting and commissioning complete all as directed by Engr-in-charge.
65M&L for replacementof unserviceable spares for water manifold and Radiator spares above 30 and upto 125 KVA DG set for the following spares:- (a)Radiator rubber hoses.
66Clamp for hump hose.
67Hose clamps.
68Hump hose.
69M&L for replacementof unserviceable spares for water manifold and Radiator spares above 125 kVA and upto 250KVA DG set for the following spares:- (a)Radiator rubber hoses.
70Clamp for hump hose.
71Hose clamps.
72Hump hose.
73M&L forInhibitor corrosion (coolant additive concentrate) required for top up (TVS Make) complete all as directed by Engr-in-charge.
74Supply and topping up of distilled water suitable for lead acid batteries of 12 volts complete all as directed by Engr-in-charge.
75S&F battery brass terminaland jelly complete all as specified and directed.
76M&L for Renewal/Replacement of unserviceable batteries with maintenance free batteries of 180 AH, 12V including connecting to DG set complete all as directed by Engr-in-charge.Make:-EXIDE
77M&L for Disconnecting all connection & remove the PT pump from engine and transport to OEM authorised service center and Calibration of PT pump for maximum efficiency by OEM Authorised Service center & replacement of PT Pump kit, gear gasket, etc in its original position by making all necessary connections complete whichever required under AGE E/M-I(U) AOR for smooth functioning of fllowingDG Set capacities complete all as directed by Engr-in-charge (a) DG Set capacity above 30 KVA to 125 KVA
78DG Set capacity above 125KVA to 250KVA
79M&L for remove the fuel injection pump from the engine transport to an authorized service centre for service, calibration and to adjust by replacing the following un serviceable worn-out spares with new appropriate make minor spares and bringing and fixing to the engine and tune up for maximum efficiency all as specified and as directed for DG set capacity above 30 KVA and upto 125 KVA :- Note: Major spares required will be measured and paid seperately.
80Supply only orfice for above above above 30 KVA and upto 125 KVAcapacity DG set
81Supply only Barrel and Plunger for above 30 KVA and upto 125 KVAcapacity DG set
82Supply only FIP Bearingfor above 30 KVA and upto 125KVA capacity DG set
83M&L for remove the fuel injection pump from the engine transport to an authorized service centre for service, calibration and to adjust by replacing the followingunservicable worn-out spares with new appropriate make minor spares and bringing and fixing to the engine and tune up for maximum efficiency all as specified and as directed for DG set capacity above 125 KVA and upto 250KVA :- Note: Major spares required will be measured and paid seperately.
84Supply only orfice for above 125 KVA and upto 250 KVA capacity DG set
85Supply only Barrel and Plunger for 125 KVA and upto 250KVA capacity DG set
86Supply only FIP Bearingfor above 125 KVA and upto 250KVA capacity DG set
87Supply and fix self starter Motor, 24 volts, Make LUCAS or its equivalent make approved by OEM of DG Set suitable for existing DG set above 82.5 KVA to 250 KVA including making all necessary electrical/mechanical connection as per recomendation of OEM of DG Set & dismantling/taking out old unserviceable self starter Motor from existing positioncomplete all as directed by Engr-in-charge
88Supply and fix self starter Motor, 12 volts, Make LUCAS or its equivalent make approved OEM of DG Set suitable for existing DG set capacity up to82.5 KVAincluding making all necessary electrical/mechanical connection as per recomendation of OEM of DG Set & dismantling/taking out old unserviceable self starter Motor from existing positioncomplete all as directed by Engr-in-charge
89S&F Flexible Bellow suitable for up to 125 KVA Gen Set. Make as per OEM
90S&F Flexible Bellow suitable for above 125KVA and up to 250 KVA Gen Set. Make as per OEM
91M&L for Servicing of DG Set panel"sindoor/outdoor type of any make/model/capacity, checking of switching ON/OFF& tripping system, Spring charge Motor working system,checking of all electrical mechanical components of AMF panel and Setting the same for proper working of Breaker, testing of operation manually and auto mode complete all as directed by Engr-in-charge. Note:-All the mechanical parts are thoroughly cleaned by suitable cleaning agent & moving parts are properly lubricated
92Supply and fix Coil of Power contactor of having capacity 400 Amps 4 pole 2NO +2NC complete all as specified and directed. Make:- L&T Cat part No. CS94195 or equivalent HPL/Schneider
93Supply and fix Power contactor of having capacity 275 Amps 4 pole 2NO +2NCcomplete all as specified and directed. Make:- C&S Cat part No LC1 FDP1854AE or equivalent HPL/Schneider
94Supply and fix Power contactor of having capacity 400 Amps 4 pole 2NO +2NCcomplete all as specified and directed. Make:- C&S Cat part No LC1 FDP3304AE or equivalent HPL/Schneider
95Supply and fix Power contactor of having capacity MCX 43 400 Amps 4 pole 2NO +2NCcomplete all as specified and directed. Make:- L&T Cat part No. CS97025 or equivalent HPL/Schneider
96Supply and fix Power contactor of having capacity MCX 33 200 Amps 4 pole 2NO +2NC complete all as specified and directed. Make:- L&T Cat part No. CS97021 or equivalent HPL/Schneider
97MCCB 400 Amps, 4 pole, 415 Volts with rapturing capacity 50 KA adjustable magnetic and thermal settings. Make : - L&T Cat Part No. CM94103OOR1OG or equivalent make of havells/ C&G
98Supply,install, test, commissioning & run the DG set"sFly-wheel Ring of Fly-wheel Assembly of existing model,sizesuitable to DG Set of capacity up to 125 KVA including taking down old Unserviceable complete all asdirected by Engr-in-Charge.
99Supply,install, test, commissioning & run the DG set"sFly-wheel Ring of Fly-wheel Assembly of existing model,sizesuitable to existing DG Set of capacity above 125kVA up to 250 KVA including taking down old Unserviceable complete all asdirected by Engr-in-Charge.
100Disconnectthe Radiator and kept aside safely and taking down the old unserviceable water pump from the existing engine of DG set any make/model, capacity up to 125 KVAsupply and fixing of new water pump &kit,reassembling the same and refixing the pump to the engine of DG set, refixing Radiator and testing,including making all Electrical/mechanical connections,commissioning as per OEM recomendation complete all as directed by Engr-in-charge.
101Disconnectthe Radiator and kept aside safely and taking down the old unserviceable water pump from the existing engine of DG set any make/model, capacity above 125KVA andup to 250 KVAsupply and fixing of new water pump &kit,reassembling the same and refixing the pump to the engine of DG set, refixing Radiator and testing,including making all Electrical/mechanical connections,commissioning as per OEM recomendation complete all as directed by Engr-in-charge.
102Supply, Fix & test run the DG set after replacing Diesel feeder Pumpof existing model,sizesuitable to DG Set of capacity 35 KVA to 250 KVA including taking down old unserviceable complete all asdirected by Engr-in-Charge.
103M&L for disconnecting all electrical & mechanical connections,Dismantle the Engine (make KIRLOSKER/ CUMMINS /GREAVES/ GREAVES COTTON/ASIATIC/ RUSTON)from 35KVA to 250 KVA DG set capacities located at various location under AGE E/M-I(U)and transported to OEM Authorised service center for complete overhauling, replacing the followingunservicable worn-out spares with new appropriate make minor spares & major spares (minor spares- up to Rs2500/Each), after assembling the spares the Engine again shfted to original existing place and reassembled to alternator& radiator,AMF panel/Electrical panel board of DG set complete testing,commissioningall as per OEM recomendation and as directed by Engr-in-charge.The quoted rate inclusive ofManpower, Crane charges for transporting engine to workshop and back after repairs Note: -(i)Major Spare parts shall be measured and paid separately.
104Gear fuel Pump
105Total Gaskets Set
106Core & cooler set
107Shaft rocker arm
108Oil seal
109Ball Bearings set
110Main Bearings set(STD)
111Material and labour for repairs to Alternator of following DG Set, transporting the same to theOEM authorised service center/work shop and carrying out the repairs such as taking out the burnt out winding and rewinding the alternator with copper wire of same guage turns and weight, checking of commentator, brushescomplete and refixing the same in its existing position after transporting back to the site and connecting up electric connections with suitable lugs complete and testing all as specified and directed.Note: Copper winding material will be measured and paid seperately under relevant Item
112Upto 125 KVA capacity
113Above 125 KVA and upto 250 KVA Capacity.
114Supply only High conductivity copper conductor winding material including necessary insulation material as requred for complete all as specified and directed by Engr-in-Chrage
115Supply & lay heavy duty PVC insulated multi stranded Copper Conductor 4 core of size 2.5 Sqmm, 230 volts, 50 HZ complete all as specified and directed.
116M&L taking down defective Turbo Charger Assembly duly disconnecting the mechanical and electrical connections from DG Set, opening and thoroughly checking to carry out repairs complete to the Turbo Charger Kit and spares as required at site including any mechanical and reassembling and refixing the turbo charger assembly to its original position and reconnecting the same for the following capacities including testing complete all as specified and directed.
117DG Set of capacity upto 125 KVA
118DG Set of capacity above 125KVA and up to250KVA
119M&L for calibration of water pump complete, overhauling, replacing of gaskets, nuts, washers etc and reassembling the same and refixing the pump to the engine and testing including taking down the old unservicable water pump of any capacity of DG set from the engine and taking it out side work to workshop, complete all as specified and directed:-
120DG Set of capacity upto 125 KVA KVA
121DG Set of capacity above 125KVA and up to250KVA
122M & L for dismantling & disconnecting all connection of the cylinder heads from diesel engine and sent to OEM authorised Service center for calibration and repairs by replacing the spares such as Valves, Value Guides, Valves seats and repairs kit and re-assembling to its original position with necessary Engine cylinder head gasket and O rings for the following capacities including testing complete all as specified and directed:-
123DG Set of capacity upto 125 KVA
124DG Set of capacity above 125KVA and up to250KVA
125M & L for maintenence free safe earthing electrode (SEE) designed pipe in pipe technology, set of 3 Nos earth pit duly inter connected with copper earth strip 25 mm x 3 mm, each earth pit having outer pipe of size76.3mm diaand inner pipe of size42.4 mm dia, each GI pipe have 2 mtrlongduly zinc and alloy coated having zinc coating (80-100) microns to whole length of pipe and alloy coating 250-300 micronto upper 300mm length of pipe, inside filled with crystal conductive compound (CCC) having anti corrosive and conductive properties to provide annular space of earth electrode and externalblack fill compound two bag of25 kg mixed with soil all arround the earth pipeforretainingmoisture, reduce the soil resistivity and dissipation of fault current, connected to earthing test point including excavation, earth work, PCC pit, RCC cover 50 mm thick, lifting rod 8mm dia, GI protection pipe 40 mm dia lightgrade for protection of inter connecting earthing strip from mechanical protection andtesting on completion, complete all as specified and directed.
126Supply and fixing Copper Strip 20 x 3.15 mm with saddles and fixing screws etc for roof conductors and down conductors above ground to interconnect the earth pit to equipment room Note: (a)Copper sockets and connector bolts nuts washers and drilling holes shall deemed to be included in the unit rate quoteed. (b)Excavation and earth work where ever required shall be carried out in this item only .(c) On testing after completion of earthingearth restiance shall be less than 1 Ohm complete all as specified and directed by Engr -in - charge
127M&L preparation of old painted surfaces of the DG Sets of 35 KVA to 125 KVA capacity including degreasing and spray painting the DG sets with one coat of synthetic enamel paint of approved colour and writing SM/MES No including painting on concrete surfaces of foundations with black paint complete all as specified and directed.
128M&L preparation of old painted surfaces of the DG Sets of the above 125 KVA and up to 250 KVA capacity including degreasing and spray painting the DG sets with one coat of synthetic enamel paint of approved colour and writing SM/MES No including painting on concrete surfaces of foundations with black paint complete all as specified and directed.
129M&L for preparation of old painted surfaces for outdoor/indoor Amf panel/LT Panel of any size with applying two coat of synthetic enamelled grey paint after removing all dust & rust and paint shall confirm to IS 2032complete all as specified .
130S&F in replacement of microprocessor based control unit suitable to DG set of any capacity with all listed parameters as per recomendation including testing complete all as specified and directed.
131S &F Door hinges of any capacity of DG Sets as suitable for existing one as specified and directed.Make Kisloskar
132S &F Door lock of any capacity of DG Sets as suitable for existing one as specified and directed.Make Kisloskar
133Supply only cotton waste for cleaning for DG Set and surrounding area complete all as specfied and directed.
134S & F in repair ofKG545 Controller , CT Coil 400/5A (KAPPA)for 250KVA, AMF Panel
135S & F in repair ofKG934V1 Controller, Harness wiring kit, VAF Meter/Timer etc incluing 2.5 Sqmm 4 core copper cable - 40 RMfor 125 KVA AMF Panel
136LTDISTRIBUTION M&L for attending, repair and rectification of external LT/HT electric supply complaints on 11000/1100 Volts grade, under ground / over head system along with necessary T & P, safety devices as per site requirement for the following type of complaints complete all as specified and directed:-
137Trimming/pruning and removing of tree branches or any other foreign objects from HT/LT over head conductor /Street light /Solar light area and clearing the OH Line of any type and size for one street light/one span of any length in 2 way /4 way/6 way conductor system. Notes: (i) Insulators of any type, connectors and ACSR conductor of any size required at site will be measured and paid separately under relevant item of this schedule. (ii) The contractor is responsible for provision of Necessary T & P and safety equipments to complete the job. (iii) Quoted rate is deemed to inclusive of Replacement of Insulators, Joining the ACSR Conductor, Jumpering and stringing the ACSR conductor etc.
138Replacement of faulty LT switch gear of any type and size fixed in panel board pole mounted boxes on walls or any other indicated places including provision of lugs/thimbles of suitable sizes. Note: - Switch gearswill bemeasured and paid separately under relevant items of this schedule.
139Replacement of blown out DO fuse, 11 KV grade of any capacity. Notes: (i) Quoted rate is deemed to be inclusive of Fuse wire of required gauge and necessary T & P required at site. (ii) No additional payments will be admissible for replacement of fuse in same system with an hour. (iii) Set of 3 fuses will be considered as one job for payment purpose.
140Dismantling of steel poles/ concrete poles of an site an location for issue of schedule of credit Notes for Item Nos 81.01 to 1.04 :- (a)The contractor will be allotted complaints at MES complaint cell on daily basis on all working days and sufficient resources will be deployed by him/her for completion of day to day complaints within 24 Hrs from the time of reporting. Any delay beyond above mentioned time limit without intimation of sufficient cause, penalties will be recovered twice of the quoted rate for each un-attended complaint. (b)A detailed log of complaints with completion/non-completion remarks from users/MES will be maintained by the contractor and the same will be updated on daily basis in consultation with Engr-in-Charge or JE E&M as detailed. (c)The contractor will make suitable arrangement for emergency complaints and will notify authorised rep/Engr-in-Charge about extraordinary circumstances for probable non-completion or delay in rectification of complaints beyond stated time limit set for disposal of complaint.In case of any dispute the decision of accepting officer will be final and binding in this regard. (d)The contractor will intimate MES authority well in advance if electric shutdown is required during rectification of complaints. (e)The quoted rate is deemed to be inclusive of transportation and other expenses required for the resource deployment at the complaint site around scattered Military station at Secunderabad. (f)The contractor will maintain location wise record of each spare utilized as per inventoy format given by AGE E/M, Secunderabd and the same shall be submitted to E/M No I store on daily basis.
141Supply only the following materials as in repairs/replacements complete all as specified and directed.
142MCCB 63 Amps, 3 pole, 415 Volts with rapturing capacity 16 KA, fixed magnetic and thermal settings
143MCCB 63 Amps, 4 pole, 415 Volts with rapturing capacity 16 KA, fixed magnetic and thermal settings
144MCCB 100 Amps, 3pole, 415 Volts with rapturing capacity 16 KA,fixed magnetic and thermal settings
145MCCB 100 Amps, 4 pole, 415 Volts with rapturing capacity 16 KA, fixed magnetic and thermal settings adjustable thermal and fixed magnetic settings.
146MCCB 160 Amps, 3 pole, 415 Volts with rapturing capacity 36 KAadjustable thermal and fixed magnetic settings.
147MCCB 160 Amps, 4 pole, 415 Volts with rapturing capacity 36 KAadjustable thermal and fixed magnetic settings.
148MCCB 200 Amps, 3 pole, 415 Volts with rapturing capacity 36 KAadjustable thermal and fixed magnetic settings.
149MCCB 200 Amps, 4 pole, 415 Volts with rapturing capacity 36 KAadjustable thermal and fixed magnetic settings.
150MCCB 250 Amps, 3 pole, 415 Volts with rapturing capacity 36 KAadjustable thermal and fixed magnetic settings.
151MCCB 250 Amps, 4 pole, 415 Volts with rapturing capacity 35 KAadjustable thermal and fixed magnetic settings.
152MCCB 400 Amps, 4 pole, 415 Volts with rapturing capacity 36 KA adjustable magnetic and thermal settings. Notefor Item Sl No 2.01 to 2.11 : Any modification/ alteration in existing panel which is required to fixing of MCCB is deemed to be included in unit rate
153Dismantling LT steel tubuler pole of any height by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole in true vertical position including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20mm graded stone aggregate) in both foundation and coping of poles all as specified in SSR Part I-2009 and applying two coats of aluminium paint to pole surface complete all as directed by Engineer-in-Charge.
154Supply, lay, commissioning and testing of cable jointing Kit for 1100 V grade cable for straight through heat shinkble jointwith jointing material and accessories suitable foraluminum conductor cable of sizeupto 120 sqmm, 3.5 Core complete all as specified and directed.
155M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional arealaid in trenches / duct or fixed to wall / passing through pipe on pole with suitable size cable glands, crimping type cable lugs for stranded aluminum conductor of following sizes complete all as specified and directed :- Note: Excavation, earth work, sand cushioning and cable protection items etc shall be measured and paid under respective items of BOQ.
1564 core X 10 Sqmm
1574 Core X 16 Sqmm
1584 Core X 25 Sqmm
1593.5 Core X 35 Sqmm
1603.5 Core X 50 Sqmm
1613.5 Core X 95 Sqmm
1623.5 Core X 120 Sqmm
1633.5 Core X 185 Sqmm
1643.5 Core X 240Sqmm
165M & L for testing earthing of installations, buildings, equipment etc and treating of earthings by pouring salt water and submit results sheet to AGE E/M No-I complete all as specified and directed. Note: Contractor has to arrange necessary tools required for the job
166Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation of PCC/Steel pole, laying of cable in trenches etc and getting out in hard / densesoil complete all as specified and directed.
167All as per item No 86.00 here in before but depth above 1.5 m & below 3 m
168Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed.
169Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
170M&L filling approved river sand in trenches for sand cushioning of laying of cables to the full width of excavated trench 8 cm thick before laying the cable and 15 cm above the cable, gently punned down, stretching and testing of cable on transformer yard etc complete all as specified and directed. Note :- Thickness of sand cushion after punning down shall be measured for payment.
171Supply and Lay reinforced precast concrete cable cover LV, Type I,flat, size 250x150x40 mm complete all as specified and directed.
172M&Lfor PCC 1:3:6 type C1 using 20mm graded aggregate set in cement mortar 1:4 as in coping/pedestals of poles including necessary form work complete and applying two coats of white wash to exposed surface of coping/platform complete all as specified and directed.
173M&Lfor PCC 1:3:6 type C2 using 40mm graded aggregate as in foundation, filling and mass concrete for pole / stay / post etc complete all as specified and directed.
174M&L brick protection with common burnt brick sub class ‘B’ of size 230x115x75mm for cable protection complete all as directed by Engr-in-charge.
175M&L, Cleaning the steel tubular poles of 9/11 metres long of any description thoroughly with necessary cleaning agent including scrapping up of old corroded paint dirt/dust/rust carefully and applying two coats of aluminum paint over a coat of red oxide primer and writing of MES No on pole with emulsion black paintcomplete all as specified and directed.
176M&L, Stickering of any type of street light pole with A1 graded radium strip of 100mm width three colour red, Yellow and green around the pole with 100mm gap in each strip at a distrance of 1.1 metre high from the ground level completeincluding white wash to the coping and marking of pole numbers with emulsion black paint complete all as directed by Engineer-in-Charge.
177Supplying, errecting and fixing steel tubular swaged poles with cast iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 metres long)including painting with two coats of aluminum paint over one coat of redoxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands with black & yellowpaint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" (inch) widecomplete all as specified and directed. Note: Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule.
178M&L Pipe bracket for street light fitting made out of 40mm dia GI pipe, medium grade, tubing bend to shape, 1.5m long fixed to pole wall including provn of two sets of clamps made out of flat iron of size 40x6 mm including of provn of bolts, nuts and washers complete all as specified and directed.
179S&F in repairs surge protection of 10 KV suitable upto 100W LED light fittings suitable to operate on input voltage 440 AC,50 Hz,complete all as specified and directed. Make:C&S / Havells/ Cromption cat part No 5RPSQ10KV/5KV-440 as approved by GE.
180Supply & lay heavy duty PVC insulated multi stranded Aluminum conductor twin core of size 4.0 Sqmm, 230 volts, 50 HZ complete all as specified and directed.
181Supply & lay GalvanisedIron tubing40mm bore, light grade in protection of cable at road crossing/hard standing/pole protection fixed with MS clamps of size 40 X 4 mm, nut bolts and washer as per site requirement including taking down old unserviceable pipes complete all as specified anddirected.
182All as per item No 101 above but GI tubing 50 mm bore.
183M&L cutting of road/hard standing upto a size not exceeding 20 cm in width and not exceeding 60 cm in depth for laying of LT UG cable/protection pipe line making good the disturbed portion so as to match existing finishing with PCC 1:2:4 type B1/cement mortar in CM (1:2) complete all as specified and directed
184Demolition of coping of pole as requiredfor placing of cable protection pipe and making good the same by using PCCcomplete al as speccified and directed. Note: Quoted rates are deemed to be inclusive of PCC
185Taking down old unsv Street light fittings in any position of any capacity, Repair of street light fittings by replacement of unsv spares and re-fixing the same in existing location. Note:- Spares for repair of street light fittings will be measured and paid under respective items.
186Servicing of ACB 4 pole 415 Volt up to 1000 amps including tripping test complete all as specified and directed
187Supply & fix, 90W LED street light withhigh quality integrated LED Luminaire with a system lumen of 11000 and system wattage 90w with an efficiency 120lumen/watt. CCT of 5700K with SDCM of < 5 and CRI >70. The housing should be separate optical and control gear compartment & bottom opening for easy maintenance and of of high quality pressure die cast aluminum with PF > 0.95 and THD < 10% & Operating temperature: -10°C to + 50°C. Input voltage of 100-300V. Lifetime of 50K hours @L70. Product should be suitable for continuous operation (16-18 Hrs. per day). The Ingress protection should be minimum IP 66 with an IK rating of 07. The luminaire should have Integratedpeanut optics to provide a high quality glare free lighting system. The Driver should be potted&should be a BIS approved driver and not a printed circuit board without casing, mounted inside the luminaire with Phase to Phase protection Over Voltage protection, Surge Voltage protection upto 10 kV & other safety test as per IS 15885 Part-2/Sec 13 . The luminaire should be capable of withstanding voltage stress of 440V for 8 Hrs., should have an auto shutdown @ 325V and have an auto recovery feature. BIS approval for Both Driver and the luminaire needs to be submitted for records before claiming RAR complete all as specified and as directed by Eng-in-charge . LUMINAIRE MAKE : Havells: ENDURASUNDOWNSL90WLED765PASYBOTG Or Equivalent inPhilips orWipro. LED MAKE Lumileds / Cree /Osram/ Bridgelux / Seoul.
188Supply & fix, LED floodlight 150W system lumens 18000lm, luminaire with pressure die cast aluminium (ADC12) housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser withInjection moulded polycarbonate/clear glass material, delivering superior light output Rated life Burning Hrs 50000 hr @ Lumen Maintenance of 70%, CCT > 5700K, IP 66 optical and electrical compartmenti.e. Built-in potted driver & impact resistance of complete luminaire > IK07. Power Factor >0.95 with mains, Surge Protection- Min 10KV along with Over voltage/ Overload, short circuit/ miss-wiring protection with other safety test as per IS 15885 Part-2/Sec 13. Universal Voltage driver to operate wide voltage range from 100 V to 270V, 50/60Hz application. Compliance to IS 10322/ IEC 60598, LM 79 & LM 80 Adherence withRoHS. UL approved MCPCB . LED Light fixture with 150W System Power consumption. LED Efficiency> 120m/w, nominal CRI >70.Luminaire manufacturer should have in- house facility accredited by NABL certified agency & Design & Development facility certified by ISO 9001:2008. The luminaire should be capable of withstanding voltage stress of 440V for 8 Hrs., should have an auto shutdown @ 325V and have an auto recovery feature. BIS approval for Both Driver and the luminaire needs to be submitted for records before claiming RAR complete all as specified and as directed by Eng-in-charge . LUMINAIRE MAKE : Havells: JETLEGANZAFL150WLED730P60DTOTG Or Equivalent in Philipsor Wipro. LED MAKE Lumileds / Cree /Osram/ Bridgelux / Seoul.
189Supply& Fix, 25W LEDDecorative Postop, Aesthetically designed LED post Top with aluminium enclosure and die casted heat sink exhibits classic look with symmetrical light distribution and excellent heat dissipation for long life. Family of post top, lantern designed to complement the geometry of the area Die-cast aluminum spigot for mounting LED driver and spun aluminum canopy which is painted white inside. Opening seperate driver compartment with IP65 protection and impact resistance of IK07.Operating temperature: -10°C to + 50°C, Operating voltage range: 140-270V, Average life L70B50: 50000 hours, High efficiency long life LED module with SMD , LED package mounted on MCPCB. Lumen, efficacy of LED >140 lm/W,Powered by built-in potted LED driver (SMPS based constant current supply) with lower THD, Output Open / Short Circuit protection, Phase to Phase protection (Operation at 415V AC), Over, Voltage protection, Surge Voltage protection upto, 4 kv with SPD & other safety test as per IS 15885 Part-2/Sec 13. THD< 10%, PF>.95, Current= 0.120A, CCT 5700K Havells Cat Ref: RUBYPT25WLED830PSYMTOPC Or Equivalent / PhilipsWipro. LED MAKE Lumileds / Cree /Osram/ Bridgelux / Seoul.
190Supply and fix in repaire,LEDBOLLARD light fitting 8Wwith aesthetic, innovative design and uniform lit diffuser at the upper portion acts as beacon in a landscape enviroment with robust IP65 rating complete all as specified and as directed by Eng-in-charge. MAKE-Havells Cat no-CONENXGBLS8WLEDPSYM830TOPC or technically equivalent in plilips/wipro.
191S&F in repairs Electronic drivers suitable for 90W LED light fittings suitable to operate on input voltage of AC 100-265 V, 50 Hz, Output DC 36 V, max 350 MA, 0.95 PF complete all as specified and directed.
192Supply and fix cable junction box thermoplastic body IP 66 , size 210mmx140mmx115mm suitable for helogen free and weather proof for out door installation with metric knockout for cable entry suitable for cable size 10-16 sqmm including clamp, lugs,cable terminal & 6-10 amps MCB complete all as specified and directed.
193M&L in repairs, Earthing complete with copper earth plate electrode of size 600 x 600 x 3.15mm thick buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5m below normal ground level connected to copper strip 20x3mm as earth lead by means of bolts, nuts, washers and check nuts made out of galvanized iron or steel all as shown on Electrical Plate No. 3 of SSR Part-I including testing on completion complete all as specified and directed by Eng-in-charge.
194Supply and fixing Copper Strip 20 x 3.15 mm with saddles and fixing screws etc for roof conductors and down conductors above ground to interconnect the earth pit to equipment room Note: (a)Copper sockets and connector bolts nuts washers and drilling holes shall deemed to be included in the unit rate quoteed. (b)Excavation and earth work where ever required shall be carried out in this item only (c) On testing after completion of earthingearth restiance shall be less than 1 Ohm complete all as specified and directed by Engr -in - charge
195Supply & Filldistilled water in batteries of solar street lights of any capacity and any height all as specified and directed by Engr in charge.
196S&F conneting and testing MCB isolator Single pole and neutral (SPN) 240 Volts of capaciyt 40 A10 KA 50 "B" curve complete Make:- Indoasian Cat part No. 811031 or equivalent as approved by GE.
197S&F conneting and testing MCB isolator three pole and neutral (TPN) 415 Volts of capaciyt 40 A16 KA 50 "c" curve complete
198S&F connecting and testing MCB isolator three pole and neutral (TPN) 415 volts of capacity 63 A16 KA 50 "c" curve complete
199M&L for repairing of automatic operation of highmast lantren including all arrangements required including crane and replacement of all unserviceable spares of highmast lighting system of height 12 m to 16 meter . Quoted rates deemed to be inclusive ofthe following:- (i) crane as required for taking down of high mast pole including light without any damage to the mast, lantern and lights etc and refixing the same after repairing of the all problem on the same position (ii) Necessary disconnection and reconnection of electrical connection. (iii) Replacement of all unserviceable sparelikeHigh mast head, high mast ring , stainless steelwire, clamp, winch, transition plate, service door , Hook ring, nose plate, cabinet, gear, reel, transmission belt etc including servicing of gear box , filling of gear oil, greasing etc complete(quoted rates deemed to be inclusive of all spares required for proper functioning of lantern system except stainless steel wire, High mast head, high mast ring etc.
200Supply only steel wire rope 6mm dia (7/19 construction)suitable for highmast system including u bolt complete all as directed
201Taking down, transport to workshop , Re-winding of electric motor 3 phase installed at highmast pole of capacity upto 2.2/3 HPand refixing of the same including necessary arrangement complete all as directed